02 XXProduct InstallationX
XXX
04 XXRoutine Maintenance
01
Monitoring Software
Interface
Main interface introduction-Home
Major Parameters
Parameter Menu
Main menu
This page is a navigation page for important parameters. Through this
page, can select the display, view, and settings of various parameters of
领先 开放 合作 创新 the system.
Main interface introduction--Temperature
领先 开放 合作 创新
Main interface introduction--Diesel
领先 开放 合作 创新
Main interface introduction--Diesel
领先 开放 合作 创新
Main interface introduction--Diesel
领先 开放 合作 创新
Main interface introduction—DC
Mid-Voltage
领先 开放 合作 创新
Change the battery charging current
.①Click ‘Charge’ to select the battery
charging Settings page
领先 开放 合作 创新
Lead-acid to lithium battery operation
(1)charging parameter Settings
.①Click ‘Charge’ to select the battery
charging Settings page
领先 开放 合作 创新
Lead-acid to lithium battery operation
(2)Confirm the BMS configuration file
领先 开放 合作 创新
Battery Test
Constant current test:
Function: In the constant current test state, the module output voltage is controlled at the "floating charge
voltage" (the default is 54.5V). By adjusting the current limiting point of the module, the battery discharge
current is kept near the "constant current test current" (default 0.2C10). If the load is less than the set value,
the discharge current is approximately equal to the load current. Constant current test is mainly used to test
battery performance. During a constant current test, if the bus voltage is less than or equal to the test stop
voltage, a test failure alarm is generated.
Automatic opening mode: Manual opening mode:
领先 开放 合作 创新
02
Product Installation
Subrack installation
领先 开放 合作 创新
Connecting ground wire
领先 开放 合作 创新
Rectifier Module Installation
Step1
Step2
Step3
领先 开放 合作 创新
Connecting T/H sensor signal cable
User panel
Step1
Step3
Interface screen printing Interface name
Withdraw the screwdriver and ensure
BTEMP1~BTEMP3 3 circuits of battery temperature sensor interface
that the dry contact signal cable is ENV.TEMP 1 circuit of ambient temperature sensor interface
secured
领先 开放 合作 创新
Connecting battery cables
领先 开放 合作 创新
Connecting battery cables-BMS
Step1
Step2
Set the position of the dial switch according to the actual
address of the BMS
领先 开放 合作 创新
Connecting AC input cable
Step1
Step2
Secure the AC input cable to the corresponding AC input
terminal
领先 开放 合作 创新
Connecting communication cables
领先 开放 合作 创新
Installation Inspection
Check hardware installation
• Check that all screws are tightened (especially those for electrical connections) and that flat washers and spring
washers are installed correctly;
• Check that the rectifier module is fully inserted into each slot and locked correctly.
领先 开放 合作 创新
03
Installation and
Commissioning
Caution
The commisioning steps may lead to Commisioning personnel must have
power failure or alarm, which needs to received appropriate technical training,
be notified to the alarm center before please refer to the commisioning
and after operation. 01 02 description for operation.
During operation, if other people are not 05 04 During the process of Commisioning, we
allowed to operate, warning sign "No shall observe while Commisioning, shut
closing, manned operation" shall be down immediately when abnormal
suspended on the distribution equipment. phenomena are found out, and continue
after finding out the cause.
领先 开放 合作 创新
Setting System Parameters
Login Language
领先 开放 合作 创新
Battery parameter setting via mornitoring module
Battery parameter
Interface
• Set the sum of rated capacities of batteries installed in the same battery shunt based on the actual
application. If two battery branches are connected in parallel (each battery group consists of four 12V/150Ah
batteries in series), the battery capacity is set to 300Ah.
Description • If the battery branch is connected in parallel to two batteries (each battery consists of four 12V/150Ah single
batteries in series), then the “Nominal capacity” is set to 300Ah.
领先 开放 合作 创新
Battery parameter setting via software
领先 开放 合作 创新
Battery Power-on Commisioning
Ture on the battery have been correctly set can the battery air switch be closed,
switch 2
otherwise the battery may be damaged.
① Set the AC input switch to OFF;
Measuring output ④ Set all switch to the status required on the actual site;
voltage 4
领先 开放 合作 创新
04
Routine Maintenance
Routine Maintenance
Maintenance Maintenance content
1.Check whether the AC input cable is loose. If so, secure the input cable;
1.AC input cable fault; 2.Check whether the AC input air switch is OFF. If so, close the air switch after processing the end circuit
AC power outage 2.The AC input air switch is OFF; fault;
3.Power grid fault. 3.Check whether the AC input voltage of the power system is lower than 50Vac. If so, deal with the power
grid fault.
1.Check whether the AC input cable is loose. If so, secure the input cable. Check whether the setting value
1.The setting of AC overvoltage alarm point is not improperly; of AC overvoltage alarm is proper or not; if not, adjust it according to the actual situation;
AC overvoltage
2.Power grid fault. 2.Check whether the AC input voltage of the power system exceeds the AC overvoltage alarm point
(default value 280Vac) and if so, deal with the AC input fault.
1.Check whether the AC undervoltage alarm value is appropriate. If the value is not appropriate, adjust it
1.The AC undervoltage alarm point is set improperly; according to the actual situation;
AC undervoltage
2.Power grid fault. 2.Check whether the AC input voltage of the power system is lower than the AC undervoltage alarm point
(default value 180Vac), and if so, deal with the AC input fault.
1.Check whether the AC is power outage, and if the AC is power outage, restore the power supply;
2.Confirm whether the operation of manually controlling load power off is carried out, if so, confirm the
1.AC power outage; operation reason, and resume power on after the operation is completed;
2.Manually control the load power off; 3.Check whether the power off voltage setting value (default value 44Vdc) of monitoring module is too high,
LLVD power off 3.The load power off voltage of the monitoring module is set too high; and if so, adjust it according to the actual situation;
4.Rectifier module fault; 4.Check whether the system capacity does not meet the load demand due to the fault of the rectifier
5.The system configuration is unreasonable. module, and if so, replace the faulty rectifier module;
5.Check whether the power system load current value is greater than the current power system capacity,
and if so, increase the power system capacity configuration or decrease the power system load.
领先 开放 合作 创新
Fault Alarm Handling
Fault type Possible causes Treatment methods
1.Check whether the AC is power outage, and if the AC is power outage, restore the power supply;
2.Confirm whether the operation of manually controlling battery power off is carried out, if so, confirm the operation
1.AC power outage; reason, and resume power on after the operation is completed;
2.Manual battery power off; 3.Check whether the voltage setting value (default 43.2 Vdc) for the BLVD power off of the monitoring module is too
BLVD power off 3.The battery voltage setting of the monitoring module is too high; high, and if so, adjust it according to the actual situation;
4.Rectifier module fault; 4.Check whether the power system capacity does not meet the load demand due to the fault of the rectifier module,
5.The system configuration is unreasonable. and if so, replace the faulty rectifier module;
5.Check whether the power system load current value is greater than the current power system capacity, and if so,
increase the power system capacity configuration or decrease the power system load.
1.Check whether the battery air switch or the fuse detection line is loose. If so, please fix the detection line;
1.The battery air switch or the fuse detection line is loose; 2.Check whether the battery air switch or the fuse is disconnected. If so, please close the circuit breaker or replace
Battery fuse disconnection 2.The battery air switch or the fuse is disconnected; the fuse after handling the battery circuit fault;
3.Contactor fault. 3.Manually control the battery contactor to close or open, and check whether the battery current changes are
consistent. If not, please replace the contactor. If not, please replace the contactor.
1.Check whether the fault indicator on the rectifier module panel is always on (red), if so, pull out the rectifier module,
1.The rectifier module is improperly connected;
Rectifier module fault and reinsert the module after the indicator goes out;
2.The rectifier module is damaged.
2.If still alarm, please replace the rectifier module.
1.Check whether the AC input voltage is higher than the maximum working voltage of the rectifier module. If so,
restore the power supply after dealing with the power supply fault;
1.The input voltage of rectifier module is too high; 2.Check whether the AC input voltage is lower than the maximum working voltage of the rectifier module. If so,
2.The input voltage of rectifier module is too low; restore the power supply after dealing with the power supply fault;
Rectifier module protection
3.The ambient temperature is too high; 3.Check whether the ambient temperature is higher than the normal working temperature of the module. If so, check
4.The rectifier module works abnormally. and eliminate the fault of temperature control system;
4.Pull out the rectifier module of the alarm, and insert the rectifier module after the indicator is off. If the alarm still
领先 开放 合作 创新 occurs, replace the rectifier module.
Thanks
Thanks