Project: Fitness Time Souq 7

Fire Fighting Hydraulic Calculations

Codes and Standards


Fire protection systems will be designed in accordance with NFPA and requirements of the local civil
defense, fire authorities having jurisdiction over work at the building project. Additionally, fire
protection systems will conform to the requirement of technical guidelines and design criteria of the
following applicable latest codes and standards

Item Subject Codes and Standards


1 Fire prevention code. NFPA 1
2 Standard for portable fire extinguishers NFPA 10
3 Standard on carbon dioxide extinguishing systems. NFPA 12
4 Standard for the installation of sprinkler systems. NFPA 13
5 Standard for the installation of standpipe and hose systems. NFPA 14
Standard for Installation of Foam‐Water Sprinkler and Foam‐Water
6 NFPA 16
Spray Systems
7 Standard for Water Tanks for Private Fire Protection NFPA 22
8 Standard for the installation of stationary pumps for fire protection NFPA 20
Standard for the inspection, testing, and maintenance of water‐based
9 NFPA 25
fire protection systems.
10 Standard for protection for laboratories using chemicals. NFPA 45
Design and Installation of Oxygen–Fuel Gas Systems for Welding,
11 NFPA 51
Cutting and Allied Processes
12 National fuel gas code. NFPA 54
13 National electrical code. NFPA 70
14 National fire alarm code. NFPA 72
15 Health Care Facilities Code. NFPA 99
16 Life safety code. NFPA 101
17 Standard for fire hose connections. NFPA 1963
18 Standard on clean agent fire extinguishing systems. NFPA 2001

Sprinkler System
The water demand for the sprinkler system shall be determined based on the following:

Ordinary Hazard (Group 1) Occupancies


Sprinkler System Design Basis and Hydraulic Criteria for all ordinary hazard occupancies shall be
as follow:

 Fire protection sprinklers area limitations shall be max. 4830 m2 on any one floor, supplied
by any one system riser or combined system riser.

 Sprinkler operation most remote design area shall be 176 m2 (1905 ft2).

 Density of water for the most remote design area shall be 0.15 gpm/ft2

 Max. Area per sprinkler head shall be 12.1 m2 (130 ft2).

 Sprinkler spacing limitation shall be 4.6 m, max. distance between sprinklers, either
On branch lines or between branch lines.

 No.Of Sprinkler Calculated 176/12 = 15 Sprinkler


Water Required For Sprinklers = 0.15 GPM/ft2 x 130 ft2 x 15 Sprinkler = 292.5 GPM

Total Fire Water Flow Rate Required

=(Sprinkler Water Flow Rate)+1 FHC @100 GPM

= 292.5+100 = 392.5 GPM

SAY 500 GPM

Fire‐Water Storage Requirement

= 500 GPM x 60 Minutes = 30000 GPM = 114 M3

Total Sprinkler System Pressure Requirement (According To Elite Program)

= 91.3 PSI = 6.3 BAR

SAY 7 Bar

Conclusion
Diesel and Electrical Fire pumps shall be:

Q= 500 GPM

H= 7 Bar

For Jockey Pump

QJ = QS x 1% = 500 x 1 % = 5 GPM

SAY 25 GPM

HJ = HS + 8 PSI = 7 Bar + 0.5 Bar = 7.5 Bar


FITNESS TIME-SOUQ 7
Fire Sprinkler Reports

for

Leejam

Prepared By:

Saudi Icon Team

August 31, 2023


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 2

General Project Data Report

General Data
Project Title: Fitness Time-Souq 7 Project File Name: Souq 7..fiw
Designed By: Saudi Icon Team Date: August 31, 2023
Code Reference: NFPA 13 Approving Agency:
Client Name: Leejam Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Ordinary 1 Sprinkler System Type:
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Viking Model:
Size: 1/2 Temperature Rating: 154 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 495.99 gpm Calculated Inflow Residual Pressure: 91.33 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 10.00 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Maximum Water Velocity: 23.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 26
Number Of Active Pipes: 25 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 15 Number Of Inactive Sprinklers: 0

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Sprinkler ---- 5.60 12.62 32.81 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 14.15 32.81 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 21.42 32.81 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 27.43 32.81 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 33.88 32.81 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Non-Sprinkler ---- N/A 46.67 32.81 100.00


6
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 48.45 32.81 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 54.68 32.81 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 12.13 32.81 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 13.60 32.81 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 21.55 32.81 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 27.44 32.81 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 33.80 32.81 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 15.16 32.81 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 15.92 32.81 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 25.40 32.81 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 32.36 32.81 0.00


17
---- 0.000 0.0 ---- 0.0 0.00

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)
Sprinkler ---- 5.60 39.84 32.81 0.00
18
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 64.04 32.81 0.00


19
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 74.77 32.81 0.00


20
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 75.83 32.81 0.00


21
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 90.90 0.00 0.00


22
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 91.33 0.00 0.00


23
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 42.91 32.81 0.00


30
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 44.73 32.81 0.00


40
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 50.32 32.81 0.00


50
---- 0.000 0.0 ---- 0.0 0.00

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 5

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inc
Node Node Group Data
(inch) (feet) (feet) (feet) h-psi)

1 2 SCHED 40 WET STEEL 1.000 0 E 9.84 2.00 11.84 120

2 3 SCHED 40 WET STEEL 1.000 0 T 9.84 5.00 14.84 120

3 4 SCHED 40 WET STEEL 1.250 0 ET 9.84 9.00 18.84 120

4 5 SCHED 40 WET STEEL 1.500 0 ET 9.84 12.00 21.84 120

5 30 SCHED 40 WET STEEL 1.500 0 T 9.84 8.00 17.84 120

30 6 SCHED 40 WET STEEL 2.000 0 2E 15.09 10.00 25.09 120

6 7 SCHED 40 WET STEEL 3.000 0 T 13.12 15.00 28.12 120

9 10 SCHED 40 WET STEEL 1.000 0 E 9.84 2.00 11.84 120

10 11 SCHED 40 WET STEEL 1.000 0 ET 9.84 7.00 16.84 120

11 12 SCHED 40 WET STEEL 1.250 0 ET 9.84 9.00 18.84 120

12 13 SCHED 40 WET STEEL 1.500 0 ET 9.84 12.00 21.84 120

13 40 SCHED 40 WET STEEL 1.500 0 ET 9.84 12.00 21.84 120

40 7 SCHED 40 WET STEEL 2.000 0 T 15.09 10.00 25.09 120

7 8 SCHED 40 WET STEEL 3.000 0 2T 13.12 30.00 43.12 120

14 15 SCHED 40 WET STEEL 1.250 0 ET 9.84 9.00 18.84 120

15 16 SCHED 40 WET STEEL 1.000 0 ET 9.84 7.00 16.84 120

16 17 SCHED 40 WET STEEL 1.250 0 ET 9.84 9.00 18.84 120

17 18 SCHED 40 WET STEEL 1.500 0 ET 9.84 12.00 21.84 120

18 50 SCHED 40 WET STEEL 1.500 0 T 9.84 8.00 17.84 120

50 8 SCHED 40 WET STEEL 2.000 0 2E 15.09 10.00 25.09 120

8 19 SCHED 40 WET STEEL 3.000 0 E 28.22 7.00 35.22 120

19 20 SCHED 40 WET STEEL 4.000 0 4E 111.55 40.00 151.55 120

20 21 SCHED 40 WET STEEL 6.000 0 GC 75.46 35.00 110.46 120

21 22 SCHED 40 WET STEEL 6.000 0 2T 29.53 60.00 89.53 120

22 23 SCHED 40 WET STEEL 6.000 0 GC 9.84 35.00 44.84 120

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 6

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -19.89 19.89 0.00 0.00 12.62

2 1 0 19.89 21.06 0.00 0.00 14.15 0.00711


2 3 0 -40.94

3 2 0 40.94 25.92 0.00 0.00 21.42 0.02476


3 4 0 -66.84

4 3 0 66.84 29.33 0.00 0.00 27.43 0.03983


4 5 0 -96.13

5 4 0 96.13 32.60 0.00 0.00 33.88 0.05778


5 30 0 -128.67

6 30 0 128.67 0.00 100.00 0.00 46.67 0.01156


6 7 0 -228.65

7 6 0 228.65 0.00 0.00 0.00 48.45 -0.00110


7 40 0 127.91
7 8 0 -356.56

8 7 0 356.56 0.00 0.00 0.00 54.68 -0.00129


8 50 0 139.43
8 19 0 -495.99

9 10 0 -19.49 19.50 0.00 0.00 12.13 0.00669

10 9 0 19.49 20.65 0.00 0.00 13.60 0.00506


10 11 0 -40.14

11 10 0 40.14 26.00 0.00 0.00 21.55 0.02445


11 12 0 -66.11

12 11 0 66.11 29.34 0.00 0.00 27.44 0.03893


12 13 0 -95.41

13 12 0 95.41 32.56 0.00 0.00 33.80 0.05638


13 40 0 -127.91

14 15 0 -21.80 21.81 0.00 0.00 15.16 0.00642

15 14 0 21.80 22.34 0.00 0.00 15.92 0.00878


15 16 0 -44.14

16 15 0 44.14 28.23 0.00 0.00 25.40 0.02870


16 17 0 -72.33

17 16 0 72.33 31.86 0.00 0.00 32.36 0.04571


17 18 0 -104.15

18 17 0 104.15 35.35 0.00 0.00 39.84 0.06595


18 50 0 -139.43

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 7

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

19 8 0 495.99 0.00 0.00 0.00 64.04 0.00012


19 20 0 -495.99

20 19 0 495.99 0.00 0.00 0.00 74.77 -0.00211


20 21 0 -495.99

21 20 0 495.99 0.00 0.00 0.00 75.83 -0.00021


21 22 0 -495.99

22 21 0 495.99 0.00 0.00 0.00 90.90 -0.00070


22 23 0 -495.99

23 22 0 495.99 0.00 0.00 -495.99 91.33

30 5 0 128.67 0.00 0.00 0.00 42.91 -0.00018


30 6 0 -128.67

40 7 0 -127.91 0.00 0.00 0.00 44.73 -0.00028


40 13 0 127.91

50 8 0 -139.43 0.00 0.00 0.00 50.32 -0.00025


50 18 0 139.43

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 8

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 5.60 32.81 19.89 12.62 1.00 19.89 0.12884 9.84 1.526


2 5.60 32.81 21.06 14.15 1.049 19.89 E 2.00 0.000
SCHED 40 WET STEEL 120 7.38 0 11.84 1.526

2 5.60 32.81 21.06 14.15 1.00 21.06 0.49005 9.84 7.274


3 5.60 32.81 25.92 21.42 1.049 40.94 T 5.00 0.000
SCHED 40 WET STEEL 120 15.20 0 14.84 7.274

3 5.60 32.81 25.92 21.42 1.25 25.92 0.31913 9.84 6.013


4 5.60 32.81 29.33 27.43 1.380 66.84 ET 9.00 0.000
SCHED 40 WET STEEL 120 14.34 0 18.84 6.013

4 5.60 32.81 29.33 27.43 1.50 29.33 0.29509 9.84 6.446


5 5.60 32.81 32.60 33.88 1.610 96.13 ET 12.00 0.000
SCHED 40 WET STEEL 120 15.15 0 21.84 6.446

30 0.00 32.81 0.00 42.91 2.00 0.00 0.14988 15.09 3.761


6 0.00 32.81 100.00 46.67 2.067 128.67 2E 10.00 0.000
SCHED 40 WET STEEL 120 12.30 0 25.09 3.761

6 0.00 32.81 100.00 46.67 3.00 100.00 0.06346 13.12 1.785


7 0.00 32.81 0.00 48.45 3.068 228.65 T 15.00 0.000
SCHED 40 WET STEEL 120 9.92 0 28.12 1.785

40 0.00 32.81 0.00 44.73 2.00 0.00 0.14825 15.09 3.720


7 0.00 32.81 0.00 48.45 2.067 127.91 T 10.00 0.000
SCHED 40 WET STEEL 120 12.23 0 25.09 3.720

7 0.00 32.81 0.00 48.45 3.00 0.00 0.14437 13.12 6.226


8 0.00 32.81 0.00 54.68 3.068 356.56 2T 30.00 0.000
SCHED 40 WET STEEL 120 15.47 0 43.12 6.226

50 0.00 32.81 0.00 50.32 2.00 0.00 0.17389 15.09 4.363


8 0.00 32.81 0.00 54.68 2.067 139.43 2E 10.00 0.000
SCHED 40 WET STEEL 120 13.33 0 25.09 4.363

9 5.60 32.81 19.50 12.13 1.00 19.50 0.12415 9.84 1.470


10 5.60 32.81 20.65 13.60 1.049 19.49 E 2.00 0.000
SCHED 40 WET STEEL 120 7.24 0 11.84 1.470

10 5.60 32.81 20.65 13.60 1.00 20.65 0.47234 9.84 7.956


11 5.60 32.81 26.00 21.55 1.049 40.14 ET 7.00 0.000
SCHED 40 WET STEEL 120 14.90 0 16.84 7.956

11 5.60 32.81 26.00 21.55 1.25 26.00 0.31274 9.84 5.893


12 5.60 32.81 29.34 27.44 1.380 66.11 ET 9.00 0.000
SCHED 40 WET STEEL 120 14.18 0 18.84 5.893

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 9

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

12 5.60 32.81 29.34 27.44 1.50 29.34 0.29101 9.84 6.357


13 5.60 32.81 32.56 33.80 1.610 95.41 ET 12.00 0.000
SCHED 40 WET STEEL 120 15.04 0 21.84 6.357

14 5.60 32.81 21.81 15.16 1.25 21.81 0.04016 9.84 0.757


15 5.60 32.81 22.34 15.92 1.380 21.80 ET 9.00 0.000
SCHED 40 WET STEEL 120 4.68 0 18.84 0.757

15 5.60 32.81 22.34 15.92 1.00 22.34 0.56308 9.84 9.484


16 5.60 32.81 28.23 25.40 1.049 44.14 ET 7.00 0.000
SCHED 40 WET STEEL 120 16.38 0 16.84 9.484

16 5.60 32.81 28.23 25.40 1.25 28.23 0.36938 9.84 6.960


17 5.60 32.81 31.86 32.36 1.380 72.33 ET 9.00 0.000
SCHED 40 WET STEEL 120 15.52 0 18.84 6.960

17 5.60 32.81 31.86 32.36 1.50 31.86 0.34224 9.84 7.476


18 5.60 32.81 35.35 39.84 1.610 104.15 ET 12.00 0.000
SCHED 40 WET STEEL 120 16.41 0 21.84 7.476

8 0.00 32.81 0.00 54.68 3.00 0.00 0.26587 28.22 9.363


19 0.00 32.81 0.00 64.04 3.068 495.99 E 7.00 0.000
SCHED 40 WET STEEL 120 21.53 0 35.22 9.363

19 0.00 32.81 0.00 64.04 4.00 0.00 0.07078 111.55 10.727


20 0.00 32.81 0.00 74.77 4.026 495.99 4E 40.00 0.000
SCHED 40 WET STEEL 120 12.50 0 151.55 10.727

20 0.00 32.81 0.00 74.77 6.00 0.00 0.00962 75.46 1.063


21 0.00 32.81 0.00 75.83 6.065 495.99 GC 35.00 0.000
SCHED 40 WET STEEL 120 5.51 0 110.46 1.063

21 0.00 32.81 0.00 75.83 6.00 0.00 0.00962 29.53 0.861


22 0.00 0.00 0.00 90.90 6.065 495.99 2T 60.00 14.206
SCHED 40 WET STEEL 120 5.51 0 89.53 15.067

22 0.00 0.00 0.00 90.90 6.00 0.00 0.00962 9.84 0.431


23 0.00 0.00 0.00 91.33 6.065 495.99 GC 35.00 0.000
SCHED 40 WET STEEL 120 5.51 0 44.84 0.431

5 5.60 32.81 32.60 33.88 1.50 32.60 0.50607 9.84 9.030


30 0.00 32.81 0.00 42.91 1.610 128.67 T 8.00 0.000
SCHED 40 WET STEEL 120 20.28 0 17.84 9.030

13 5.60 32.81 32.56 33.80 1.50 32.56 0.50057 9.84 10.934


40 0.00 32.81 0.00 44.73 1.610 127.91 ET 12.00 0.000
SCHED 40 WET STEEL 120 20.16 0 21.84 10.934

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 10

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

18 5.60 32.81 35.35 39.84 1.50 35.35 0.58715 9.84 10.476


50 0.00 32.81 0.00 50.32 1.610 139.43 T 8.00 0.000
SCHED 40 WET STEEL 120 21.97 0 17.84 10.476

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 11

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) Area (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

1 5.60 32.81 12.62 130.00 0.153 19.89


Sub Totals For Non-Group 130.00 0.153 19.89

2 5.60 32.81 14.15 130.00 0.162 21.06


Sub Totals For Non-Group 130.00 0.162 21.06

3 5.60 32.81 21.42 130.00 0.199 25.92


Sub Totals For Non-Group 130.00 0.199 25.92

4 5.60 32.81 27.43 130.00 0.226 29.33


Sub Totals For Non-Group 130.00 0.226 29.33

5 5.60 32.81 33.88 130.00 0.251 32.60


Sub Totals For Non-Group 130.00 0.251 32.60

9 5.60 32.81 12.13 130.00 0.150 19.50


Sub Totals For Non-Group 130.00 0.150 19.50

10 5.60 32.81 13.60 130.00 0.159 20.65


Sub Totals For Non-Group 130.00 0.159 20.65

11 5.60 32.81 21.55 130.00 0.200 26.00


Sub Totals For Non-Group 130.00 0.200 26.00

12 5.60 32.81 27.44 130.00 0.226 29.34


Sub Totals For Non-Group 130.00 0.226 29.34

13 5.60 32.81 33.80 130.00 0.250 32.56


Sub Totals For Non-Group 130.00 0.250 32.56

14 5.60 32.81 15.16 130.00 0.168 21.81


Sub Totals For Non-Group 130.00 0.168 21.81

15 5.60 32.81 15.92 130.00 0.172 22.34


Sub Totals For Non-Group 130.00 0.172 22.34

16 5.60 32.81 25.40 130.00 0.217 28.23


Sub Totals For Non-Group 130.00 0.217 28.23

17 5.60 32.81 32.36 130.00 0.245 31.86


Sub Totals For Non-Group 130.00 0.245 31.86

18 5.60 32.81 39.84 130.00 0.272 35.35


Sub Totals For Non-Group 130.00 0.272 35.35

Totals For All Groups 1950.00 0.203 396.42

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 12

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 9
HMD Actual Residual Pressure: 12.13 psi
HMD Actual Flow: 19.50 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.264 gpm/ft²
Application Average Area Per Sprinkler: 100.00 ft²
Sprinkler Flow: 396.42 gpm
Average Sprinkler Flow: 26.43 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 18 - 50 ) 21.97 ft/sec
Maximum Velocity Pressure ( In Pipe 18 - 50 ) 3.25 psi

Allowable Maximum Nodal Pressure Imbalance: 0.1000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0934 psi
Actual Average Nodal Pressure Imbalance: 0.0326 psi
Actual Maximum Nodal Flow Imbalance: 0.0659 gpm
Actual Average Nodal Flow Imbalance: 0.0167 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 25
Number Of Flowing Sprinklers: 15

Pipe System Water Volume: 286.43 gal

Sprinkler Flow: 396.42 gpm


Non-Sprinkler Flow: 100.00 gpm

Minimum Required Residual Pressure At System Inflow


91.33 psi
Node:
Demand Flow At System Inflow Node: 495.99 gpm

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Fitness Time-Souq 7
Hell Page 13

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100
91
90

80

70
Pressure psi

60

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 91.33 psi
Calculated Flow Rate: 495.99 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 14.21 psi

C:\ ...\Souq 7.fiw Thursday, September 7, 2023, 3:28 AM


Ø2
mm 6 "
00
40 46
00
mm 30Ø
1.5 5
30 "
" 00
Ø3 mm
Ø1
.5"
mm 4
00
40 30
7 00
m Ø1
20 m .25
40 " 3
"
m Ø3
00
0m 13 30
00
Ø1
23 " "
Ø6
mm
34
2
000
Ø4 mm
m 8
21 0m 12 Ø1
Ø6"
" 860 50 30
00 "
mm
9000

22
3" 1
GV
CV

Ø 18 11
~
23
FIRE PUMP 30
00
mm
17 10
19

16
9

15

14

You might also like