Professional Documents
Culture Documents
A Design Guide For Performance Assessment of Solar Light-Pipes 2002
A Design Guide For Performance Assessment of Solar Light-Pipes 2002
149–169
are schematically shown in Figure 1. A light- designed diffusers are used to improve the day-
pipe system has mainly three parts, namely a light performance of light-pipes even further.
clear dome, one or several connected tubes,
possibly incorporating bends and a diffuser. The 3. The design of a light-pipe system
clear dome, usually mounted on the outside of
the roof gathers sky light and sunlight. Produced A precise design of a light-pipe system is only
from clear polycarbonate material, the dome is possible via a thorough understanding of the illu-
designed to remove undesirable ultra violet (UV) minance transmittance of the system. Light-pipes
light and can seal the light-pipe against the are designed to collect light from both the sky
ingress of dust, rain and snow. The dome meets and the sun. The two components of daylight
®re resistance requirements and due to its shape illuminance are collected by the hemisphere
is self-cleaning. shaped dome, followed by multiple re¯ection of
The second part of light-pipe system consists sunlight and skylight through the re¯ecting tube.
of one or several connected light-re¯ecting Daylight then reaches the inner surface of the
tubes. The internal surface of the light-re¯ecting light-pipe diffuser wherein a refraction followed
tube is coated with a highly re¯ective mirror ®n- by a light-scattering takes place before it is intro-
ish material (typically with a re¯ectance in duced within buildings.
excess of 0.95) that helps to achieve a high trans- Since the external environmental factors such
mittance. The light-re¯ecting tube is adaptable to as sky clarity, sky-diffuse radiance distribution
incorporate any bends around structural building and sun’s position change dynamically, the light-
components as shown in Figure 1(b). Daylight pipe’s overall ef®ciency of illuminance trans-
gathered by the dome at roof level is then trans- mission also changes continuously.
mitted downwards via the mirrored tubes and The determination of light-pipe system con-
reaches the third part of light-pipe system, the ®guration aimed at achieving a given internal
diffuser. illuminance under given sky conditions would
The diffuser takes the form of a white poly- be the task of a light-pipe designer. It may be
carbonate ¯at or opal dome installed on the ceil- logical to assume that a light-pipe system’s illu-
ing in the room to be illuminated. The convex minance performance would depend on: (a) geo-
shape of the dome allows the light to be evenly metrical factors such as its length, diameter,
diffused into the space below. Recently, new number of bends, angle of bend and the diffuser
types of diffuser have been made available type, and (b) the above mentioned external
including a crystal effect surface ®nish with environmental factors. Thus, a mathematical
either ¯at or recessed ends. These newly model that encompasses the above factors would
be desirable.
the given point P(x,y,z), Eexternal is the total external seal the inside space from ingress of daylight.
illuminance and DPF(x,y,z) is the light-pipe Day- Sophisticated data-logging equipment inside the
light Penetration Factor for the given point. room was protected from the effects of weather.
Light-pipes are daylighting devices that utilize The room was equipped with power supply unit
both sunlight and skylight. It has been reported to support a PC, data-logger and multiple indoor
that the sun’s position has an effect on the light- illuminance sensors.
pipe’s performance.5 When the sky is clear, the
solar altitude a s in¯uences the transmittance of 5.2 Light-pipes
sunlight within the light-pipes. However, when To enable the performance comparison
the sky is overcast or part-overcast, the in¯uence between different light-pipes, the test room was
of the sun’s position becomes weaker since sun- designed for ease of installation of light-pipes
light may no longer be the major component of with various designs. Initially, a total of eight
external global illuminance. Hence in the present light-pipes with varied con®gurations (straight
context the transmittance of light-pipes is con- runs plus those with multiple bends) were sup-
sidered to be a function of a s and the sky clear- plied by the project co-sponsor. The diameters
ness index kt (de®ned as the ratio of global to of these light-pipes were 210 mm, 330 mm,
the extra-terrestrial irradiance). Based on the 420 mm and 530 mm. All the light-pipes use
performance modelling of a straight light-pipe,4 clear polycarbonate domes, 610 mm long sil-
Zhang and Muneer have given the formulation verized aluminium tubes and opal polycarbon-
de®ned by Equation (2): ated diffusers.
DPF(x,y,z) 5 (a0 1 a1 a s 1 a2 a s
2
5.3 Sensors and data-logger
1 a3 kt 1 a4 kt2 1 a5 a s kt) / D2 (2) One Kipp and Zonen CM11 global
pyranometer sensor was ®xed on the roof of the
where D is the distance from light-pipe diffuser test room. The pyranometer was calibrated by
centre to a given position P(x,y,z). Equation (2) is the UK Meteorological Of®ce in November
only applicable for straight light-pipes and there- 1999 and its desiccant charge was renewed just
fore cannot be used as a general design tool for before the commencement of the measurement.
pipes of other con®gurations i.e., pipes with A further calibration check was performed in
bends. A generalized performance model that August 2001. A permanent shielded output sig-
covers light-pipes of all typical con®gurations nal cable was included and was routed into the
ought to take account of environmental as well test room and connected to a Grant’s Squirrel
as geometrical factors. 1200 Series data-logger.
Three indoor illuminance sensors supplied by
5. Experimental set-up Megatron Ltd of Watford, UK were employed
to record the internal illuminance produced by
5.1 The Craighouse test room the light-pipes. The actual sensing element was a
A purpose built test facility was established selenium photoelectric Cell Type M black resin
within the Craighouse campus of Napier Univer- potted, 42 mm diameter 3 20 mm high with
sity. Within the open grounds the test room was integral cable. This type of cell converts the
located on ¯at ground with an open southern energy from the light falling onto it directly into
aspect. electrical energy, which when converted into a
The test room was 3.0 m long 3 2.4 m wide signal is transmitted along the cable to the Squir-
with a height of 2.5 m. Inside the test room all rel data-logger.
four sides and the roof had hardboard cladding To enable the measurement of internal illum-
nailed to the frame. All edges and the door sur- inance achieved by various light-pipes with
rounds were covered with heavy paper tape to bends, one stand on which photoelectric sensors
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 153
could be mounted was used. The use of the Table 1 Designs of light-pipes that were monitored
adjustable stand ensured that photoelectric sen- Design Diameter, mm Type Length, Bends
sors measured the illuminance emitted from the mm number
light-pipe diffuser on a plane parallel to the cross
section of the light-pipe diffuser. The adjustable 1 210 straight 60 N/A
2 210 straight 120 N/A
stand consisted of two components, a commonly 3 210 elbowed 60 1
available photographer’s tripod and a table. The 4 210 elbowed 60 2
¯exibility offered by the tripod made the slope 5 330 straight 60 N/A
6 330 straight 120 N/A
and the distance of the plane where illuminance 7 330 elbowed 60 1
sensors were mounted adjustable. The table was 8 330 elbowed 60 2
manufactured from a piece of high-density poly- 9 330 elbowed 60 3
10 330 elbowed 60 4
styrene 25 mm thick, 1 m wide and 1.5 m long. 11 420 straight 120 N/A
Prior to use, the table was painted with a matt 12 420 straight 60 N/A
black ®nish to eliminate any light re¯ection into 13 530 straight 60 N/A
14 530 straight 120 N/A
areas within the sensors’ range. 15 530 elbowed 60 1
Daylight penetration factor (DPF) for a ¯at dif- mulation that includes 12 coef®cients (a0 ± a10
fuser were calculated for all data points. Using the and m) is given by Equation (3):
DPF model (Equation 2), the corresponding DPF
that can be achieved by an opal diffuser under the S2 DPF(x,y,z) 5 (a0 1 a1kt 1 a2a s 1 a3kta s
same a s and kt were calculated to enable a per-
formance comparison. Figure 2 shows the com- 1 ak 2
4 ta s 1 a5kta 2
s 1 ak 2 2
6 ta s )
parisons of the estimated internal illuminances due r (a7 1 a8 Ap 1 a9 cot a s 1 a1 0 Ap cot a
R2(H/D)m / D2
s)
Figure 2 Comparison between external and internal illuminance due to different diffusers
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 155
Table 2 Coef cients used in Equations (3–7)
Models a0 a1 a2 a3 a4 a5 a6 a7 a8 a9 a1 0
Equation (3) 356.7 2 572.4 2 1.2 2 10.2 42.8 0.5 2 0.9 137.7 3.5 2 0.5 0.5
Equation (4)a 62.5 2 17.2 2.6 136.0 4.3 1.1 2 0.4
Equation (5) 305.0 2 190.5 2 2.9 2 5.3 2 5.8 0.2 0.2 133.8 4.0 7.1 2 2.1
Equation (6)b 192.5 2 108.8 2 0.3 132.4 4.4 8.6 2 2.6
Equation (7) 356.7 2 572.4 2 1.2 2 10.2 42.8 0.5 2 0.9 137.7 3.5 2 0.5 0.5
a
Equation (4) is the simpli ed model of Equation (3)
b
Equation (6) is the simpli ed model of Equation (5)
inclusion of a s and kt and D2 terms has already sity, the number of re¯ections required is pro-
been discussed with reference to Equation (2). portional to Ap and cota s. Therefore, a linear
What now follows is a justi®cation of the function that combines Ap and cota s has been
remainder of the terms included within Equation presently employed to account for the number of
(3). As a daylight re¯ecting device, the light- inter-re¯ections occurring within the light-pipe.
pipe’s transmission is affected by the re¯ectance This explains the second factor in Equation (3),
of its interior coating material. Based on physical namely r (a7 1 a8 Ap 1 a9 cot a s 1 a1 0 Ap cot a s ).
reasoning presented in Section 3, it is possible A consideration of the manner of the spread
to show that a light-pipe’s transmittance is a of daylight by light-pipe diffusers within interior
function of the number of re¯ections required for spaces led to the adoption of the last factor in
a ray of light to descend the pipe and its re¯ec- Equation (3) i.e., (H/D)m/D2, where 1 # m # 2.
tance (Figure 3). The higher the re¯ectance of For a given point in space, to obtain its illumin-
the pipe’s interior surface (r ), the higher the ance resulting from a point or ®nite light source,
light-pipe’s daylight transmittance. Edmonds et the inverse square law and the cosine law must
al.5 reported that for sunlight of any given inten- hold. However, if a light-pipe diffuser is to be
considered as a point light source, the cosine law
should be applied only once, hence m 5 1; while
on the other hand, if the diffuser could be treated
as a ®nite light source, then the cosine law must
be applied twice, once for the emanation of light
and the other for its incidence (or projection) on
the horizontal plane. This requires m to be equal
to 2. Thus a compromise was achieved by using
a variable m. The `1/D2’ term embodies the
application of the inverse square law.
Using the above-mentioned measured Craig-
house data set, Equation (3) was ®tted. Good
agreement between the measured data and calcu-
lated values was obtained and in this respect Figure
4 shows the scatter plot of the predicted internal
illuminance against measured data. The trend line
was found to have a slope of 0.98 and the coef-
®cient of determination was noted to be 0.95.
Model validation was also undertaken by esti-
Figure 3 Light entering a light-pipe descends via a series mation of the Mean Bias Error (MBE), the Root
of inter-re ections Mean Square Error (RMSE) and the Percentage
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
156 A design guide for performance assessment of solar light-pipes
Figure 4 Scatter plot of calculated due to Equation 3 (y-axis) against measured internal illuminance (x-axis) for straight
light-pipes (units 5 lux)
!
S (Eestimated 2 Emeasured) 2
5 Values for the coef®cients used in Equation (4)
no. of data points
a
Maxm ea s ure d : The maximum value of measured internal illuminance due to light-pipes, lux
b
Meanm ea s ure d : The mean value of measured internal illuminance due to light-pipes, lux
c
Equation (4): the simpli ed model of Equation (3)
d
Equation (6): the simpli ed model of Equation (5)
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 157
Figure 5 Scatter plot of calculated due to Equation (5) (y-axis) against measured internal illuminance (x-axis) for
elbowed light-pipes (units 5 lux)
Figure 6 Scatter plot of calculated due to Equation (7) (y-axis) against measured internal illuminance (x-axis) for
straight light-pipes (units 5 lux)
are listed in Table 2. Calculated internal illumin- factor (floss) within Equation (5). Lb and flen are
ance based on the procedure using Equation (4) subsumed within a modi®ed expression for Ape.
were plotted and regressed against correspond- The factor (1-floss)N used in Equation (5)
ing measured data. The slope of the best-®t trend accounts for the overall transmittance ef®ciency
line is 0.98, and the coef®cient of determination of the N bend(s),
R2 is 0.95. The MBE, RMSE and PAD for the E2 DPF(x,y,z) 5
simpli®ed S-DPF model were found to be ±3 lux,
29 lux and 13% respectively (Table 3). (a0 1 a1kt 1 a2a s 1 a3kta s
1 ak 2
4 ta s 1 ak 2
5 ta s 1 ak 2 2
6 ta s )
7.2 Elbowed light-pipe DPF model (E-DPF)
To predict the DPF(x,y,z) of elbowed light-pipe r (a7 1 a8 Ap 1 a9 cot a s 1 a1 0 Ap cot a s )
R2(1 2
systems (30-degree bends), the energy loss due
to each bend has to be considered. The length floss)N (H/D)m/D2 (5)
of each bend (Lb) and the number of bends (N) where Ape 5 (L 1 flenLb) / 2R and L is the length
have been accounted for by the use of an of straight light-pipe, flen the equivalent-length
equivalent-length factor (flen) and the energy-loss factor, Lb the sum of the linear lengths of all
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
158 A design guide for performance assessment of solar light-pipes
bends and R the radius of light-pipe. floss is the The MBE was found to be -2 lux. The RMSE
energy-loss factor for each 30-degree bend, most was 23 lux which was 2% of the maximum illu-
commonly used in a light-pipe system. Values minance (931 lux) and 22% of the mean illumin-
for the coef®cients used in Equation (5) are ance (103 lux). The PAD of the estimated
listed in Table 2. internal illuminance was found to be 25%. A
Using an optimization procedure, regressed scatter plot of the calculated against measured
coef®cients in Equation (5) were determined. internal illuminance is shown in Figure 5. The
The `best’ value for flen was found to be 0.65 slope of the trend line was found to be 0.97 and
and the value for floss was found to be 0.2, which the coef®cient of determination was noted as
is in good agreement with Carter’s study.7 0.97.
The performance of the E-DPF model was Equation 5 was further simpli®ed and the sim-
then evaluated using MBE, RMSE and PAD. pli®ed E-DPF is given below:
Figure 7 DPF for 420mm-diameter light-pipe as a function of a s and kt , (a) for a straight light-pipe and (b) for a light-
pipe with two bends (D 5 H 5 1.2 m)
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 159
Figure 8 Effect of aspect ratio on DPF, (a) for a straight light-pipe and (b) for a light-pipe with one bend (420mm-
diameter, D 5 H 5 1.2 m)
E2 DPF(x,y,z) 5 (a0 1 a1kt 1 a2a s)´ the coef®cient of determination was noted as
0.97. Results are shown in Table 3.
r (a3 1 a4 Ap 1 a5 cot a s 1 a6 Ap e cota s )
R (1 2
2
Figure 9 Comparison of the predicted DPFs for straight light-pipe and elbowed light-pipes with one, two, three and
four bends (530 mm-diameter, a s 5 45°, D 5 1.2 m, H 5 1 m)
istics, another approach, namely the `radiative Using the Craighouse test room database for
view factors’ method has been applied to enable all straight light-pipes, the view factor F v(x,y,z)
a performance comparison between the two dif- for each data point has been calculated and the
ferent approaches. value of the coef®cients in Equation (7) have
The view factor between any two surfaces is been re-®tted. Figure 6 shows the scatter plot
de®ned as that fraction of the radiative energy of the estimated internal illuminances due to
leaving an emitting surface that is intercepted by the proposed V-DPF model against the meas-
the receiving surface. The proposed view factor ured data. The RMSE and MBE for the pro-
model V-DPF of a straight light-pipe is shown posed V-DPF model were found to be 52 lux
in Equation (7), where Fv(x,y,z) is the view factor and -9 lux, corresponding to 27 lux and -1 lux
between the ceiling mounted light diffuser and for the proposed S-DPF model (Equation 3).
the given point P(x,y,z). The slope of the trend line for a plot of calcu-
lated versus measured data was found to be
V2 DPF(x,y,z) 5 (a0 1 a1kt 1 a2a s
0.94 and the coef®cient of determination was
1 a3kta s 1 ak 2
4 ta s 1 ak 2
5 ta s 0.86. The corresponding ®gures for the pro-
posed S-DPF model (Equation 3) were 0.98
1 ak 2 2
6 ta s )r (a7 1 a8 Ap 1 a9 cot a s 1 a1 0 Ap cot a s)
´
and 0.95. Results are shown in Table 3.
R2Fv(x,y,z) (7)
The method for calculating the view factors from 8. Parametric analysis
differential areas to spherical segments is given
by Naraghi.8 For the sake of completeness the A number of environmental and geometrical fac-
entire formulation is provided in Appendix I. tors have been identi®ed that in¯uence the day-
However, only case numbers III and V are of light transmission of light-pipes. In this section a
interest within the present context. parametric analysis of those factors is presented.
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 161
Table 4 Light-pipe design guideline for mid-summer for Kew, UK (Time 5 10 am, 1 July, Height of diffuser to the
working plane 5 2 m)
600 mm Clearb 140 100 50 425 295 140 740 515 245 1250 870 415
Part-overcastc 80 60 30 245 170 85 430 300 145 725 505 240
Overcastd 45 30 15 125 90 45 220 155 75 370 260 125
1200 mm Clear 80 55 30 295 205 100 555 385 185 995 695 330
Part-overcast 45 35 15 170 120 60 320 225 110 575 400 190
Overcast 25 20 10 90 60 30 165 115 55 295 205 100
1800 mm Clear 45 30 15 205 140 70 415 290 140 790 550 265
Part-overcast 25 20 10 120 85 40 240 170 80 460 320 155
Overcast 15 10 5 60 45 20 125 85 40 235 165 80
2400 mm Clear 25 20 10 140 100 50 310 220 105 630 440 210
Part-overcast 15 10 5 80 60 30 180 125 60 365 255 120
Overcast 10 5 5 45 30 15 95 65 30 185 130 65
3000 mm Clear 15 10 5 100 70 35 235 165 80 500 350 165
Part-overcast 10 5 5 60 40 20 135 95 45 290 205 100
Overcast 5 5 5 30 20 10 70 50 25 150 105 50
3600 mm Clear 10 5 5 70 50 25 175 125 60 400 280 135
Part-overcast 5 5 5 40 30 15 100 70 35 230 160 80
Overcast 5 5 5 20 15 10 55 40 20 120 85 40
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
162 A design guide for performance assessment of solar light-pipes
Table 5 Light-pipe design guideline for winter for Kew, UK (Time 5 10 am, 1 February, Height of diffuser to the
working plane 5 2 m)
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest.
fuser is proportional to (H/D)1.3 and inversely straight light-pipe with an increasing number
proportional to D2. of bends.
600 mm Clearb 95 70 35 295 205 100 515 360 175 875 610 290
Part-overcastc 55 40 20 160 110 55 280 195 95 470 330 160
Overcastd 30 20 10 85 60 30 150 105 50 255 180 85
1200 mm Clear 55 40 20 200 140 70 380 265 130 690 480 230
Part-overcast 30 20 10 110 75 40 205 145 70 370 260 125
Overcast 15 15 5 60 45 20 115 80 40 205 140 70
1800 mm Clear 30 20 10 140 95 45 285 200 95 540 380 180
Part-overcast 15 15 5 75 55 25 155 110 50 295 205 100
Overcast 10 10 5 40 30 15 85 60 30 160 110 55
2400 mm Clear 20 15 5 95 65 35 210 145 70 425 300 145
Part-overcast 10 10 5 50 35 20 115 80 40 230 160 80
Overcast 5 5 5 30 20 10 65 45 20 125 90 45
3000 mm Clear 10 10 5 65 45 25 155 110 55 335 235 115
Part-overcast 5 5 5 35 25 15 85 60 30 180 130 60
Overcast 5 5 5 20 15 10 45 35 15 100 70 35
3600 mm Clear 5 5 5 45 30 15 115 80 40 265 185 90
Part-overcast 5 5 5 25 20 10 65 45 20 145 100 50
Overcast 5 5 5 15 10 5 35 25 15 80 55 30
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest.
and (6), the internal illuminances that can be ing the inter-re¯ection of diffuse as well as beam
achieved by a ¯at diffuser ®tted light-pipe can illuminance within rooms and also bearing in
be determined. Further work would however be mind the fact that light-pipes are primarily pro-
required for a more precise assessment of the viders of diffuse illuminance, the internal re¯ec-
latter diffuser which has only recently been tion characteristics of light-pipes were treated as
introduced in the market. being of similar order as windows. Therefore,
for the Craighouse test room, the contribution of
8.6 Effect of internal re¯ection internal-re¯ected illuminance to the total illum-
The internal surfaces (ceiling, roof and ¯oor) inance that is received at survey points can be
of the Craighouse test room were painted white qualitatively assessed by comparing it to that of
which has a high re¯ectance, the assessment of a window operating under similar conditions.
the contribution of internal re¯ected illuminance The surface re¯ectance of the test room has
is therefore necessary to enable an assessment been matched using the CIBSE Lighting Guide9
of the contribution of internal re¯ection on DPF. and was found to be 0.74. By abbreviated analy-
In the absence of any other information regard- sis, the contribution of internal re¯ection to the
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
164 A design guide for performance assessment of solar light-pipes
Table 7 Light-pipe design guideline for mid-summer for Kew, UK (Time 5 mid-noon, 1 July, Height of diffuser to the
working plane 5 2 m)
600 mm Clearb 160 110 55 475 330 160 830 580 275 1395 975 465
Part-overcastc 110 75 40 330 230 110 570 400 190 965 675 320
Overcastd 55 40 20 160 110 55 275 195 95 465 325 155
1200 mm Clear 90 65 30 335 235 110 625 440 210 1120 780 375
Part-overcast 65 45 20 230 160 80 435 305 145 775 540 260
Overcast 30 25 10 110 80 40 210 145 70 375 260 125
1800 mm Clear 55 40 20 235 165 80 475 330 160 895 625 300
Part-overcast 35 25 15 160 115 55 330 230 110 620 435 205
Overcast 20 15 10 80 55 30 160 110 55 300 210 100
2400 mm Clear 30 20 10 165 115 55 360 250 120 720 505 240
Part-overcast 20 15 10 115 80 40 250 175 85 495 350 165
Overcast 10 10 5 55 40 20 120 85 40 240 170 80
3000 mm Clear 20 15 10 115 80 40 270 190 90 575 405 195
Part-overcast 15 10 5 80 55 30 190 130 65 400 280 135
Overcast 10 5 5 40 30 15 90 65 30 195 135 65
3600 mm Clear 10 10 5 80 60 30 205 145 70 465 325 155
Part-overcast 10 5 5 55 40 20 145 100 50 320 225 110
Overcast 5 5 5 30 20 10 70 50 25 155 110 55
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest.
light-pipe DPF of largest diameter (0.53 m) engineering design, Tables 4±9 provide the
light-pipe was obtained as only 5% of the total internal illuminances at various distances that
DPF using the chart given by Muneer.10 can be achieved by opal diffuser light-pipes of
Presently undertaken analysis shows that the varying geometrical con®gurations operating
maximum contribution of internal re¯ection to under a set of three weather conditions for Kew,
the total internal illuminance measured on each London.11 The Tables also cover a set of three
survey point in the Craighouse test room will seasonal variations: summer, winter, and autumn
not exceed the level of 5%. In summary, for the and spring together.
present DPF model, the effect of internal re¯ec- Based on E-DPF (Equation 5), it has been
tion is of a low order. found that light-pipe’s daylight transmission
reduction factor due to the use of one 30-degree
9. Light-pipe design guidelines bend is around 0.2. This factor can be used as a
simple guideline for elbowed light-pipe design.
The proposed model S-DPF (Equation 3) enables It has also been noted that the ef®ciency loss due
the prediction of the internal illuminances that to the introduction of bends is a function of solar
are achievable by opal diffuser light-pipes of altitude, which means that for different weather
various con®gurations and under different sky conditions and different times of the year, the
conditions. As a set of guidelines for practical actual transmission reduction factor differs. The
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 165
Table 8 Light-pipe design guideline for winter for Kew, UK (Time 5 mid-noon, 1 February, Height of diffuser to the
working plane 5 2 m)
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest.
600 mm Clearb 115 80 40 355 245 120 620 430 205 1045 730 350
Part-overcastc 65 45 25 200 140 65 345 240 115 585 410 195
Overcastd 35 25 15 105 75 35 180 125 60 305 215 105
1200 mm Clear 65 45 25 245 170 80 460 325 155 830 580 275
Part-overcast 40 25 15 135 95 45 260 180 85 465 325 155
Overcast 20 15 10 70 50 25 135 95 45 240 170 80
1800 mm Clear 35 25 15 170 120 55 345 240 115 655 460 220
Part-overcast 20 15 10 95 65 35 195 135 65 365 255 125
Overcast 10 10 5 50 35 20 100 70 35 190 135 65
2400 mm Clear 20 15 10 115 80 40 255 180 85 520 365 175
Part-overcast 15 10 5 65 45 25 145 100 50 290 205 100
Overcast 10 5 5 35 25 15 75 55 25 150 105 50
3000 mm Clear 15 10 5 80 55 30 190 135 65 415 290 140
Part-overcast 10 5 5 45 35 15 110 75 35 230 160 80
Overcast 5 5 5 25 20 10 55 40 20 120 85 40
3600 mm Clear 10 5 5 55 40 20 145 100 50 325 230 110
Part-overcast 5 5 5 30 25 10 80 55 30 185 130 60
Overcast 5 5 5 20 15 5 45 30 15 95 70 35
da 5 the distance between the projection of the diffuser centre on the working plane and the point of interest.
proposed models. The slope of the scatter plot conditions due to sensitivity related problems of
of the internal illuminances calculated by S-DPF sensors the errors would be larger.
(Equation 3) model plotted against the measured The effects of geometrical and environmental
data was noted to be 0.98 and the coef®cient factors on the daylighting performance of light-
of determination (R2) was 0.95. The Root Mean pipes are analysed. Based on the above two DPF
Square Error (RMSE) and Mean Bias Error models, practical guidelines for light-pipe engin-
(MBE) for S-DPF model were found to be 27 eering design are put forward. Tables that pro-
lux and -1 lux. The corresponding ®gures of the vide the internal illuminance that are achievable
slope for the scatter plot, R2-value, RMSE and by light-pipes at any given point on the working
MBE for E-DPF (Equation 5) model were 0.97, plane under varying weather conditions are
0.97, 23 lux and -2 lux. It is worth mentioning presented.
that the model errors are low under clear-sky The S-DPF and E-DPF models are inherently
conditions when the possible energy savings are statistical in nature. Hence their application is
the largest. However, under low illuminance limited to the respective input dataset. As such
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
X Zhang, T Muneer and J Kubie 167
the lumen output calculation of light-pipes up to Appendix A: The view factor between a
2 m in length and solar altitude up to 60° (mid- plane element and a spherical sector
summer sun position for southern England) can
be treated with con®dence. Further measurement
work is underway with longer pipes.
Acknowledgements
11. References
H S D
3 Oakley G, Riffat SB, Shao L. Daylight 1 12 LH
5 cos2
performance of lightpipes. Solar Energy 2000.
1
FdA12
Î
A2
2p
D 12 L2
4 Zhang X, Muneer T. A mathematical model for
2(1 2 2L 2 2 D2 2 H2 1 2HL)
the performance of light-pipes. Lighting Res. 1
S! Î Î
D
5 Edmonds IR, Moore GI, Smith GB, Swift PD. (1 1 D2 1 H2 2 2HL 1 2D 1 2 L 2)(D 1 2 L2 2 11 LH)
Daylighting enhancement with light-pipes 3 tan2 1
(1 1 D2 1 H2 2 2HL 2 2D 1 2 Î L 2) (D 1 2 Î L2 1 12 LH)
coupled to laser-cut light-de¯ecting panels.
Lighting Res. Technol. 1995; 27: 27±35. Î D2 2 11 2HL 2 (D2 1 H 2)L2 2 Î D2 2 11 2H 2 2 (D2 1 H 2)H2
1 2
6 Muneer T, Abodahab N, Weir G, Kubie J. D2 1 H2
H2 1
H2
(D2 2
(D2 1
1) (D2 1
H 2)L
H 2)
D
SÎ DG SÎ DJ
Press, 2000.
H(1 2 D2 2 H 2) 12 H2
7 Carter DJ. The measured and predicted 2 sin2 1
1 2sin 2 1
D
H2 1 (D2 2 1) (D 2 1 H 2)
performance of passive solar light pipe systems.
Lighting Res. Technol. 2001; 33. II: D ,
12 LH
and 2 1 , H, L:
8 Naraghi MHN. Engineering Notes. American Î 12 L2
H Î
Institution of Aeronautics and Astronautics,
!
1 1 2 H2 D2 1 H2 2 1)(1 2 H 2)
1987. FdA12 5 tan2 1
2
A2
p D2 1 H2 2 1 D2 1 H2
S DJ
9 The Society of Light and Lighting. CIBSE
H H D2 1 Î H2 2 1
Lighting Guide 11: Surface re¯ectance and 2 3
cos2 1
D
(D2 1 2
H )
colour. London: The Society of Light and 2
12
Lighting, 2001. III: when L . 0D.
LH
and H , 2 1
10 Muneer T. Solar radiation and daylight models Î 12 L2
Downloaded from lrt.sagepub.com at HOWARD UNIV UNDERGRAD LIBRARY on February 20, 2015
168 A design guide for performance assessment of solar light-pipes
FdA12 A2 5
1
2p H cos2 1
S 12
Î
D 12
LH
L2
D 1
Î (1 1
2(1 2
D2 1
2L 2 2
H2 2
D2 2
2HL)2 2
H2 1
4D2(1 2
2HL)
L 2)
photometric speci®cation from which other
measures could be derived.
tan2 1
S! (1 1 D2 1 H2 2 2HL 1 Î
2D 1 2
Î
L2)(D 1 2 Î
Î
L2 2 11 LH)
D 2) The ratio of ¯ux output to ¯ux entering: the
(1 1 D 1
2
H 2 2
2HL 2 2D 1 2 L )(D 1 2
2
L 1 2
12 LH) ef®ciency of the device.
Î D2 2 11 2HL 2 (D 2 1 H 2)L2 H 3) The ratios of the illuminance received on
1 2 1 2
D2 1 H2 (D2 1
3
given surfaces from the device to the lumin-
H 2 )2
cos2 1
SÎ H2 1
H2 (D2 1
(D 2 2
H 2)L
1)(D 2 1 H 2)
DJ ance of sky patches: Daylight Coef®cients.
4) The ratios of the received illuminances to the
IV: when L . 0D,
12 LH
and H , 2 1
external horizontal illuminance: the proposed
Î 12 L2 Daylight Penetration Factors for light-pipes,
when L , 0D,
12 LH
and
1
, H, 2 1
analogous with the Daylight Factor for con-
Î 12 L2
L
ventional windows.
H
FdA12 A
z
5 2 3
(D2 1 H 2 )2
V: when D ,
LH 2 1
and H ,
1 Authors’ response to Professor PR
Î
H J
L
1
1 2 L2
1 2 2L2 2 D 2 2 H 2 1 2HL
Tregenza
5 11
FdA12 A2
2p
Î (1 1 D2 1 H2 2 2HL) 2 2 4D2(1 2 L 2)
X Zhang, T Muneer and J Kubie