Professional Documents
Culture Documents
Isha Rana Structural Report
Isha Rana Structural Report
Isha Rana Structural Report
i
Contents
List of Figures...............................................................................................iii
List of Tables................................................................................................iv
1 Introduction............................................................................................1
1.1 An Overview of Earthquake-Resistant Design.....................................................1
1.2 Earthquake Resistant Design Philosophy.............................................................2
2 Description of the Building....................................................................4
2.1 Building Description.............................................................................................4
2.2 Location of Building.............................................................................................5
3 Numerical modeling...............................................................................6
4 Structural analysis................................................................................10
4.1 Load cases considered.........................................................................................10
4.2 Load combination...............................................................................................10
4.3 Mass Source........................................................................................................10
4.4 Dead loads...........................................................................................................10
4.5 Live load.............................................................................................................12
4.6 Seismic Loading..................................................................................................13
4.7 Story Drift and displacement Calculations.........................................................14
4.8 Modal analysis and modal mass participation....................................................17
4.9 Base Shear and Seismic weight..........................................................................18
4.10 Analysis of Internal Forces Developed in Frames..........................................18
5 Design....................................................................................................20
5.1 Column design summary....................................................................................21
5.2 Beam Design Summary......................................................................................24
5.3 Slab Design Summary.........................................................................................28
5.4 Staircase Design Summary.................................................................................28
5.5 Foundation Design Summary..............................................................................28
6 CONCLUSION.....................................................................................30
7 RECOMMENDATIONS.....................................................................30
ANNEXES....................................................................................................31
ANNEX -I: REFERENCES..........................................................................................31
ANNEX-II: SAMPLE DESIGN CALCULATIONS....................................................32
SAMPLE BEAM DESIGN BY ETABS(C-1/2, ground Floor)................................32
SAMPLE COLUMN DESIGN (A3-First Floor).......................................................33
SAMPLE SLAB DESIGN.........................................................................................35
SAMPLE ISOLATED FOOTING DESIGN(A-3 grid)............................................38
SAMPLE STRAP FOOTING DESIGN(B-2/4 grid).................................................40
SAMPLE COMBINED/MAT FOOTING DESIGN(B-1,B-2,C-1,C-2 grid)............47
SAMPLE STAIRCASE DESIGN.............................................................................51
SAMPLE BEAM COLUMN CAPACITY CHECK.................................................53
ii
List of Figures
Figure 2-1 : Ground floor Plan of Building.........................................................................4
Figure 2-2 : Seismic Hazard of Himalayas..........................................................................5
Figure 3-1 : 3D model created in ETABS...........................................................................6
Figure 3-2 : Ground Floor plan modeled in ETABS...........................................................7
Figure 3-3 : First Floor plan modeled in ETABS................................................................7
Figure 3-4 : Second floor plan modeled in ETABS............................................................8
Figure 3-5 : Elevation on grid A-A......................................................................................8
Figure 3-6 : Elevation on grid B-B......................................................................................9
Figure 3-7 : Elevation on grid C-C......................................................................................9
Figure 4-1 : Wall load........................................................................................................11
Figure 4-2 : Floor finish load.............................................................................................11
Figure 4-3 : Live load........................................................................................................12
Figure 4-4 : Terrace live load............................................................................................12
Figure 4-5 : Drift ratio in Eqx Service loading..................................................................14
Figure 4-6 : Drift ratio in Eqy service loading.................................................................15
Figure 4-7 : Drift ratio in Eqx ultimate loading...............................................................15
Figure 4-8 : Drift ratio in Eqy ultimate loading.................................................................16
Figure 4-9 : Displacement in Eqx Service loading............................................................16
Figure 4-10 : Displacement in Eqy service loading...........................................................17
Figure 4-11 : Sample Bending Moment Diagram for frames along Grid 1/1-1.2DL+1.5LL
...........................................................................................................................................19
Figure 4-12 : Sample Shear force Diagram for frames along Grid 1/1 -1.2DL+1.5LL)...19
Figure 4-13 : Sample Axial force Diagram for frames along Grid 1/1-1.2DL+1.5LL......19
Figure 5-1 : Rebar of column in Grid A............................................................................21
Figure 5-2 : Rebar of column in Grid B............................................................................21
Figure 5-3 : Rebar of column in Grid C............................................................................22
Figure 5-4 : Rebar in Ground floor beam.........................................................................24
Figure 5-5 : Rebar in first floor beam................................................................................24
Figure 5-6 : Rebar in Second floor beam..........................................................................25
Figure 5-7 : Base reaction for footing design....................................................................28
iii
List of Tables
Table 2-1 : Building Description.........................................................................................4
Table 4-1 : Mass source.....................................................................................................10
Table 4-2 : Dead loads unit weight....................................................................................10
Table 4-3 : Dead load applied............................................................................................11
Table 4-4 : Live load applied.............................................................................................12
Table 4-5 : Seismic Coefficient Calculation as per NBC 105:2020..................................13
Table 4-6 : Modal mass Participation ratio from ETABS.................................................17
Table 4-7 : Base Shear of structure....................................................................................18
Table 5-1 : Column Design Summary...............................................................................22
Table 5-2 : Beam Design Summary...................................................................................26
Table 5-3 : Footing Design Summary...............................................................................29
iv
EXECUTIVE SUMMARY
The primary objective of the project is to analyze and design the structural elements of
the buildings based on NBC standards. The seismic coefficient method is adopted to
analyze the earthquake response of the building.
Finite element analysis showed that the anticipated performance of the buildings
subjected to the design earthquake meets NBC code seismic hazard level requirement for
building. The building response for drift, displacement is also calculated.
The structure is designed to complying the guidelines and the NBC standards.
Story drifts are within the acceptable limits under DBE level earthquakes.
** The structural design is carried on the architectural drawing provided. This report solely emphases and
confines itself to technical aspects of the structure and does not comment on other aspects of the structure.
v
1 Introduction
1.1 An Overview of Earthquake-Resistant Design
Nepal lies in an earthquake prone zone. It is located in the boundary between Indian plate and
Tibetan plate. Thus, Nepal experiences earthquakes frequently. Earthquakes are the most
sudden, dramatic and devastating natural calamities. Although they last only for few seconds
to minutes, they are the most devastating ones. Past records of the earthquake show that
eighteen major earthquakes have hit Nepal till now. So, special consideration of earthquake
forces while designing a building is mandatory in Nepal.
Designing building against earthquake forces does not mean that we are making the building
earthquake-proof. Although earthquake proof structures may be viable in terms of engineering
but they are not financially viable. However, it is possible to design and build earthquake-
resilient (more precisely seismic resilient) structures. According to this philosophy, no matter
how much severe earthquake occurs, the building won’t collapse although it may be
irreparably damaged. In, this background, it is ensured that this building has been designed to
withstand all the acting loads including the earthquake forces making it seismic resistant.
The structural design alone is not enough to ensure the safety of a building, equally
important, is its construction. The role of a contractor is of paramount importance as he is the
one to execute the construction work at site. He is required to execute the work according to
drawings supplied by the consultant to him and detailing has to be carefully followed. A large
percentage of failure of the building is attributed to poor quality of construction. Past
experiences from damages have shown that quality of material and workmanship play an
important role in good seismic behavior of the buildings. Hence, quality assurance of
construction works is the key to good seismic performance of a building.
Severity of ground shaking at a given location during an earthquake can be minor, moderate
and strong. Relatively, minor shakings occur frequently, moderate shakings occasionally and
strong shakings rarely. For instance, on average annually about 800 earthquakes of magnitude
5.0-5.9 on Richter scale occur in the world while the number is only about 19 for magnitude
of range 7.0-7.9 on Richter scale. So, should we design and construct a building to resist that
1
rare earthquake shaking that may come only once in 500 years or even once in 2000 years at
the chosen project site, even though the life of the building itself may be only 50 or 100 years?
Since it costs money to provide additional earthquake safety in buildings, a conflict arises:
Should we do away with the design of buildings for earthquake effects? Or should we design
the buildings to be “earthquake proof” wherein there is no damage during the strong but rare
earthquake shaking? Clearly, the former approach can lead to a major disaster, and the second
approach is too expensive. Hence, the design philosophy should lie somewhere in between
these two extremes.
The engineers do not attempt to make earthquake proof buildings that will not get damaged
even during the rare but strong earthquakes; such buildings will be too robust and also too
expensive. Instead, the engineering intention is to make buildings earthquake resistant and
affordable; such buildings resist the effects of ground shaking, although they may get
damaged severely but would not collapse during the strong earthquake. Thus, safety of people
and contents is assured in earthquake-resistant buildings, and thereby a disaster is avoided.
This is a major objective of seismic design codes throughout the world.
a) Under minor shakings which occur frequently, the main members of the buildings that
carry vertical and lateral forces should not be damaged; however non-structural parts may
sustain repairable damages. It is assured that the building will be fully operational within a
short time and the repair costs will be small
b) Under moderate shakings which are occasional, the structural elements may sustain
repairable damage, while the non-structural elements may be heavily damaged; the building
will be operational followed by repair and re-strengthening of the damaged structural
elements and replacing of damaged non-structural elements.
2
c) Under strong shakings which are rare, the main members may sustain severe damage, but
the building should not collapse; the building may become dysfunctional for further use, but
will stand so that people can be evacuated and property recovered.
The degree to which the building is to be assured against the possibility of damage must be
considered while designing the building. Important buildings like hospitals, health posts, fire
stations, post offices communication towers, electric power houses which play a critical role
in post-earthquake activities must remain functional immediately after the earthquake and
hence require higher degree of assurance against possible damage. Public buildings,
educational buildings, busy commercial complex etc. where the risk of human loss is high and
some critical structures like nuclear power plants, dams, etc. whose collapse may cause
secondary disasters are also designed to assure higher level of safety against earthquakes.
Other buildings like residential buildings, offices, mercantile buildings etc. are designed for
lower level of safety, while the design philosophy mentioned above is always maintained.
However, the level of safety to be assured in the design may also depend upon the demand of
the client.
Design of buildings to resist earthquakes involves controlling the damage to acceptable levels
at a reasonable cost. Contrary to the common thinking that any crack in the building after an
earthquake means the building is unsafe for habitation, some damage in non-structural
elements may be unavoidable. Different types of damages (mainly visualized through cracks;
especially so in concrete and masonry buildings) may occur in buildings during earthquakes.
Some of these cracks are acceptable (in terms of both their size and location), while others are
not. In general, qualified technical professionals may only be knowledgeable of the causes and
severity of damage in earthquake-resistant buildings.
3
2 Description of the Building
2.1 Building Description
The building to be analyzed and designed here is a two and half story residential building to
be constructed on behalf of Mrs. Isha Rana. The proposed site is located at Lalitpur. The
ground floor plan of the building is presented below in Figure 2-1. The building description is
presented in Table 2-1: Building Description.
4
Max distance along Y: 8.26 m
Wall and Partition 9” and 5” Brick Masonry in cement mortar
in outside and inside respectively
Structural features
Structural System RCC Frame Structure
Foundation Type RCC Isolated Footings,Strap and Combined
footing
Loads Resisting Elements
Columns 350 mm X350 mm
Beams Main beam: 230mm X 350mm
Secondary beam: 230mm X 300mm
Slab 125 mm
Geotechnical Features
Soil Test Not Available
Soil Type (assumed) Type D (As per NBC)
Allowable bearing capacity assumed 120 KN/m2
Material
Grade of concrete: M20 for column, beam, slab and footings.
Grade of Reinforcement steel for RCC Fe 500
5
3 Numerical modeling
A three dimensional finite element model of the whole structural system is created in
ETABS.v18. The structural system is considered as a Special Moment Resisting Frame
structure. Main components to be modeled are: Beams, Columns & Slabs. Beams and
columns are modeled as frame elements while slabs are modeled as four-nodded shell
elements. The support condition at the base is idealized as a fixed support and hence any
moment release at the base of columns is neglected. The moment release at the beam/column
joints is also neglected. Self-weight of the parapet wall is applied onto the beams in the form
of uniformly distributed loads. The inner partition wall load is applied by creating null beam
as positioned in architectural drawing.
6
Figure 3-4 : Ground Floor plan modeled in ETABS
7
Figure 3-6 : Second floor plan modeled in ETABS
8
Figure 3-8 : Elevation on grid B-B
9
4 Structural analysis
For the purpose of structural analysis various Nepal Standard Code and Indian Standard codes
are followed for loadings, load combinations and other analysis procedures.
I. 1.2DL±1.5LL
II. DL+0.3LL±EQx
III. DL+0.3LL±EQy
10
Reinforcement Steel 78.50 KN/m³
Brick Masonry 19.2 KN/m3
11
4.5 Live load
Live loads are applied on floor slabs on the basis of usage of rooms, as specified in IS 875
part II.
12
4.6 Seismic Loading
The building is analyzed for the seismic load as per NBC 105 2020. The seismic design data
assumed for the building is summarized below.
The approximate time period of the building is calculated as per clause 7.6.2 for RC moment
resisting frame. The calculated fundamental time period is Tx= 0.374 sec in both X and Y
directions.
Period of vibration
For reinforcement moment resisting
frame T1=1.25k1h0.75 0.463 sec
Lower period of flat part of spectrum(Ta) 0.5 sec
Upper period of flat part of spectrum(Tc) 2 sec
Peak spectral acceleration normalized by
PGA(α) 2.25 sec
Coefficient that controls the descending
branch of the spectrum 0.8
13
Elastic site spectra for Vertical loading
Cv(Tv)= 2/3 Z 0.233333
14
Figure 4-15 : Drift ratio in Eqy service loading
Maximum story drift due to service seismic load along y: 0.0024
Maximum allowable drift ratio in Serviceability Limit State is 0.006 as per NBC 105
2020
15
Figure 4-17 : Drift ratio in Eqy ultimate loading
Maximum story drift due to Ultimate seismic load along y: 0.0025x4=0.01
Maximum allowable drift ratio in Ultimate Limit State is 0.025 as per NBC 105 2020
16
Figure 4-19 : Displacement in Eqy service loading
17
Modal 11 0.017 0 0 1 1 1
0.0000030
Modal 12 0.012 58 0 1 1 1
The total mass participation in both considered direction is greater than the 90% of the total
lateral force. A building has regular modes of oscillation in two principal plan directions as
the mass participation factor for first three modes is greater than 65%.
18
Figure 4-20 : Sample Bending Moment Diagram for frames along Grid 1/1-
1.2DL+1.5LL
Figure 4-21 : Sample Shear force Diagram for frames along Grid 1/1 -1.2DL+1.5LL)
Figure 4-22 : Sample Axial force Diagram for frames along Grid 1/1-1.2DL+1.5LL
19
5 Design
The design of reinforced concrete structural members includes selection of material properties
(grade of steel and concrete), shape and size of cross section, factor of safety and amount of
steel required. The design of reinforced concrete members is carried out using limit state
method as per IS 456: 2000. The limit state method is the modern and latest design
methodology. This method evolved around 1970’s. Limit state method is based on the concept
of multiple safety factors and attempts to provide adequate safety at the ultimate loads and
adequate serviceability at service loads. For the design of the members, IS 456:2000 and
design aid SP 16 has been used. Footings have been checked for vertical loads due to dead
load and live load only. Square footings have been adopted from seismic point of view that
reversal stress may occur. And footing beams are provided for column at foundation for more
rigidity of building and also need for the column located at boundary. Longitudinal
reinforcement in beams and columns has been calculated based on critical load combination.
Spacing of the shear reinforcement has been calculated as per the ductility criteria as defined
in IS 13920 -1993. Some sample designs are shown later on in this report.
Beams and columns have been designed using ETABS while slab, staircase and foundations
are designed manually. Samples of manual design calculation of critical slab, footings and
staircase are shown in this report in ANNEX-II: SAMPLE DESIGN CALCULATIONS. The
structural design of sections and reinforcements are presented in the drawing.
20
5.1 Column design summary
21
Figure 5-25 : Rebar of column in Grid C
GF 1006 4 16 4 16
A1
1st 980 4 16 4 12
C1-
350x350 2nd 980 4 16 4 12
C1- GF 980 4 16 4 16
350x350
B1 1st 980 4 16 4 12
2nd 1061 4 16 4 12
C1- C1
350x350 GF 1060 4 16 4 16
1st 980 4 16 4 12
22
2nd 980 4 16 4 12
C1-
350x350 GF 995 4 16 4 16
1st 980 4 16 4 12
A2 2nd 980 4 16 4 12
C1-
350x350 GF 980 4 16 4 16
1st 980 4 16 4 12
B2 2nd 1026 4 16 4 12
C1-
350x350 GF 1017 4 16 4 16
1st 980 4 16 4 12
C2 2nd 1057 4 16 4 12
C2-
350x350 GF 1051 4 16 4 16
A3 1st 1302 4 16 4 16
C1-
350x350 GF 1008 4 16 4 16
1st 980 4 16 4 12
B3 2nd 1089 4 16 4 12
C1-
350x350 GF 1042 4 16 4 16
1st 980 4 16 4 12
C3 2nd 1092 4 16 4 12
23
5.2 Beam Design Summary
28
Figure 5-28 : Rebar in Second floor beam
25
Table 5-10 : Beam Design Summary
Diameter of Rebar
Beam
Floor Left Middle Right
ID
Top Bottom Top Bottom Top Bottom
1-A/B Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
1-B/C Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
2-A/B Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
2-B/C Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
3-A/B Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
3-B/C Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
A-1/2 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
A-2/3 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
B-1/2 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
B-2/3 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
C-1/2 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
C-2/3 Ground Floor 2-16(Th)+3-12(Ext) 3-16(TH) 2-16(Th) 3-16(TH) 2-16(Th)+3-12(Ext) 3-16(TH)
1-A/B 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
1-B/C 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
2-A/B 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
2-B/C 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
3-A/B 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
3-B/C 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
A-1/2 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
A-2/3 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
B-1/2 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
B-2/3 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
C-1/2 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
C-2/3 1st floor 2-16(Th)+1-16(Ext) 2-16+1-12(Th) 2-16(Th) 2-16+1-12(Th) 2-16(Th)+1-16(Ext) 2-16+1-12(Th)
1-A/B 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
1-B/C 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
30
2-A/B 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
2-B/C 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
3-B/C 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
A-1/2 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
B-1/2 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
B-2/3 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
C-1/2 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
C-2/3 2nd floor 2-12(TH)+1-12(Ext) 3-12(Th) 2-12(TH) 3-12(Th) 2-12(TH)+1-12(Ext) 3-12(Th)
All floor secondary beam 3-12(Th) 3-12(Th) 3-12(Th) 3-12(Th) 3-12(Th) 3-12(Th)
Note:-Th=Throughout rebar, Ext =Extra rebar, secondary beam size=230x300 with 3 nos 12 mm bar at top and bottom
27
5.3 Slab Design Summary
Size: 125mm
Reinforcement:
Let’s provide 8mm@150mm c/c both ways with usual layouts/curtailments wherever required
For more details, refer structural drawings
32
Table 5-11 : Footing Design Summary
Footing pad
Footing type Size(mm*mm) Depth(mm) Reinforcement
IF1(A-3) 1500 X1500 450 mm 12 mm bar @150 c/c both way
F1(A-2,B-3) 1900 X 1900 450 mm 12 mm bar @150 c/c both way
EF1(A-1,C-3) 1700 X 1700 450 mm 12 mm bar @150 c/c both way
CF1(B1,C1,C2,B2) 4000x4900 450 mm 16 mm bar @150 c/c both way
Combined footing at top and bottom
Strap beam
SB1(connecting F1& 350x500 6 nos 16 mm @150 c/c at top and 4 nos 16
EF1) mm @150 c/c at bottom with 3 legged 10
mm bars @150 c/c
Tie beam
LTB1 & UTB1 230 x300 Longitudinal bars: 3-12dia top & bottom
Stirrups : 2-legged 8 dia @ 6" c/c
For more details, refer structural drawing
29
6 CONCLUSION
After the analysis of the building components, the building is found to be safe against the
gravity as well as Seismic Loads. The section sizes and reinforcements are sufficient enough
to withstand all kinds of possible axial, shear, flexural and torsional forces. The building is
designed to make it good enough to assure Life Safety under Design Basis Earthquake
considered for Zoning factor 0.35, Importance Factor 1.0 and soft soil condition as per
NBC205:2020. Bearing capacity of the soil is taken as 120 KN/m 2. M20 grade of concrete is
used for columns, beams, slabs and foundations. Ductile detailing as per IS13920:1993 has
been extensively adopted while detailing.
7 RECOMMENDATIONS
Design and construction of the structure are inter – related jobs. A performance of a building
depends upon a work and material quality during the construction more than the intensions
pursued during structural design. A large percentage of structural failures are attributed due to
poor quality of construction. Therefore, to assure the proper safety, material and work quality
should be maintained during the construction. Structural designer will be responsible for all
the designs but not for any faulty constructions happened at site beyond his supervision.
Following recommendations are made by the structural designer.
1. It is recommended to strictly follow the section sizes and reinforcements provided in the
structural drawings.
2. It is recommended that the site engineer should be responsible to handle the problems that
may arise during construction. He/she shall also be responsible for maintaining the material
and process quality during construction.
3. It is strictly recommended that any changes in the design shall be done only with the
consultation of the structural designer.
4. It is strictly recommended to maintain the standards in the grade of cement and
reinforcement steel. It is recommended to run a cube test to ensure the strength and quality of
the concrete ratio used. It is also recommended test the reinforcement steels to ensure the
quality of steel used.
30
ANNEXES
ANNEX -I: REFERENCES
IS: 456 – 2000 Code of Practice for Plain and Reinforced Concrete
IS: 875 (Parts 1-5) Code of practice for design loads (other than earthquake)
for buildings and structures (second revision)
Part 1 – Dead loads Part
2 – Imposed load
SP: 16 – 1980 Design Aids for Reinforced Concrete to IS: 456 – 1978
Pillai, U.C. and Menon,D. Reinforced Concrete Design, second edition, Tata
McGraw Hill Publishing Company Ltd, New Delhi, 2003
31
ANNEX-II: SAMPLE DESIGN CALCULATIONS
Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
230 350 230 0 40 40
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
32
Design Design -Moment +Moment Minimum Required
-Moment +Moment Rebar Rebar Rebar Rebar
kN-m kN-m mm² mm² mm² mm²
Top (+2 Axis) -39.9511 321 0 321 153
Bottom (-2 Axis) 0 160 0 0 160
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
350 350 58 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500
33
ɣC ɣS
1.5 1.15
34
SAMPLE SLAB DESIGN
The design calculation of slab critical slab has been shown in sample slab design
2.0 Loading:
Dead Load: (DL) 3.125 KN/m2
Other Dead Load: (ODL) 2 KN/m2
Live Load: (LL) 2 KN/m2
Total Load: (w) 7.125 KN/m2
Factored Load: (wu) 10.6875 KN/m2
1.181
35
Short span moments:
Support S 7.185 KN-m
Mid Span M 5.395 KN-m
36
7.0 Check for shear stress:
Maximum shear force: Vu 18.089 KN
Shear Stress: tv 0.173 N/mm2
β 7.257
Concrete Shear Strength: tc 0.399 N/mm2
Shear Strength factor: K 1.3
Shear Strength of Slab: tc' 0.5187 > 0.173 N/mm2
OK
37
SAMPLE ISOLATED FOOTING DESIGN(A-3 grid)
Given
Data
Size of column
Bc = 350 mm
Dc = 350 mm
Column Load (V) = 171.8933 KN
Bearing Capacity (qa) = 120 KN/m2
Grade of Concrete (fck) = 20 Mpa
Grade of Steel (fy)= 500 Mpa
Size of footing
L= 1.255 m
B= 1.255 m
Provided (L) = 1.500 m
Provided (B) = 1.500 m
38
depth (d)= 400 mm
Punching shear(τ'V) = 0.161 N/mm2
Ok
Provided depth (d) = 400 mm
Overall Depth (D)= 450 mm
39
Development Length
40
1.Datas
Grade of concrete(fck)= 20 N/mm2
Strength og steel(fy)= 500 N/mm2
Size of column(C1)= 350 x 350 mm
Size of column(C2)= 350 x 350 mm
Factored load on column(P1)= 323.98 KN
Service load on column including wt (P1)
= 237.59 KN
Factored load on column(P2)= 535.66 KN
Service load on column(P2) including
wt= 392.82 KN
Distance between centre of column(s)= 3.135 m
Allowable bearing capacity(q0)= 120 KN/m2
Centre of footing 1 from property
line(x')= 0.175 m
2.Size of footing
Deternination of reactions
Distance of R1 from P1(e) 0.65 m
Distance of R1 From P2 2.485 m
Reaction at footing F1(R1) 299.73 KN
Reaction at footing F2(R2) 330.67 KN
FS against overturning
(characteristic loads ) 6.32 >1.5,OK
Dimension of Footing F2
Footing Area required for F2 3.27 m2
Size of footing F2(B2) 1.81 m
Provided size for footing F2 1.90 m Ok
Dimension of Footing F1
Area of footing A1 required 2.50 m
Length 1.70
Breadth of footing 1.70 m
41
Depth requirement from flexural moment
Factored Soil Pressure= R/A
155.57 KN/m2 OK
width of strap beam= 0.35 m
Cantilever projection of slab= 0.68 m
Maximum moment at the face of strap KN-m per m
beam= 35.44 length
Depth required from moment criteria=
115.43 mm
β= 13.66
Tc= 0.31
suppose Tv<Tc
155.57*(0.68-d/1000)*1000/(d*1000)=0.31
d= 224.01 mm
adopt d= 400.00 mm
Overall depth(D)= 450.00 mm
42
Bar size= 12 mm
Spacing required= 166.32 mm
Spacing Provided= 150 mm
Ast provided= 753.98 mm2
% of Ast= 0.17 OK
Provide 1.7mx1.7mx0.45m size F1 footing with 12mm bar at 150 mm spacing
c/c on both way
124.55 mm
β= 13.66
Tc= 0.31
suppose Tv<Tc
137.4*(0.775-d/1000)*1000/(d*1000)=0.31
d= 236.31 mm
adopt d= 400.00 mm
Overall depth(D)= 450.00 mm
43
Mu=41.26KN-m
5.Design of Strap
beam
356.38 589.23
264.47 261.06
Distance from
Location F shear force(KN) Moment(KN)
F 0 0.0 0.00
E-left 0.175 -46.3 4.05
E-right 0.175 310.1 4.05
44
G 1.35 0.0 -177.75
D 1.70 -93.2 -161.32
C 2.36 -93.2 -88.56
B-left 3.31 -341.2 117.80
B-right 3.31 248.0 117.80
A 4.26 0.0 0.00
Maximum Negative
moment Shear force 177.75 KN-m
-341.2
-93.2 -93.2
0 -46.30.5 1 1.5 2 2.5 3 3.5 4 4.5
248.0
310.1
-88.56
0.004.05 0.00
117.80
45
drequired= 436.95 mm
dprovided= 450 mm
Overall depth= 500 mm
Tv 1.876 N/mm2
pt= 0.511
β= 4.55
46
Tc= 0.50 N/m2
since Tc<Tv, Shear reinforcement is required
vus= 217.20 KN
Dia of bars= 10 mm
no of legged of
stirupps= 3
Spacing of stirupps= 212.346 mm
Spacing provided= 150 mm
Hence provide 350mm*500mm strap beam with 3 legged 10 mm bars at 150 c/c
spacing.
Gross Area 20 m2
(A)=
Load
Joint Comb Ultimat Workin
Story Grid o e Load g Load
kN kN X1 Y1 P*X1 P*Y1
Base B1 472.92 315.28 0 0 0.000 0.00
Base C1 303.63 202.42 3.135 0 951.880 0.00
Base C2 396.84 264.56 3.135 3.92 1244.093 1555.61
Base B2 726.74 484.49 0 3.92 0.000 2848.82
self
weight
4404.433
Total Load 1900.13 1267 2195.9735 6
47
Center of gravity of Xg Yg
load= 1.16 2.32
2 Calculations :
1. Center of geometry[C.G.] from grid B
(Xg) = 1.31 m
(Yg) = 2.27 m
2. Center of loads[C.L.]
(XL) = 1.16 m
(YL) = 2.32 m
3. Eccentricity
Along x-direction,ex = -0.154 m
Along y-direction,ey = 0.048 m
4. Moment of inertia
Along x-direction,Ix= 39.216 m4
Along y-direction,Iy= 26.133 m4
48
0 C2 1.83 1.65 53.537 OK
0 B2 -1.31 1.65 76.985 OK
B-C
l= 3.32
1-1 97.86
2-2 107.90
Shear Check:
Shear strength of concrete t'c for M20 grade 1.11803
=0.25sqrt(fck) = N/mm2
49
column load = 202.42 KN
Vu = 303630 N
Coeff of
a= 1 d
value of
b= 600 2c
c= -271574.928
d= 301.31 mm
50
Ast
Dia of bar Spacing Remark
Grid Max BM Ast required Provide
Provided Provided s
d
B-B 187.371 1,161.73 16 150 1340.41 OK
C-C 127.957 773.11 16 150 1340.41 OK
1-1 97.858 584.00 16 150 1340.41 OK
2-2 107.899 646.55 16 150 1340.41 OK
3 Load on landing
51
self weight of slab = 3.13 KN/m2
floor finish 1.20 KN/m2
live load 3.00 KN/m2
load per m sq. 7.33 KN/m2
factored load 10.99 KN/m2
load/m 10.99 KN/m
4 Crtitical Flight
4.1 Rebar calculation
span of landing A 0.38 m
span of landing B 1 m
span of flight 1.8 m
Span of landing A with support 0.495
Span of landing B with support 1.115
effective span of flight with
support 1.8
effective span 3.41
reaction at B support 16.48 kN
reaction at A support 19.64 kN
point of maximum moment(x) 1.432 m
Max.bending moment 15.03 KNm
Ast required 364.28 mm2
spacing required 310.47005 mm
spacing provided 150 mm
Ast Provided 753.98224 mm2
Providing 12mm dia. @ 150mm c/c as main rebar
52
V= 19.64 KN
L0 0.144 m
Ldmax= 909.289 mm
Ld provided 679.6875 mm
OK
53
Now,p/fck= 0.066 d'/b 0.11
Mu/fck*b*D2= 0.15
pu/fck*b*d 0.19
No of Rebar % of
No of bar Bar dia bar Bar dai area reabr
4 16 4 12 1256 1.03
Asc 1.03
Materials
Grade of concrete(fck)= 20 N/mm2
grade of
steel(fy)= 500 N/mm2
Beam A-1/2
area(mm
location no dia no dia ) %
Top 2 16 3 12 741.4159 1.04
Bottom 3 16 603.1858 0.85
Effective span 3995 mm
54
d'/d 0.133
From table of Sp16
Mu/Bd2 3.7
Hogging
moment= 81.25 KN-m
Materials
Grade of concrete(fck)= 20 N/mm2
grade of
steel(fy)= 500 N/mm2
Beam A-1/2
area(mm
location no dia no dia ) %
Top 2 16 3 12 741.4159 1.04
Bottom 3 16 603.1858 0.85
Effective span 3920 mm
55
d'/d 0.133
From table of
Sp16
Mu/Bd2 3.7
Hogging
moment= 105.98 KN-m
56