ALUMINUM BAND GENERAL NOTES

JACKETING
1. ALL DIMENSIONS ARE IN MILLIMETERS AND PIPE SIZE ARE IN INCHS UNLESS OTHERWISE SPECIFIED.
1 VAPOR BARRIER 2. ALL PLUMBING MATERIAL AND INSTALLATION SHALL COMPLY WITH AMIES-S-060 AND ALL ASSOCIATED

OUTDOOR PIPING
(VINYL TAPE) FIBER GLASS
FIBER GLASS DOCUMENTS.
PIPE
PLASTER OR
INSULATION
3. ALL PIPING WITHIN ROOMS WITH CEILING SHALL BE CONCEALED UNLESS OTHERWISE INDICATED ON
SPACKLING COMPOUND PIPE SLEEVE
PIPE SLEEVE INSULATION 1 THE DRAWINGS. PIPING SHALL NOT BE EMBEDED IN CONCRETE WALLS, FLOORS AND CEILINGS.
PIPE PIPE 4. SLIP JOINTS ARE PROHIBITED IN WATER DISTRIBUTION PIPING SYSTEMS. 1
5. CPVC PRESSURIZED PIPE FOR COLD WATER AND HOT WATER PIPE SHALL BE SUSPENDED ON HANGERS
OR SUPPORTED ON FIXED BRACKETS. SUCH SUPPORTS SHALL PERMIT LONGITUDINAL PIPE MOVEMENT
IN EXPANSION AND CONTRACTION WITHOUT ABRASION, CUTTING, OR RESTRICTION. FIXED BRACKETS

A
SHALL BE USED AT CHANGES IN DIRECTION OR PIPING SIZE TO PREVENT PIPE MOVEMENT IN RESPONSE

INDOOR PIPING
TO THRUST FROM INTERNAL PRESSURE.
BONDING ADHESIVE 1 U - BOLTS
6. COLOR CODING: PIPE COLOR CODING SHALL COMPLY WITH SAUDI ARAMCO ENVIRONMENTAL HEALTH
TAPPING 1 PLASTER OR CODE TABLE-2 "PIPING SYSTEM COLOR-CODE".
PIPE INSULATION 1 ESCUTCHEON SPACKLING COMPOUND 7. PLASTIC PRESSURE PIPING SYSTEMS WITHIN BUILDINGS SHALL BE PROVIDED WITH EXPANSION LOOPS,
ONLY FOR EXPOSED ESCUTCHEON
(UNIT : mm) TO OCCUPIED AREA ONLY FOR EXPOSED BENDS OR OFFSETS TO ACCOMMODATE MOVEMENTS IN THE AMOUNT OF 2 MM PER METER (3 INCHES
TO OCCUPIED AREA
INSULATION
PER 100 FEET) IN COLD WATER DISTRIBUTION CPVC PIPING SYSEM, AND 5 MM PER METER (6 INCHES
REMARKS
ITEM PIPE MATERIAL PIPE SIZE
(OPERATING TEMP.) 1 NON-INSULATED PIPE INSULATED PIPE GALV. STEEL ANGLE PER 100 FEET) IN HOT WATER DISTRIBUTION CPVC PIPING SYSTEM.
THICK.
1 RIGID INSULATION 8. A PRESSURE TYPE ANTI-SIPHON VALVE SHALL BE USED ON ALL WATER PIPING DIRECTLY CONNECTED
DRINKING WATER - SLEEVE SCHEDULE
1 TO ANY MOSQUE OR MUSALLAH ABLUTION STATION. THE VALVE SHALL BE LOCATED NOT LESS THAN
1 CPVC ALL 25 (UNIT : mm)
PIPE U-BOLT SCHEDULE (UNIT : mm) 150 MM (6 IN) ABOVE THE OVERFLOW OR FLOOD LEVEL RIM OF THE HIGHEST FIXTURE OR TANK THAT
PIPE SIZE
(DN) 15 20 25 32 40 50 65 80 100 REMARKS
HOT WATER CPVC ALL 25 15°C ~ 60°C ITEM PIPE SIZE IT SERVES.
(DN)
EXPOSED CONDENSATE UPVC ALL 25 - NON-INSULATION PIPE 40 40 40 50 80 80 100 150 150 15 20 25 40 50 50 65 80 100 150 REMARKS 9. A PRESSURE TYPE ANTI-SIPHON VALVE SHALL BE USED ON EACH HOSE CONNECTION SUCH AS
WATER DRAIN 1 ITEM HAMMAM ABLUTION HOSES, GARDENING HOSES, ETC.
SANITARY DRAIN UPVC ALL - - A 80 80 80 100 100 150 150 150 200 DRINKING WATER
INSULATED PIPE
10. LIQUIDS AT A TEMPERATURE ABOVE 60°C SHALL NOT BE DISCHARGED DIRECTLY INTO ANY DRAINAGE
U - BOLTS 10 10 10 10 10 10 10 10 12 12
BATTERY ROOM DRAIN UPVC ALL - - 80 80 80 100 100 150 150 150 200 HOT WATER SYSTEM.
- - 11. PLASTIC PIPE SHALL BE SUPPORTED AT EACH STORY OR AT A MAXIMUM INTERVAL OF 10 FT (3.0 M),
1 CHEMICAL STORE BUILDING DRAIN PP ALL
ANGLE 40 x 40 x 5t 50 x 50x 6t 65 x 65 x6t AND ON EITHER SIDE OF A TEE OR WYE AT HORIZONTAL TAKEOFF POINTS. PRESSURE PIPING
REMARKS: SHALL BE ADEQUATELY BLOCKED TO PREVENT HORIZONTAL DISPLACEMENT FROM THE VERTICAL.
1. INSULATION MATERIALS SHALL BE
1 12. HANGERS AND ANCHORS SHALL BE OF METAL OF SUFFICIENT STRENGTH TO MAINTAIN THEIR
- CLOSED CELL ELASTOMERIC THERMAL INSULATION WITH 0.048-0.08 gm/cm AND PROPORTIONAL SHARE OF THE WEIGHT OF PIPE AND CONTENTS. THE MINIMUM HANGER WIDTH FOR
THERMAL CONDUCTIVITY 0.035 W/mK AT MEAN TEMP
REMARKS:
1 PLASTIC PIPE SHALL BE 2 IN (50 MM).
- PREFORMED FLEXIBLE ELASTOMERIC CELLULAR THERMAL INSULATION WITH VAPOR BARRIER
2. FOR OUTDOOR PIPE, JACKETING 0.5mm THK. ALUMINUM AND/OR 0.5mm THK. STS 316L SHEET CLADDING REMARKS: 1. ALL DRINKING WATER AND HOT WATER PIPES SHALL BE FIXED WITH U-BOLT.
1
3. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND/OR HARDWARE. 1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND/OR HARDWARE. 2. FOR INSULATED PIPE, HANGER SIZE SHALL BE SELECTED AS PER INSULATION THICKNESS.
1
1 1 DRINKING & HOT WATER PIPE INSULATION 2 CAULKING METHOD & PIPE WALL SLEEVE 3 PIPE U-BOLT 1

1 15 AAV

15 STRAINER

15 BALL VALVE

HANGER WIDTH : 50 MM PIPE HANGER SCHEDULE (UNIT : mm) PIPE HANGER SCHEDULE (UNIT : mm)
PIPE CLAMP ROD PIPE
SIZE ROD
HANGER PITCH REMARKS SIZE A HANGER PITCH REMARKS
(DN) SIZE SIZE (DN) SIZE
1
15 80 ø10 1500 15 21~24 ø10 1500

20 80 ø10 1500
A INSULATION
20 25~28 ø10 1500

25 80 ø10 1500 25 32~35 ø10 1500

32 100 ø10 2000 32 42~45 ø10 2000

INSULATION 40 100 ø10 2000 40 48~51 ø10 2000


RIGID INSULATION 50 100 ø10 3000 50 58~63 ø10 3000
1 HOTDIP GALV.
HOTDIP GALV., 65 125 ø12 3000 65 62~78 ø12 3000

80 125 ø12 3000 PIPE SUPPORT CLAMP WITH RUBBER 80 84~89 ø12 3000
PIPE SUPPORT CLAMP WITH RUBBER
100 150 ø16 3000 100 109~114 ø16 3000 TEE

1 1 1

REMARKS:
1
1. ALL DRINKING & HOT WATER PIPES SHALL BE INSTALLED WITH INSULATED CLAMP. 1
2. PIPE HANGER WITH RUBBER.
REMARKS:
1
3. PROTECTION AND DISINFECTION OF DOMESTIC WATER PIPING: ALL NEWLY CONSTRUCTED AND EXISTING REPAIRED
OR MODIFIED DOMESTIC WATER PIPING SHALL BE PROTECTED FROM CONTAMINATION DURING INSTALLATION, AND 1. ALL DRINKING WATER AND HOT WATER PIPES SHALL BE FIXED WITH CLAMP.
SHALL BE DISINFECTED IN ACCORDANCE WITH THE REQUIREMENTS OF SAUDI ARAMCO ENVIRONMENTAL HEALTH REMARKS:
2. PIPE HANGER WITH RUBBER.
CODE, GI-0151.006. 3. FOR INSULATED PIPE, HANGER SIZE SHALL BE SELECTED AS PER INSULATION THICKNESS. 1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND/OR HARDWARE.

4 PIPE HANGER (INSULATION PIPE) 1 5 PIPE HANGER (NONE INSULATION PIPE) 6 AUTO AIR VENT 000-HDAI-390203
PLUMBING GENERAL DETAIL-3
-003
000-HDAI-390203
1 -002 PLUMBING GENERAL DETAIL-2

000-HDAI-390103 PLUMBING SYMBOL & LEGEND

Drawing No DESCRIPTION
FINISHED FLOOR SLOPE TO DRAIN
REFERENCE DRAWINGS
ROUND LOOSE-SET TRACTOR GRATE
FLOOR FINISH FLOOR FINISH
FINISHED FLOOR
1 ACCESS COVER

1
TRAP PRIMER CONNECTION
BALL VALVE
HOSE BIBB BRONZE BRASS
BODY AT 45°
15 DRINKING WATER
VENT PIPE
VACUUM BREAKER LEVEL LOCK SCREWS
SLAB 1 IFC 17-JAN-2024 ISSUE FOR CONSTRUCTION J.S. SONG D.K. KIM Y.B. IM
ADAPTER SLAB
ADAPTER NIPPLE BODY SLAB BODY
PIPE SLAB
0 IFR 25-SEP-2023 ISSUE FOR REVIEW D.H. NOH D.K. KIM Y.B. IM
PLUG
45° COUPLING Issued Reviewed Approved
Rev. Step Rev. Date Revision Description
1 by by by

AMIRAL
BY FIELD

PIPE PIPE
TRAP ARM TO
DRAINAGE LINE PROJECT
PIPE 45° BEND PIPE
This document is the property of AMIRAL and shall not be disclosed to third parties or reproduced without permission of the owner.
90 P-TRAP WITH SOLVENT
This document has been generated by an Electronic Document Management System. When printed it is considered as a for information
FINISH FLOOR only copy. The controlled copy is the screen version and it is the holder's responsibility that he/she holds the latest valid version.

PLUMBING GENERAL DETAILS-1


REMARKS: REMARKS: REMARKS:
REMARKS: 1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER 1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER 1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND/OR HARDWARE. Doc Type: DRW Discipline: HVA Phase: DE Class: 2 System / Subsystem: NA Equipment Type: NA
1. THESE ILLUSTRATIONS DO NOT PRECLUDE THE USE OF OTHER METHODS AND/OR HARDWARE. METHODS AND/OR HARDWARE. 2. WET FLOOR SLOPE SHALL NOT BE LESS THAN 1% (10 mm/m) AND NOT MORE THAN 2% (20 mm/m). FLOOR SLOP SHALL BE VERIFIED AND
Contractor Site
2. MINIMUM - TRAP AND TRAP ARM SIZE AS PER SAES-S-060 2. MINIMUM - TRAP AND TRAP ARM SIZE AS PER SAES-S-060 SHALL LEAVE NO WATER POND.
METHODS AND/OR HARDWARE. Document - Reference:
-
Number :
Company Rev: Scale: Format: Sheet:
7 HOSE BIBB DETAIL 8 FLOOR DRAIN (FD) 9 CLEANOUT (CO) 10 FLOOR CLEANOUT (FCO) Document SA-AMI-000-HDAI-390203 1 NONE A1 001
ID :
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF AMIRAL. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF AMIRAL.