Cat Electronic Technician 2016B v1.0


Configuration

01.03.2017 16:22

PowerWizard 2.1
Parameter Value
ECM Part Number 3505852-00
ECM Serial Number 1773E107TX
Software Group Part Number 4555183-00
Software Group Release Date MAR2014
Software Group Description EMCP 4.2 French, v4.4 PROD, 18 March 2014

Description Value TT
Analog Inputs
Analog Input #1 Signal Type Voltage
Analog Input #1 Signal Range 0.5 to 4.5 V
Analog Input #1 Data Identification Engine Oil Pressure
Analog Input #1 Minimum Data Range 0,000
Analog Input #1 Maximum Data Range 3494,000
Analog Input #1 Low Warning Event Threshold 200
Analog Input #1 Low Warning Event Delay Time 0,0 sec
Analog Input #1 Low Shutdown Event Threshold 120
Analog Input #1 Low Shutdown Event Delay Time 0,0 sec
Analog Input #2 Signal Type Resistive Sender
Analog Input #2 Configuration Code Map #6
Analog Input #2 Data Identification Engine Coolant Temperature
Analog Input #2 High Warning Event Threshold 95
Analog Input #2 High Warning Event Delay Time 0,0 sec
Analog Input #2 High Shutdown Event Threshold 107
Analog Input #2 High Shutdown Event Delay Time 0,0 sec
Analog Input #2 Low Warning Event Threshold 1
Analog Input #2 Low Warning Event Delay Time 0,0 sec
Analog Input #3 Signal Type Disabled
Analog Input Supply Voltage 5 Volt
Automatic Start/Stop

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 2 of 29

Engine Start Fault Protection Activation Delay Time 30 sec


Crank Duration 7 sec
Crank Cycle Rest Interval 7 sec
Engine Purge Cycle Time with Ignition 0,0 sec
Engine Purge Cycle Time without Ignition 0 sec
Engine Start Sequence Delay Time 0 sec
Maximum Number of Crank Cycles 3
Cooldown Duration 3 min
Start Aid Activation Time 6 sec
Crank Alert Activation Time 0 sec
Crank Terminate RPM 300 rpm
Engine Cooldown Speed Configuration Rated Speed
Engine Operating State Input Configuration Hardwired Input
Fuel Priming Feature Enable Status Enabled
Engine Forced Idle Feature Enable Status Disabled
Emergency Stop Switch Active State Configuration High
SCADA Data Link Remote Control Enable Status Disabled
ECU Fault Reset Active Time 0,1 sec
Battery Voltage Monitor
High Battery Voltage Warning Event Threshold 15,8 Volts
High Battery Voltage Warning Event Notification Delay
30 sec
Time
High Battery Voltage Shutdown Event Threshold 30,0 Volts
High Battery Voltage Shutdown Event Notification Delay
30 sec
Time
Low Battery Voltage Warning Event Threshold 11,3 Volts
Low Battery Voltage Warning Event Notification Delay
30 sec
Time
Low Battery Charging System Voltage Warning Event
12,5 Volts
Threshold
Low Battery Charging System Voltage Warning Event
30 sec
Notification Delay Time
Low Cranking Voltage Warning Event Threshold 0,0 Volts
Low Cranking Voltage Warning Event Notification Delay
2 sec
Time
Crank Attempt/Successful Start Counter
Customer Password Security Level to Reset Crank/Start
3-Factory, Single Use
Counters
Data Link: RS-485 SCADA
SCADA Data Link Baud Rate 19200 baud

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 3 of 29

SCADA Data Link Parity None


SCADA Data Link Slave Address 1
SCADA Data Link Access Password 00000000
RS-485 Bias Resistor Enable Status Disabled
Digital Inputs
Digital Input #1 Usage Type System Event
Digital Input #1 Active State Configuration Low
Event Input Function #1 Event Notification Delay Time 0 sec
Event Input Function #1 Suspect Parameter Number Custom Event
Event Input Function #1 Failure Mode Identifier Condition Exists
Digital Input #2 Usage Type System Event
Digital Input #2 Active State Configuration Low
Event Input Function #2 Event Notification Delay Time 0 sec
Event Input Function #2 Suspect Parameter Number Custom Event
Event Input Function #2 Failure Mode Identifier Condition Exists
Digital Input #3 Usage Type System Event
Digital Input #3 Active State Configuration Low
Event Input Function #3 Event Notification Delay Time 0 sec
Event Input Function #3 Suspect Parameter Number Custom Event
Event Input Function #3 Failure Mode Identifier Condition Exists
Digital Input #4 Usage Type System Event
Digital Input #4 Active State Configuration Low
Event Input Function #4 Event Notification Delay Time 0 sec
Event Input Function #4 Suspect Parameter Number Custom Event
Event Input Function #4 Failure Mode Identifier Condition Exists
Digital Input #5 Usage Type System Event
Digital Input #5 Active State Configuration Low
Event Input Function #5 Event Notification Delay Time 0 sec
Event Input Function #5 Suspect Parameter Number Custom Event
Event Input Function #5 Failure Mode Identifier Condition Exists
Digital Input #6 Usage Type System Event
Digital Input #6 Active State Configuration Low
Event Input Function #6 Event Notification Delay Time 0 sec
Event Input Function #6 Suspect Parameter Number Custom Event
Event Input Function #6 Failure Mode Identifier Condition Exists
Digital Outputs
Digital Output #1 Usage Type Disabled
Digital Output #2 Usage Type Disabled

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 4 of 29

Engine Coolant Temperature Monitor


Engine Coolant Temperature Sensor Configuration Sensor
Engine Oil Pressure Monitor
Engine Oil Pressure Sensor Configuration Sensor
Low Idle Low Engine Oil Pressure Warning Event
160 kPa
Threshold
Low Idle Low Engine Oil Pressure Shutdown Event
100 kPa
Threshold
Low Engine Oil Pressure Step Speed 1350 rpm
Engine Speed Monitor
Flywheel Teeth 126
Engine Overspeed Setpoint 1700 rpm
Engine Underspeed Warning Event Threshold 1350 rpm
Engine Underspeed Warning Event Notification Delay
2,0 sec
Time
Engine Underspeed Shutdown Event Threshold 1250 rpm
Engine Underspeed Shutdown Event Notification Delay
2,0 sec
Time
Engine Speed Sensor Configuration Sensor
Generator Drive Ratio 1,000 Ratio
Enhanced Engine Monitor
Engine Cylinder Temperature Sensor Installation Status Not Installed
Number of Engine Cylinders 1
Enhanced Generator Monitor
Generator Winding Temperature Sensor Installation
Not Installed
Status
Generator Bearing Temperature Sensor Installation
Not Installed
Configuration
Event Response Configuration - Diagnostic Events
Accessory Data Link Diagnostic Response Configuration Activate Warning Condition
Accessory Data Link Diagnostic Audible Alert Yes
Accessory Data Link Diagnostic Breaker #1 Trip No
Accessory Data Link Diagnostic Breaker #2 Trip No
Activate Hard Shutdown
Engine Speed Sensor Diagnostic Response Configuration
Condition
Engine Speed Sensor Diagnostic Audible Alert Yes
Engine Speed Sensor Diagnostic Breaker #1 Trip No
Engine Speed Sensor Diagnostic Breaker #2 Trip No
Primary Data Link Diagnostic Response Configuration Activate Warning Condition
Primary Data Link Diagnostic Audible Alert No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 5 of 29

Primary Data Link Diagnostic Breaker #1 Trip No


Primary Data Link Diagnostic Breaker #2 Trip No
RS-485 SCADA Data Link Diagnostic Response
Activate Warning Condition
Configuration
RS-485 SCADA Data Link Diagnostic Audible Alert No
RS-485 SCADA Data Link Diagnostic Breaker #1 Trip No
RS-485 SCADA Data Link Diagnostic Breaker #2 Trip No
RS-485 SCADA Data Link Diagnostic Fault Protection
No
Timer
RS-485 Annunciator Data Link Diagnostic Response
Activate Warning Condition
Configuration
RS-485 Annunciator Data Link Diagnostic Audible Alert No
RS-485 Annunciator Data Link Diagnostic Breaker #1
No
Trip
RS-485 Annunciator Data Link Diagnostic Breaker #2
No
Trip
RS-485 Annunciator Data Link Diagnostic Fault Protection
No
Timer
Battery Charger Failure Diagnostic Response
Activate Warning Condition
Configuration
Battery Charger Failure Diagnostic Audible Alert Yes
Engine Controller Not Responding Diagnostic Response
Disable Condition
Configuration
Engine Controller Not Responding Diagnostic Audible
No
Alert
Engine Controller Not Responding Diagnostic Breaker #1
No
Trip
Engine Controller Not Responding Diagnostic Breaker #2
No
Trip
Analog Input #1 Diagnostic Response Configuration Activate Warning Condition
Analog Input #1 Diagnostic Audible Alert No
Analog Input #1 Diagnostic Breaker #1 Trip No
Analog Input #1 Diagnostic Breaker #2 Trip No
Analog Input #2 Diagnostic Response Configuration Activate Warning Condition
Analog Input #2 Diagnostic Audible Alert No
Analog Input #2 Diagnostic Breaker #1 Trip No
Analog Input #2 Diagnostic Breaker #2 Trip No
Analog Input #3 Diagnostic Response Configuration Activate Warning Condition
Analog Input #3 Diagnostic Audible Alert No
Analog Input #3 Diagnostic Breaker #1 Trip No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 6 of 29

Analog Input #3 Diagnostic Breaker #2 Trip No


Event Response Configuration - Engine Protection
Events
Hard Shutdown & Active Only
Air Damper Closed Event Response Configuration
Condition
Air Damper Closed Event Audible Alert Yes
Activate Hard Shutdown
Emergency Stop Activated Event Response Configuration
Condition
Emergency Stop Activated Event Audible Alert Yes
Emergency Stop Activated Event Breaker #1 Trip No
Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Coolant Level Warning Event Audible Alert Yes
High Engine Coolant Level Warning Event Breaker #1
No
Trip
High Engine Coolant Level Warning Event Breaker #2
No
Trip
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
No
Trip
High Engine Coolant Level Shutdown Event Breaker #2
No
Trip
Low Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Coolant Level Warning Event Audible Alert Yes
Low Engine Coolant Level Warning Event Breaker #1 Trip No
Low Engine Coolant Level Warning Event Breaker #2 Trip No
Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Coolant Level Shutdown Event Audible Alert Yes
Low Engine Coolant Level Shutdown Event Breaker #1
No
Trip
Low Engine Coolant Level Shutdown Event Breaker #2
No
Trip
High Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event Audible
Yes
Alert

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 7 of 29

High Engine Coolant Temperature Warning Event


No
Breaker #1 Trip
High Engine Coolant Temperature Warning Event
No
Breaker #2 Trip
High Engine Coolant Temperature Warning Event Fault
Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event
Yes
Audible Alert
High Engine Coolant Temperature Shutdown Event
No
Breaker #1 Trip
High Engine Coolant Temperature Shutdown Event
No
Breaker #2 Trip
High Engine Coolant Temperature Shutdown Event Fault
Yes
Protection Timer
Low Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Engine Coolant Temperature Warning Event Audible
Yes
Alert
Low Engine Coolant Temperature Warning Event Breaker
No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
No
#2 Trip
Low Engine Coolant Temperature Warning Event Fault
No
Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Failure To Start Shutdown Event Audible Alert Yes
Engine Failure To Start Shutdown Event Breaker #1 Trip No
Engine Failure To Start Shutdown Event Breaker #2 Trip No
High Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Level Warning Event Audible Alert Yes
High Engine Oil Level Warning Event Breaker #1 Trip No
High Engine Oil Level Warning Event Breaker #2 Trip No
High Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Level Shutdown Event Audible Alert Yes
High Engine Oil Level Shutdown Event Breaker #1 Trip No
High Engine Oil Level Shutdown Event Breaker #2 Trip No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 8 of 29

Low Engine Oil Level Warning Event Response


Activate Warning Condition
Configuration
Low Engine Oil Level Warning Event Audible Alert Yes
Low Engine Oil Level Warning Event Breaker #1 Trip No
Low Engine Oil Level Warning Event Breaker #2 Trip No
Low Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Level Shutdown Event Audible Alert Yes
Low Engine Oil Level Shutdown Event Breaker #1 Trip No
Low Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Pressure Warning Event Audible Alert Yes
Low Engine Oil Pressure Warning Event Breaker #1 Trip No
Low Engine Oil Pressure Warning Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Fault Protection
Yes
Timer
Low Engine Oil Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Pressure Shutdown Event Audible Alert Yes
Low Engine Oil Pressure Shutdown Event Breaker #1
No
Trip
Low Engine Oil Pressure Shutdown Event Breaker #2
No
Trip
Low Engine Oil Pressure Shutdown Event Fault Protection
Yes
Timer
High Engine Oil Temperature Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Temperature Warning Event Audible
Yes
Alert
High Engine Oil Temperature Warning Event Breaker #1
No
Trip
High Engine Oil Temperature Warning Event Breaker #2
No
Trip
High Engine Oil Temperature Warning Event Fault
No
Protection Timer
High Engine Oil Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Temperature Shutdown Event Audible
Yes
Alert
High Engine Oil Temperature Shutdown Event Breaker

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 9 of 29

#1 Trip No
High Engine Oil Temperature Shutdown Event Breaker
No
#2 Trip
High Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Low Engine Oil Temperature Warning Event Response
Disable Condition
Configuration
Low Engine Oil Temperature Warning Event Audible Alert Yes
Low Engine Oil Temperature Warning Event Breaker #1
No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
No
Trip
Low Engine Oil Temperature Warning Event Fault
Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
Disable Condition
Configuration
Low Engine Oil Temperature Shutdown Event Audible
No
Alert
Low Engine Oil Temperature Shutdown Event Breaker #1
No
Trip
Low Engine Oil Temperature Shutdown Event Breaker #2
No
Trip
Low Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Unexpected Engine Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Unexpected Engine Shutdown Event Audible Alert Yes
Unexpected Engine Shutdown Event Breaker #1 Trip No
Unexpected Engine Shutdown Event Breaker #2 Trip No
Engine Overspeed Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Overspeed Shutdown Event Audible Alert Yes
Engine Overspeed Shutdown Event Breaker #1 Trip No
Engine Overspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Warning Event Response
Activate Warning Condition
Configuration
Engine Underspeed Warning Event Audible Alert Yes
Engine Underspeed Warning Event Breaker #1 Trip No
Engine Underspeed Warning Event Breaker #2 Trip No
Engine Underspeed Warning Event Fault Protection Timer Yes
Engine Underspeed Shutdown Event Response Activate Hard Shutdown

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 10 of 29

Configuration Condition
Engine Underspeed Shutdown Event Audible Alert Yes
Engine Underspeed Shutdown Event Breaker #1 Trip No
Engine Underspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Shutdown Event Fault Protection
Yes
Timer
High Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Exhaust Temperature Warning Event Audible Alert Yes
High Exhaust Temperature Warning Event Breaker #1
No
Trip
High Exhaust Temperature Warning Event Breaker #2
No
Trip
High Exhaust Temperature Warning Event Fault
No
Protection Timer
High Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Exhaust Temperature Shutdown Event Audible Alert Yes
High Exhaust Temperature Shutdown Event Breaker #1
No
Trip
High Exhaust Temperature Shutdown Event Breaker #2
No
Trip
High Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Exhaust Temperature Warning Event Audible Alert Yes
Low Exhaust Temperature Warning Event Breaker #1
No
Trip
Low Exhaust Temperature Warning Event Breaker #2
No
Trip
Low Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Exhaust Temperature Shutdown Event Response
Disable Condition
Configuration
Low Exhaust Temperature Shutdown Event Audible Alert No
Low Exhaust Temperature Shutdown Event Breaker #1
No
Trip
Low Exhaust Temperature Shutdown Event Breaker #2
No
Trip

Low Exhaust Temperature Shutdown Event Fault No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 11 of 29

Protection Timer
High Fuel Level Warning Event Response Configuration
Activate Warning Condition
High Fuel Level Warning Event Audible Alert Yes
High Fuel Level Warning Event Breaker #1 Trip No
High Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
High Fuel Level Shutdown Event Response Configuration
Condition
High Fuel Level Shutdown Event Audible Alert Yes
High Fuel Level Shutdown Event Breaker #1 Trip No
High Fuel Level Shutdown Event Breaker #2 Trip No
Low Fuel Level Warning Event Response Configuration Activate Warning Condition
Low Fuel Level Warning Event Audible Alert Yes
Low Fuel Level Warning Event Breaker #1 Trip No
Low Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
Low Fuel Level Shutdown Event Response Configuration
Condition
Low Fuel Level Shutdown Event Audible Alert Yes
Low Fuel Level Shutdown Event Breaker #1 Trip No
Low Fuel Level Shutdown Event Breaker #2 Trip No
External Tank High Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank High Fuel Level Warning Event Audible
Yes
Alert
External Tank High Fuel Level Warning Event Breaker #1
No
Trip
External Tank High Fuel Level Warning Event Breaker #2
No
Trip
External Tank High Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank High Fuel Level Shutdown Event Audible
Yes
Alert
External Tank High Fuel Level Shutdown Event Breaker
No
#1 Trip
External Tank High Fuel Level Shutdown Event Breaker
No
#2 Trip
External Tank Low Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank Low Fuel Level Warning Event Audible
Yes
Alert
External Tank Low Fuel Level Warning Event Breaker #1
No
Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 12 of 29

External Tank Low Fuel Level Warning Event Breaker #2


No
Trip
External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker
No
#1 Trip
External Tank Low Fuel Level Shutdown Event Breaker
No
#2 Trip
Fuel Leak Event Response Configuration Activate Warning Condition
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 Trip No
Fuel Leak Event Breaker #2 Trip No
Service Maintenance Interval Warning Event Response
Disable Condition
Configuration
Service Maintenance Interval Warning Event Audible
No
Alert
High Gas Pressure Warning Event Response
Activate Warning Condition
Configuration
High Gas Pressure Warning Event Audible Alert Yes
High Gas Pressure Warning Event Breaker #1 Trip No
High Gas Pressure Warning Event Breaker #2 Trip No
High Gas Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Gas Pressure Shutdown Event Audible Alert Yes
High Gas Pressure Shutdown Event Breaker #1 Trip No
High Gas Pressure Shutdown Event Breaker #2 Trip No
Low Gas Pressure Warning Event Response Configuration Activate Warning Condition
Low Gas Pressure Warning Event Audible Alert Yes
Low Gas Pressure Warning Event Breaker #1 Trip No
Low Gas Pressure Warning Event Breaker #2 Trip No
Low Gas Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Gas Pressure Shutdown Event Audible Alert Yes
Low Gas Pressure Shutdown Event Breaker #1 Trip No
Low Gas Pressure Shutdown Event Breaker #2 Trip No
Engine Intake Manifold Charge Combustion Event Activate Hard Shutdown
Response Configuration Condition
Yes
Engine Intake Manifold Charge Combustion Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 13 of 29

Audible Alert
Engine Intake Manifold Charge Combustion Event
No
Breaker #1 Trip
Engine Intake Manifold Charge Combustion Event
No
Breaker #2 Trip
Engine Intake Manifold Charge Combustion Event Fault
No
Protection Timer
Remote Emergency Stop Activated Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Remote Emergency Stop Activated Shutdown Event
Yes
Audible Alert
Remote Emergency Stop Activated Shutdown Event
Yes
Breaker #1 Trip
Remote Emergency Stop Activated Shutdown Event
Yes
Breaker #2 Trip
Event Response Configuration - Generator
Protection Events
High Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
High Generator Bearing #1 Temperature Warning Event
No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown
Yes
Event Audible Alert
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown
No
Event Fault Protection Timer
Low Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 14 of 29

Breaker #1 Trip No
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown Event
Disable Condition
Response Configuration
Low Generator Bearing #1 Temperature Shutdown Event
No
Audible Alert
Low Generator Bearing #1 Temperature Shutdown Event
No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown Event
No
Fault Protection Timer
Generator Overcurrent Warning Event Response
Activate Warning Condition
Configuration
Generator Overcurrent Warning Event Audible Alert Yes
Generator Overcurrent Warning Event Breaker #1 Trip No
Generator Overcurrent Warning Event Breaker #2 Trip No
Generator Overcurrent Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Overcurrent Shutdown Event Audible Alert Yes
Generator Overcurrent Shutdown Event Breaker #1 Trip No
Generator Overcurrent Shutdown Event Breaker #2 Trip No
Generator Over Frequency Warning Event Response
Activate Warning Condition
Configuration
Generator Over Frequency Warning Event Audible Alert Yes
Generator Over Frequency Warning Event Breaker #1
No
Trip
Generator Over Frequency Warning Event Breaker #2
No
Trip
Generator Over Frequency Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Over Frequency Shutdown Event Audible Alert Yes
Generator Over Frequency Shutdown Event Breaker #1
No
Trip
Generator Over Frequency Shutdown Event Breaker #2
No
Trip
Generator Under Frequency Warning Event Response
Activate Warning Condition
Configuration

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 15 of 29

Generator Under Frequency Warning Event Audible Alert Yes


Generator Under Frequency Warning Event Breaker #1
No
Trip
Generator Under Frequency Warning Event Breaker #2
No
Trip
Generator Under Frequency Warning Event Fault
Yes
Protection Timer
Generator Under Frequency Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Under Frequency Shutdown Event Audible
Yes
Alert
Generator Under Frequency Shutdown Event Breaker #1
No
Trip
Generator Under Frequency Shutdown Event Breaker #2
No
Trip
Generator Under Frequency Shutdown Event Fault
Yes
Protection Timer
Generator Reverse Power Warning Event Response
Disable Condition
Configuration
Generator Reverse Power Warning Event Audible Alert No
Generator Reverse Power Warning Event Breaker #1 Trip No
Generator Reverse Power Warning Event Breaker #2 Trip No
Generator Reverse Power Shutdown Event Response
Disable Condition
Configuration
Generator Reverse Power Shutdown Event Audible Alert No
Generator Reverse Power Shutdown Event Breaker #1
No
Trip
Generator Reverse Power Shutdown Event Breaker #2
No
Trip
Generator Over Voltage Warning Event Response
Activate Warning Condition
Configuration
Generator Over Voltage Warning Event Audible Alert Yes
Generator Over Voltage Warning Event Breaker #1 Trip No
Generator Over Voltage Warning Event Breaker #2 Trip No
Generator Over Voltage Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Over Voltage Shutdown Event Audible Alert Yes
Generator Over Voltage Shutdown Event Breaker #1 Trip No
Generator Over Voltage Shutdown Event Breaker #2 Trip No
Generator Under Voltage Warning Event Response
Activate Warning Condition
Configuration

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 16 of 29

Generator Under Voltage Warning Event Audible Alert Yes


Generator Under Voltage Warning Event Breaker #1 Trip No
Generator Under Voltage Warning Event Breaker #2 Trip No
Generator Under Voltage Warning Event Fault Protection
Yes
Timer
Generator Under Voltage Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Generator Under Voltage Shutdown Event Audible Alert Yes
Generator Under Voltage Shutdown Event Breaker #1
No
Trip
Generator Under Voltage Shutdown Event Breaker #2
No
Trip
Generator Under Voltage Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Earth Fault Event Response Configuration
Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 Trip No
Earth Fault Event Breaker #2 Trip No
Generator Winding #1 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #1 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #1 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #1 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #1 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #1 High Temperature Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Generator Winding #1 High Temperature Shutdown
Yes
Event Audible Alert
Generator Winding #1 High Temperature Shutdown
No
Event Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown
No
Event Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown
No
Event Fault Protection Timer
Generator High Power Warning Event Response
Activate Warning Condition
Configuration

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 17 of 29

Generator High Power Warning Event Audible Alert Yes


Generator High Power Warning Event Breaker #1 Trip No
Generator High Power Warning Event Breaker #2 Trip No
Generator Reverse Reactive Power Warning Event
Disable Condition
Response Configuration
Generator Reverse Reactive Power Warning Event
No
Audible Alert
Generator Reverse Reactive Power Warning Event
No
Breaker #1 Trip
Generator Reverse Reactive Power Warning Event
No
Breaker #2 Trip
Generator Reverse Reactive Power Shutdown Event
Disable Condition
Response Configuration
Generator Reverse Reactive Power Shutdown Event
No
Audible Alert
Generator Reverse Reactive Power Shutdown Event
No
Breaker #1 Trip
Generator Reverse Reactive Power Shutdown Event
No
Breaker #2 Trip
Programmable Trip Point #1 Condition Exists Event
Disable Condition
Response Configuration
Programmable Trip Point #1 Condition Exists Event
No
Audible Alert
Programmable Trip Point #1 Condition Exists Event
No
Breaker #1 Trip
Programmable Trip Point #1 Condition Exists Event
No
Breaker #2 Trip
Programmable Trip Point #1 Condition Exists Event Fault
No
Protection Timer
Programmable Trip Point #2 Condition Exists Event
Disable Condition
Response Configuration
Programmable Trip Point #2 Condition Exists Event
No
Audible Alert
Programmable Trip Point #2 Condition Exists Event
No
Breaker #1 Trip
Programmable Trip Point #2 Condition Exists Event
No
Breaker #2 Trip
Programmable Trip Point #2 Condition Exists Event Fault
No
Protection Timer
Event Response Configuration - Other System
Events
High Battery Voltage Warning Event Response

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 18 of 29

Configuration Activate Warning Condition


High Battery Voltage Warning Event Audible Alert Yes
High Battery Voltage Warning Event Breaker #1 Trip No
High Battery Voltage Warning Event Breaker #2 Trip No
High Battery Voltage Shutdown Event Response Activate Soft Shutdown
Configuration Condition
High Battery Voltage Shutdown Event Audible Alert Yes
High Battery Voltage Shutdown Event Breaker #1 Trip No
High Battery Voltage Shutdown Event Breaker #2 Trip No
Low Battery Voltage Warning Event Response
Activate Warning Condition
Configuration
Low Battery Voltage Warning Event Audible Alert Yes
Low Battery Voltage Warning Event Breaker #1 Trip No
Low Battery Voltage Warning Event Breaker #2 Trip No
Low Battery Voltage Warning Event Fault Protection
No
Timer
Low Battery Charging System Voltage Warning Event
Activate Warning Condition
Response Configuration
Low Battery Charging System Voltage Warning Event
Yes
Audible Alert
Low Battery Charging System Voltage Warning Event
No
Breaker #1 Trip
Low Battery Charging System Voltage Warning Event
No
Breaker #2 Trip
Low Battery Charging System Voltage Warning Event
No
Fault Protection Timer
Generator Breaker Open Event Response Configuration Active Only Condition
Generator Breaker Open Event Audible Alert No
Generator Breaker Closed Event Response Configuration Active Only Condition
Generator Breaker Closed Event Audible Alert No
Engine In Cooldown Event Response Configuration Active Only Condition
Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Mismatch Warning
Activate Warning Condition
Event Response Config
Engine Speed-Generator Output Freq Mismatch Warning
Yes
Event Audible Alert
Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #2 Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 19 of 29

Generator Control Not in Automatic Warning Event Warning & Active Only
Response Configuration Condition
Generator Control Not in Automatic Warning Event
Yes
Audible Alert
Activate Hard Shutdown
Earth Leakage Event Response Configuration
Condition
Earth Leakage Event Audible Alert Yes
Earth Leakage Event Breaker #1 Trip No
Earth Leakage Event Breaker #2 Trip No
Emergency Power System Supplying Load Event Warning & Active Only
Response Configuration Condition
Emergency Power System Supplying Load Event Audible
No
Alert
Low Cranking Voltage Warning Event Response
Disable Condition
Configuration
Low Cranking Voltage Warning Event Audible Alert No
Low Cranking Voltage Warning Event Breaker #1 Trip No
Low Cranking Voltage Warning Event Breaker #2 Trip No
Analog Input #1 Custom Parameter High Warning Event
Activate Warning Condition
Response Configuration
Analog Input #1 Custom Parameter High Warning Event
Yes
Audible Alert
Analog Input #1 Custom Parameter High Warning Event
No
Breaker #1 Trip
Analog Input #1 Custom Parameter High Warning Event
No
Breaker #2 Trip
Analog Input #1 Custom Parameter High Warning Event
No
Fault Protection Timer
Analog Input #1 Custom Parameter High Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Analog Input #1 Custom Parameter High Shutdown
Yes
Event Audible Alert
Analog Input #1 Custom Parameter High Shutdown
No
Event Breaker #1 Trip
Analog Input #1 Custom Parameter High Shutdown
No
Event Breaker #2 Trip
Analog Input #1 Custom Parameter High Shutdown
No
Event Fault Protection Timer
Analog Input #1 Custom Parameter Low Warning Event
Activate Warning Condition
Response Configuration
Yes
Analog Input #1 Custom Parameter Low Warning Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 20 of 29

Audible Alert
Analog Input #1 Custom Parameter Low Warning Event
No
Breaker #1 Trip
Analog Input #1 Custom Parameter Low Warning Event
No
Breaker #2 Trip
Analog Input #1 Custom Parameter Low Warning Event
No
Fault Protection Timer
Analog Input #1 Custom Parameter Low Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Analog Input #1 Custom Parameter Low Shutdown Event
Yes
Audible Alert
Analog Input #1 Custom Parameter Low Shutdown Event
No
Breaker #1 Trip
Analog Input #1 Custom Parameter Low Shutdown Event
No
Breaker #2 Trip
Analog Input #1 Custom Parameter Low Shutdown Event
No
Fault Protection Timer
Analog Input #2 Custom Parameter High Warning Event
Activate Warning Condition
Response Configuration
Analog Input #2 Custom Parameter High Warning Event
Yes
Audible Alert
Analog Input #2 Custom Parameter High Warning Event
No
Breaker #1 Trip
Analog Input #2 Custom Parameter High Warning Event
No
Breaker #2 Trip
Analog Input #2 Custom Parameter High Warning Event
No
Fault Protection Timer
Analog Input #2 Custom Parameter High Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Analog Input #2 Custom Parameter High Shutdown
Yes
Event Audible Alert
Analog Input #2 Custom Parameter High Shutdown
No
Event Breaker #1 Trip
Analog Input #2 Custom Parameter High Shutdown
No
Event Breaker #2 Trip
Analog Input #2 Custom Parameter High Shutdown
No
Event Fault Protection Timer
Analog Input #2 Custom Parameter Low Warning Event
Activate Warning Condition
Response Configuration
Analog Input #2 Custom Parameter Low Warning Event
Yes
Audible Alert
Analog Input #2 Custom Parameter Low Warning Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 21 of 29

Breaker #1 Trip No
Analog Input #2 Custom Parameter Low Warning Event
No
Breaker #2 Trip
Analog Input #2 Custom Parameter Low Warning Event
No
Fault Protection Timer
Analog Input #2 Custom Parameter Low Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Analog Input #2 Custom Parameter Low Shutdown Event
Yes
Audible Alert
Analog Input #2 Custom Parameter Low Shutdown Event
No
Breaker #1 Trip
Analog Input #2 Custom Parameter Low Shutdown Event
No
Breaker #2 Trip
Analog Input #2 Custom Parameter Low Shutdown Event
No
Fault Protection Timer
Analog Input #3 Custom Parameter High Warning Event
Activate Warning Condition
Response Configuration
Analog Input #3 Custom Parameter High Warning Event
Yes
Audible Alert
Analog Input #3 Custom Parameter High Warning Event
No
Breaker #1 Trip
Analog Input #3 Custom Parameter High Warning Event
No
Breaker #2 Trip
Analog Input #3 Custom Parameter High Warning Event
No
Fault Protection Timer
Analog Input #3 Custom Parameter High Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Analog Input #3 Custom Parameter High Shutdown
Yes
Event Audible Alert
Analog Input #3 Custom Parameter High Shutdown
No
Event Breaker #1 Trip
Analog Input #3 Custom Parameter High Shutdown
No
Event Breaker #2 Trip
Analog Input #3 Custom Parameter High Shutdown
No
Event Fault Protection Timer
Analog Input #3 Custom Parameter Low Warning Event
Activate Warning Condition
Response Configuration
Analog Input #3 Custom Parameter Low Warning Event
Yes
Audible Alert
Analog Input #3 Custom Parameter Low Warning Event
No
Breaker #1 Trip
Analog Input #3 Custom Parameter Low Warning Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 22 of 29

Breaker #2 Trip No
Analog Input #3 Custom Parameter Low Warning Event
No
Fault Protection Timer
Analog Input #3 Custom Parameter Low Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Analog Input #3 Custom Parameter Low Shutdown Event
Yes
Audible Alert
Analog Input #3 Custom Parameter Low Shutdown Event
No
Breaker #1 Trip
Analog Input #3 Custom Parameter Low Shutdown Event
No
Breaker #2 Trip
Analog Input #3 Custom Parameter Low Shutdown Event
No
Fault Protection Timer
Event Response Configuration - Custom Events
Custom Event #1 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #1 Condition Exists Event Audible Alert No
Custom Event #1 Condition Exists Event Breaker #1 Trip No
Custom Event #1 Condition Exists Event Breaker #2 Trip No
Custom Event #1 Condition Exists Event Fault Protection
No
Timer
Custom Event #2 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #2 Condition Exists Event Audible Alert No
Custom Event #2 Condition Exists Event Breaker #1 Trip No
Custom Event #2 Condition Exists Event Breaker #2 Trip No
Custom Event #2 Condition Exists Event Fault Protection
No
Timer
Custom Event #3 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #3 Condition Exists Event Audible Alert No
Custom Event #3 Condition Exists Event Breaker #1 Trip No
Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
No
Timer
Custom Event #4 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #4 Condition Exists Event Audible Alert No
Custom Event #4 Condition Exists Event Breaker #1 Trip No
Custom Event #4 Condition Exists Event Breaker #2 Trip No
Custom Event #4 Condition Exists Event Fault Protection

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 23 of 29

Timer No
Custom Event #5 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #5 Condition Exists Event Audible Alert No
Custom Event #5 Condition Exists Event Breaker #1 Trip No
Custom Event #5 Condition Exists Event Breaker #2 Trip No
Custom Event #5 Condition Exists Event Fault Protection
No
Timer
Custom Event #6 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #6 Condition Exists Event Audible Alert No
Custom Event #6 Condition Exists Event Breaker #1 Trip No
Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
No
Timer
Event System
Engine Running Conditions - Custom Event Digital Input Activate
Engine Running Conditions - Engine Running Do Not Activate
Engine Running Conditions - Volts/Hertz within Limits Do Not Activate
Engine Running Conditions - Engine Running at Rated
Do Not Activate
Speed
Fuel Transfer
Fuel Fill/Drain Feature Enable Status Disabled
Fuel Fill Activation Tank Level Percentage Threshold 0,0 %
Fuel Fill Deactivation Tank Level Percentage Threshold 100,0 %
Generator AC Monitor
Generator Connection Configuration Wye (or Star) Connection
Generator Potential Transformer Primary Winding Rating 1 Volts
Generator Potential Transformer Secondary Winding
1 Volts
Rating
Generator Current Transformer Primary Winding Rating 150 Amps
Generator Current Transformer Secondary Winding
5 Amps
Rating
Number of Generator Poles 4 Poles
Generator Rated Frequency 50 Hz
Generator Rated Voltage 400 Volts
Generator Rated Power 70 kW
Generator Rated Apparent Power 88 kVA
Maximum Generator Voltage Output Bias Percentage 5%
Generator AC Power Monitor

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 24 of 29

Customer Password Security Level to Reset Generator


3-Factory, Single Use
Energy Meters
Generator Current Monitoring
Generator Definite Time Overcurrent Warning Event
110 %
Percentage Threshold
Generator Inverse Time Overcurrent Shutdown Event
0,82 sec
Time Multiplier
Generator Definite Time Overcurrent Shutdown Event
125 %
Percentage Threshold
Generator Definite Time Overcurrent Shutdown Event
10,0 sec
Notification Delay Time
Generator Inverse Time Over Current Shutdown Event
110 %
Threshold
Generator Inverse Definite Minimum Time Curve Type
Normal Inverse Curve
Configuration
Generator Over/Under Frequency
Generator Over Frequency Warning Event Percentage
105,0 %
Threshold
Generator Over Frequency Warning Event Notification
10 sec
Delay Time
Generator Over Frequency Shutdown Event Percentage
110,0 %
Threshold
Generator Over Frequency Shutdown Event Notification
2 sec
Delay Time
Generator Under Frequency Warning Event Percentage
95,0 %
Threshold
Generator Under Frequency Warning Event Notification
4 sec
Delay Time
Generator Under Frequency Shutdown Event Percentage
90,0 %
Threshold
Generator Under Frequency Shutdown Event Notification
4 sec
Delay Time
Generator Over/Under Voltage
Generator Over Voltage Warning Event Percentage
105 %
Threshold
Generator Over Voltage Warning Event Notification Delay
10 sec
Time
Generator Over Voltage Shutdown Event Percentage
110 %
Threshold
Generator Over Voltage Shutdown Event Notification
2 sec
Delay Time
Generator Under Voltage Warning Event Percentage

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 25 of 29

Threshold 95 %
Generator Under Voltage Warning Event Notification
4 sec
Delay Time
Generator Under Voltage Shutdown Event Percentage
90 %
Threshold
Generator Under Voltage Shutdown Event Notification
4 sec
Delay Time
Generator Reverse Power
Generator Reverse Power Warning Event Percentage
5%
Threshold
Generator Reverse Power Warning Event Notification
10 sec
Delay Time
Generator Reverse Power Shutdown Event Percentage
10 %
Threshold
Generator Reverse Power Shutdown Event Notification
10 sec
Delay Time
Generator Reverse Reactive Power Warning Event
5,00 %
Percentage Threshold
Generator Reverse Reactive Power Warning Event
10 sec
Notification Delay Time
Generator Reverse Reactive Power Shutdown Event
10,00 %
Percentage Threshold
Generator Reverse Reactive Power Shutdown Event
10 sec
Notification Delay Time
Integrated Voltage Regulator
Voltage Regulator Control Source Configuration External Control
Programmable Cycle Timer
Programmable Cycle Timer #1 Activation Day - Sunday Deactivate
Programmable Cycle Timer #1 Activation Day - Monday Deactivate
Programmable Cycle Timer #1 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #1 Activation Day -
Activate
Wednesday
Programmable Cycle Timer #1 Activation Day - Thursday Deactivate
Programmable Cycle Timer #1 Activation Day - Friday Deactivate
Programmable Cycle Timer #1 Activation Day - Saturday Deactivate
Programmable Cycle Timer #1 Activation Start Time 720 min
Programmable Cycle Timer #1 Active Time 7 min
Programmable Cycle Timer #1 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #1 Output #2 Activation
Inactive
Configuration

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 26 of 29

Programmable Cycle Timer #2 Activation Day - Sunday Deactivate


Programmable Cycle Timer #2 Activation Day - Monday Deactivate
Programmable Cycle Timer #2 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #2 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #2 Activation Day - Thursday Deactivate
Programmable Cycle Timer #2 Activation Day - Friday Deactivate
Programmable Cycle Timer #2 Activation Day - Saturday Deactivate
Programmable Cycle Timer #2 Activation Start Time 0 min
Programmable Cycle Timer #2 Active Time 1 min
Programmable Cycle Timer #2 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #2 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #3 Activation Day - Sunday Deactivate
Programmable Cycle Timer #3 Activation Day - Monday Deactivate
Programmable Cycle Timer #3 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #3 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #3 Activation Day - Thursday Deactivate
Programmable Cycle Timer #3 Activation Day - Friday Deactivate
Programmable Cycle Timer #3 Activation Day - Saturday Deactivate
Programmable Cycle Timer #3 Activation Start Time 0 min
Programmable Cycle Timer #3 Active Time 1 min
Programmable Cycle Timer #3 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #3 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #4 Activation Day - Sunday Deactivate
Programmable Cycle Timer #4 Activation Day - Monday Deactivate
Programmable Cycle Timer #4 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #4 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #4 Activation Day - Thursday Deactivate
Programmable Cycle Timer #4 Activation Day - Friday Deactivate
Programmable Cycle Timer #4 Activation Day - Saturday Deactivate
Programmable Cycle Timer #4 Activation Start Time 0 min
Programmable Cycle Timer #4 Active Time 1 min
Programmable Cycle Timer #4 Output #1 Activation
Inactive
Configuration

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 27 of 29

Programmable Cycle Timer #4 Output #2 Activation


Inactive
Configuration
Programmable Cycle Timer #5 Activation Day - Sunday Deactivate
Programmable Cycle Timer #5 Activation Day - Monday Deactivate
Programmable Cycle Timer #5 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #5 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #5 Activation Day - Thursday Deactivate
Programmable Cycle Timer #5 Activation Day - Friday Deactivate
Programmable Cycle Timer #5 Activation Day - Saturday Deactivate
Programmable Cycle Timer #5 Activation Start Time 0 min
Programmable Cycle Timer #5 Active Time 1 min
Programmable Cycle Timer #5 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #5 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #6 Activation Day - Sunday Deactivate
Programmable Cycle Timer #6 Activation Day - Monday Deactivate
Programmable Cycle Timer #6 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #6 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #6 Activation Day - Thursday Deactivate
Programmable Cycle Timer #6 Activation Day - Friday Deactivate
Programmable Cycle Timer #6 Activation Day - Saturday Deactivate
Programmable Cycle Timer #6 Activation Start Time 0 min
Programmable Cycle Timer #6 Active Time 1 min
Programmable Cycle Timer #6 Output #1 Activation
Inactive
Configuration
Programmable Cycle Timer #6 Output #2 Activation
Inactive
Configuration
Programmable Cycle Timer #7 Activation Day - Sunday Deactivate
Programmable Cycle Timer #7 Activation Day - Monday Deactivate
Programmable Cycle Timer #7 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #7 Activation Day -
Deactivate
Wednesday
Programmable Cycle Timer #7 Activation Day - Thursday Deactivate
Programmable Cycle Timer #7 Activation Day - Friday Deactivate
Programmable Cycle Timer #7 Activation Day - Saturday Deactivate
Programmable Cycle Timer #7 Activation Start Time 0 min
Programmable Cycle Timer #7 Active Time 1 min

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 28 of 29

Programmable Cycle Timer #7 Output #1 Activation


Inactive
Configuration
Programmable Cycle Timer #7 Output #2 Activation
Inactive
Configuration
Electronic Control Module Reduced Power Mode
Electronic Control Module Reduced Power Mode Enable
Disabled
Status
Electronic Control Module Reduced Power Mode Delay
10 min
Time
Relay Outputs
Relay Output #1 Usage Type Command/Status Parameter
Relay Output #1 Command/Status Parameter Data
Starter Motor Relay
Identification
Relay Output #2 Usage Type Command/Status Parameter
Relay Output #2 Command/Status Parameter Data
Fuel Control Relay
Identification
Relay Output #3 Usage Type Command/Status Parameter
Relay Output #3 Command/Status Parameter Data
Start Aid
Identification
Relay Output #4 Usage Type Command/Status Parameter
Relay Output #4 Command/Status Parameter Data
Horn Control
Identification
Relay Output #5 Usage Type System Event
Relay Output #5 Event Suspect Parameter Number Any Suspect Parameter Number
General Event - Any Warning or
Relay Output #5 Event Trigger Condition
Shutdown
Relay Output #6 Usage Type Command/Status Parameter
Relay Output #6 Command/Status Parameter Data
V/Hz Within Limits
Identification
Relay Output #7 Usage Type Command/Status Parameter
Relay Output #7 Command/Status Parameter Data
Transfer Fuel In
Identification
Relay Output #8 Usage Type Command/Status Parameter
Relay Output #8 Command/Status Parameter Data
Common Warning
Identification
Service Maintenance Interval
Maintenance Level 1 Cycle Interval Hours 0 hours
Maintenance Level 1 Cycle Interval Days 0
Customer Password Security Level to Reset Service
3-Factory, Single Use
Maintenance Interval

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017
Page 29 of 29

kW Relay Setpoints
Programmable Trip Point Function #1 Trigger Condition Disabled
Programmable Trip Point Function #1 Percentage
0%
Threshold
Programmable Trip Point Function #1 Hysteresis
0%
Percentage
Programmable Trip Point Function #1 Trip Activation
0 sec
Delay Time
Programmable Trip Point Function #1 Trip Deactivation
0 sec
Delay Time
Programmable Trip Point Function #2 Trigger Condition Disabled
Programmable Trip Point Function #2 Percentage
0%
Threshold
Programmable Trip Point Function #2 Hysteresis
0%
Percentage
Programmable Trip Point Function #2 Trip Activation
0 sec
Delay Time
Programmable Trip Point Function #2 Trip Deactivation
0 sec
Delay Time
Configuration Data
Engine Serial Number Not Programmed
Display Preferences
Display Pressure Units Configuration bar
Display Temperature Units Configuration Degrees Centigrade (Celsius)
Display Volume Units Configuration liters

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport3.HTM 01.03.2017