HB-B150I
Automatic simple sealing swing door
SWING-TYPE
AUTOMATIC
ST. STEEL
SIMPLY SEALING
HB-B150I
1.
Introduction
Type of Panel
Available motors Stainless
HPL Glazing
steel
- NEXT 150 automation for swing doors, motorized opening and closing,
for a leaf with maximum width of 1200 mm.
- Maximum weight for each leaf: 150 kg (up to 1000 mm)
- Automation dimensions (H x P x L) 60x75x420 mm ✓ ✓ ✓
- Suitable for environments where the filtered air pressure introduced by
ventilation systems does not exceed 15Pa.
Basic Components (included)
Aluminium cover in natural anodized-silver colour ✓ ✓ ✓
Aluminium support base ✓ ✓ ✓
Grey ABS side caps ✓ ✓ ✓
Brushless motor with built-in encoder, featuring high performance, low
wear, low power consumption ✓ ✓ ✓
Pull or push arm ✓ ✓ ✓
Leaf panel complete with dedicated frames and gaskets ✓ ✓ X
Leaf complete with profiles, 44.2 glazing, and dedicated gaskets X X ✓
Digital selector and safety sensors ✓ ✓ ✓
2.
AUTOMATIONS
Operation description
Doors intended for operating rooms, laboratories, The aluminium profiles of the fixing plate, cover and
clinics, and highly aseptic environments in general, for sliding guide are made of extruded EN AW-6060
intensive use and delta pressure not exceeding 15 Pa. aluminium alloy, in accordance with the EN 573-1
Tightness is provided by expanded EPDM gaskets Standard, with T6 finishing state in accordance with
mounted on the aluminium profiles that cover three Standard EN 515; the leaf motion control arms are
sides of the leaf perimeter. A rigid-bristle brush is made of AISI 304 steel, while the sealing gaskets are
installed as standard on the bottom edge. made of co-extruded EPDM.
3.
Stainless Steel Panel
4.
FRAME PROFILE FOR SWING DOOR
Material
Profiles made of extruded EN AW-6060 aluminium is closing the wall shoulder. The two components
alloy in accordance with Standard EN 573-1, with T6 are then assembled into a single body during the
finishing state in accordance with Standard EN 515. installation stage; they are adjusted through fixing
Fixing brackets made of pressure-cast Zamak; pawls located inside the frame.
alignment brackets made of polyamide.
Hinges made of steel or of extruded aluminium in the Field of application
leaded leaf version. The frame-extension system can be used for 85 to 165
mm thick walls; adding further extensions allows it to
Features be installed on up to 300 mm thick walls.
The wall frame consists of two main components: a
load-bearing frame and an extension module. The
frame, assembled in our workshop, is the structural
part of the wall frame, while the function of the
extension, which is assembled in our workshop too,
Frame profile
Extension profile
5.
VISION PANEL
Insulating glass
1
Size refers to the large plate.
6.
Accessories for SWING doors
H-MAN001I-AB
H-MAN001
H-KIEPA
H-KIEPMA
Lead plate
7.
CERTIFICATIONS
1
Directive 2011/65/EU (RoHS2), as subsequently amended by Delegated Directive 2015/863/EU (RoHS3)
2
Laboratory measurement of airborne sound insulation according to standards UNI EN ISO 10140-2:2010
and UNI EN ISO 717-1:2013 on sliding door.
8.
Hermetic seal kit
Applicable to panel leaves ranging between 340 and In the fixed frame the regular gasket is replaced
1230 mm in size, which can be installed on single- or with one made of a co-extruded EPDM mix, which
double-leaf manual and automatic doors. increases air tightness and noise dampening.
9.
CERTIFICATIONS
Automatic hermetically
sealing swing door
HB-B150 HB-B300
European Directives
DM 2006/42 CE
DEMC: EMC 2014/30/EU
DBT: LVD 2014/35/EU
2011/65/EU (RoHS2)
2015/863/EU (RoHS3) 1
European Standards
EN16005
EN13849-1; EN13849-2
EN61000-6-2; EN61000-6-3
EN60335-2-103
Certifications
R.P. NO. 351667 2
R.P. NO. 351668 3
CAD-AUT-002-IT4
1
Directive 2011/65/EU (RoHS2), as subsequently amended by Delegated Directive 2015/863/EU (RoHS3).
2
Air permeability according to standard UNI EN 1026:2016, and relevant rating according to standard UNI EN 12207:2017
on single-leaf door.
Classification
Test type Test standard Class
standard
Referred to total surface D
Permeability
to air Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 C
under pressure
Final D
Permeability Referred to total surface D
to air
Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 C
under negative pres-
sure Final D
1
Directive 2011/65/EU (RoHS2), as subsequently amended by Delegated Directive 2015/863/EU (RoHS3).
2
Air permeability according to standard UNI EN 1026:2016, and relevant rating according to standard UNI EN 12207:2017
on single-leaf door.
Classification
Test type Test standard Class
standard
Referred to total surface D
Permeability
to air Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 C
under pressure
Final D
Permeability Referred to total surface D
to air
Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 C
under negative pres-
sure Final D
3
Air permeability according to standard UNI EN 1026:2016, and relevant rating according to standard UNI EN 12207:2017
on single-leaf door.
Classification
Test type Test standard Class
standard
Referred to total surface B
Permeability
to air Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 A
under pressure
Final B
Permeability Referred to total surface B
to air
Referred to the length of the opening joints UNI EN 1026 UNI EN 12207 A
under negative pres-
sure Final B
4
Field of direct application of the results of lab tests carried out in accordance with the standard uni en 1026:2016
10.
HOSPITAL finishes
LABEL S.p.A. Via Umberto Ilariuzzi 17/A - 43126 San Pancrazio Parmense (PARMA) Italy
T. +39 0521 6752 - infocom@labelspa.it
www.labelspa.com
AZIENDA CERTIFICATA
SISTEMA QUALITÀ
UNI EN 9001:2015