Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

Catalogue

01 XMonitoring software interfaceXX

02 XXProduct InstallationX

03 Installation and commissioning

XXX
04 XXRoutine Maintenance
01
Monitoring Software
Interface
Main interface introduction-Home

Major Parameters

In which you can read the


main info as shown

Parameter Menu

In which you can set


the parameters

Main menu
This page is a navigation page for important parameters. Through this
page, can select the display, view, and settings of various parameters of
领先 开放 合作 创新 the system.
Main interface introduction--Temperature

Float charge voltage decrease value = (Battery


temperature measuring value- 25) ×Temperature
compensation coefficient

When rectifier communication fail or system


over/under voltage,temperature compensation
function will be invalid. When anyone battery
temperature sensor is fault or disconnect,
temperature compensation function will be
invalid. When there are multiple temperature
sensors, select the lowest temperature for
temperature compensation

领先 开放 合作 创新
Main interface introduction--Diesel

Set the start-up process of the Diesel

First we click system button, And then in


System Power Mode select Mains_DG,
last click Set

领先 开放 合作 创新
Main interface introduction--Diesel

Set the DI and DO of the Diesel


according to the actual situation

领先 开放 合作 创新
Main interface introduction--Diesel

According to the actual situation to set the


way to control the DG, such as voltage,
current and so on, we recommend voltage
control. Then set the start voltage and stop
voltage. In addition, we need to set other
start and stop conditions to disable.

领先 开放 合作 创新
Main interface introduction—DC

Mid-Voltage

When Battery cells voltage are unbalance over


the setting parameter, it will generate alarms.

领先 开放 合作 创新
Change the battery charging current
.①Click ‘Charge’ to select the battery
charging Settings page

②Enter the charge value you want to


adjust in this box and click ‘set’ to write it

③Wait for the page to refresh. If the


current value is changed here, the setting
is successful

领先 开放 合作 创新
Lead-acid to lithium battery operation
(1)charging parameter Settings
.①Click ‘Charge’ to select the battery
charging Settings page

②Adjust the battery capacity parameters


and charging coefficient according to the
actual total battery capacity

③Turn off Boost charge mode

领先 开放 合作 创新
Lead-acid to lithium battery operation
(2)Confirm the BMS configuration file

Select the BMS/BCM screen and check


whether FiberHome provides the BMS
protocol. If not, manually select the BMS
protocol,If no protocol file is displayed in
the option box, import it by referring to the
upgrade guide.

领先 开放 合作 创新
Battery Test
Constant current test:
Function: In the constant current test state, the module output voltage is controlled at the "floating charge
voltage" (the default is 54.5V). By adjusting the current limiting point of the module, the battery discharge
current is kept near the "constant current test current" (default 0.2C10). If the load is less than the set value,
the discharge current is approximately equal to the load current. Constant current test is mainly used to test
battery performance. During a constant current test, if the bus voltage is less than or equal to the test stop
voltage, a test failure alarm is generated.
Automatic opening mode: Manual opening mode:

领先 开放 合作 创新
02
Product Installation
Subrack installation

Step1:Push the Subrack into the 19-inch rack

Step2:install fixing screws


(If the mounting ear holes do not match the
positions, adjust them based on actual
installation conditions)

领先 开放 合作 创新
Connecting ground wire

Front view of SFXPS-48-18-MI

Step1:Connect one end of the protective


ground wire to the PE terminal of the AC input of
the subrack.

Step2:Connect the other end of the protective


ground wire to the grounding bar screw on the
cabinet/rack.

Top view of SFXPS-48-18-MI

领先 开放 合作 创新
Rectifier Module Installation

Step1

Hold the handle on the front panel of the


rectifier, hold the module, and slowly push
SFXPS-48-18-MI
the module into the slot where the rectifier is
fixed.

Step2

Slowly push the rectifier until the front panel


of the rectifier is flush with the panel of the
power distribution subrack.

Step3

Fasten the screws on the front panel of the


rectifier clockwise to lock the rectifier to the
power distribution subrack.

领先 开放 合作 创新
Connecting T/H sensor signal cable
User panel
Step1

Use a straight screwdriver to push the


contact strip corresponding to the dry
contacts to make the metal spring piece of
the dry contact bounce
Step2

Install the signal cable to the


corresponding dry contact interface

Step3
Interface screen printing Interface name
Withdraw the screwdriver and ensure
BTEMP1~BTEMP3 3 circuits of battery temperature sensor interface
that the dry contact signal cable is ENV.TEMP 1 circuit of ambient temperature sensor interface

secured
领先 开放 合作 创新
Connecting battery cables

Route the battery cable, make it get


01
through the hole on the right side of
the subrack, or remove the front top
cover wiring;
Without the cover

02 Fasten the negative


battery cable to the
battery air switch(BAT);

03 Fasten the positive battery cable to


the RTN+ bus bar.

领先 开放 合作 创新
Connecting battery cables-BMS

Step1

Connect the 485 communication of the user interface


board with the 485 communication of the battery pack

Step2
Set the position of the dial switch according to the actual
address of the BMS

领先 开放 合作 创新
Connecting AC input cable
Step1

Insert the 220V/380V three-phase four wire AC input cable from


the back of the subrack and remove the front top cover wiring

Step2
Secure the AC input cable to the corresponding AC input
terminal

Terminal for AC input


Terminal for AC input

领先 开放 合作 创新
Connecting communication cables

领先 开放 合作 创新
Installation Inspection
Check hardware installation

• Check that all screws are tightened (especially those for electrical connections) and that flat washers and spring
washers are installed correctly;
• Check that the rectifier module is fully inserted into each slot and locked correctly.

Check electrical connections

• Check that all the air switch are in OFF status;


• Check that the flat washer and the spring washer are installed safely on all terminals and that all OT terminals are connected
together completely and correctly;
• Check whether the battery is installed correctly and the battery cables are connected correctly;
• Check that the input and output cables are correctly connected to the grounding cables.The power input meets the requirements

Check cable installation

• Check that all cables are securely connected;


• Check that all cables are aligned neatly and are tightly connected to their nearest cables without twisting or over-
bending;

领先 开放 合作 创新
03
Installation and
Commissioning
Caution
The commisioning steps may lead to Commisioning personnel must have
power failure or alarm, which needs to received appropriate technical training,
be notified to the alarm center before please refer to the commisioning
and after operation. 01 02 description for operation.

The process of commisioning is live During power equipment Commisioning,


work. Please stand on dry insulation before any "closing operation", it is
while operating. Do not wear watches, 06 03 necessary to check whether the status
necklaces and other metal objects, of the relevant unit or part meets the
and keep tools insulated. requirements.

During operation, if other people are not 05 04 During the process of Commisioning, we
allowed to operate, warning sign "No shall observe while Commisioning, shut
closing, manned operation" shall be down immediately when abnormal
suspended on the distribution equipment. phenomena are found out, and continue
after finding out the cause.

领先 开放 合作 创新
Setting System Parameters

Login Language

Preset username: operator After the monitoring unit is powered


(1)LAN communication interface
Preset password: 10000 (2)RS485 communication interface
on, the LCD displays a language
(For more permission, please (3)Operation indicator selection interface. Select Chinese
(4)General warning indicator
consult the manufacturer) (5)Seveice indicator (6)Handle (7)Key or English by using the "UP" or
"DN". Press the "ENT" key and then
enters the default system
information interface.

领先 开放 合作 创新
Battery parameter setting via mornitoring module
Battery parameter

Parameters Setting Charging settings Battery capacity Battery type


Step

Interface

• Set the sum of rated capacities of batteries installed in the same battery shunt based on the actual
application. If two battery branches are connected in parallel (each battery group consists of four 12V/150Ah
batteries in series), the battery capacity is set to 300Ah.
Description • If the battery branch is connected in parallel to two batteries (each battery consists of four 12V/150Ah single
batteries in series), then the “Nominal capacity” is set to 300Ah.

领先 开放 合作 创新
Battery parameter setting via software

Float charge voltage setting:


For Lead-acid battery,FC voltage and boost
voltage have different voltage;for lithium
battery fc voltage=boost charge voltage

Battery charging current limit coefficient


setting: battery charging current cannot be
greater than 0.1C10

领先 开放 合作 创新
Battery Power-on Commisioning

1 Ture off AC input


Caution:
Only after the battery parameters of the monitoring module

Ture on the battery have been correctly set can the battery air switch be closed,
switch 2
otherwise the battery may be damaged.
① Set the AC input switch to OFF;

3 Ture on AC input ② Set the battery switch to ON;

③ Set the AC input switch to ON;

Measuring output ④ Set all switch to the status required on the actual site;
voltage 4

⑤ After 10 minutes of observation, the monitoring module has no alarm


information except door magnetic alarm (configured). The parameters of
Check whether current and voltage of battery and load are normal, i.e. battery power-on
5
alarms Commisioning is completed.

领先 开放 合作 创新
04
Routine Maintenance
Routine Maintenance
Maintenance Maintenance content

items Inspection items Inspection method Repair conditions Treatment methods

The voltage of the battery


Whether the voltage output is
Electrical Multimeter branch or load branch exceeds
normal
the set range
See Fault alarm handling of
manual

Whether the indicator is


Fault inspection Visual inspection Fault alarm
normal

The coating of power system


Damaged or deformed
Appearance has no peeling and no Visual inspection Repaint and repair the shell
appearance of power system
scratches

Check the cable connection


Whether the power grounding
between the power grounding
Grounding point is properly connected to Visual inspection, inspection Retighten grounding points or
point and the grounding bar in
detection the grounding bar of the with screwdriver, wrench, etc. replace grounding cables
the equipment room is not
equipment room
reliable
领先 开放 合作 创新
Fault Alarm Handling
Fault type Possible causes Treatment methods

1.Check whether the AC input cable is loose. If so, secure the input cable;
1.AC input cable fault; 2.Check whether the AC input air switch is OFF. If so, close the air switch after processing the end circuit
AC power outage 2.The AC input air switch is OFF; fault;
3.Power grid fault. 3.Check whether the AC input voltage of the power system is lower than 50Vac. If so, deal with the power
grid fault.

1.Check whether the AC input cable is loose. If so, secure the input cable. Check whether the setting value
1.The setting of AC overvoltage alarm point is not improperly; of AC overvoltage alarm is proper or not; if not, adjust it according to the actual situation;
AC overvoltage
2.Power grid fault. 2.Check whether the AC input voltage of the power system exceeds the AC overvoltage alarm point
(default value 280Vac) and if so, deal with the AC input fault.

1.Check whether the AC undervoltage alarm value is appropriate. If the value is not appropriate, adjust it
1.The AC undervoltage alarm point is set improperly; according to the actual situation;
AC undervoltage
2.Power grid fault. 2.Check whether the AC input voltage of the power system is lower than the AC undervoltage alarm point
(default value 180Vac), and if so, deal with the AC input fault.

1.Check whether the AC is power outage, and if the AC is power outage, restore the power supply;
2.Confirm whether the operation of manually controlling load power off is carried out, if so, confirm the
1.AC power outage; operation reason, and resume power on after the operation is completed;
2.Manually control the load power off; 3.Check whether the power off voltage setting value (default value 44Vdc) of monitoring module is too high,
LLVD power off 3.The load power off voltage of the monitoring module is set too high; and if so, adjust it according to the actual situation;
4.Rectifier module fault; 4.Check whether the system capacity does not meet the load demand due to the fault of the rectifier
5.The system configuration is unreasonable. module, and if so, replace the faulty rectifier module;
5.Check whether the power system load current value is greater than the current power system capacity,
and if so, increase the power system capacity configuration or decrease the power system load.

领先 开放 合作 创新
Fault Alarm Handling
Fault type Possible causes Treatment methods

1.Check whether the AC is power outage, and if the AC is power outage, restore the power supply;
2.Confirm whether the operation of manually controlling battery power off is carried out, if so, confirm the operation
1.AC power outage; reason, and resume power on after the operation is completed;
2.Manual battery power off; 3.Check whether the voltage setting value (default 43.2 Vdc) for the BLVD power off of the monitoring module is too
BLVD power off 3.The battery voltage setting of the monitoring module is too high; high, and if so, adjust it according to the actual situation;
4.Rectifier module fault; 4.Check whether the power system capacity does not meet the load demand due to the fault of the rectifier module,
5.The system configuration is unreasonable. and if so, replace the faulty rectifier module;
5.Check whether the power system load current value is greater than the current power system capacity, and if so,
increase the power system capacity configuration or decrease the power system load.

1.Check whether the battery air switch or the fuse detection line is loose. If so, please fix the detection line;
1.The battery air switch or the fuse detection line is loose; 2.Check whether the battery air switch or the fuse is disconnected. If so, please close the circuit breaker or replace
Battery fuse disconnection 2.The battery air switch or the fuse is disconnected; the fuse after handling the battery circuit fault;
3.Contactor fault. 3.Manually control the battery contactor to close or open, and check whether the battery current changes are
consistent. If not, please replace the contactor. If not, please replace the contactor.

1.Check whether the fault indicator on the rectifier module panel is always on (red), if so, pull out the rectifier module,
1.The rectifier module is improperly connected;
Rectifier module fault and reinsert the module after the indicator goes out;
2.The rectifier module is damaged.
2.If still alarm, please replace the rectifier module.

1.Check whether the AC input voltage is higher than the maximum working voltage of the rectifier module. If so,
restore the power supply after dealing with the power supply fault;
1.The input voltage of rectifier module is too high; 2.Check whether the AC input voltage is lower than the maximum working voltage of the rectifier module. If so,
2.The input voltage of rectifier module is too low; restore the power supply after dealing with the power supply fault;
Rectifier module protection
3.The ambient temperature is too high; 3.Check whether the ambient temperature is higher than the normal working temperature of the module. If so, check
4.The rectifier module works abnormally. and eliminate the fault of temperature control system;
4.Pull out the rectifier module of the alarm, and insert the rectifier module after the indicator is off. If the alarm still
领先 开放 合作 创新 occurs, replace the rectifier module.
Thanks
Thanks

You might also like