Report:
We inspected the fire alarm software of SECTRON panel in the car park B and found:
- The MGC software can connect All the panels via netwok with no problem.
- The network of SECTRON panels consist of 19 network panels.
- We succeded in changing the ESD dongole number to be 5032 same as the old ESD number of panels.
- The data couldn't be taken from the network panel as it is giving failure during progress of transfering.
The solution:
- The only way to solve the fire panels is to write a new program again from scratch then send to all panels.
- We will use the point list shown in the panel and take it point by point then make the new program.
- The new program will be delivered to the customer.
--------------------------
END