Contents Introduction
Introduction .......................................2 Capacity Ratings 50Hz(R-407C) ....17 SKM PACS Series Packaged Air Conditioners
Legend..............................................2 Capacity Ratings 60Hz(R-407C) ....19 are designed and manufactured to
Nomenclature ...................................2 Fan Performance Data ...................21 meet the requirements of the Gulfs severe
Component Features ........................3 Field Connections ...........................23 climatic conditions and are buill specifically for
Optional Features ............................ 6 Field Wiring Requirement Schem .. 23 outdoor installations, either on ground or roof
Selection Procedure .........................8 Typical Wiring Diagram...................24 level.
Engineering Specifications 50Hz ......9 Electrical Data ................................25
Engineering Specifications 60Hz ....11 Filters and Weights .........................29 The PACS Series Packaged Air Conditioners
Capacity Ratings 50Hz(R-22) .........13 Dimensional Data... ........................30 are ideal for warehouses, large halls, schools,
Capacity Ratings 60Hz(R-22) .........15 Installation ......................................34 mosques, or wherever the requirement is for
Guide Specifications .......................35 a heavy duty unit with a hermetic compressor.
Nomenclature
PACS-52 19 CY
Packaged Power Supply Code
Air Conditioner Y: 380-415V/3Ph/50Hz
P: 440V/3Ph/50Hz You name it.....We cool it.
Scroll Compressor R: 380V/3Ph/60Hz
E: 460V/3Ph/60Hz
Power supply frequency T: 220V/3Ph/60Hz
5 = 50 Hz
6 = 60 Hz C: for R407C, omitted if R-22
The PACS Series Packaged Air Conditioners is yet another unique Condenser coils are manufactured of seamless copper tubes
series from SKM incorporating a high efficiency cooling coil, heavy mechanically bonded to aluminum fins to ensure optimum heat
duty evaporator blower and motor resulting in an extremely rugged, transfer.
long-life, energy efficient, self-contained unit that will provide cooling
at higher efficiency over a long and extended life. Compared to the
traditional units available in the market, the PACS series Packaged
Units are very Iow on energy consumption.
The common standard features of all PACS series Packaged Units SKM PACS series, all models, are restricted to a 14FPI (1.8 mm)
include the following. fin spacing condenser coil. Gulf dust storms and the general level
of available maintenance in Gulf countries ensures this condenser
coil design shall provide long life and maintenance-free operation
with the least possibility operational blockage on the condenser.
Compressor Ample condenser surface and sensible air flow across the condenser
ensures a low temperature differential between condensing
Compressors used in PACS packaged unit series are hermetically temperature and the high Gulf ambients making the PACS
sealed, compact scroll with the following features: packaged unit perform efficiently and durably.
• Status
• Outputs
• Inputs
• Alarms
Microprocessor Controller
• Set points
All PACS series package units are equipped with a full function • Password
microprocessor based controller as a standard feature. The
controller is factory programmed for the control of evaporator fan,
compressors and condenser fans. The controller comes with a
built in keypad and display for simple but meaningful man machine
System Control Philosophy
interface. This controller provides complete operational control for
the unit and has built-in auto diagnostic capability that can signal
normal operation or alarm conditions as well as shutting down the The unit may be enabled or disabled through the control on/off
unit or system if necessary. switch in the unit mounted control panel. Control is based on room
temperature sensed by room unit. Evaporator fan motor starts first.
Compressors will be staged based on the set point and actual room
temperature. On an increase in room temperature, cooling stages
will be added and on a decrease in room temperature, cooling
stages will be removed from the system.
System Protection
Room Unit
The intelligent microprocessor based controller monitors all the
The controller comes with a loose supplied sleek and elegant design
safeties related to the unit and makes the necessary protections,
room unit for installing in the conditioned space. Communication by shutting down the entire unit or the effected circuit. The
between unit controller and room unit is through two wire interface. protection includes:
The communication cable should be 2 core, twisted pair, unscreened
with stranded conductors. Maximum distance between room unit and • Low suction pressure.
controller can be 700 meters. The room unit has a built in sensor
for measuring the room temperature. It transmits room temperature, • High discharge pressure.
set point, unit operating mode etc. to the unit controller. Control of • High compressor motor temperature. (For compressors with
the compressors is based on room temperature and the set point,
as standard. If unit control needs to be based on duct temperature, internal motor protector).
please specify during time of order. • Compressor short cycling.
• Evaporator fan motor overload
• Roll & push knob and 3 function buttons. Volt free contacts for run status, common fault status, auto mode
status and provision for remote on/off shall be provided as option
• Battery backed up built in real time clock. if required.
• Multiple authorization level to provide tight security for the control In addition, the PACS microprocessor can support the major BMS
system. protocols such as BACnet, Modbus & LON. Extra hardware may
be required depending on the protocol.
• Capacity control based on room temperature or return air
temperature.
• Alarm history.
Optional Features • A bag filter section to house 22”, 30” or 36” deep bag filters
having efficiencies as desired can also be provided, as required.
PACS series heavy duty packaged air- conditioners are available Filter sections come with latches to provide easy access for
with a multitude of optional features which makes design and removal and for maintenance.
selection extremely easy and capable of matching the most stringent • On 100% fresh air applications an initial sand trap louvre can
of requirements. effectively minimize entrance of sand into the air stream, sand
trap louvre (ASL) available on request.
Alternative Condenser Material
• High efficiency mini pleat panel filters are available as an
Made of copper tubes and alternative fin material and/or protective alternative for bag filter where space is limited. Filter sections
coating. come with latches to provide easy access for removal and for
• For Copper Fins, specify (FC). maintenance.
• For electrotinned Copper Fins only, specify (CFT).
• For Copper Finned Coils electrotinned post manufacturing, To order a sand trap louvre from SKM specify fresh air opening
specify (FCT). size with option ASL.
• For Pre-Coated aluminum fins, specify (FAP).
• For Aluminum Fins with Aeris post Coat Protection, specify
(FAA). Galvanized Frame And Base (GFB)
• For Copper Fins with Aeris post Coat Protection,specify (FCA).
Steel frame and base which are hot dip galvanized after
manufacturing process. This is recommended for highly corrosive
environments.
Alternative Evaporator Material
With or without sand trap louvre and bird screen on fresh air Side.
Electric heating batteries are made up of finned heating elements, This option is necessary and available for PACS models rated
constructed from high quality 80/20 nickel chrome resistance wire for 440V/3PH/50Hz or 460V/3PH/60Hz or power supplies without
centred in metal tube by compressed magnesium oxide. Helical neutral. When ordering for these voltages, this option must be
fins are tightly wound around the tubular heating element. ordered.
Heater batteries when ordered comes with stage contactors, primary Voltage Monitoring Module (VMM)
auto reset thermal safety cut-out, secondary manual reset thermal
safety cut-out and air flow switch. Power fuses / circuit breaker are To prevent PACS unit operation in the event of Phase loss, Phase
provided for heaters with total ampere exceeding 48 amperes. For reversal, and Under / Over voltage on the incoming line voltage.
smaller heaters, power fuses can be provided if specified. Control
of the heaters will be from the PACS microprocessor. Voltage Monitoring Module as per DEWA (DVM)
Under voltage relay as per DEWA regulations. This option is available
Following are the optional kW ratings for electric heater. Ratings
other than those specified here can be supplied on request. Consult for Dubai, UAE only.
SKM for details
Hot Gas Bypass System (GBP) BMS Interface Volt free Contacts (VFC)
With solenoid to enable operation of a large sized unit at very low Volt free contacts for run status, common fault status, auto mode
loads, during low load demand due to application requirements or status and provision for remote on/off shall be provided as option if
where unit is selected to work on 100% fresh air applications. required. For additional requirements, please contact SKM.
To provide energy saving benefits over mechanical thermostatic For interfacing the units with major BMS protocols such as BACNet,
Modbus or LON. Extra hardware may be required depending on the
expansion valve (TXV).
protocol.
Selection Procedure
PACS series packaged air-conditioners should be selected with care and using sound engineering judgement. Selections based on matching
total capacity alone or air flow rate alone may not be correct. To meet requirements of a specific application, sample procedure for selection
is given in examples below.
Selection Procedure :
Enter packaged unit capacity ratings R-22 at given condition and select unit size PACS - 5219 having total cooling capacity 203.1 MBh
(59.5 kW), and sensible cooling 149 MBH (43.7 kW), PI = 19.9 kW. Total sensible cooling capacities & power to be interpolated for
untabulated data.
Actual sensible capacity = Rated sensible capacity + 0.0011 (1 - BPF)(EDB - 80) x cfm - IP Units
Actual sensible capacity = Rated sensible capacity + 0.00123 (1 - BPF)(EDB - 26.7) x l/s - SI Units
SKM Computer Selections are available for quick, detailed and accurate selections.
ENGINEERING SPECIFICATIONS - 50 Hz
Model PACS 5215 5219 5224 5225 5228 5234 5239 5245 5249
TR 14.6 18.3 21.1 23.7 26.9 30.9 35.0 41.4 47.4
Cooling Capacity (1) (R-22)
kW 51.2 64.4 74.2 83.5 94.5 108.5 123.1 145.5 166.8
TR 13.5 16.9 19.6 22.0 24.9 28.6 32.5 38.3 43.8
Cooling Capacity (2) (R-22)
kW 47.3 59.5 68.9 77.5 87.7 100.7 114.2 134.7 154.1
TR 14.0 17.7 20.9 23.6 26.3 30.3 34.5 40.3 45.7
Cooling Capacity (1) (R-407C)
kW 49.1 62.2 73.5 82.9 92.6 106.7 121.3 141.7 160.6
TR 12.6 16.0 19.1 21.6 23.9 27.7 31.6 36.8 41.8
Cooling Capacity (2) (R-407C)
kW 44.4 56.1 67.2 75.8 84.0 97.3 111.0 129.5 146.9
Type - Hermetic Scroll Compressor
Quantity - 2 2 2 2 2 2 2 2 2
Compressor
US Gal 0.87 / 0.87 0.87 / 0.87 0.95 / 0.95 0.95 / 0.95 1.64 / 1.64 2.11 / 1.64 2.11 / 1.64 2.11 / 2.11 2.11 / 2.11
Oil Charge Ckt (A / B)
Liter 3.3 / 3.3 3.3 / 3.3 3.6 / 3.6 3.6 / 3.6 6.2 / 6.2 8 / 6.2 8/8 8/8 8/8
Type - Air cooled 3 or 4 rows 14 FPI (1.8mm) fin spacing, Cu tubes, Al fins
Condenser Coil ft² 26.3 26.3 26.3 35.6 40.0 40.0 53.3 64.0 72.0
Face Area
m² 2.4 2.4 2.4 3.3 3.7 3.7 5.0 5.9 6.7
Type - Propeller direct drive 960 RPM
Code / Quantity - 723/2 823/2 823/2 823/3 823/3 823/3 829/3 823/4 829/4
Condenser Fan
cfm 13400 17360 16400 25200 26160 24780 32040 36480 42880
Air Flow Rate
l/s 6324 8193 7740 11893 12346 11695 15121 17217 20237
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.75/2 1.5/2 1.5/2 1.5/3 1.5/3 1.5/3 1.5/3 1.5/4 1.5/4
Type - Direct expansion, Aluminum Fins, Copper Tubes
Evaporator Coil ft² 11.7 13.6 14.6 17.2 18.8 20.8 23.4 29.2 34.4
Face Area
m² 1.1 1.3 1.4 1.6 1.7 1.9 2.2 2.7 3.2
Type - Centrifugal double inlet double width belt drive
Code / Qty. - N15/1 N12/2 N12/2 N15/2 N15/2 N15/2 N15/2 N18/2 N18/2
Evaporator Fan
cfm 5200 6600 7300 8600 9400 10400 11700 14600 17200
Air Flow Rate
l/s 2454 3115 3445 4059 4436 4908 5522 6890 8117
Type - Totally enclosed, fan cooled Class F insulation, 4-pole IP55
Evaporator Motor
Size kW 2.2 3.0 4.0 4.0 5.5 5.5 7.5 7.5 11.0
lbs 12.3 / 12.3 12.6 /12.6 15.9 / 15.9 16.4 / 16.4 18.9 / 18.9 23 / 17.3 25.5 / 25.5 34.2 / 29.2 34.7 / 34.7
Refrigerant (R-22) Operating Charge Ckt (A / B)
kg 5.6 / 5.6 5.7 / 5.7 7.2 / 7.2 7.5 / 7.5 8.6 / 8.6 10.4 / 7.9 11.6 / 11.6 15.5 / 13.2 15.7 / 15.7
lbs 11.7 / 11.7 41255.0 15.1 / 15.1 15.5 / 15.5 17.9 / 17.9 21.7 / 16.4 24.1 / 24.1 32.4 / 27.6 32.9 / 32.9
Refrigerant (R-407C) Operating Charge Ckt (A / B)
kg 5.3 / 5.3 5.4 / 5.4 6.8 / 6.8 41097.0 8.1 / 8.1 9.8 / 7.4 10.9 / 10.9 14.7 / 12.5 14.9 / 14.9
Number of Refrigerant Circuits - 2 2 2 2 2 2 2 2 2
lbs 2065 2203 2376 2826 3062 3309 3552 4548 4859
Unit Operating Weight
kg 937 999 1078 1282 1389 1501 1611 2063 2204
Table 4
Notes :
(1). Capacity rating in accordance with AHRI standard 210/240 & 340 / 360.
(2). Capacity ratings based on evaporator entering air temperatures of 80/67 ºF (26.7/19.4 ºC) dry bulb/wet bulb and condenser entering air
temperature of 115 ºF (46 ºC).
(3). Capacity is gross capacity which does not include the effect of evaporator fan motor heat.
(1). Capacity rating in accordance with AHRI standard 210/240 & 340 / 360.
(2). Capacity ratings based on evaporator entering air temperatures of 80/67 ºF (26.7/19.4 ºC) dry bulb/wet bulb and condenser entering air
temperature of 115 ºF (46 ºC).
(3). Capacity is gross capacity which does not include the effect of evaporator fan motor heat.
ENGINEERING SPECIFICATIONS - 60 H z
Model PACS 6218 6223 6228 6230 6234 6240 6246 6253 6260
TR 16.8 21.5 24.7 27.9 31.2 36.0 40.9 48.3 55.3
Cooling Capacity (1) (R-22)
kW 59.1 75.4 87.0 98.1 109.6 126.5 143.7 169.9 194.4
TR 15.6 19.9 23.0 25.9 29.0 33.5 38.0 44.9 51.3
Cooling Capacity (2) (R-22)
kW 54.7 69.8 80.9 91.1 101.9 117.6 133.6 157.7 180.4
TR 16.4 20.7 24.1 27.1 30.2 34.8 39.4 46.3 52.6
Cooling Capacity (1) (R-407C)
kW 57.6 72.7 84.6 95.2 106.0 122.3 138.7 162.7 184.9
TR 14.8 18.7 22.0 24.7 27.3 31.7 36.1 42.2 47.9
Cooling Capacity (2) (R-407C)
kW 52.1 65.7 77.3 86.9 95.9 111.4 126.8 148.4 168.5
Type - Hermetic Scroll Compressor
Quantity - 2 2 2 2 2 2 2 2 2
Compressor
US Gal 0.87 / 0.87 0.87 / 0.87 0.95 / 0.95 0.95 / 0.95 1.64 / 1.64 2.11 / 1.64 2.11 / 1.64 2.11 / 2.11 2.11 / 2.11
Oil Charge Ckt (A / B)
Liter 3.3 / 3.3 3.3 / 3.3 3.6 / 3.6 3.6 / 3.6 6.2 / 6.2 8 / 6.2 8/8 8/8 8/8
Type - Air cooled 3 or 4 rows 14 FPI (1.8mm) fin spacing, Cu tubes, Al fins
Condenser Coil ft² 26.3 26.3 26.3 35.6 40.0 40.0 53.3 64.0 72.0
Face Area
m² 2.4 2.4 2.4 3.3 3.7 3.7 5.0 5.9 6.7
Type - Propeller direct drive 1150 RPM
Code / Quantity - 723/2 823/2 823/2 823/3 823/3 823/3 829/3 823/4 829/4
Condenser Fan
cfm 15880 21140 20020 30720 31860 30210 38700 44400 51760
Air Flow Rate
l/s 7495 9977 9448 14498 15036 14258 18264 20954 24428
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 1.1/2 2.2/2 2.2/2 2.2/3 2.2/3 2.2/3 2.2/3 2.2/4 2.2/4
Type - Direct expansion, Aluminum Fins, Copper Tubes
Evaporator Coil ft² 11.7 13.6 14.6 17.2 18.8 20.8 23.4 29.2 34.4
Face Area
m² 1.1 1.3 1.4 1.6 1.7 1.9 2.2 2.7 3.2
Type - Centrifugal double inlet double width belt drive
Code / Qty. - N15/1 N12/2 N12/2 N15/2 N15/2 N15/2 N15/2 N18/2 N18/2
Evaporator Fan
cfm 5200 6600 7300 8600 9400 10400 11700 14600 17200
Air Flow Rate
l/s 2454 3115 3445 4059 4436 4908 5522 6890 8117
Type - Totally enclosed, fan cooled Class F insulation, 4-pole IP55
Evaporator Motor
Size kW 3.0 4.0 4.0 5.5 5.5 5.5 7.5 7.5 11.0
lbs 12.8 / 12.8 13.1 / 13.1 16.5 / 16.5 17.2 / 17.2 19.7 / 19.7 24 / 18.1 26.5 / 26.5 35.6 / 30.3 36.2 / 36.2
Refrigerant (R-22) Operating Charge
kg 5.8 / 5.8 41066.0 7.5 / 7.5 7.8 / 7.8 41161.0 10.9 / 8.2 12.0 / 12.0 16.1 / 13.7 16.4 / 16.4
lbs 12.2 / 12.2 12.5 / 12.5 15.7 / 15.7 16.2 / 16.2 18.7 / 18.7 22.6 / 17.1 25.1 / 25.1 33.7 / 28.7 34.2 / 34.2
Refrigerant (R-407C) Operating Charge
kg 5.5 / 5.5 5.7 / 5.7 7.1 / 7.1 7.4 / 7.4 8.5 / 8.5 10.3 / 7.7 11.4 / 11.4 15.3 / 13 15.5 / 15.5
Number of Refrigerant Circuits - 2 2 2 2 2 2 2 2 2
lbs 2116 2270 2436 2931 3145 3399 3646 4667 4991
Unit Operating Weight
kg 960 1030 1105 1329 1426 1542 1654 2117 2264
Table 6
Notes :
(1). Capacity rating in accordance with AHRI standard 210/240 & 340 / 360.
(2). Capacity ratings based on evaporator entering air temperatures of 80/67 ºF (26.7/19.4 ºC) dry bulb/wet bulb and condenser entering air
temperature of 115 ºF (46 ºC).
(3). Capacity is gross capacity which does not include the effect of evaporator fan motor heat.
Notes: Table 7
(1). Ratings are based on 80ºF (26.7ºC) entering air dry bulb temperature. (2). Capacity is gross capacity which does not include the
effect of evaporator fan motor heat. (3). Direct interpolation is permissible. Do not extrapolate. (4). Shaded values are at 120ºF (49ºC)
condenser entering air temperature.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
Notes: Table 8
(1). Ratings are based on 80ºF (26.7ºC) entering air dry bulb temperature. (2). Capacity is gross capacity which does not include the
effect of evaporator fan motor heat. (3). Direct interpolation is permissible. Do not extrapolate. (4). Shaded values are at 120ºF (49ºC)
condenser entering air temperature.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
Notes: Table 10
(1). Ratings are based on 80ºF (26.7ºC) entering air dry bulb temperature. (2). Capacity is gross capacity which does not include the
effect of evaporator fan motor heat. (3). Direct interpolation is permissible. Do not extrapolate. (4). Shaded values are at 120ºF (49ºC)
condenser entering air temperature.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
Table 11
Notes:
(1). Ratings are based on 80ºF (26.7ºC) entering air dry bulb temperature. (2). Capacity is gross capacity which does not include the
effect of evaporator fan motor heat. (3). Direct interpolation is permissible. Do not extrapolate. (4). Shaded values are at 120ºF (49ºC)
condenser entering air temperature.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
Notes: Table 13
(1). Ratings are based on 80ºF (26.7ºC) entering air dry bulb temperature. (2). Capacity is gross capacity which does not include the
effect of evaporator fan motor heat. (3). Direct interpolation is permissible. Do not extrapolate. (4). Shaded values are at 120ºF (49ºC)
condenser entering air temperature.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data
pages (25 - 28) should be referred for the same.
Power hook-ups and control wiring of room unit as per Electrical hook-up diagram is all that is required to electrically connect any model of
PACS series .
Every PACS series package air conditioning unit requires, at most, field installed fused disconnect switches or circuit breakers, and room unit.
Refer below for a schematic representation of required field electrical hook-ups for a standard PACS series packaged air conditioning unit.
All field wiring must be done in accordance with applicable local and national codes.
For maximum recommended for fuse sizing and minimum circuit amps for cable sizing, see Page 25~28 of this bulletin.
Duct work should be connected with flexible connections to the PACS series. One or two drains suitably trapped, are required to be connected
to the drain outlet of all models of PACS series.
L1 L2 L3 N
*L *N
3 PHASE,
3 WIRE SYSTEM
440V/3PH/50Hz CIRCUIT BREAKER
220V/3PH/60Hz OR FUSED
460V/3PH/60Hz DISCONNECT SWITCH
(NOT BY SKM)
3 PHASE,
4 WIRE SYSTEM
380-415V/3PH/50Hz
L1
L2
380V/3PH/60Hz
L3
N
GROUND
L1
L2
ROOM UNIT
(LOOSESUPPLY) LINE VOLTAGE
FIELD WIRING
LOW VOLTAGE
FIELD WIRING
+ -
CE+ CE-
CONTROLLER
TERMINALS
CE+
UNIT
CE-
2 CORE UNSCREENED TWISTED PAIR CABLE (BY OTHERS)
PACS-SERIES
CONTROL PANEL
**PACS SERIES UNITS RATED FOR 440V/3PH/50HZ, 460V/3PH/60HZ, OR POWER SUPPLIES WITH OUT NEUTRAL
REQUIRE SEPARATE SOURCE OF CONTROL POWER SUPPLY THRU FIELD SUPPLIED & INSTALLED 15A/220V FUSED
CONTROL DISCONNECT SWITCH OR ORDER WITH FACTORY BUILT IN OPTION ' CXT '.
24
24
L3
N
C1 C2
T2 T1 M1 M2 S2 S1 T2 T1 M1 M2 S2 S1 C3 C4 C5 C6 C7
CM-1 CM-2
CR1 CR2
ROOM UNIT
(LOOSE SUPPLY)
NOTE:-
Typical Wiring Diagram
* Typical wiring diagram given hereis for units with 380~ 415/3/50 or
380/3/60, 4 wirepower supplies.
G G
OL * Wiring diagrams for 440/3/50, 220/3/60 or 460/3/60
I I CR1 CR2 CS + - power supplies areavailable on request.
MPCB5
2COREUNSCREENED * For 440/3/50 or 460/3/60 or power supplies without neutral,
LPS-1
LPS-2
TWISTED PAIR CABLE CXToption is amust.
(BY OTHERS)
RUN/STOP
DISC. PRESSURE-1
DISC. PRESSURE-2
MCB2 L E GEND
TFR TRANSFORMER
CS CONTROL SWITCH MPM MOTOR PROTECTOR MODULE
C CONTACTOR MPCB MOTOR PROTECTOR CIRCUT BREAKER
CCH CRANKCASEHEATER OL OVERLOAD RELAY
MCB MINIATURECIRCUIT BREAKER LSV LIQUID LINESOLENOID VALVE
CFM CONDENSER FAN MOTOR EFM EVAPORATOR FAN MOTOR
CM COMPRESSOR MOTOR CR CONTROL RELAY
24~_ RS485 PB LPS LOWPRESSURESWITCH
FIELD WIRING
HPS HIGH PRESSURESWITCH
M
M
M
M
M
M
M
B-
X1
X2
X3
X4
X5
X6
X7
X8
B1
B2
B3
A+
D1
D2
DG
CE-
REF
CE+
5V=
5V=
DU1
DU2
T1
T2
T3
T4
T5
T6
T7
24V=
24V=
** Provide Overcurrent, short circuit, earth fault protection &
disconnect means as required by local and national electric mode.
PACS Series - R22 & R407C
INFO
24V
SKM Packaged Air Conditioners
220~ 240V
ESC
C1 C2
T8
T9
24~_
G0
Q12
Q11
Q14
Q22
Q21
Q24
Q33
Q34
Q43
Q44
Q53
Q54
Q64
Q73
Q74
Q84
C
D01
D02
DL1
DN
DL2
T10
T11
T12
T13
T-IP
T-HI
CCH1
CCH2
HPS-1
HPS-2
LSV-1 LSV-2
COMP.-1
COMP.-2
CFM1
CFM2
CFM3
CFM4
EFM
E C1 C2 C3 C4 C5 C6 C7
SKM
SKM
SKMPackaged
PackageAir
Packaged AConditioners
d Air
ir C
Conditioning
ond
dittioning U
Units
nits
PACS
PACH
PACHSeries
Serie-sR22
Series R2&2 R407C
- R22
Electrical Data (R-22)
Power Supply : 380-415V/3PH/50Hz
Model Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan Motor
PACS MFA MCA ICF QTY RLA Each LRA Each QTY FLA Each LRA Each FLA LRA
5105 32 20 81 1 11 74 1 1.1 3.9 2.7 12.6
5107 32 22 113 1 12 101 1 2.4 8.9 2.7 12.6
5108 40 26 107 1 15 98 2 1.1 3.9 3.6 19.2
5109 50 32 139 1 19 130 2 1.1 3.9 3.6 19.2
5210 40 34 94 2 11 74 2 1.1 3.9 5.2 26.3
5112 63 38 155 1 23 145 2 1.1 3.9 5.2 26.3
5213 50 39 130 2 12 101 2 2.4 8.9 5.2 26.3
5114 80 47 192 1 28 175 2 2.4 8.9 5.2 26.3
5215 63 46 129 2 15 98 2 2.4 8.9 5.2 26.3
5219 80 60 177 2 19 130 2 3.9 17.2 6.6 35.6
5224 100 69 197 2 23 145 2 3.9 17.2 8.6 45.6
5225 100 77 203 2 24 145 3 3.9 17.2 8.6 45.6
5228 125 89 240 2 28 175 3 3.9 17.2 11.8 67.3
5234 160 100 280 1+1 37 28 215 175 3 3.9 17.2 11.8 67.3
5239 160 112 293 2 37 215 3 3.9 17.2 16.0 105.6
5245 200 128 352 1+1 46 37 270 215 4 3.9 17.2 16.0 105.6
5249 200 144 368 2 46 270 4 3.9 17.2 23.2 148.5
Table 17
Legend
MFA Maximum Fuse Amps (for fuse sizing), complies with RLA Rated Load Amps. (at worst operating condition)
NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with
NEC article 440-33.
ICF Maximum Instantaneous Current Flow
Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage
Legend
MFA Maximum Fuse Amps (for fuse sizing), complies with RLA Rated Load Amps. (at worst operating condition)
NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with
NEC article 440-33.
ICF Maximum Instantaneous Current Flow
Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage
F
F
F
MODEL FLAT FILTER VEE FILTER BAG FILTER
PACS- F G
SIZE H x L QTY. SIZE H x L QTY. SIZE H x L QTY. SIZE H x L QTY. SIZE H x L QTY.
5105 20 33.6 20x20 [508x508] 1
6106 [508] [853] 20x16 [508x406] 2 16x16 [406x406] 4 20x12 [508x305] 1
5107 20 40
[508] [1016] 20x20 [508x508] 2 16x20 [406x508] 4 20x20 [508x508] 2
6108
5108 20 40
6109 20x20 [508x508] 2 16x20 [406x508] 4 20x20 [508x508] 2
weights
LOADING POINTS TOTAL LOADING POINTS TOTAL
PACS- UNIT PACS- UNIT
A1 A2 A3 A4 WEIGHT A1 A2 A3 A4 WEIGHT
Ib. 219 226 291 294 1029 Ib. 223 230 293 296 1043
5105 6106
Kg. 99 103 132 133 467 Kg. 101 104 133 134 473
Ib. 223 230 305 308 1066 Ib. 227 235 309 312 1082
5107 6108
Kg. 101 104 138 140 483 Kg. 103 106 140 141 491
Ib. 309 309 401 382 1401 Ib. 315 315 407 388 1425
5108 6109
Kg. 140 140 182 173 636 Kg. 143 143 185 176 646
Ib. 328 328 433 414 1503 Ib. 334 334 440 421 1529
5109 6111
Kg. 149 149 197 188 682 Kg. 152 152 200 191 694
Ib. 347 351 426 427 1551 Ib. 356 361 431 433 1580
5210 6211
Kg. 157 159 193 194 703 Kg. 161 164 196 196 717
Ib. 347 347 450 431 1576 Ib. 356 356 458 439 1610
5112 6114
Kg. 157 157 204 195 715 Kg. 161 161 208 199 730
Ib. 363 369 449 453 1634 Ib. 375 381 456 460 1673
5213 6214
Kg. 165 167 204 205 741 Kg. 170 173 207 209 759
Ib. 329 352 424 457 1562 Ib. 343 366 431 465 1605
5114 6117
Kg. 149 160 192 207 708 Kg. 155 166 196 211 728
Ib. 448 456 577 584 2065 Ib. 465 472 586 593 2116
5215 6218
Kg. 203 207 262 265 937 Kg. 211 214 266 269 960
Ib. 481 490 609 622 2203 Ib. 502 511 622 636 2270
5219 6223
Kg. 218 222 276 282 999 Kg. 227 232 282 288 1030
Ib. 508 518 666 684 2376 Ib. 524 535 679 698 2436
5224 6228
Kg. 230 235 302 310 1078 Kg. 238 243 308 317 1105
Ib. 633 642 774 777 2826 Ib. 667 677 792 795 2931
5225 6230
Kg. 287 291 351 352 1282 Kg. 303 307 359 360 1329
Ib. 684 695 840 843 3062 Ib. 709 719 857 860 3145
5228 6234
Kg. 310 315 381 382 1389 Kg. 322 326 389 390 1426
Ib. 721 724 958 907 3309 Ib. 748 750 976 925 3399
5234 6240
Kg. 327 328 434 411 1501 Kg. 339 340 443 420 1542
Ib. 761 772 1008 1010 3552 Ib. 790 799 1027 1030 3646
5239 6246
Kg. 345 350 457 458 1611 Kg. 359 362 466 467 1654
Ib. 992 1024 1268 1265 4548 Ib. 1025 1060 1293 1290 4667
5245 6253
Kg. 450 465 575 574 2063 Kg. 465 481 587 585 2117
Ib. 1073 1112 1335 1339 4859 Ib. 1111 1152 1362 1366 4991
5249 6260
Kg. 487 504 605 607 2204 Kg. 504 523 618 620 2264
Table 28
Dimensional Data
6
PACS Models: 5105 to 5107 & 6106 to 6108
A1
LE GEND A3
1 - EVAPORATOR COIL
CERTIFIED DRAWINGS ARE
2 - EVAPORATOR FAN AVAILABLE ON REQUEST
3 - EVAPORATOR FAN MOTOR
4 - COMPRESSOR MODEL DIMENSIONS
5 PACS- L W A E
- CONDENSER COIL
5105 70 45 34 33.6
6 - CONTROL PANEL 6106 [1778] [1142] [864] [853]
7 - CONDENSER FAN 5107 74 56 38 40
6108 [1880] [1422] [965] [1016]
A2 A4
ALL DIMENSIONS ARE IN INCHES [mm]
10 DRAIN Ø1 [25] x2Nos. 10
[254] [254]
W L
E 1 36 A
= 13.03 = [25] [914]
[38]
6 [331] 1.5 7
11.38
[289]
FILTERED
7.1
[181] 5
[1312]
VENTILLATION
51.65
[1167]
ON BOTH SIDES
45.94
[508]
20
CABLE ENTRY
[51]
MODEL DIMENSIONS
PACS- L W H A B C D E J G
5108 81 68 45.94 36 45 20 7.13 40 11.38 13.03
6109 [2057] [1727] [1167] [914] [1143] [508] [181] [1016] [289] [331]
5109 85 68 52.42 40 45 24 7.56 40 13.43 15.55
6111 [2159] [1727] [1332] [1016] [1143] [610] [192] [1016] [341] [395]
*5210
6211
85
[2159]
68
[1727]
62.42
[1585]
40 45 30
[1016] [1143] [762]
9.08
[231]
43
[1092]
15.91
[404]
18.54
[407]
ACCESS
5112 85 68 62.42 40 45 30 9.08 43 15.91 18.54
6114 [2159] [1727] [1585] [1016] [1143] [762] [231] [1092] [404] [407]
G 7 6
J
FILTERED
VENTILLATION
ON BOTH SIDES
D
[1312]
51.65
H
[100]
3.94
DETACHABLE
PLATE FOR
CABLE ENTRY
[51]
1 2 3 4
2
RIGGING HOLES 5
Ø.79 [20] 4Nos. 15
ACCESS PANEL
[381]
LEGEND
1 - EVAPORATOR COIL
ACCESS
2 - EVAPORATOR FAN
3 - EVAPORATOR FAN MOTOR
4 - COMPRESSOR
5 - CONDENSER COIL
CERTIFIED DRAWINGS ARE
6 - CONTROL PANEL AVAILABLE ON REQUEST
A2 A4
7 - CONDENSER FAN
ALL DIMENSION S ARE IN IN CHES [mm] DRAIN Ø1[25] x2Nos.
76
98
[1931]
[2489]
56
1 40 58
[1422]
18.54 [25] [1016] [1473]
[38]
1.5
[471]
7 6
[231]
15.91
[404]
9.08
[1611]
FILTERED
63.42
VENTILLATION
[1337]
52.63
ON BOTH SIDES
[762]
30
DETACHABLE
PLATE FOR
CABLE ENTRY
[51]
2
1 2 3 5 4
[125]
4.92
RIGGING HOLES
Ø.79 [20] 4Nos. 15 ACCESS PANEL
BOTH SIDES
[381]
10 6 10
PACS Models:5114 & 6117 [254] [254]
MODEL: PACS- 5114/6117 A1 A3
A2 A4
DRAIN Ø1 [25] x2Nos.
70 84
[1778] [2134]
56 1 40 44
[1422] [25] [1016] [1118]
[38]
1.5
= 18.54 =
[471]
7
9.1 15.91
[404]
[231]
[1585]
62.42
[1312]
51.65
5
[762]
30
DETACHABLE
PLATE FOR
CABLE ENTRY
[51]
2
1 2 3 4
[100]
3.94
RIGGING HOLES
Ø.79[20] 4Nos. ACCESS PANEL ACCESS
15
BOTH SIDES
[381]
Dimensional Data
PACS Models: 5219 to 5224 & 6223 to 6228
10 10
LE G E ND [254] [254]
A1 A3
CERTIFIED DRAWINGS ARE
1 - EVAPORATOR COIL AVAILABLE ON REQUEST
2 - EVAPORATOR FAN
3 - EVAPORATOR FAN MOTOR
4 - COMPRESSOR
5 - CONDENSER COIL
6 - CONTROL PANEL
7 - CONDENSER FAN
ALL DIMENSIONS ARE IN INCHES [mm] ACCESS
MODEL DIMENSIONS
PACS- W H H1 D E F J G
5219 84 59.41 52.63 7.56 65.4 43.66 13.43 15.55
6223 [2134] [1509] [1337] [192] [1661] [1109] [341] [395]
5224 84 59.41 52.63 7.56 70 43.66 13.43 15.55
6228 [2134] [1509] [1337] [192] [1778] [1109] [341] [395]
A2 A4
DRAIN Ø1 [25] x2Nos.
W 98
[2489]
E 1 40
[25] [1016]
[38]
1.5
F
7
J
6
D
H
H1
[762]
30
[51]
2
1 2 3 5 4 DETACHABLE PLATE
[125]
4.92
MODEL DIMENSIONS
PACS- H H1 L B C
5225 65.87 53.63 120 80 33
6230 [1673] [1362] [3048] [2023] [838]
5228 68.87 61.63 116 76 36 ACCESS
6234 [1749] [1565] [2946] [1930] [914]
5234 72.87 61.63 116 76 40
6240 [1851] [1565] [2946] [1930] [1016]
5239 77.87 73.63 120 80 45
6246 [1978] [1870] [3048] [2023] [1143]
ALL DIMENSIONS ARE IN INCHES [mm]
A2 A4
88 DRAIN Ø1 [25] x2Nos.
[2235] L
75
[1905] 1 40 B
[38]
[1328]
7
8.5 15.91
[404]
6
[217]
H
H1
C
[51]
2
10 10
LEG END [254] [254]
A1 A3
CERTIFIED DRAWINGS ARE
1 - EVAPORATOR COIL AVAILABLE ON REQUEST
2 - EVAPORATOR FAN
3 - EVAPORATOR FAN MOTOR
4 - COMPRESSOR
5 - CONDENSER COIL
6 - CONTROL PANEL
7 - CONDENSER FAN
MODEL DIMENSIONS
ACCESS
PACS- H H1 C D
5245 93.98 77.63 56 10.75
6253 [2387] [1972] [1422] [273]
5249 99.24 85.63 66 6
6260 [2521] [2175] [1676] [152]
ALL DIMENSIONS ARE IN INCHES [mm]
A2 A4
DRAIN Ø1 1/4 [32] x2Nos.
88 127
[2235] [3226]
75 1 43
[1905] [25] [1092]
21.93 21.93
[38]
1.5
[557] [557]
7
18.82
[478]
D
6
H
H1
C
DETACHABLE
PLATE FOR
CABLE ENTRY
[51]
2
RIGGING HOLES 1 15 2 3 5 4
[125]
4.9
SPACE REQUIRMENT
Models A B C
5105 6106
5107 5108 40
5108 6109
5109 6111 50
5210 5211 50 65
5112 6114
5213 6214
5114 6117 62
5215 6218
66
5219 6223
76 76
5224 6228
5225 6230
5228 6234 81
70
5234 6240
81
5239 6246 90
5245 6253 96
78
5249 6260 108
ALL DIMENSIONS ARE IN INCHES Table 29
Installation
SPACING FOR SERVICE SPACING FOR AIR FLOW
A B
A
B
DUCT
DUCT
B
B B
DUCT
B
A
DUCT
C
DUCT
DUCT
B B
B
A
GUIDE SPECIFICATIONS
GENERAL FEATURES EVAPORATOR FAN(S) & MOTOR
Packaged air conditioners shall be composed of compressor(s), Fans of evaporators shall be forward curved, double inlet double
condenser & evaporator coils with fans, refrigerant piping, electrical width (DIDW), centrifugal type, statically & dynamically balanced,
components & enclosing cabinet in one piece. mounted on a single heavy duty shaft with permanently lubricated
bearings & driven by V belt with an adjustable variable pitch motor
These units shall be factory assembled, internally wired, fully pulley.
refrigerant charged with R22 or R407C, tested under strict quality
standards & are suitable for outdoor installation on rooftop or ground Motor shall be Totally Enclosed Fan Cooled (TEFC), 4 poles, class-F
level with ducted system. insulated, minimum IP55 protection & wired to unit control panel.
Units should be capable to operate from 50°F (10°C) to 120°F REFRIGERANT PIPING
(48.9°C) ambient temperature, and shall be selected in accordance
with project requirements and installed as per Installation, Operation Refrigerant circuit piping shall be fabricated from ACR grade copper
& Maintenance Manual. including shut-off valve, filter drier & thermostatic expansion valve.
COMPRESSOR(S) Suction line shall be insulated with ½” (12 mm) wall thickness
enclosed cell pipe insulation with maximum k factor 0.28 Btu.in/ft2 h°f.
Compressor shall be hermetic scroll, refrigerant gas cooled furnished
with internal overload protection device, internal pressure relief
value, crankcase heater, and shall be mounted on rubber isolators. CASING
Casing shall be made of hot dip galvanized, phosphatized steel
CONDENSER COIL(S) sheets which are then electrostatically polyester powder coated
to provide an extremely tough, scratch resistance & excellent anti-
Condenser coils shall be air cooled with integral sub cooler, corrosive protection. Casing shall pass 1000 hours in 5% salt spray
constructed of seamless copper tubes 3/8” OD mechanically testing at 95°F (35°C) & 95% relative humidity as per ASTM B117.
expanded into wavy plate type aluminum fins with maximum 14
FPI (1.8mm) spacing. Evaporator section shall be sealed with vinyl gaskets & completely
insulated faced with black glass tissue (BGT) heavy density, fire
These coils shall be tested against leakage by air pressure of 450 retardant, permanent odorless fiberglass insulation of minimum 1”
psig (3100 kPa) under water, cleaned & dehydrated at the factory. (25 mm) thickness & 32 kg/m3 density having maximum k factor
0.23 Btu.in/ft2 h°f. (0.033 W / m °k).
CONDENSER FAN(S) & MOTOR(S)
Unit casing shall be provided with access panels for easy service
Unit shall be furnished with a direct driven propeller type, & maintenance of all unit parts.
discharging air upward, these fans to be equipped with Aluminum
blades, permanently lubricated bearings, and inherent corrosion FILTERS
resistance shaft. Each condenser fan shall be balanced statically
and dynamically at the factory. Complete fan assembly is provided Units shall be supplied with a range of filter sections with flat filter or
with suitable acrylic coated fan guard. vee filter 1” or 2” thick, with 54% or 72% dust arrestance, respectively,
in accordance with ASHRAE 52.1, if so specified.
Motor shall be Totally Enclosed Air Over (TEAO), 6 poles, with
class F insulation, minimum IP55 protection and factory wired to A bag filter section to house 22”, 30”, or36” deep bag filters having
unit control panel. efficiency as desired shall be provided, if so specified.
Evaporator coil shall be constructed of seamless copper tubes 3/8” For 100%, Fresh Air application, a sand trap louver shall be provided,
OD mechanically bonded to aluminum (copper) cross-wave fins if so specified.
with maximum 12 FPI (2.1mm) spacing.
GUIDE SPECIFICATIONS
CONTROL PANEL DISPLAY INFORMATION
The unit mounted control panel enclosure shall be fabricated out The package units shall offer an LCD display which will
of heavy gauge sheet steel in phosphatized powder coated baked allow the operator to access different parameters of the
finish. The enclosure shall conform to IP54 as per guidelines unit. Operator shall be able to view and change the unit
in IEC 529. A hinged access door and key-fastener shall be parameters. The display information shall include:
provided for easy access and security. The panel shall be factory
wired in accordance with NEC 430 & 440, labeled, tagged and • Status
features 220V / 240V controls and shall include the following as • Outputs
a minimum. • Inputs
• Alarms
• All compressors shall be with DOL starting. • Set points
• Individual compressor, condenser fan motors and evaporator • Password
fan motor contactors.
• Motor protector circuit breaker for condenser and evaporator
The intelligent microprocessor based controller shall monitor
fan motors.
• Control circuit breaker. all the safeties related to the unit and makes the necessary
• Control circuit on/off switch. protections, by shutting down the entire unit or the effected
• Microprocessor control boards. circuit. The protections shall include:
• Control Relays.
• Power and control terminal blocks. • Low suction pressure.
• High discharge pressure.
• High compressor motor temperature.
• Compressor short cycling.
• Evaporator fan motor overload.
MICROPROCESSOR CONTROL
Volt free contacts for run status, common fault status, auto
Package units shall be equipped with a full function microprocessor mode status and provision for remote on/off shall be available
based controller as a standard feature. The controller shall be factory as option.
programmed for the control of evaporator fan, compressors and
condenser fans. The controller shall come with a built in keypad In addition, the unit microprocessor shall be able to support
and display for simple but meaningful man machine interface. This the major BMS protocols such as BACnet, Modbus & LON as
controller shall provide complete operational control for the unit and option.
shall have built-in auto diagnostic capability that can signal normal
operation or alarm conditions as well as shutting down the unit or
system if necessary.
Dubai Riyadh
P.O Box: 98822 )DZD]5HI $LU&RQGLWLRQLQJ&R
Dubai, United Arab Emirates P.O Box: 85123
Tel: +9714 2940 900 Riyadh, Saudi Arabia
Fax: +9714 2940029 Tel: +96 61 4794499
email: dubaisales@skm.ae Fax: +96 61 4785354
_________________________ HPDLOVDOHHP#IDZD]JURXSFRP
_________________________
Qatar
4DWDURI¿FH Egypt
0DQQDL7UDGLQJ&R:// 9 Mosadak Street
P.O Box: 76 UGÀRRU'RNNL*L]D(J\SW
Doha, Qatar Tel: +20 2 7619617 / +20 2 7621974
Tel: +974 4455 8787 / 4455 8788 Fax: +20 2 7621973
Fax: +974 4455 8781 email: egyptsales@skm.ae
email: dohasales@skm.ae _________________________
+9$&#PDQQDLFRPTD
_________________________ $/0HVVLOD+9$&(TXLSPHQW)DFWRU\
3DUWRI6.0$&IDFWRU\LQ6DXGL$UDELD
,UDT 6DXGL$UDELD(DVWHUQSURYHQDQFH
$O5DZELWW$O,UDTLD&R AD Dammam
Erbil – Bagdad – Basra QGLQGXVWULDOFLW\
Tel: +964 7507441111 $ETLTPDLQURDG+DLO6WUHHW
+964 7711117776 Tel No: +966-3-8123332/4/5
+965 99608916 Fax No: +966-3-8123337 / +966-3-8123092
HPDLOLQIR#DOUDZDELWWFRP
www.skm.ae
You name it.....We cool it 37
083/2012
37