Lu 2015

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Energy Conversion and Management 91 (2015) 238–248

Contents lists available at ScienceDirect

Energy Conversion and Management


journal homepage: www.elsevier.com/locate/enconman

Experimental study of crosswind effects on the performance of small


cylindrical natural draft dry cooling towers
Yuanshen Lu ⇑, Zhiqiang Guan, Hal Gurgenci, Kamel Hooman, Suoying He, Desikan Bharathan
Queensland Geothermal Energy Centre of Excellence, Qld 4072, Australia
School of Mechanical and Mining Engineering, The University of Queensland, Qld 4072, Australia

a r t i c l e i n f o a b s t r a c t

Article history: Crosswind effect is a common issue which limits the cooling efficiency of natural draft dry cooling towers
Received 27 August 2014 (NDDCTs) of all sizes. On short NDDCTs with total heights less than 30 m, this effect might be much more
Accepted 6 December 2014 significant. Following the authors’ previous numerical investigation on crosswind effects in a 15 m-tall
Available online 24 December 2014
cylindrical NDDCT, an experimental study was carried out and is presented in this paper. The study used
a 1:12.5 scaled cooling tower model equipped with an electric resistance heater simulating horizontally
Keywords: placed heat exchangers. The air velocity, temperature, and the heat input on the model were measured at
Natural draft dry cooling towers
different crosswind speeds in a wind tunnel. Comparisons against CFD models show good agreement
Crosswind effect
Scaled cooling tower model
between the experimental and numerical results when the similarity conditions between the CFD model
Wind tunnel testing and the experimental model are fully satisfied. Based on these results, the total heat transfer rate of
Natural convection heat transfer NDDCTs was proposed to be a combination of a natural convective heat transfer term and a forced con-
vective one. In small cooling towers, the natural convection term is comparable with the forced convec-
tion term. This explains why the correlation of the total heat transfer with the wind speed has a
turnabout point below which the heat transfer decreases with increasing crosswind speed and above
which it does the reverse. The turnabout point occurs when the sum of natural and forced convection
terms is the minimum.
Ó 2014 Elsevier Ltd. All rights reserved.

1. Introduction high-temperature fossil-fired plants, these renewable plants need


to dump more waste heat for every unit of power they generate.
The cooling tower performance is crucial to the power conver- This makes the cooling efficiency of their NDDCTs more important.
sion efficiency of power plants. It is reported that about 0.3 GW h The Queensland Geothermal Energy Centre of Excellence (QGECE)
of total net power generation loss each year in the United States is developing small-size geothermal and solar thermal power
can be attributed to cooling tower systems operating at efficiencies plants for Australia. These plants have net generation capacities
below their design values [1]. Natural draft dry cooling towers of only a few megawatts and are more likely located in arid areas
(NDDCTs) are used in areas where water is scarce [2]. In contrast of Australian interior. Therefore small-size NDDCTs equipped with
to fan-cooled condensers, natural draft towers are designed to horizontal air-cooled surface heat exchangers are proposed [3]. The
work like chimneys relying on the buoyancy of hot air. Traditional study shows that the heights of these towers can be decreased to
large scale fossil fired power plants usually require NDDCTs taller below 30 m while still being able to deliver the desired cooling
than 100 m to produce enough airflow. Renewable thermal power capacity under normal conditions [4].
generators, e.g. geothermal and solar thermal, operate using the The cooling performance of a NDDCT is often affected by many
same principles as fossil-fired thermal plants. Leaving the environmental factors, which are not considered in existing design
high-concentration solar thermal generators aside as a notable theories of cooling towers. Crosswind is one of the most important
exception, these renewable plants usually operate at relatively factors. A variety of investigations and measurements on wet and
low temperatures. The power generation efficiencies are dry natural draft cooling towers subject to crosswinds have been
necessarily lower at lower temperatures. Therefore, compared to carried out. Du Preez and Kroger [5,6] conducted a two-month long
full scale measurement of an operating natural draft dry-cooling
tower and revealed that wind effect on such towers causes a signif-
⇑ Corresponding author. Tel.: +61 7 336 542 48. icant reduction in the heat dissipation rate of the tower. They also
E-mail address: y.lu7@uq.edu.au (Y. Lu).

http://dx.doi.org/10.1016/j.enconman.2014.12.018
0196-8904/Ó 2014 Elsevier Ltd. All rights reserved.
Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248 239

Nomenclature

A area (m2) S/ volumetric source term for variable quantity /


Aa, Afr, Ar air-side area, front area and fin-root area of heat T, Ta temperature, air temperature (K)
exchangers, respectively (m2) Tavg, Tr mean air temperature and heater surface tempera-
Ac surface area of numerical cell (m2) ture, respectively (K)
a constant DTa, DT⁄ air temperature difference (K) and dimensionless
a1–a4 coefficients temperature difference
C discharge coefficient U, V, W velocity components in x-, y-, and z-direction (m s1)
c constant Vc numerical cell volume (m3)
cp specific heat (J kg1 K1) v velocity scalar (m s1)
D tower diameter (m) x, y, z cartesian co-ordinates
d outer diameter of finned tube (m)
Eu Euler number Greek letters
F source term for momentum equations a permeability (m2)
Fr Froude number b bulk thermal expansion coefficient (K1)
FT temperature correction factor l viscosity (kg m1 s1)
Gr Grashof number q, q density and mean density (kg m3)
H height, elevation (m)
h convective heat transfer coefficient (W m2 K1)
Vectors
Gk, Gkb generation term of k due to mean velocity gradients V velocity
and buoyancy, respectively
Gx, Gxb generation term of x due to mean velocity gradients
and buoyancy, respectively Subscripts
Kr, Kh, Km pressure loss coefficient a air
k turbulent kinetic energy (m2 s2) cw cross wind
e effective
ma air mass flow rate (kg s1)
Nu Nusselt number h heater
n exponent hx heat exchanger
i, o inside or inlet and outside or outlet
P pressure (Pa)
Pr Prandtl number m, p model and prototype
pt, pd fin pitch and tube diagonal pitch, respectively (m) N pure natural convection
Q heat transfer rate (W) r radiator
t tower
q heat flux (W m2)
R gas constant (J kg1 K1) u overall
Re Reynolds number 0, ref reference value
S modulus of the mean rate-of-strain tensor

compared their measurements with numerical simulations and the inlet height (i.e. distance between the horizontal heat
reported good agreement [5]. Wei et al. [7] investigated the exchangers and ground) is usually over 12 m [15] which accounts
crosswind effect on NDDCTs with vertical heat exchangers through for only 1/10 of the total tower height, while in the 15 m-tall
a 1:200 scaled experiment model and concluded that wind lowers small NDDCT the inlet height is 3 m. The larger ratio of inlet
the efficiency of dry-cooling towers. Numerical studies by Su et al. height to total tower height in small towers exposes more
[8], Fu and Zhai [9], Al-Waked and Behnia [1,10], Reshadatjoo et al. proportion of the tower to crosswind. Finally, because less tower
[11], and Goodarzi et al. [12,13] arrived at similar results. All of and heat exchanger support is needed resulting in a smaller flow
these previous studies focused on large natural draft dry cooling resistance, the horizontal airflow effect in small tower inlet is rel-
towers over 100 m in height and 70 m in base diameter with heat atively stronger. As the result of these factors, the natural convec-
rejection rates exceeding 100 MW. tion airflow in small NDDCTs is much more vulnerable to wind.
However, on small natural draft dry cooling towers with the But this does not mean crosswind effect is always harmful. In fact,
height less than 30 m, the crosswind effect could be very different if the heat exchanger bundles are arranged horizontally and allow
from that in large towers. The authors conducted a numerical the air flows downward (reversely) freely, it was found that cross-
investigation on a 15 m-tall small natural draft dry cooling tower wind could enhance the total heat transfer of the tower in certain
[14]. In this study, a 3D full scale CFD tower model was simulated conditions [14].
under different wind speeds. At crosswind speeds up to 5 m/s, the Previous studies by the authors were all based on numerical
effect was similar to those observed in other studies with taller simulations. In this paper, results from an experimental study are
towers: the tower performance decreased with increasing cross- reported. A scaled version of the prototype 15 m-tall natural draft
wind speed. But further increase of the wind speed resulted in a dry cooling tower used in previous CFD studies was built and
reversal of this tendency [14]. No such reversal has been explicitly tested in a wind tunnel. The heat exchangers were modelled using
reported in previous studies. There are several aspects in which a round finned-tube electric heater coupled with extra flow resis-
short towers differ from large ones. Firstly, because of the shorter tance. The experimental data were analysed and compared with
height, the natural convective buoyancy effect in small towers is the CFD results. Finally, the variation of cooling tower heat dump-
much weaker. Secondly, small cooling towers are not simply ing rate with the crosswind speed were quantitatively explained
scaled copies of large ones. For example, in large cooling towers, through a proposed general expression.
240 Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248

2. Experiment design and rigs set up laboratory. For example, if the dimension of scaled tower model is
1/10 of the prototype, the vaN in the model is required to be 10
2.1. Scaling law of the model times larger by the similarity of ReD. However under that large
vaN, Fr in the model will never equal to that in the prototype. For
The cylinder-shaped prototype natural draft dry cooling tower similar reasons, Grashof number cannot satisfy the similarity
modelled in the previous CFD study is 15 m tall and 12 m in the either. Furthermore, the density ratio qao/qai is not considered in
diameter with a 3 m tower inlet height [16]. The air motion in this the similarity either as it is dependent to the air temperature dif-
numerical model is driven by buoyancy, which satisfies the ferences. As a result, only limited similarity conditions were able
momentum conservation equation using Boussinesq’s approxima- to be achieved between the prototype and the experimental model,
tion, i.e.: and Table 1 summarizes all the key dimensionless parameters and
dV their similarity criteria used in the scaled cooling tower model.
q0 ^  rP þ l$2 V
¼ q0 gbðT  T 0 Þk ð1Þ The subscripts m and p in Table 1 denote model and prototype,
dt
respectively. Eq. (8) is satisfied by controlling the wind speed. Eqs.
where the term with k ^ represents the buoyancy force, existing only
(9) and (10) are implemented by finding proper air temperatures
in vertical direction. Constants q0 and T0 are the ambient (refer- and flow resistance, which will be discussed below. To increase
ence) density and temperature, respectively. With the presence of the validity of the experimental findings, a supplementary CFD
crosswind, the mean velocity of air flow inside the cooling tower, model was built with exactly the same dimensions as the experi-
va, can be proposed as a function of eight parameters, namely: mental rig.
v a ¼ f ðv aN ; v cw ; qai ; qao ; H; D; g; lÞ ð2Þ
2.2. Model set up
where vaN is the averaged air flow velocity in the tower under pure
natural convection condition (windless condition); vcw is the cross- The scaled experimental model is 1.2 m tall and 0.96 m in diam-
wind speed at the height of tower outlet. qai and qao are the inlet eter with a scale ratio of 1:12.5, and has the same cylindrical shape
and outlet air densities. Since the air is assumed as ideal gas here, as its prototype. The model consists of three main components: a
the densities are calculated through qa = P0/RT, where R = 287.08 J/ cylindrical tube as the cooling tower body, a circular finned-tube
kg K and the absolute ambient pressure P0 is roughly 1 atm. H and electric heater as the horizontally arranged flat heat exchangers
D are tower height and diameters, respectively. As a key parameter and a stand as the tower base supports, as shown in Fig. 1.
in NDDCT’s design theories, vaN satisfies the draft equation:

qa v 2aN Table 1
ðqai  qao ÞgðH  Hi Þ  K hx ð3Þ
2 The key scaling parameters used in the experimental model.

where Hi is the tower inlet height, Khx is the pressure loss coefficient Scaling parameters Similarity criteria
H H
of heat exchangers. Aspect ratio of tower (7)
D m ¼ D p
In order to make the airflow condition in the scaled experimen-    
Crosswind speed ratio v cw v cw (8)
v aN m ¼ v aN p
tal model similar to that in the CFD prototype, Eqs. (1) and (2) are ! !
Froude number – Fr (9)
nondimensionalized first, yielding: v aN
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
q qao ¼ v aN ffi
pffiffiffiffiffiffiffiffiffiffiffiffiffiffi
q qao
ai gH ai gH
qao qao
m p
dV  Gr ^ 1    
¼ 2 Tk  Eur P þ $2 V  ð4Þ Euler number – Eu DP a
qa v 2aN m ¼
DP a
qa v 2aN p
(10)
dt Re Re
 
va v cw qao H 2
¼F ; ; ; Fr ; ReD ð5Þ
v aN v aN qai D
where the Grashof number Gr, the Reynolds number ReD, the Euler Unit mm
number Eu, and the densimetric Froude number Fr are defined
below: 960
2 3
gbðT r  T av g Þq aH qa v aN D
Gr ¼ ; ReD ¼ ;
l2 l
DP a 1 v aN
Eu ¼  K hx ; Fr ¼ qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ð6Þ
qa v 2aN 2 qai qao
gH
qao

In Eq. (6), Tavg, qa, and DPa are the mean air temperature, the
mean air density, and the air pressure loss across the heat exchan- 960
ger bundles, respectively. Tr is the mean surface temperature of
heat exchangers. Both Gr and ReD are based on the cooling tower
dimensions. It is noted that the Gr is actually related to Re2D =Fr 2 .
Because the Boussinesq’s approximation states that (qai  qao)/
qao = b(Tao  Tai), whereas (Tao  Tai) correlates with (Tr  Tavg). In
addition to Grashof number and other dimensionless numbers in
Eq. (6), three new independent dimensionless parameters are
defined in Eq. (5), namely: wind speed ratio vcw/vaN, density ratio
24 0
qao/qai, and cooling tower aspect ratio H/D.
Theoretically, the dynamic similarity between the scaled model
and the prototype is achieved when all above dimensionless
parameters are the same for both. However, it is impossible to sat-
isfy the similarity for ReD and Fr at the same time in a wind tunnel Fig. 1. The dimensions of the scaled cooling tower model with the round heater.
Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248 241

The heater contains 27 heating spiral-fin tube elements of dif- 2.3. Testing instruments and methods
ferent lengths which are specially designed and manufactured so
that they generate same heat at each unit length. The heater is The schematic diagram of the experiment system is shown in
powered by three-phase AC and has a maximum heating power Fig. 2. In the cooling tower model, the temperature sensors are
of 25 kW. All the heating tube elements are arranged in a plane arranged at five levels: underneath (90 mm under the heater), hea-
with a constant spacing Pt of 35 ± 2 mm between any two tubes. ter level, bottom (50 mm above the heater), middle (480 mm above
The tube diameter – do and fin diameter – df are 13 ± 0.2 mm and the heater), and top (50 mm below the tower exit), while the veloc-
24.8 ± 0.2 mm, respectively. ity sensors are mainly in the middle level of the tower body. Tem-
The geometric dimensions of the heater need not be scaled with perature sensors at the heater level are directly attached to the
the dimension ratio since the heat exchanger bundles are treated surfaces of finned tubes. At other levels, both temperature and
as a high-temperature porous medium in authors’ studies. There- velocity sensors are arranged in either a central straight line align-
fore the heater only needs to provide heat and resistance for the ing with the wind direction in a pitch of 120 mm or a circular pat-
airflow. The local heat transfer details and the flow fields between tern around the central axis, as seen in Fig. 2. Table 2 lists the main
the tubes are not of interest to the purposes of the current study. sensors/instruments used.
The overall pressure drop coefficient through the heater Kh can The experiment is run based on two basic modes: constant
be calculated using the correlation for single-row heat exchanger heating power and constant heater surface temperature. In the first
bundles with similar dimensions [17], i.e.: mode, the electric power of the heater is fixed, which corresponds
 1:849 to the CFD model with a constant heat flux. In the second mode,
Pt Aa the surface temperature of the heater finned tube is monitored
K h ¼ 2:271Re0:325
c ð11Þ
do Ac by the attached sensors and controlled by the PC. This constant
temperature equals to the heater surface temperature in pure free
where the Reynolds number Rec = qvcdo/l is based on the minimum convection when there is no crosswind. This model corresponds to
flow area of the heater. Ac and Aa is the minimum free flow area and the CFD model with a fixed heat exchanger temperature.
total surface area of the heater, respectively. During the measurements, the flow conditions at each cross-
The pressure loss of the heater is not enough to validate Eq. (10) wind speed remain stable for at least 10 min before starting lod-
and a round mesh screen is placed just above the heater during the ging the measured data. And the lodgment is at a sampling rate
experiments to supply the extra pressure resistance. The pressure of 1 Hz lasting for at least 10 min.
loss coefficient Km can be estimated by the following correlation:
  
1 1  a2 2.4. Wind tunnel
Km ¼ ð12Þ
C2 a2
An open circuit wind tunnel [18] is used in the experiment. The
where a is mesh permeability, and C is discharge coefficient, which main fan of the tunnel is a centrifugal blower driven by a 75 kW
is given as a function
pffiffiffiffiffiffi of mesh aperture-based Reynolds number Re, motor with the capacity to deliver up to 20 m3 air per second
namely: C ¼ 0:1 Re for range Re 6 20. By selecting a proper mesh [19]. The working section where the cooling tower model is placed
size, the total pressure loss coefficient Kh + Km achieves a value that has a length of 8 m and the cross-section of 1.75 m by 1.75 m.
satisfies Eq. (10). There is a clearance of 0.55 m between tower top and the section
The electric input power of the heater is adjustable through a ceiling.
three-phase thyristor controller. So the air exiting the heater can Considering that the limited ceiling height may affect the heat
obtain a desired temperature Tao and consequently a density qao dumping performance of the cooling tower model, a parallel test
under pure natural convection conditions. With this controlled was done with a part of working section replaced by an open chan-
density, the similarity in Froude number, i.e. Eq. (9) can be nel without the ceiling. The channel simply consists of two smooth
satisfied. boards which the two vertical walls on two sides. The channel has

Sensors arrangements in
cross-section of the tower Cooling tower

Data
Sensors Top acquisition
system
Middle
36° 300 mm

Bottom Heater
2m power
Circular pattern Heater
controller
Wind
direction
120 mm Ambient Underneath

PC
Signal
conversion
Central line pattern module

Fig. 2. The schematic diagram of experiment system and the layouts of the sensors.
242 Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248

Table 2
Sensors/instruments used in the experiment.

Quantities measured Sensors/instruments Measuring range Uncertainty/accuracy


Air temperature Thermistor 0–150 °C ±0.2 °C
RTD 0–150 °C ±0.2 °C
Air velocity Hot-wire anemometer (OMEGA) 0–5.08 m/s ±1.5% of full measuring range
Hot-wire anemometer (TSI) 0–30 m/s ±3% of reading
Current Digital voltage/ampere meter 0–90 A ±0.5% of reading
Voltage Digital voltage/ampere meter 0–500 V ±0.5% of reading

the same height and span as the wind tunnel working section so criteria are that the scaled residuals of all variables (except energy)
that it can join up with the remaining part of latter perfectly. The drop to the order of 105 and the monitored variables remain sta-
scaled cooling tower model was tested inside the open channel, ble when iterating. The 1.2 m-high CFD model is discretised by the
and in spite of the absence of ceiling, the airflow attacking on the structured prism mesh. The cell size of near wall or in high-gradi-
tower model is found generally uniform. The measured results ent regions is refined to 20 mm, so that the total amount of the
were compared with those obtained in the original working sec- mesh cells is around 1,750,000. A test for grid independence was
tion. It was found both results had small differences less than 7% done before the final simulations.
for the crosswind speed of 1.5 m/s or higher, but at lower speeds
there were some moderate differences up to 26%. Therefore, final
results for low crosswind speeds (<1.5 m/s) discussed in this study
were actually obtained in the open channel configuration. 3.2. Boundary conditions

The no-slip adiabatic wall boundary condition in [14] is applied


3. Comparable CFD model for validation
on two lateral sides. The top face is set as the wall or pressure out-
let boundary, with the latter corresponding to the open channel
Since the flow conditions for the scaled tower model and the
tests. The upstream and downstream faces of the domain are set
15 m-tall cooling tower prototype are not completely similar, a
to velocity inlet and pressure outlet, respectively. In the velocity
new 3D CFD model which is identical to the experimental cooling
inlet boundary the uniform velocity profile of the wind tunnel is
tower was built to validate the results obtained in the wind tunnel
used with the turbulence intensity I calculated by:
tests. This CFD tower model has the exactly same geometric
dimensions: 1.2 m tall, 0.96 m in diameter, and 0.24 m in tower
inlet height as well as the same characteristics of heat exchangers. 1=8
I ¼ 0:16Rehd ð13Þ
The computational domain has the same size of the wind tunnel
working section as shown in Fig. 3 for windy conditions, while
for the no-wind case, a cylindrical domain [14] is used. where Rehd is the Reynolds number based on hydraulic diameter
The modelling approach described in author’s previous work which is 1.75 m here.
[14] is used in this CFD model, which is briefly summarized here. The 1.2 m-tall CFD model uses the porous media associated
with the radiator boundary simulate the heat exchanger. The por-
3.1. Solver and mesh ous media represent the pressure loss across the heat exchanger by
adding an additional source term Fi in each momentum equation,
The numerical simulation is implemented using the commercial while the radiator boundary condition only reflects the heat trans-
CFD code Fluent. The pressure-based steady-state solver is used, fer between the heat exchangers and the air by computing the heat
which bases the governing equations on the conservation equa- flux qr. Fi and qr are calculated using the equations below [21]:
tions of mass, momentum, and energy. The airflow turbulence is
modelled using the realizable k–e model which has a better ability  
to capture the mean feature of complex flow structures than the le K
Fi ¼  v þ qv 2 ði ¼ x; y; zÞ and qr ¼ hr ðT r  T ao Þ ð14Þ
standard k–e model does at a same computing cost [20]. The air a i 2 i
is treated as incompressible through the Boussinesq’s approxima-
Both the aerodynamic and thermal characteristics of this heat
tion. The second order of upwind and segregated algorithm-SIM-
exchanger model are same as those in the experimental model
PLE are applied to the discretization scheme. The convergence
rather than the CFD prototype. Specifically, a is the permeability
of mesh screen and K is the sum of kh and km in Eqs. (11) and
(12). The total convective heat transfer coefficient hr can be
Wind
Unit: m roughly estimated by the heat transfer correlation proposed in
direction 8
[17] which is also valid for this heater, i.e.:
Velocity
0.96 Wall/Pressure outlet
inlet
 0:209
Wall hr do Pt
1.2 Nu ¼ ¼ 0:495Re0:509
c ð15Þ
1.75 k do
* Wall
Pressure With above modelling approaches, all the dimensionless scaling
y outlet
parameters in this CFD model are identical to those in the experi-
Porous medium 1.75 ment. The results from this model will be therefore directly com-
x
z and Radiator pared with the experiment results. The comparison with the
Porous jump
15 m-tall prototype will also be reported in terms of dimensionless
numbers, although its agreement with the experimental results is
Fig. 3. The identical CFD cooling tower model and the boundary conditions. expected to be weaker for the full-scale cooling tower.
Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248 243

4. Results and discussions Table 3


The uncertainty of measured velocity and temperature when the heating power is
5.216 kW.
4.1. Non-wind case and error analysis
Measured quantity Arithmetic mean over all Standard
sensors deviation
The scaled NDDCT model was tested in a pure natural convec-
tion manner first without using the wind tunnel. The heater in this Velocity at middle level 0.32 m/s 0.03 m/s
Top level temperature 42.5 °C 0.8 °C
case worked at certain constant powers. The natural convective
Middle level temperature 43.1 °C 0.4 °C
airflow velocity and temperature were measured by the sensors Bottom level temperature 43.3 °C 0.2 °C
at positions illustrated in Fig. 2. Figs. 4 and 5 plot the real time Underneath level 25.9 °C 0.2 °C
mean data recorded at different levels in a period of 700 s when temperature
the constant power is P he ¼ 5:216 kW. Ambient (inlet) 24.7 °C 0.04 °C
temperature
The uncertainty analysis for each sensor was done based on the
measured data following the procedure introduced in [22]. Table 3
lists the mean velocity and temperature at each corresponding
Table 4
level and their standard deviations. Velocity data has a relative
A comparison between the experimental and CFD results when the heating power is
large uncertainty which indicates that the free convective air flow 5.216 kW.
in such scale tower is highly turbulent. Therefore, the measure-
Parameters Measurement 1.2 m-tall CFD model
ment should be taken over a long period of time (>10 min).
A direct comparison of the results between the measurement Mean air velocity (vaN) 0.32 m/s 0.33 m/s
Mean air outlet temperature 43.3 °C 43.6 °C
and the identical scaled CFD model (1.2 m-tall) is made in Table 4,
(bottom level)
which indicates good agreement between both. Total heat transfer rate (QN) 4926 W 5099 W
The total heat transfer rate 4926 W in the measurement column
refers to the heat absorption rate which is calculated by Eq. (16)
using the average temperature and air velocity in Table 4:
The measurement results in the no-wind case have verified that
the target similarity is satisfied for the Froude number and Euler
qai þ qao
Q N ¼ ma C pa ðT ao  T ai Þ ¼ v aN AC pa ðT ao  T ai Þ ð16Þ number. Table 5 tabulates the calculated Fr and Eu of the CFD pro-
2
totype and the scaled model at the heating power of 5.216 kW. The
other dimensionless parameters in Eqs. (4) and (5) except the wind
where qai and qao are calculated using q = P0/RT. This calculated speed ratio are also included in the table for a comparison.
heat transfer rate is 5.6% smaller than the heating power of the hea-
ter Phe. 4.2. Crosswind effects at constant heat flux

The measurements under crosswinds was run first at the con-


0.8
Mean air velocity stant heating power mode, e.g. the heater operated at
0.7 Phe ¼ 5:216 kW. Correspondingly, the radiators in CFD models
0.6 had constant heat flux.
Velocity (m/s)

0.5
4.2.1. Mean velocity
0.4
Under wind conditions, the hot airflow speed va inside the
0.3 tower is dependent on both the buoyancy and the crosswind,
0.2 and its direction is no longer as uniform as in the case of no-wind.
0.1 In the experiment, va is the mean value over all the measurements
of the anemometers arranged in both the layouts at the model
0
0 100 200 300 400 500 600 700 middle level. As defined in Eq. (5), the ratio va/vaN is a function of
Time (s) vcw/vaN. Fig. 6 shows the correlation obtained in the experiment
model (solid line), the 1.2 m-tall identical CFD model and the pro-
Fig. 4. The real-time mean air velocity at tower model middle level as indicated totype CFD model (15 m-tall). The error bars show the measure-
under pure free convection condition when the heating power is 5.216 kW. ment uncertainty estimations for both x and y axis.
All three show a similar turn-around trend that first decrease
and then increase with a minimum somewhere. But the slopes of
50 the curve for the 15 m-tall prototype CFD model are different from
Top
45 the other two. This is mostly because the similarity between the
Middle
Temperature (°C)

40 Bottom
Underneath Table 5
35
Ambient Comparisons of the dimensionless parameters between the prototype cooling tower
30 and the scaled model.

25 Parameters CFD prototype Scaled model


(15 m-tall) (at the heating power
20 of 5.216 kW)

15 Froude number – Fr 0.104 0.109


0 100 200 300 400 500 600 700 Euler number – Eu 27.31 26.37
Aspect ratio – H/D 1.25 1.25
Time (s)
Reynolds number – ReD 276,103 17,774
Grashof number – Gr 3.19  1012 4.27  109
Fig. 5. The real-time mean air temperature at different levels as indicated under
Density ratio – qao/qai 0.963 0.941
pure free convection condition when the heating power is 5.216 kW.
244 Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248

2 absolute air speeds were taken in CFD models. Calculations on


1.8 measurement these results suggest that the averaged air speed at the plane in
CFD 15 m-tall Fig. 7(b) is the lowest with the highest speed occurring in Fig. 7(d).
1.6
CFD 1.2 m-tall
1.4
1.2 4.2.2. Temperature distribution
va / vaN

1 The temperature distribution is investigated to better under-


stand the airflow behaviour. The air temperature is measured at
0.8
seven positions along the aforementioned central line of each level
0.6
inside the cooling tower model. To eliminate the influence of the
0.4
environmental temperature on the experiment results, the temper-
0.2
ature difference DTa is defined in Eq. (17):
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 DT a ¼ T a  T 0 ð17Þ
vcw / vaN
where Ta and T0 are the temperature at the measurement point and
Fig. 6. Air velocity vcw/vaN changes with the crosswind speed at middle plane as
constant inlet temperature, respectively. Figs. 8–10 plot the distri-
indicated, both experimental and numerical results at constant heat flux.
butions of the DTa in the central lines with error bars at different
levels as indicated when crosswind speed changes from 0 m/s to
model and the prototype in CFD simulations is not completely sat- 3 m/s. The x-axis in these figures is ratio of x to tower diameter D,
isfied. On the other hand, the comparison between the experimen- where x is the x-coordinate of the position of a temperature sensor.
tal result and that in the 1.2-tall m CFD model shows a generally And the crosswind direction is same as the x-axis, namely: x/D = 0 is
good agreement. Some difference occurs when the velocity ratio windward side while x/D = 1 is leeward side.
is 11 or more. The temperature distributes nearly symmetric along with the
It is noted that the speed sensors used in the experiment only central line at any level of the tower in free convection case. The
measured the local air speeds at the sensor tips but not the precise crosswind tends to increase the temperature much more on wind-
flow directions. This fact implies that the observed increase of air ward side than on leeward side in the tower top, as the draft air-
speed post the critical wind speed in the measurement can be flow on windward side slows down while on the other side the
attributed more to the airflow circulations in the cooling tower ambient cool air penetrates into the tower. At the measuring level
than the acceleration of the uni-directional airflow. In fact, similar underneath the heat exchangers, temperature increases signifi-
situations can be found in the CFD results from the 1.2 m-tall cool- cantly in windward side when the crosswind speed rises. These
ing tower model. Fig. 7 shows the velocity vectors at mid-xy plane profiles clearly indicate that the reversed airflow occurs at wind-
of the cooling tower under no-wind condition and at crosswind ward part due to the local air vortices, which brings heat down
speeds of 2 m/s, 4 m/s, and 6 m/s, respectively. 2 m/s, 4 m/s, and from the heat exchangers. At bottom level above the heat exchang-
6 m/s correspond to vcw/vaN of around 6.25, 12.5, and 18.75, respec- ers, the maximum temperature position generally moves from
tively. The red dashed lines represent the plane where the speed windward side towards leeward side as the wind speed increases,
sensors were placed in the experiment and where the averaged because the negative pressure zone under the heat exchanger in

Fig. 7. Velocity vectors at mid-xy plane under no-wind condition (a) and when crosswind speed = 2 m/s (b), 4 m/s (c) and 6 m/s (d).
Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248 245

40 0 m/s windward side is expanding. The position where vortex centre is


35
0.5 m/s has the lowest air speed and thus highest temperature.
0.75 m/s The temperature distribution obtained in experiment then is
30 1 m/s
compared with the results of the 1.2 m-tall CFD model using the
Ta-T0 (°C)

2 m/s
25 3 m/s dimensionless temperature difference as defined in Eq. (18):
4 m/s
20 Ta  T0
DT  ¼ ð18Þ
15 T aN  T 0
x/D=0
x/D=1
10 where the divider TaN  T0 is the temperature difference between
the outlet and inlet air of heat exchangers in pure natural convec-
5 y
0 0.2 0.4 0.6 0.8 1 z x tion case. Figs. 11, 12 are 13 show (Ta  T0)/(TaN  T0) in the central
x/ D lines of tower bottom, top, and under the heat exchangers from
both the experiment results with uncertainty estimations and the
Fig. 8. Temperature distributions in the central line of bottom level at different CFD results at crosswind speeds as indicated.
crosswind speed at constant heat flux.
These comparisons show a satisfying agreement between the
experiment and CFD results for bottom and underneath levels.
However at the tower top, the temperature distribution predicted
35 0 m/s
by CFD behaves quite different from that in experiment. In fact, the
0.5 m/s
30
0.75 m/s
air flow field near either the tower outlet or the tower inlet is
1 m/s rather complicated. Fig. 14 shows the turbulence intensity contour
25
2 m/s at the mid-xy plane of the 1.2 m-tall CFD model at the wind speed
Ta-T0 (°C)

20 3 m/s of 4 m/s. High turbulence intensity occurs in both the regions.


4 m/s
15
Under such a physical condition, the CFD results in the particular
regions would be sensitive to the choice of the turbulence model.
x/D=0
10 x/D=1 It is possible that the realizable k–e model used in this study over-
5 estimates the vortices [20,23]. Thus, the degree of the mixing of the
y
hot air coming up the tower with the cooler crosswind is overesti-
0 mated, resulting in different exit-plane temperatures. The situation
0 0.2 0.4 0.6 0.8 1 z x
x/ D might be improved with a more complicated, non-RANS
(Reynolds-Averaged Navier–Stokes) turbulence model like LES
Fig. 9. Temperature distributions in the central line of top level at different
crosswind speeds and constant heat flux. (Large Eddy Simulation) [24].

2 CFD 0.75 m/s


30 0 m/s
CFD 4 m/s
0.5 m/s
Measurement 0.75 m/s
(Ta-T0) / (TaN -T0)

25 0.75 m/s 1.5


Measurement 4 m/s
1 m/s
Ta-T0 (°C)

20 2 m/s
1
3 m/s
15 4 m/s
0.5
10
x/D=0
5 0
x/D=1 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
0 y x/D
0 0.2 0.4 0.6 0.8 1 x
z
x/ D Fig. 12. A comparison of temperature distributions in central line of top level when
crosswind speed is 0.75 m/s and 4 m/s between the experiment and CFD results at
Fig. 10. Temperature distributions in central line underneath the heater at different constant heat flux.
crosswind speeds and constant heat flux.

2.5
1.4 CFD 0.75 m/s
CFD 4m/s
2 1.2 Measurement 0.75 m/s
(Ta-T0) / (TaN -T0)

Measurement 4 m/s
(Ta-T0) / (TaN -T0)

1
1.5
0.8

1 0.6
CFD 0.75 m/s 0.4
0.5 CFD 4m/s
Measurement 0.75 m/s 0.2
Measurement 4 m/s
0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
x/D x/D

Fig. 11. A comparison of temperature distributions in central line of bottom level Fig. 13. A comparison of temperature distributions in central line underneath the
when crosswind speed is 0.75 m/s and 4 m/s between the experiment and CFD heat exchangers when crosswind speed is 0.75 m/s and 4 m/s between the
results at constant heat flux. experiment and CFD results at constant heat flux.
246 Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248

Fig. 14. Turbulent intensity contour at the mid-xy plane when crosswind speed is 4 m/s from CFD results.

4.3. Crosswind effect on overall heat transfer rate at constant heat the measurement result agrees quite well with the one in its iden-
exchanger temperatures tical 1.2 m-tall CFD model with the latter slightly larger. But at
higher velocity ratios (i.e. >12), the CFD curve starts flattening
To examine the crosswind effect on the total heat transfer of the out. This fact provides evidence that CFD model overestimates
heat exchanger, the experiment at variable heating power mode the airflow vortices near cooling tower outlet at high wind velocity
was conducted. During the measurements, the electric power of ratios and thus results in an underestimation of the cooling tower
the heater was regulated, so that the temperature of the heater performance.
surface at all wind speeds was maintained at the same value as The interesting trend of the heat transfer rate was preliminarily
the surface temperature in pure natural convection case. Because explained in author’s previous work as that with the presence of
of the energy conservation, this power was roughly equal to the crosswind, the heat from the horizontal heat exchanger bundles
total heat transfer rate by finned tubes of heater – Q. Correspond- is taken away by both the upward air stream through the tower
ingly the radiator in CFD models was set to a fixed temperature. outlet and the horizontal airflow through the tower inlet [14].
Similarly, a dimensionless total heat transfer rate can be defined The latter enhances significantly as the wind speed increases,
as Q/QN, where QN is the heat dumping rate in pure natural convec- resulting in a rise of the total heat transfer rate. In fact, the first
tion case. It is proposed that Q/QN is a function of wind velocity way in which heat is transferred and dissipated is dominated by
ratio vcw/vaN as well, i.e.: natural convection in upward direction, while the second way is
mainly via forced convection in horizontal direction. So the heat
 
Q v cw transfer in the cooling tower under crosswinds is a combined con-
¼f ð19Þ
QN v aN vection problem. If Nunatural and Nuforced denote the heat transfer
due to pure natural convection and pure forced convection respec-
The correlation obtained from the experiment data with error tively. The overall heat transfer coefficient of the cooling tower
bars are displayed in Fig. 15 where a comparison with the results under crosswind conditions – Nu can be expressed as [25]:
of two CFD models, namely 1.2 m-tall and 15 m-tall, is given as
 1=n
well. Nu ¼ Nunnatural þ Nunforced ð20Þ
All the total heat transfer rate curves in Fig. 15 experience a
similar trend-first decrease and then increase with the minimums where the exponent n is a constant and is suggested to be 3 or 4
at certain wind velocities. And for the reason again that the incom- [25].
plete similarity between the scaled tower model and 15 m-tall CFD In non-wind condition, the heat transfer coefficient NuN, which
model, the curve for the latter shows different behaviours. It is is exactly the same number as the pure natural convection coeffi-
noted from Fig. 15 that at wind velocity ratio between 0 and 12, cient Nunatural, can be calculated by empirical correlations whose
general term is similar to NuN ¼ a1 Rebd Pr1=3 , where Red is based on
the diameter of the heat exchanger tubes d and the air velocity
1.4 at the minimum free flow area – vc [15]. The exponents b varies
1.2 slightly case to case around 0.6 for 103 < Red < 2  105 [15,25].
Obviously vc is always proportional to vaN, thus Red = f(vaN).
1
When the crosswind exists, the vertical hot airflow is deflected
0.8 and thus slower while just leaving the tower exit, resulting in the
Q / QN

reduction in Nunatural. In an earlier study, Hooman [26] has con-


0.6 Measurement
cluded that the heat transfer coefficients ratio Nunatural/NuN can
0.4 CFD 15 m-tall
be roughly expressed using wind velocity ratio vcw/vaN, namely:
CFD 1.2 m-tall vffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
0.2 Nunatural uu 1
 tqffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ð21Þ
0 NuN
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 1 þ ðv cw =v aN Þ2
vcw / vaN
On the other hand, the forced convection heat transfer occurs
Fig. 15. The total heat dumped by the cooling tower at different crosswind speeds mainly when the airflow parallel passing by the heat exchanger
at constant heat exchanger temperatures. bundles. If one assumes the bundle to be a hot square plane, the
Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248 247

1.4 5. Conclusions
1.2
The effect of crosswind on the small natural draft dry cooling
1 towers is investigated in the wind tunnel experiment. The study
CFD results of 15m-tall
tower uses a 1:12.5 scaled cooling tower model equipped with a round
0.8 Combined convection
electric heater. The air velocity, temperature, and the heating
Q / QN

0.6 Natural convection term power have been measured under different crosswind conditions.
Forced convection term The experimental results are compared with the results from its
0.4
prototype CFD model – a 15 m-tall, 12 m in diameter NDDCT,
0.2 and a same-size CFD model (1.2 m-tall, 0.96 m in diameter). Based
on the comparison, a rough correlation of heat transfer rate and the
0
0 10 20 30 40 50 crosswind speed is proposed. The experimental study finds:
vcw / vaN
1. The results of the experiment and the 15 m-tall prototype CFD
Fig. 16. The heat dump rate–wind speed correlation for the 15 m-tall NDDCT. model show a similar trend in the heat dissipation rate subject
to the crosswind but the slopes of the curves are different. This
is because the similarity between the experimental rig and the
convective heat transfer coefficient over the plane is approximately
prototype is not completely satisfied. However, the results for
in the term of Nuforced ¼ a2 Recx Pr 1=3 [27], where Rex is based on the
the experimental rig and its exact CFD representation agree
forced parallel airflow speed and the distance x from the leading
generally well, which indicates that the CFD modelling is
edge of the bundle. Here x is relevant to the length or width of a
reasonable.
heat exchanger bundle. Obviously Rex correlates with the cross-
2. The cooling tower model experiment verifies that the reversed
wind speed vcw, i.e. Rex = f(vcw). c is typically 0.8 [28]. Therefore,
airflow exist near the heat exchanger level as the CFD models
similar to Eq. (21), a ratio of Nuforced to NuN can be defined, which
predicted. In certain high wind speeds, the CFD model might
is a function of vcw/vaN as well, i.e.:
overestimate the vortices near the tower outlet, resulting in a
pessimistic prediction of the cooling tower performance in this
crosswind speed range.
 0:8 3. The heat transfer coefficient of NDDCTs under crosswind can be
Nuforced a2 Re0:8
x Pr
1=3
v cw
¼ ¼ a4 ð22Þ proposed as a combination of a pure natural convection heat
NuN a1 Red Pr 1=3
0:6 v aN
transfer coefficient and a forced one. In small cooling towers,
Based on Eqs. (20)–(22), it can be finally proposed that: because of the low buoyancy-induced airflow, natural convec-
tion heat transfer is comparable with forced convection at high
wind speed range. Therefore, the total heat transfer rate experi-
 n  n 1=n ences a turnabout at a certain crosswind velocity. Below this
Nu Nunatural Nuforced velocity, the total heat transfer decreases with increasing wind
¼ þ
NuN NuN NuN speed. As the crosswind speed is increased above this critical
8" 9
<   0:25n " 
#  #n 1=n value, the forced-convection component becomes more and
v cw 2 v cw 0:8 = Q more dominant and the total heat transfer rate increases with
¼ 1 þ a3 þ a4  ð23Þ
: v aN v aN ; QN increasing crosswind speed.

In Eq. (23), a3 is an additional speed ratio correction factor to Acknowledgements


the proposal of Hooman [26]. Both a3 and a4 are functions of many
parameters including the Red and/or Grashof number of the cooling This research was performed as part of the Australian Solar
tower in still air, heat exchanger characteristics, and the cooling Thermal Research Initiative (ASTRI), a project supported by the
tower shape, e.g. the aspect ratio, etc. In NDDCTs, Q/QN is roughly Australian Government, through the Australian Renewable Energy
equal to Nu/NuN. Agency (ARENA).
Eq. (23) gives a general term of correlations between heat trans-
fer coefficient ratio Nu/NuN and the wind velocity ratio vcw/vaN for References
horizontal heat exchanger NDDCTs subject to crosswind. For a par-
ticular instance – the 15 m-tall prototype cooling tower discussed [1] Al-Waked R, Behnia M. The effect of windbreak walls on the thermal
in this paper, a standard nonlinear regression analysis has been performance of natural draft dry cooling towers. Heat Transfer Eng
2005;26(8):50–62.
made based on the above results to find out that the values of a3 [2] Zou Z, Guan Z, Gurgenci H. Optimization design of solar enhanced natural draft
and a4 are 0.033 and 0.052, respectively. The squared residual of dry cooling tower. Energy Convers Manage 2013;76:945–55.
this regression – R2 is 0.958 for n = 3. Thus, the correlation of Eq. [3] Gurgenci H, Guan Z. Dirigible natural draft cooling tower in geothermal and
solar power plant applications. In: 14th IAHR cooling tower and air-cooled
(23) with these numbers is plotted using the solid line in Fig. 16. heat exchanger conference, Stellenbosch, South Africa; 2009. p. 1–4.
The natural draft convection term and forced convection term in [4] Lu Y, Guan Z, Gurgenci H. Development of small natural draft dry cooling
Eq. (23) are also presented in the figure, while the dots repeat towers for geothermal power plants. In: The 15th IAHR cooling tower and air-
cooled heat exchanger conference, Beijing, China; 2011. p. 308–16.
the CFD results of the 15 m-tall tower shown in Fig. 15. [5] Du Preez AF, Kroger DG. Effect of wind on performance of a dry-cooling tower.
In small NDDCTs, the forced convection term gradually becomes Heat Recovery Syst CHP 1993;13(2):139–46.
comparable with natural convection one as the crosswind gets fas- [6] Du Preez AF, KrÖGer DG. Effect of the shape of the tower supports and walls on
the performance of a dry-cooling tower subjected to cross winds. Heat Transfer
ter, which is the direct reason why the overall heat dump rate fol-
Eng 1995;16(2):42–9.
lows the V-shaped trend. It is noted that this trend is different from [7] Wei QD, Zhang BY, Liu KQ, Du XD, Meng XZ. A study of the unfavorable effects
the one observed in large cooling towers which continuously of wind on the cooling efficiency of dry cooling-towers. J Wind Eng Ind
declines with the increase of the wind speed [5,10,26]. The reason Aerodyn 1995;54:633–43.
[8] Su MD, Tang GF, Fu S. Numerical simulation of fluid flow and thermal
is that the natural draft effect in large cooling towers is sufficiently performance of a dry-cooling tower under cross wind condition. J Wind Eng
strong so that the forced convection term is negligible. Ind Aerodyn 1999;79(3):289–306.
248 Y. Lu et al. / Energy Conversion and Management 91 (2015) 238–248

[9] Fu S, Zhai ZQ. Numerical investigation of the adverse effect of wind on the heat [19] French HM, Foster MP. A new wind tunnel facility for atomisation studies. In:
transfer performance of two natural draft cooling towers in tandem Conference on engineering in agriculture, Albury, NSW, Australia; 1992.
arrangement. Acta Mech Sin 2001;17(1):24–34. [20] Shih T-H, Liou WW, Shabbir A, Yang Z, Zhu J. A new k–e eddy viscosity model
[10] Al-Waked R, Behnia M. The performance of natural draft dry cooling towers for high reynolds number turbulent flows. Comput Fluids 1995;24(3):227–38.
under crosswind: CFD study. Int J Energy Res 2004;28(2):147–61. [21] A. Inc., FLUENT User’s Guide, in, ANSYS Inc., New Hampshire, USA; 2011.
[11] Reshadatjoo H, Pormahmod N, Moltagh SY. The effect of cross-winds on an [22] JCGM, Evaluation of measurement data — Guide to the expression of
indirect dry cooling tower with or without windbreaks. Proc Inst Mech Eng uncertainty in measurement, in, BIPM, France; 2008.
Part A – J Power Energy 2011;225(A5):635–46. [23] Franke J, Hirsch C, Jensen AG, Krüs HW, Schatzmann M, et al.
[12] Goodarzi M, Ramezanpour R. Alternative geometry for cylindrical natural draft Recommendations on the use of CFD in wind engineering. In: Jpaj vB, editor.
cooling tower with higher cooling efficiency under crosswind condition. Proceedings of the international conference on urban wind engineering and
Energy Convers Manage 2014;77:243–9. building aerodynamics. In: van Beeck JPAJ (Ed.), COST Action C14, Impact of
[13] Goodarzi M, Keimanesh R. Heat rejection enhancement in natural draft cooling Wind and Storm on City Life Built Environment, von Karman Institute, Sint-
tower using radiator-type windbreakers. Energy Convers Manage Genesius-Rode, Belgium; 2004.
2013;71:120–5. [24] Zhang Z, Zhai ZQ, Zhang W, Chen QY. Evaluation of various turbulence models
[14] Lu Y, Guan Z, Gurgenci H, Zou Z. Windbreak walls reverse the negative effect of in predicting airflow and turbulence in enclosed environments by CFD: Part 2-
crosswind in short natural draft dry cooling towers into a performance comparison with experimental data from literature. HVAC&R Res
enhancement. Int J Heat Mass Transf 2013;63:162–70. 2007;13(6):871–86.
[15] Kroger DG. Air-cooled heat exchangers and cooling towers. Tulsa, Okl, [25] Çengel YA, Ghajar AJ, Kanoglu M. Heat and mass transfer: fundamentals and
USA: Pennwell Corp; 2004. applications. New York: McGraw Hill Higher Education; 2011.
[16] Lu Y, Guan Z, Gurgenci H. CFD simulations on small natural draft dry cooling [26] Hooman K. Theoretical prediction with numerical and experimental
towers. In: Brandner PA, Pearce BW, editors. the 18th Australasian fluid verification to predict cross wind effects on the performance of cooling
mechanics conference australasian fluid mechanics society Launceston, towers. Heat Transfer Eng 2015;36(5):480–7.
Australia; 2012. [27] ASHRAE, ASHRAE HANDBOOK: Fundamentals, IP Edition ed., American Society
[17] Huisseune H, T’Joen C, Brodeoux P, Debaets S, De Paepe M. Thermal hydraulic of Heating, Refrigerating and Air-Conditioning Engineers Inc., Atlanta, GA,
study of a single row heat exchanger with helically finned tubes. J Heat USA; 2009.
Transfer-Trans ASME 2010;132(6):61801. [28] Incropera FP, Dewitt DP, Bergman TL, Lavine AS. Fundamentals of heat and
[18] He S, Guan Z, Gurgenci H, Hooman K, Lu Y, Alkhedhair AM. Experimental study mass transfer. 6th ed. USA: John Wiley & Sons Inc.; 2007.
of film media used for evaporative pre-cooling of air. Energy Convers Manage
2014;87:874–84.

You might also like