Professional Documents
Culture Documents
Work Order Details
Work Order Details
Work Order Details
Number
Account University Of Warwick Bill to Account Estates Office – Finance The University of
Warwick
Location Name UoW-Dunsmere Billing Address Estates Office Gibbet Hill Road
Coventry,
CV4 7AL
Location Address Westwood Campus
Coventry,
CV4 7AL
Work Details
Subject Control circuit keeps blowing on the panel in Dunsmere. This is located in the calorifier room.
Description Control circuit keeps blowing on the panel in Dunsmere. This is located in the calorifier room.
Please book the job to University of Warwick, Dunsmere, 03.022
Resolution SA-2169127 - Muhammad Tahir Shaheen - 20/07/2023 09:47 - 1). Location: Dunsmere West Wood
Description 2). Arrival Time: 13:15 19/07/2023
3). Description: After getting the call I met with Will Cutting (Warwick Electric Team Member) and asked him all details or
complaint he got. Then I went to the site and checked continuity of every cable that was belong to that fuse. Nothing was
short circuit so after verification I installed new 6Amp fuse and leave it testing. It’s still working. This fuse is providing
power to Panel Light, Panel switches and some relays and voltage rating of this fuse is 24V
There are ampere rating charts that is fixed on panel which tell the rating of all fuses that installed in BMS panel. Faulty
fuse name is CF1 and rating should be 6Amp as per chart. Today (20/07/2023) I went again to check the fuse with
Ampere Meter and took the current reading and its 2.24 Amps. So technically everything working fine. And 6Amp fuse
shouldn’t blow up on 2.24Amp. Even caretaker boiler is also working.
There is also one relay that is loose in the base, and it comes out sometime. I have placed it properly if it will come out
again then we will have to replace the relay and base for relay.
4). Job Complete: Yes
5). Next Step Required: May be yes if Relay fell out again.
6). Quote Required: No
7). Leaving Time: 14:30 19/07/2023
8). End of Day Report, Signed by: Muhammad Tahir Shaheen
Labor Summary
Appointment Number Actual End Reg. Labor Summary (mins) OT Labor Summary (mins) PT Labor Summary (mins)
Materials Used
Product Product Description Quantity Consumed Created Date
Work Order 02780016
Number
Expenses
Expense ID Description Expense Type
Additional Charges
Additional Charge ID Additional Charge Type Quantity
Recommended Repairs
Created Date Recommended Repair Description Status
Thank you for your business! Satisfied customers are our highest priority. If you have any questions or comments please call us.
Customer Signature
Signature
Signed By
Date
Type Customer
Equipment
Sub Location Asset Equipment Make Equipment Model Serial Number
Undisclosed Undisclosed
Work Completed
Completed Name Asset Equipment Tag