DECSB Reply NAEC 317 - P2213 TQ 002 - TNB Substation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

TNB SUB-STATION BUILDING

1a) The SHS120x120x8mm available in market? Or substitute it with SHS125x125x8mm? OK, use SHS 125x125x8mm

1b) The LP125x65x20x3mm is NOT the common Lipped Channel or High Tensile C-Purlin in market OK, use YCP 1230, 127x51x16x3
Can just substitute it with the YCP1230 that available from the well-known Purlin vendor, CH Yodoform?

2) The "TRUSS SUPPORT C/W INSERT PL" is under NAEC Scope of Work?
Truss support by NAEC.
If Yes, please provide the Drawing for STAR-000-EXE-DECSB-KLCS-CVS-DWG-0103 Insert plate by others.

NAEC-317_P2213-TQ-002 Page 1 / 3
3) To avoid clashing with weldment on L100x100x6mm, the Purlin need to raise up 10mm? Ok.

4) The Handrail on RC Staircase are under NAEC scope of work?


If Yes, please provide the Drawing for STAR-000-EXE-DECSB-KLCS-CVS-DWG-0103
Yes, handraill is under NAEC's scope. Refer new drawing,
Height of TNB substation handrail revised to 900mm

NAEC-317_P2213-TQ-002 Page 2 / 3
5) How the Connection Detail of Purlin to the Water Tank Area? To be provided.

6) The Cat Ladder already omitted? As it only shown in Architect Drawing but NOT shown in Construction Drawing

CAT ladder still maintained, Refer RC staircase detail & cage ladder STAR-000-EXE-DECSB-KLCS-CVS-DWG-0103_1 (1)
NAEC-317_P2213-TQ-002 Page 3 / 3