Professional Documents
Culture Documents
Min 184 Rev. 6
Min 184 Rev. 6
SINGLE PHASE TO
THREE PHASE
STATIC CONVERTER
As Per
RDSO Specification No.ELRS/Spec/SI/0018
(Rev.1.0) March, 2006
Amendment No: 1
TYPE MIN184
Copyright © 2022 Medha Servo Drives Pvt. Ltd. All rights reserved.
Medha logo is registered of Medha Servo Drives Pvt. Ltd. Any other
trademarks are the property of their respective owners.
ANNEXURE 1 :
Electrical Schematic for 180kVA Static Converter Part-1
ANNEXURE 2 :
Electrical Schematic for 180kVA Static Converter Part-2
ANNEXURE 3 :
Outline and Mounting Details 180kVA Inverter - MIN184KVA
ANNEXURE 4 :
Static Converter Frame Stage 7 - 184kVA
IMPORTANT
WARNING !
HIGH LEAKAGE CURRENT
Earth Connection essential
Before connecting supply.
DANGER
High Voltage Working area.
Equipment contains hazardous voltages and
Controls, hazardous rotating mechanical parts(fans)
TH
I S
PA
GE
IS
IN
TE
NT
IO
NA
LL
Y
LE
FT
BL
AN
K
Chapter 1
SAFETY MESSAGES
For the best results with the MIN184 converter, carefully read this manual
and all of the warning labels attached to the converter before installing and
operating it and follow the instructions exactly. Keep this manual handy for
quick reference.
HIGH VOLTAGE:
This symbol indicates high voltage. It calls your attention to items or
operations that could be dangerous to you and other persons operation on
this equipment. Read the message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of the two signal
words : CAUTION or WARNING, as described below.
WARNING:
Indicates a potentially hazardous situation which, if not avoided, can result in
serious injury or death.
CAUTION:
Indicates a potentially hazardous situation which,if not avoided, can result in
minor to moderate injury, or serious damage to the product. The situation
described in the CAUTION, if not avoided, may lead to serious results.
Important safety measures are described in CAUTION (as well as
WARNING), so be sure to observe them.
TIP: Tips give a special instruction that can save time or provide other
benefits while installing or using the product. The tip calls attention to an idea
that may not be obvious to first-time users of the product.
WARNING: Wait at least five (5) minutes after turning off the input power
supply before performing maintenance or an inspection. Otherwise, there is
a danger of electric shock due to residual power.
8 IM - 41 rev 6
Chapter 2
SYSTEM DESCRIPTION
10 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
IM- 41 rev 6 11
Chapter 2 - System Description Medha Servo Drives Pvt. Ltd.
Starting
Name of the Rated
Rating current in
Sl.No. Code Auxiliary Current
(kW) Amps
Machine (at 415V)
(at 415V)
Motor for main
1 MCP 1, 2 &3 3 x 10.5kW 3 x 23.1 A 154.85
compressors
Table 3.5(b)
12 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Ÿ Once the Converter reaches up to a steady state voltage and frequency, the
Converter ON potential free contact is activated (LSCHBA on loco driver's
desk). MCP 1 and MCP 2, which are DOL (Direct On Line) can now be
switched ON or OFF, depending upon the compressed air level requirements
for the locomotive brake circuit.
Ÿ Time delay of 5 seconds is provided between switch ON of MCP 1 & MCP 2.
Ÿ When the locomotive stops for more than 20 minutes, MVRH, MVMT 1 and
MVMT 2 are switched OFF to save energy. This is done by first switching
OFF the Converter and then restarting it after reconfiguring the load
connections through the load contactors.
IM- 41 rev 6 13
Chapter 2 - System Description Medha Servo Drives Pvt. Ltd.
K
AN
BL
FT
LE
Y
LL
NA
IO
NT
TE
IN
IS
GE
PA
I S
TH
14 IM- 41 rev 6
Chapter 3
BLOCK DIAGRAM
830 V / 760 V
Single Phase 830 V AC
50 Hz at
1 7 7
Step Down
Input Section
Transformer
2 8
Battery
Rectifier
Charger
Assembly
Assembly
3
LC Filter &
Brake
Chopper 9 10
Lights Load &
4 Battery Baby
Load Compressor
Inverter
Assembly
5
Output Sine
Filter and
CT's
6
3 Phase
Output
415V(L-L)50Hz Fig 3.1
Chapter 3 - Block Diagram Medha Servo Drives Pvt. Ltd.
F1
680V
680V
R1 R2
MOV1
MOV3
15 mf/1700 V
C1
680V
680V
C2
C3
MOV2
MOV4
F2 T1 T2
0V
T3
12V 50V
0V
12V
50V
0V
Fig 3.2
Input Protection circuits
(a) Input Fuses
(b) Snubber
(c) Metal Oxide Varistors
The input terminals are directly wired to 650 A fast blow semiconductor
fuses. These fuses disconnect the converter in the event of input side short
circuit (after the fuses) or over current. Two micro switches are mounted on
both the fuses. With these switches, the status of fuses are continuously
monitored by the main control card.
While locomotive is running, there is a chance of getting voltage surges on
the transformer secondary i.e., on input to 180 kVA unit due to pantograph
bouncing. Snubber circuit and metal oxide varistors protect the converter
from the external voltage surges.
Current transformers are used in the input section to measure the input
current.
Step down input voltage is used for zero crossing detection, which is
internally used in the thyristor angle firing control card for measuring and
displaying the input voltage.
16 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
The half controlled thyristor bridge operates at an improved power factor with
almost equally distributed heat loss in thyristors and diodes. Freewheeling
action in semi converters ensures the continuous load current and improved
power factor.
R R
TH1 D1
C C
DC Link
INPUT
R R
TH2 D2
C C
TAFC Card
Fig 3.3
Thyristor and diode modules are mounted on a forced cooled aluminum heat
sink. Each thyristor and diode has their own suppression network for transient
voltage sharing. All of these components are mounted on the heat sink to
make complete rectifier sub assembly. Heat sink is galvanically isolated from
high voltage.
Fins of the heat sinks are external to the rectifier cubicle and are cooled by
two blowers. Over temperature of the rectifier heat sink is sensed by main
controller through a thermal switch with over temperature limit at 90°C. The
semiconductor side of the heat sink assembly is protected from the
locomotive environment with proper shielding.
Once the input voltage is within allowable range and command is ON,
thyristor trigger pulses are issued by thyristor angle firing control card through
the thyristor drive circuit. These thyristor trigger pulses are controlled
according to input voltage variation and the output load variation in order to
maintain invariable DC Link.
IM- 41 rev 6 17
Chapter 3 - Block Diagram Medha Servo Drives Pvt. Ltd.
L2
5.5mH / 600A
R
I
E S S
N
C E E
V
T C C9 C10 C29 C
1 E
I T T
R
F I I
6 T
I O O
7 E
E N Q1 N
R
R
BRAKE CHOPPER
CARD
Fig 3.4
polypropylene capacitors are mounted in the mid section of the cubicle. The
electrolytic capacitors bank is mounted in the inverter cubicle, since they
need to be physically close to the inverter bridge for safe operation of the
IGBT switches. The inductor and polypropylene capacitors are mounted in an
IP21 enclosure to allow the unnecessary heat from this component to
disperse to ambient without heating up the rectifier cubicle.
The capacitor bank is made up of 450 V electrolytic capacitors with two
devices connected in series to give a voltage rating of 900 V for the DC link.
18 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
T1 D1 T3 D3 T5 D5
3 Phase IM
W Load
DC Link V
Vs C
Voltage U
T4 D4 T6 D6 T2 D2
Fig 3.5
The inverter IGBTs are switched at high frequency, giving a total harmonic
current distortion of less than 3% for an induction motor type load, whilst
optimizing semiconductor switching losses and overall efficiency. Each of the
semiconductor has a voltage rating of 1700 V and the parallel combination of
modules per phase has sufficient current rating and thermal capacity to cope
up with all of the specified combinations of direct on line starting currents.
I C33 – C35 T4
S S
N O
E E
V U
C C39-C41 C
E T5 T
T T
R P
I I
T U
O O
E T6 T
N N
R
L3 C36 – C38
Fig 3.6
The inductors, in conjunction with output RFI capacitors, limit the rate of rise
of voltage at the output terminals during IGBTs switching. As stated in the
above paragraph, current transformers are fitted in each output phase, to
provide feedback signal for displaying all three-phase currents, for phase
current imbalance detection. Sensing of output current is also used in
maintaining adequate output voltage with various load conditions and to
ensure the protection against the output side faults.
IM- 41 rev 6 19
Chapter 3 - Block Diagram Medha Servo Drives Pvt. Ltd.
R
3 PHASE
OUTPUT Y 3 PHASE
after OUTPUT
FILTERING B
F9
440V
0V
T8
0V 110V
230V
0V
L4
C43 C42
BLOWER-1
2 1
TB7
F5
BAT CHAR MC
2 1
TB7
BLOWER-2
F6
2 1
TB7
BLOWER-3
F7
2 1
TB7
BLOWER-4
F8
Fig 3.7
20 IM- 41 rev 6
Chapter 4
830V AC
INPUT
Step down Transformer & Batteries &
Battery Charger Load
Circuit
I/P Fuse
Traction
Snubber MOV Step Down Transducer
Traction
Motors
circuit VF Display RS 232
Transformer Card
Motors
Thyristor Angle
1f Traction
Firing Control MC Card
= Motors
Card 110V
Analog
Card
Traction
DC Link
PS3 PS2 PS1
LC Filter
Motors
Power Supply
Card
Brake Chopper
415 AC
OUTPUT
Chapter 4 - Main cards in Converter section, Medha Servo Drives Pvt. Ltd.
Battery Charger section &
Description
DISPLAY SW1
SW2
SI UNIT OK
EXTERNAL FAULT
CHBA O.K
RS232
ALARM RESET
22 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
There are five LEDs, which indicate the status and fault conditions as given
below,
The display board receives data from the main control card and drives the
VFD display and LEDs.
SW1 and SW2 are used to check the values of input voltage
and input current, 3-Ph output voltages, 3-Ph currents, Battery
charger voltage, current and battery voltage.
IM- 41 rev 6 23
Chapter 4 - Main cards in Converter section, Medha Servo Drives Pvt. Ltd.
Battery Charger section &
Description
24 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Q4:- BLSI signal (ON COMMAND FOR SIV) received from MPCS through
QVSM relay and Relay output signal given to MC card for BLSI enable.
IM- 41 rev 6 25
Chapter 4 - Main cards in Converter section, Medha Servo Drives Pvt. Ltd.
Battery Charger section &
Description
K
AN
BL
FT
LE
Y
LL
NA
IO
NT
TE
IN
IS
GE
PA
I S
TH
26 IM- 41 rev 6
Chapter 5
3 2
15 14
28 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
6
7
12 8
13 5
11
Fig 5.2(a)
10
9
Fig 5.2(b)
From Fig 5.2(a) and (b) :
17 20 19
Fig 5.3
IM- 41 rev 6 29
Chapter 5 - Details of Main Components Medha Servo Drives Pvt. Ltd.
21 21
22
26
24 23
25 25
Fig 5.4
From Fig 5.4 :
21. Input Fuses with Micro Switches
22. Input Connections
23. Output Connections
24. Reverse Polarity LED
25. Earth Leak Current sensors
26. SIV to Loco inter Connections
28. GD CARD-1
28 29
29. GD CARD-2
30. GD CARD-3
30 31
31. GD CARD-4
32 33 32. GD CARD-5
33. GD CARD-6
Fig 5.5
30 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
36
35
Fig 5.6
From Fig 5.6 :
35. Blower transformer sine filter inductor
36. Blower transformer
37
38
Fig 5.7
As shown in Fig 5.7, Display unit is the user interface to the system.
37. Push Button – 1
38. Push Button – 2
Above mentioned buttons are used to scroll through various parameters such
as input voltage, input current, output voltages, output currents, charger
voltages, charger currents. By pressing these two push buttons at a time for
a while, displays the latest fault details.
Fault log data is downloaded from the main controller via RS232 connection.
Reset acknowledgment switch is used for the alarm (buzzer) reset.
In addition to these, textual display and LED indication show the status of the
converter.
IM- 41 rev 6 31
Chapter 5 - Details of Main Components Medha Servo Drives Pvt. Ltd.
K
AN
BL
FT
LE
Y
LL
NA
IO
NT
TE
IN
IS
GE
PA
I S
TH
32 IM- 41 rev 6
Chapter 6
TYPES OF FAULTS AND PROTECTIONS
According to the location of fault occurrence, faults are mainly categorized as,
● Internal faults
● External faults
These are useful in predicting the fault cause whether it is internal to the
converter system or outside of the converter system.
34 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
IM- 41 rev 6 35
Chapter 6 - Types of Faults Medha Servo Drives Pvt. Ltd.
and Protections
36 IM- 41 rev 6
Chapter 7
COMMISSIONING
7.1 Handling
● Lift only with adequate equipment and trained persons. Lift always upright
position and do not overturn.
● Improper lifting and handling can cause serious or fatal personal injury
and substantial property damage.
● While lifting the equipment, use all the four eye bolts. Do not try to lift with
any two of the eye bolts.
● Equipment center of gravity is offset from center line.
7.2 Installation
● The static converter cubicle is designed to mount inside the locomotive
with eight bolts of M16 size.
● The converter unit should be installed inside the locomotive in vertical
position and fixed to solid surface from upper and lower sides.
● Position of the unit in locomotive should be adjusted such that its inlet and
outlet match with those in the locomotive.
● The converter shall be mounted in such a way that the front window
facilitates easy reading of status and faults.
7.3 Earthing
Connect the body of converter cubicle via earthling studs to the earthling
provided in the loco.
7.4 Connections
Fig 7.1 shows major connections of 180 kVA static converter unit to input
supply, output load and battery supply, charging sections and DC loads.
Fig 7.1
Chapter 7 - Commissioning Medha Servo Drives Pvt. Ltd.
RELAY RELAY
BASED BASED
SL.NO MEDHA SIV Internal
WIRE LOCOS LOCOS
DESCRIPTION FERRULE
RAILWAY RAILWAY
FERRULE FERRULE
1 INPUT 830V -- 120 sq.mm A991 A991
2 INPUT OV -- 120 sq.mm A992 A992
3 OUTPUT “U” 16 120 sq.mm A965 A965
4 OUTPUT “V” 18 120 sq.mm A966 A966
5 OUTPUT “W” 20 120 sq.mm A967 A967
6 CON1 (Charger +Ve) 131 10 sq.mm X003 X003
7 CON2 (Charger -Ve) 108 10 sq.mm B-313 B-313
8 CON3 (Batt. –Ve) 108 10 sq.mm B-313 B-313
9 CON4 (Batt. +Ve) 120 10 sq.mm C003/1 C003/1
10 CON5 (110 VDC +Ve) 8 4 sq.mm K747 K747
11 CON6 (110 VDC –Ve) 2 4 sq.mm B-695 B-695
12 CON7 (Enable) 58 4 sq.mm F732 F035
13 CON8 (110 VDC +Ve) 54 4 sq.mm L747 L747
14 CON9 (S.I.OK) 55 4 sq.mm A188 A018
15 CON10 -- -- NC NC
16 CON11 (S.I.FAULT) 57 4 sq.mm A734 A017
17 CON12 (CHARG. OK) 56 4 sq.mm A973 A973
18 CON13 (110 VAC) 59 4 sq.mm J169 J968
19 CON14 (110 VAC) 61 4 sq.mm A170 A984
38 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
IM- 41 rev 6 39
Chapter 7 - Commissioning Medha Servo Drives Pvt. Ltd.
In order to make the SI unit safe to work on, the battery supply must
be isolated externally and wait at least 5 minutes to allow capacitors
to discharge completely.
One can easily know the values of Input Voltage, Input Current,
Output Voltages, Output Currents, Battery Charging Voltage and
Battery Charging current by using the push buttons on the display
board.
operational with full load and display shows “system healthy” message in
normal operating condition. Run the static converter for 15 minutes.
40 IM- 41 rev 6
Chapter 8
Fig 8.1
Chapter 8 - Application & Data Analysis Software Medha Servo Drives Pvt. Ltd.
Fig 8.1
● By clicking on the software, main menu screen appears as shown in Fig 8.2.
Fig 8.2
42 IM - 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Fig 8.3
Fig 8.4
● Select the COM port and click on connect symbol as shown in Fig 8.5.
Fig 8.5
IM - 41 rev 6 43
Chapter 8 - Application & Data Analysis Software Medha Servo Drives Pvt. Ltd.
Fig 8.6
● Click on ‘File’ and select ‘Download Memory Serial Port’ as shown in Fig 8.7
Fig 8.7
● By selecting ‘Download Memory Serial Port’ a screen appears as shown in
Fig 3.8. Select ‘Faults Only’ option and enter the Loco No, Unit No and Shed
Name and click on ‘Download’ as shown in Fig. 3.8.
Fig 8.9
● By clicking on ‘Date Time Selection’, a prompt window appears to enter start
date & time and End date & time as shown in Fig 8.10.
Fig 8.10
Fig 8.11
IM - 41 rev 6 45
Chapter 8 - Application & Data Analysis Software Medha Servo Drives Pvt. Ltd.
● Select ‘Fault Messages with Data Pack’ and click on ‘Download’ as shown in
Fig 8.12.
Fig 8.12
Fig 8.13
Fig 8.14
46 IM - 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Fig 8.15
● By clicking on ‘Exit’ in Fault log screen as shown in Fig 8.16, a default screen
appears as shown in Fig 8.17.
Fig 8.16
Fig 8.17
IM - 41 rev 6 47
Chapter 8 - Application & Data Analysis Software Medha Servo Drives Pvt. Ltd.
K
AN
BL
FT
LE
Y
LL
NA
IO
NT
TE
IN
IS
GE
PA
I S
TH
48 IM - 41 rev 6
Chapter 9
MAINTENANCE
During POH, the work MUST be carried out with the equipment
switched OFF and isolated from the supply. Always allow at least 5
minutes for capacitors to discharge after isolating the equipment.
Chapter-9 Maintenance Medha Servo Drives Pvt. Ltd.
50 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
IM- 41 rev 6 51
Chapter-9 Maintenance Medha Servo Drives Pvt. Ltd.
Price/Unit
Sl.No. CODE DESCRIPTION
Rs.
46 SP184121030 BLOWER GASKET - 184 220
47 SP184121031 SNUB. RES. INSULATOR FOR THYRISTOR/DIODE 350
48 SP184121032 DOOR LOCK SCREW FOR INVERTER 45
49 SP184121033 DISPLAY DOOR FOR INVERTER 870
50 SP184121041 THYRISTOR HEAT SINK BOTTOM 14,200
51 SP184121042 INVERTER IGBT HEAT SINK BOTTOM 21,400
52 SP184121043 OUTPUT CAPACITOR BUSBAR 1 1,120
53 SP184121044 OUTPUT CAPACITOR BUSBAR 3 1,120
INVERTER IGBT BUSBAR SET WITH INSULATORS FOR
54 SP184121045 24,500
ONE PHASE
INVERTER IGBT & CAPACITOR BUSBAR SET WITH
55 SP184121046 25,100
INSULATOR
56 SP184121047 DISPLAY UNIT MIMIC FILTER ASSY. 1,500
57 SP184121048 DISPLAY UNIT BOX WITH MIMIC FILTER FOR INVERTER 3,100
58 SP184121049 DOOR GASKET FOR INVERTER 7,800
59 SP184121050 BATTERY CHARGER HEATSINK WITH GASKET 13,200
60 SP184141001 BAT-CHAR I/P START CURRENT LIMIT RESISTOR 180
61 SP184141003 THYRISTOR / DIODE SNUBBER RESISTOR 3,240
62 SP184141004 BREAK CHOPPER RESISTOR ASSY 15,300
63 SP184141005 I/P SURGE PROTECTOR SET 48,400
64 SP184141007 DC LINK CAPACITOR 1,42,500
65 SP184141009 IGBT SNUBBER FOR INVERTER 1,750
66 SP184141010 THYRISTOR / DIODE SNUBBER CAPACITOR 13,600
67 SP184141011 I/P RECTIFIER DIODE 29,500
68 SP184141012 BAT-CHARGER RECTIFIER DIODE 1,290
69 SP184141014 INVERTER IGBT 12,800
70 SP184141016 I/P RECTIFIER THYRISTOR 28,000
71 SP184141017 VOLT FREE CONTACTORS SET 1,900
72 SP184141018 HEAT SINK THERMAL SWITCH 320
73 SP184141019 OUTPUT CURRENT SENSOR 1,110
74 SP184141020 INPUT CURRENT SENSOR 920
75 SP184141021 DC LINK CURRENT SENSOR 13,400
76 SP184141022 BREAK CHOPPER CURRENT SENSOR 7,300
77 SP184141023 INT / EXT EARTH FAULT CURRENT SENSOR 2,500
78 SP184141024 HEAT SINK COOLING BLOWER 14,200
79 SP184141025 BLOWER FUSE 6
80 SP184141026 BLOWER FUSE HOLDER 45
81 SP184141027 BAT-CHARGER INPUT FUSE 120
82 SP184141028 INPUT FUSE FOR STATIC CONVERTER 8,100
83 SP184141029 BLOWER INPUT FUSE 150
84 SP184141030 110VAC INPUT FUSE 145
85 SP184141031 RESET SWITCH FOR STATIC CONVERTER 135
86 SP184141032 INPUT FUSE FAIL FEED BACK SWITCH FOR SIV 1,200
87 SP184141033 EARTH LEAKAGE BY PASS SWITCH 350
88 SP184141034 STATIC CONVERTER ENABLE SWITCH 350
89 SP184141035 BAT-CHARGER OUTPUT CONTACTOR 5,700
90 SP184141036 BAT-CHARGER IN PUT CONTACTOR 1,220
52 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Price/Unit
Sl.No. CODE DESCRIPTION
Rs.
91 SP184141037 ENABLE AND CHARGER SELECTION SWITCH 350
92 SP184141038 INVERTER SET WITH IGBTs PER PHASE 1,40,000
93 SP184141039 I/P SNUBBER RESISTOR ASSY. 8,800
94 SP184141040 BREAK CHOPPER RESISTOR SET 10,200
95 SP184141042 DC LINK BLEADER RESISTOR SET 17,500
96 SP184141043 DC LINK CAPACITOR BUSBAR SET 6,500
97 SP184141044 BAT-CHARGER IGBT WITH SNUBBER CAPACITOR 6,400
98 SP184141045 BREAK CHOPPER IGBT WITH SNUBBER CAPACITOR 14,200
99 SP184141047 BAT-CHARGER BLOCKING DIODE 950
100 SP184141048 DC LINK VOLTAGE SENSOR 20,500
101 SP184141049 I/P TERMINAL BLOCK S/A 1,200
102 SP184141050 O/P TERMINAL BLOCK S/A 1,500
103 SP184151001 DC LINK CAPACITOR BANK 1,10,000
104 SP184151002 BAT-CHARGER O/P FILTER S/A 2,600
105 SP184151003 DV/DT CAPACITOR BANK SET 1,00,500
106 SP184151004 BLOWER SINE FILTER S/A 3,500
107 SP184151005 INPUT SNUBBER CAPACITOR SET 21,000
108 SP184151006 BAT-CHARGER INDUCTOR 24,750
109 SP184151007 BLOWER SINE FILTER INDUCTOR 3,500
110 SP184151008 BLOWER TRASFORMER 9,200
111 SP184151009 INPUT VOLTAGE FEED BACK TRANSFORMER 3,200
112 SP184151010 BAT-CHARGER TRASFORMER 29,300
113 SP184151011 DC LINK INDUCTOR FOR MIN184 2,30,000
114 SP184151012 DI/DT INDUCTOR FOR MIN184 2,02,000
115 SP184201001 FLAT RIBBON CABLES SET 12,500
116 SP184201002 VOLTAGE / CURRENT SENSOR CABLES SET 4,200
117 SP184201003 CONTROL CABLES SET 56,600
118 SP184201004 BATTERY CHARGER CABLES SET 12,200
119 SP184201005 DC LINK POWER CABLES SET 27,900
120 SP184201006 INVERTER POWER CABLES SET 22,000
121 SP184201007 CABLE - I/P FUSE F1 TO TH1&TH2 JUNCTION 2,100
122 SP184201008 CABLE - I/P FUSE F2 TO D1&D2 JUNCTION 2,100
123 SP184201009 CABLE - TH1& D1 JUNCTION TO L2 2,700
124 SP184201010 CABLE FROM U-PH OF DI/DT TO OUTPUT 3,900
125 SP184201011 CABLE FROM V-PH OF DI/DT TO OUTPUT 3,700
126 SP184201012 CABLE FROM W-PH OF DI/DT TO OUTPUT 3,700
127 SP184201013 DATA DOWNLOADING CABLE 2,750
128 SP184201014 CABLE - TH2& D2 JUNCTION TO CAPACITOR 2,450
IM- 41 rev 6 53
Chapter-9 Maintenance Medha Servo Drives Pvt. Ltd.
Control Unit
with Static
Converter
54 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
IM- 41 rev 6 55
Chapter-9 Maintenance Medha Servo Drives Pvt. Ltd.
K
AN
BL
FT
LE
Y
LL
NA
IO
NT
TE
IN
IS
GE
PA
I S
TH
56 IM- 41 rev 6
Chapter 10
TROUBLESHOOTING PROCEDURE
CAUTION: The heat sink fins have a high temperature. Be careful not to
touch them. Otherwise, there is danger of getting burned.
Occurrence of every fault leads to fault log entry (fault log data and various
parameter values are stored in main micro controller) and audible buzzer
indication with LED indication.
Status of
Message on
S.No. Converter on fault Probable Cause Action to be taken
Display
occurrence
INPUT SIDE
58 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
4. Check the voltage
indication on driver's
cabin, whether it is
also indicating the
same OHE voltage
or not.
5. Wait until input
voltage stabilize
within the working
limits
6. Now converter will
function on it's own,
4. Indication of Input if it is not functioning
voltage in range even after Input
LED (RED) voltage stabilizes,
check for the Input
voltage sensing
circuit (in Transducer
card) and the 12 V
section of the step
down transformer.
7. Even the fault
condition still
persists,
communicate the
same to the service
staff.
Ÿ Fuses (F1 &F2)
1. Do not switch ON
may be blown.
the converter with
input available till
Ÿ Dead short circuit
the fault is cleared.
on the auxiliary
2. Check micro switch
side.
connection (wire
93) of input fuse.
Ÿ Short circuit in
3. Check Input fuses
the DC Link filter
(F1, F2).
(LC) side.
1. Rectifier OFF 4. Check whether
short circuit exists
Ÿ Short circuit in
2. Converter in DC Link filter
the connecting
functions in the (LC ) Circuit of
cable between
normal way after converter.
3 Input Fuse Fail rectifier and
clearing the fault. 5. Check whether
inverter section.
short circuit exists
3. Indication of in the connecting
Ÿ High voltage
Input voltage in cable between
spikes on
range LED (RED) rectifier and
auxiliary
inverter section.
transformer
6. Check the OHE
secondary (MOV
voltage at the time
burnt).
of fuse fail from
fault log data.
Ÿ Loose contact in
7. Check the micro
the fuse fail
switches contact
detection circuit
and fuse fail
(contact of micro
sensing circuit.
switches)
IM- 41 rev 6 59
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
8. If none of the above
things are noticed ,
then communicate
the same with
service staff.
1. Rectifier OFF.
2. Converter
restarts itself
(automatically) 1. Check the output
3. If the fault loads, load
condition is connections.
removed Ÿ Output Over load Rectify the problem
converter works if exists.
normally. Ÿ Overload due to 2. Check the DC Link
4. Input current DC Link LC filter LC filter of the
Input Current High fault is of converter(if converter.
4. counted by the
High any defect). 3. Check the rectifier
main controller. section and restart
5. However, if the Ÿ Defect in Input the system.
fault persists for Current sensing 4. If still the fault
more than 2 circuit. persists, don’t
times, 3rd time close the DJ and
it's a latched inform the condition
shut down. to the service staff.
6. Indication of
Internal fault
LED (RED).
RECTIFIER SECTION
1. Rectifier OFF.
2. Converter 1. This fault occurs ,
restarts it self When the DC Link
(automatically) voltage is < 500 V.
3. If the fault 2. Check the rectifier
Ÿ Fault in the
condition is assembly input and
rectifier section.
removed output connections.
converter works 3. Check the DC Link
Ÿ Over loading at
normally. filter circuit
the OUTPUT
4. DC Link Voltage connections
section
DC Link Voltage LOW fault is 4. Check the DC Link
5. LOW counted by the voltage sensor and
Ÿ DC Link voltage
(3 times) main controller. sensing circuit.
sensor and
5. However , if the 5. Check the Thyristor
sensing circuit
fault persists for angle firing control
more than 2 card and its
Ÿ Thyristor angle
connections.
times, 3rd time firing control card
6. If still the fault
it's a latched or connections.
persists, don’t
shut down. close the DJ and
6. Indication of inform the condition
Internal fault to the service staff.
LED (RED).
60 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
IM- 41 rev 6 61
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
5. However, if the
fault persists for
more than 2 5. If still the fault
times, 3rd time it's persists, don’t close
a latched shut the DJ and inform
down. the condition to the
6. Indication of service staff.
Internal fault LED
(RED).
1. Rectifier OFF.
2. Converter
restarts itself
(automatically)
3. If the fault 1. Check the loads
condition is and load
removed connections.
converter works Ÿ Fault in the
normally. rectifier section. 2. Check the
4. Chopper healthiness of the
Current HIGH Ÿ Out side due to DC Link.
Chopper fault is counted faulty load.
9.
Current high by the main 3. Check healthiness
controller. Ÿ Fault may be in of TAFC card.
5. However, if the TAFC card (due
fault persists for to unregulated 4. If still the fault
more than 2 DC link) persists, don’t
close the DJ and
times, 3rd time inform the condition
it's a latched to the service staff.
shut down.
6. Indication of
Internal fault
LED (RED).
1. Rectifier OFF.
2. Converter
restarts it self
(automatically) 1. Check the current
3. If the fault Ÿ Chopper current sensor feed back
condition is sensor or its and Analog card.
removed sensing circuit.
converter works 2. Check the
normally. Ÿ Brake chopper healthiness of
4. Chopper fault is card or Chopper Break chopper
10. Chopper fault counted by the IGBT. card, IGBT and
main controller. Chopper resistors.
5. However, if the
fault persists for Ÿ Chopper 3. If still the fault
more than 2 resistors or its persists, don’t
times, 3rd time connections. close the DJ and
it's a latched inform the condition
shut down. to the service staff.
6. Indication of
Internal fault
LED (RED).
62 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Check whether the
air flow path to the
rectifier is not
obstructed.
2. Check the heat
Ÿ Heat sink sink cooling blower.
Cooling blower 3. Check healthiness
of output loads,
1. Rectifier OFF. Ÿ Actual ambient which if faulty can
temperatures cause continuous
2. Converter overload of rectifier
restarts itself Ÿ Continuous and thus over
(automatically) overload of temperature.
on finding LOW rectifier due to 4. Check whether the
Rectifier over rectifier faulty load. ambient is less
11.
temperature temperature i.e than 55°C or not.
on clearance of Ÿ Thermal switch 5. Check the
the fault on rectifier heat healthiness of
sinks. thermal switch on
3. Indication of the rectifier heat
Internal fault Ÿ Chopper sink.
LED (RED). conduction or 6. Check the break
it's Thermal chopper current
switch on heat and heat sink
sink temperature.
7. If still the fault
persists, don’t
close the DJ and
inform the condition
to the service staff.
INVERTER SECTION
1. Check the Inverter
assembly.
1. Rectifier OFF. 2. Check the
2. Converter healthiness of the
restarts it self Ÿ Inverter load and load
(automatically) assembly connections.
3. If the fault 3. Check the
condition is Ÿ Over loading at healthiness of
removed the OUTPUT PWM card
converter works section. 4. Check the voltage
normally. sensors and
4. Inverter fault is Ÿ PWM card or its sensing circuit
12. Inverter fault counted by the connections connections.
main controller. 5. Check the
5. However , if the Ÿ Inverter power healthiness of the
fault persists for supply output sine filter.
more than 2 6. Check the
times, 3rd time Ÿ Output Voltage healthiness of
it's a latched sensing circuit. inverter power
shut down. supply card.
6. Indication of Ÿ Output sine filter If still the fault
Internal fault persists, don’t close
LED (RED). the DJ and inform
the condition to the
service staff.
IM- 41 rev 6 63
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Check whether the
air flow path to the
inverter heat sink is
not obstructed.
2. Check the heat
sink cooling blower.
3. Check healthiness
Ÿ Heat sink
of output loads,
1. Rectifier OFF. Cooling blower
which if faulty can
cause continuous
2. Converter Ÿ Actual ambient
overload of inverter
restarts it self temperatures
and thus over
(automatically)
temperature.
on finding LOW Ÿ Continuous
4. Check whether the
Inverter Over inverter overload of
13. ambient is less
temperature temperature i.e inverter due to
than 55°C or not.
on clearance of faulty load.
5. Check the
the fault.
healthiness of
Ÿ Thermal switch
thermal switch on
3. Indication of on inverter heat
the inverter heat
Internal fault sink.
sinks.
LED (RED).
6. Ensure the sensing
Ÿ Analog card
circuit function and
connections in
Analog card.
7. If still the fault
persists and inform
the condition to the
service staff.
OUTPUT SECTION
1. Check the rectifier
1. Rectifier OFF. output and
2. Converter connections
restarts it self between DC Link
(automatically) filter to Inverter.
3. If the fault 2. Check the Inverter
condition is Ÿ Rectifier output assembly.
removed 3. Check the
converter works Ÿ TAFC card healthiness TAFC
normally. assembly card and its
4. Output voltage connections.
Output voltage high fault is Ÿ Inverter 4. Check the voltage
14. counted by the
HIGH assembly sensors and
main controller. sensing circuit
5. However , if the Ÿ Output Voltage connections in TDC
fault persists for sensing circuit. IF card.
more than 2 5. Check the
times, 3rd time Ÿ Output sine filter healthiness of the
it's a latched output sine filter.
shut down. 6. If still the fault
6. Indication of persists, don’t
Internal fault close the DJ and
LED (RED). inform the condition
to the service staff.
64 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Check the rectifier
output and
connections
1. Rectifier OFF. between DC Link
2. Converter filter to Inverter.
restarts it self 2. Check the Inverter
(automatically) assembly.
3. If the fault 3. Check the
condition is healthiness of the
Ÿ Rectifier output
removed load and load
converter works connections.
Ÿ Inverter
normally. 4. Check the Inverter
assembly
4. Output voltage output connections
low fault is to the load.
Output voltage Ÿ Load side due to
15. counted by the 5. Check the voltage
LOW faulty load.
main controller. sensors and
5. However, if the sensing circuit
Ÿ Output Voltage
fault persists for connections.
sensing circuit.
more than 2 6. Check the
healthiness of the
times, 3rd time Ÿ Output sine filter
output sine filter.
it's a latched 7. Check the
shut down. healthiness of
6. Indication of TAFC card
Internal fault 8. If still the fault
LED (RED). persists, don’t
close the DJ and
inform the condition
to the service staff.
1. Rectifier OFF. 1. Check the
2. Converter healthiness of
restarts it self loads and load
(automatically) connections.
3. If the fault
condition is 2. Check the Inverter
removed Ÿ Load side due to
output connections
converter works faulty load (high
to the loads.
normally. single phase
4. Single phase load).
3. Check Output
Single Phase voltage fault is voltage sensing
16. counted by the Ÿ Output voltage
voltage fault circuit.
main controller. sensing circuit.
5. However, if the 4. Check Inverter
fault persists for Ÿ Inverter
assembly.
more than 2 assembly.
times, 3rd time 5. If still the fault
it's a latched persists, don’t
shut down. close the DJ and
6. Indication of inform the condition
Internal fault to the service staff.
LED (RED).
IM- 41 rev 6 65
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Rectifier OFF.
2. Converter 1. Check the
restarts it self healthiness of
(automatically) loads and load
3. If the fault connections.
condition is 2. Check the Inverter
removed Ÿ Load side due to output connections
converter works faulty load. to the loads.
normally. 3. Check Output
4. Output current Ÿ Output current current sensing
Output current high fault is sensing circuit. circuit.
17. counted by the
HIGH 4. Check Inverter
main controller. Ÿ Inverter assembly.
5. However, if the assembly. 5. Check the
fault persists for healthiness of
more than 2 Ÿ Output sine filter. output sine filter
times, 3rd time 6. If still the fault
it's a latched persists, don’t
shut down. close the DJ and
6. Indication of inform the condition
external fault to the service staff.
LED (RED).
1. Rectifier OFF. 1. Check the
2. Converter healthiness of
restarts it self loads and load
(automatically) connections
3. If the fault (imbalances in the
condition is loads).
removed Ÿ Load side due to 2. Check the Inverter
converter works faulty load. output connections
normally. to the loads.
4. Single phase Ÿ Output current 3. Check the
Single phase current fault is sensing circuit. healthiness of
18. counted by the
current output sine filter.
main controller. Ÿ Inverter 4. Check Inverter
5. However, if the assembly. assembly.
fault persists for 5. Check Output
more than 2 Ÿ Output sine filter. current sensing
times, 3rd time circuit.
it's a latched 6. If still the fault
shut down. persists, don’t
6. Indication of close the DJ and
external fault inform the condition
LED (RED). to the service staff.
66 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Rectifier OFF. 1. Check the
2. Converter Ÿ Load side due to healthiness of the
permanently faulty load. loads.
shuts down 2. Check the load
Converter runs , Ÿ Cable cables connection
only after reset connections from static
of the control between static converter to loads.
OUTPUT short
19. supply (Reset converter output 3. Check the
circuit switch on the and loads. healthiness of
front panel is output sine filter.
used to reset Ÿ PWM card 4. Check the
the latched unit). functionality of
3. Indication of Ÿ Inv. gate drive PWM and Gate
external fault card drive card and it's
LED (RED). connections.
1. Check the blower
healthiness.
1. Audible buzzer
indication. 2. Check blower
Ÿ Blower function.
current sensor and
2. Indication of current sensing
Ÿ Blower current
internal fault circuit In charger
sensing circuit.
LED (RED). MC card.
20. Blower fault
Ÿ Blower fuses.
3. Static converter 3. Check the blower
functions transformer (step
Ÿ Blower sine filter
normally even down transformer
and Transformer
on detection of connected at the
this fault. static converter
output side)
healthiness.
EARTH FAULT
1. Rectifier OFF.
2. Converter waits
in by pass
mode.
3. Converter 1. Check the wiring at
restarts it self. DC Link output
4. If the fault side.
condition is 2. Check the wiring
removed between inverter
converter works input and output.
normally. 3. Check the
5. Internal earth Ÿ Earth fault at
Internal earth insulation levels of
21. fault is counted Rectifier, DC link
fault (3 times) DC link inductor
by the main or inverter side.
and di/dt inductor.
controller. 4. Check the
6. However, if the healthiness of
fault persists for Analog card
more than 2 5. Check the Blower
times, 3rd time transformer
it's a latched insulation levels.
shut down.
7. Indication of
internal fault LED
(RED).
IM- 41 rev 6 67
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
1. Rectifier OFF.
2. Converter waits
in by pass
mode.
3. Converter
restarts it self
(automatically).
4. If the fault
condition is
removed
converter works 1. Check the Load
normally. side connections.
External earth 5. External earth Ÿ Earth fault at the
22.
fault fault is counted load side
2. Check the load
by the main insulation levels.
controller.
6. However, if the
fault persists for
more than 2
times, 3rd time
it's a latched
shut down.
7. Indication of
external fault
LED (RED).
BATTERY CHARGER SECTION
1. Audible buzzer
indication.
1. Check the
2. Visible LED healthiness of
indication. Charger CC card.
Charger voltage Ÿ Charger CC card
23. (CHBA LED –
HIGH Ÿ Feedback wiring
OFF(GREEN)) 2. Verify the all the
connections of CC
3. Indication card.
Internal fault
LED (RED)
1. Audible buzzer
indication.
68 IM- 41 rev 6
Medha Servo Drives Pvt. Ltd. MIN184 - Operation & Maintenance Manual
Status of
Message in
Sl.no Converter on fault Probable Cause Action to be taken
Display
occurrence
Ÿ Indication
External fault Ÿ Check the battery
Ÿ Battery Charger
Charging LED (RED). charger section
25. section output
current HIGH output load and
load.
Ÿ Only fault battery.
logging.
1. Check the battery
1. Rectifier OFF.
charger assembly.
Ÿ Load side 2. Check the load
2. Converter
connections. side connections.
restarts it self
3. Check the Thermal
(automatically)
Ÿ Battery charger switch connections
on finding LOW
assembly. to the Analog card.
CHBA Over CHBA
26. 4. Check the
temperature temperature i.e
Ÿ Thermal switch healthiness of
on clearance of
on charger heat Thermal switch.
the fault.
sink. 5. If still the fault
persists, don’t
3. Indication of
Ÿ Analog card close the DJ and
Internal fault
inform the condition
LED (RED).
to the service staff.
1. Rectifier OFF.
2. Converter
restarts it self Ÿ Control supply 1. Check the 110 V
(automatically) (110 V) connections to the
on recovery of converter.
Control supply
27. control supply Ÿ Power supply
failure
i.e on clearance cards 2. Check the control
of the fault. supply connections
Ÿ TDC IF card. at TDC IF card.
3. Indication of
Internal fault
LED (RED).
1. Audible buzzer 1. Check healthiness
indication. of Battery charger
CC and MC card,
2. Visible LED charger IGBT.
indication.
(CHBA -OK Ÿ Check charger 2. Check charger
28. CHBA fault
green LED - section load.
OFF))
3. If still the fault
3. Indication persists, inform the
Internal fault condition to the
LED (RED) service staff.
IM- 41 rev 6 69
Chapter-10 Troubleshooting Medha Servo Drives Pvt. Ltd.
Procedure
From:
To
M/S MEDHA SERVO DRIVES (P) LTD.
P-4/5B, I.D.A, NACHARAM
Hyderabad – 500 076
Phone: +91 40 27171101
Fax: +91 40 27174908
Remarks :
Signature: Stamp:
Date:
70 IM- 41 rev 6
Annexure - 1 MIN184 - Operation and Maintenance Manual
IM - 41 rev 6
Annexure - 2 MIN184 - Operation and Maintenance Manual
IM - 41 rev 6
Annexure - 3 MIN184 - Operation and Maintenance Manual
IM - 41 rev 6
Annexure - 4 MIN184 - Operation and Maintenance Manual
IM - 41 rev 6
Operation and Maintenance Manual