Rosemount 848T High Density Temperature Measurement Family: Product Data Sheet
Rosemount 848T High Density Temperature Measurement Family: Product Data Sheet
February 2013
00813-0100-4697, Rev LB
Innovative temperature measurement for high density applications that provide installation and
operational savings
Independently configurable inputs that support RTD, thermocouple, ohm, mV, 0-10 volt, and 4–20 mA
signals
Enclosure options and intrinsically safe design allows for installation close to any process, including
hazardous areas
WirelessHART™ capabilities extends the full benefits of PlantWeb® to previously inaccessible locations
Industry first Measurement Validation diagnostic can identify a variety of process concerns including
sensor degradation, sensor wiring connectivity, high vibration (affecting the measurement), and
abnormal process variations.
Rosemount 848T Family February 2013
2 www.rosemount.com
Rosemount 848T Family February 2013
FOUNDATION
fieldbus
IEC-approved WirelessHART® protocol
Emerson SmartPower™ Solutions provide an intrinsically safe
Power Module, allowing field replacements without removing the
transmitter from the process, keeping personnel safe and reducing
maintenance costs
Emerson Process Management’s layered approach to wireless
network security ensures that data transmissions are secure
3
February 2013 Rosemount 848T Family
Contents
High density temperature measurement. . . . . .page 2 The Rosemount 848T Wireless Temperature
The Rosemount 848T FOUNDATION fieldbus Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
FOUNDATION
fieldbus
4
Rosemount 848T Family February 2013
FOUNDATION
fieldbus
848T accepts eight independently configurable sensor inputs, and can be mounted
close to the process to improve data quality. FOUNDATION fieldbus architecture allows up
to 128 temperature measurements to be transmitted on a single H1 fieldbus line.
Additionally, the 848T is bus-powered, further reducing the amount of required wiring
to install the device. The robust design has proven itself in thousands of successful
installations. Capabilities include:
Eight independently configurable inputs, including 2- and 3-wire RTDs,
thermocouples, mV, 2- and 3-wire ohms, and 4-20 mA signals
Industry first Measurement Validation diagnostic
Fieldbus functionality with 8 AI blocks, 2 MAI blocks, 4 ISEL Blocks, and backup LAS
Capabilities
600 Vdc isolation and integral transient protection
Table 1. Rosemount 848T FOUNDATION fieldbus Ordering Table
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Expanded
FOUNDATION
Yes(4)
fieldbus
6
Rosemount 848T Family February 2013
FOUNDATION
fieldbus
Expanded
LT Test to -60 °F (-51.1 °C)
Conduit Electrical Connector
Standard Standard
(7) ® ★
GE M12, 4-pin, Male Connector (eurofast )
GM(7) A size Mini, 4-pin, Male Connector (minifast®) ★
Typical Model Number: 848T F I5 S001 T1 B6 JA2
(3) The Rosemount 848T ordered with component approval is not approved as a stand-alone unit. Additional system certification is required.
(4) Enclosure Option JX3 must be ordered with Product Certification Code E6. (O-ring for the JX3 enclosure rated to -20 °C).
(5) S002 is only available with Product Certification N5, N6, N1, NC, NK, and NA.
(7) Available with no approval or Intrinsically Safe approvals only. For FM Intrinsically Safe (option code I5), install in accordance with Rosemount drawing
00848-4402.
7
February 2013 Rosemount 848T Family
Specifications
Functional Alarms
FOUNDATION
Inputs the alarms to HI-HI, HI, LO, or LO-LO with a variety of priority
Eight independently configurable channels including levels and hysteresis settings.
combinations of 2- and 3-wire RTDs, thermocouples, mV, and
Electromagnetic compatibility compliance testing
2- and 3-wire ohm inputs. 4–20 mA inputs using optional
connector(s). Meets the criteria under European Union Directive
2004/108/EC
Outputs
Meets the criteria under IEC 61326: 2006
Manchester-encoded digital signal that conforms to IEC
61158 and ISA 50.02. Stability
Status ±0.1% of reading or 0.1 °C (0.18 °F), whichever is greater,
If self-diagnostics detect a sensor burnout or a transmitter for 2 years for RTDs.
failure, the status of the measurement will be updated ±0.1% of reading or 0.1 °C (0.18 °F), whichever is greater,
accordingly.
for 1 year for thermocouples.
Ambient temperature limits
Self calibration
–40 to 185 °F (–40 to 85 °C)
The transmitter’s analog-to-digital circuitry automatically
Accuracy (Pt 100 @ reference condition: 20 °C) self-calibrates for each temperature update by comparing the
±0.30 °C (±0.54 °F) For the complete list see “Accuracy” on dynamic measurement to extremely stable and accurate
page 10. internal reference elements.
(1) Reference conditions are -40 to 60 °C (-40 to 140 °F) with 30 meters
(100 feet) of sensor lead length 18 AWG wire.
8
Rosemount 848T Family February 2013
FOUNDATION
Since the temperature value always contains the
fieldbus
using the optional junction box, the transmitter can be
mounted onto a panel or a 2-in. pipe stand (with option measurement status, this block allows the selection to be
code B6). restricted to the first “good” measurement.
Entries for optional junction box Multiple Analog Input Block (MAI)
No Entry The MAI block allows the eight AI blocks to be multiplexed
Used for custom fittings together so they serve as one function block on the H1
Cable Gland segment, resulting in greater network efficiency.
9 x M20 nickel-plated brass glands for 7.5–11.9 mm
unarmored cable
Conduit
5 plugged 0.86-in. diameter holes suitable for installing
1/2-in. NPT fittings
(1) Add 35.2 oz (2.2 lb, 0.998 kg) for nickel-plated brass glands.
Environmental ratings
Type 4X and IP66 with optional junction box. JX3
Explosion-proof enclosure rated to -4 °F (-20 °C).
Function blocks
Analog Input (AI)
Processes the measurement and makes it available on the
fieldbus segment.
Allows filtering, alarming, and engineering unit changes.
9
February 2013 Rosemount 848T Family
Accuracy
Table 2. Input Options/Accuracy
Accuracy Over
Input Ranges
Sensor Option Range(s)
FOUNDATION
fieldbus
Sensor Reference °C °F °C °F
2- and 3-Wire RTDs
Pt 50 ( = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.57 ± 1.03
Pt 100 ( = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.28 ± 0.50
Pt 100 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.30 ± 0.54
Pt 100 ( = 0.003916) JIS 1604, 1981 –200 to 645 –328 to 1193 ± 0.30 ± 0.54
Pt 200 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.54 ± 0.98
Pt 200 ( = 0.003916) JIS 1604; = 0.003916, 1981 –200 to 645 –328 to 1193 ± 0.54 ± 0.98
Pt 500 IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.38 ± 0.68
Pt 1000 IEC 751; = 0.00385, 1995 –200 to 300 –328 to 572 ± 0.40 ± 0.72
Ni 120 Edison Curve No. 7 –70 to 300 –94 to 572 ± 0.30 ± 0.54
Edison Copper Winding No.
Cu 10 –50 to 250 –58 to 482 ± 3.20 ± 5.76
15
Cu 100 (a=428) GOST 6651-94 -185 to 200 -301 to 392 ± 0.48 ±0.86
Cu 50 (a=428) GOST 6651-94 -185 to 200 -301 to 392 ± 0.96 ±1.73
Cu 100 (a=426) GOST 6651-94 -50 to 200 -58 to 392 ± 0.48 ±0.86
Cu 50 (a=426) GOST 6651-94 -50 to 200 -58 to 392 ± 0.96 ±1.73
Thermocouples—Cold Junction Adds + 0.5 °C to Listed Accuracy
NIST Type B (Accuracy varies 100 to 300 212 to 572 ± 6.00 ± 10.80
NIST Monograph 175
according to input range) 301 to 1820 573 to 3308 ± 1.54 ± 2.78
NIST Type E NIST Monograph 175 –200 to 1000 –328 to 1832 ± 0.40 ± 0.72
NIST Type J NIST Monograph 175 –180 to 760 –292 to 1400 ± 0.70 ± 1.26
NIST Type K NIST Monograph 175 –180 to 1372 –292 to 2501 ± 1.00 ± 1.80
NIST Type N NIST Monograph 175 –200 to 1300 –328 to 2372 ± 1.00 ± 1.80
NIST Type R NIST Monograph 175 0 to 1768 32 to 3214 ± 1.50 ± 2.70
NIST Type S NIST Monograph 175 0 to 1768 32 to 3214 ± 1.40 ± 2.52
NIST Type T NIST Monograph 175 –200 to 400 –328 to 752 ± 0.70 ± 1.26
DIN L DIN 43710 –200 to 900 –328 to 1652 ± 0.70 ± 1.26
DIN U DIN 43710 –200 to 600 –328 to 1112 ± 0.70 ± 1.26
w5Re26/W26Re ASTME 988-96 0 to 2000 32 to 3632 ± 1.60 ± 2.88
Type L GOST R 8.585-2001 -200 to 800 -328 to 1472 ± 0.71 ±1.28
Terminal Temperature -50 to 85 -58 to 185 ±0.50 ±0.90
Millivolt Input—Not approved for use with CSA Option Code I6 –10 to 100 mV ± 0.05 mV
2- and 3-Wire Ohm Input 0 to 2000 ohms ± 0.90 ohm
4–20 mA (Rosemount)(1) 4–20 mA ± 0.01 mA
4–20 mA (NAMUR)(1) 4–20 mA ± 0.01 mA
FOUNDATION
NIST Type Temperature Range (°C)
fieldbus
Temperature(1)
RTD
Pt 50 ( = 0.00391) 0.004 °C (0.0072 °F) NA
Pt 100 ( = 0.00391) 0.002 °C (0.0036 °F) NA
Pt 100 ( = 0.00385) 0.003 °C (0.0054 °F) NA
Pt 100 ( = 0.003916) 0.003 °C (0.0054 °F) NA
Pt 200 ( = 0.003916) 0.004 °C (0.0072 °F) NA
Pt 200 ( = 0.00385) 0.004 °C (0.0072 °F) NA
Pt 500 0.003 °C (0.0054 °F) NA
Pt 1000 0.003 °C (0.0054 °F) NA
Cu 10 0.03 °C (0.054 °F) NA
Cu 100 (a=428) 0.002 °C (0.0036 °F) NA
Cu 50 (a=428) 0.004 °C (.0072 °F) NA
Cu 100 (a=426) 0.002 °C (0.0036 °F) NA
Cu 50 (a=426) 0.004 °C (.0072 °F) NA
Ni 120 0.003 °C (0.0054 °F) NA
Thermocouple (R = the value of the reading)
0.014 °C R 1000
Type B 0.032 °C - (0.0025% of (R - 300)) 300 R < 1000
0.054 °C - (0.011% of (R - 100)) 100 R < 300
Type E 0.005 °C + (0.00043% of R) All
0.0054 °C + (0.00029% of R) R0
Type J, DIN Type L
0.0054 °C + (0.0025% of |R|) R 0
0.0061 °C + (0.00054% of R) R0
Type K
0.0061 °C + (0.0025% of |R|) R 0
Type N 0.0068 °C + (0.00036% of R) All
Type R, Type S 0.016 °C R 200
0.023 °C - (0.0036% of R) R 200
0.0064 °C R0
Type T, DIN Type U
0.0064 °C - (0.0043% of |R|) R 0
0.007 °C R 0
GOST Type L
0.007 °C + (0.003% of IRI) R0
Millivolt 0.0005 mV NA
2- and 3-wire Ohm 0.0084 ohms NA
4–20 mA (Rosemount) 0.0001 mA NA
4-20 mA (NAMUR) 0.0001 mA NA
(1) Change in ambient is in reference to the calibration temperature of the transmitter (20 °C (68 °F) typical from the factory).
11
February 2013 Rosemount 848T Family
Product certifications
Hazardous locations certifications
FOUNDATION
fieldbus
Temperature Code:
Table 6. Entity Parameters for Non Incendive Field
(1) T4A (Tamb = –40 to 85 °C)
Power/Bus Sensor T5 (Tamb = –40 to 70 °C)
Vmax = 42.4 V VOC = 12.5 V
Ci = 2.1nF ISC = 4.8 mA NK Non-Incendive for use in Class I, Division 2, Groups A, B,
Li = 0 Po = 15 mW C, D (suitable for use with Non-Incendive field wiring)
CA = 1.2 F when installed in accordance with Rosemount Drawing
00848-4404.
LA = 1 H
Temperature Code:
(1) Entity parameters apply to entire device, not individual sensor channel. T4A (Tamb = -40 to 85 °C)
T5 (Tamb = -40 to 70 °C)
Rosemount Enclosure Required.
Wiring Indoor Hazardous (Classified) Locations.
12
Rosemount 848T Family February 2013
FOUNDATION
ISC = 4.8 mA
fieldbus
Ci = 2.1 nF Po = 15 mW
Li = 0 H Po = 15 mW
Li = 0 CA = 1.2 F
CA = 1.2 F
LA = 1 H
LA = 1 H
I6 Intrinsically Safe, Division 2 (1) Entity parameters apply to entire device, not individual sensor
channels.
For use in Class I, Division 1, Groups A, B, C, D; when
installed per Rosemount drawing 00848-4405.
N6 Class I, Division 2
Temperature Code: Suitable for use in Class I, Division 2, Groups A, B, C, D.
T3C (Tamb = –50 to 60 °C) when installed per Rosemount drawing 00848-4405.
Temperature Code:
Suitable for Class I, Division 2, Groups A, B, C, D. Rated
T3C = (–50 Ta 60 °C)
42.4 VDC max. Not valid with S002 option.
Must be installed in a suitable enclosure as determined
acceptable by the local inspection authority.
13
February 2013 Rosemount 848T Family
European certifications 2.) The apparatus will not meet the 500 V rms isolation
test required by Clause 6.4.12 in EN 60079-11:2007.
ATEX approvals This must be taken into account when installing the
apparatus.
I1 Intrinsic Safety
FOUNDATION
(1) Entity parameters apply to entire device, not individual sensor channels. Special Conditions for Safe Use (x):
2.) The apparatus will not meet the 500 Vrms isolation NOTE:
test required by Clause 6.4.12 in EN 60079-11:2007. NE is valid with S001 Input Type ONLY
This must be taken into account when installing the
apparatus. N1 ATEX Type n
Certification Number: Baseefa09ATEX0095X
ATEX Marking II 3 G
IA FISCO (Fieldbus Intrinsically Safe Concept) Intrinsic
Ex nL IIC T5 (Tamb = –40 to 65 °C)
Safety
Certificate Number: BASEEFA09ATEX0093X
ATEX Marking II 1 G Table 14. Entity Parameters
Ex ia IIC T4 (Tamb = –50 to 60 °C)
Power/Bus Sensor
1180
Ui = 42.4 Vdc Uo = 12.5 Vdc
Table 12. ATEX Approved Entity Parameters
Ci = 0 Io = 4.8 mA
Power/Bus Sensor Li = 0 Po = 15 mW
Ui = 17.5 V Uo = 12.5 V Co = 1.2 F
Ii = 380 mA Io = 4.8 mA Lo = 1 H
Pi = 5.32 W Po = 15 mW
Ci = 0 Ci = 1.2 F Special Conditions for Safe Use (x):
Li = 0 Li = 1 H
1.) Provisions shall be made, external to the apparatus,
Special Conditions for Safe Use (x): to prevent the rated voltage of the apparatus supply is
not exceeded by transient disturbances of more than
1.) This apparatus must be installed in an enclosure
40%
which affords it a degree of protection of at least IP20.
Non-metallic enclosures must have a surface resistance
of less than 1 Gohm. Light alloy or zirconium enclosures
must be protected from impact and friction when
installed.
14
Rosemount 848T Family February 2013
FOUNDATION
NC ATEX Type n Component
fieldbus
Certification Number: Baseefa09ATEX0094U Table 15. IECEx Approved Entity Parameters
ATEX Marking II 3 G
Power/Bus Sensor
Ex nA nL IIC T4 (Tamb = –50 to 85 °C)
Ex nA nL IIC T5 (Tamb = –50 to 70 °C) Ui = 30 V Uo = 12.5 V
Ii = 300 mA Io = 4.8 mA
Pi = 1.3 W Po = 15 mW
Ci = 2.1 F Ci = 1.2 F
Note:
Li = 0 Li = 1 H
NC IS VALID WITH S001 INPUT TYPE ONLY
Special Conditions of Safe Use (x):
Special Conditions for Safe Use (x): 1.) The apparatus must be installed in an enclosure that
1.) The component must be housed in a suitable provides a degree of protection of at least IP20.
certified enclosure that provides a degree of protection Non-metallic enclosures must be suitable to prevent
of at least IP54 and meets the relevant material and electrostatic hazards and light alloy or zirconium
environmental requirements of EN 60079-0, and enclosures must be protected from impact and friction
EN-60079-15. when installed.
2.) Provisions shall be made, external to the apparatus, 2.) The apparatus is not capable of withstanding the
to prevent the rated voltage (42.4 Vdc) being exceeded 500 V isolation test required by IEC 60079-11: 2006
by transient disturbances of more than 40%. clause 6.3.12. This must be taken into account when
installing the apparatus.
3.) The electrical circuit is connected directly to earth:
this must be taken into account when installing the
apparatus. IG IECEx FISCO
Certificate No.: IECExBAS09.0030X
Ex ia IIC T4 (Tamb = – 50 to 60 °C)
ND ATEX Dust Ignition Proof
Certification Number: BAS01ATEX1315X Table 16. IECEx Approved Entity Parameters
ATEX Marking II 1 D
Power/Bus Sensor
T90C (Tamb = – 40 to 65 °C) IP66
Ui =17.5 V Uo = 12.5 V
Ii = 380 mA Io = 4.8 mA
Special Conditions for Safe Use (x): Pi = 5.32 W Po = 15 mW
Ci = 2.1 F Ci = 1.2 F
1.) The user must ensure that the maximum rated Li = 0 Li = 1 H
voltage and current (42.4 Vdc, 22 mA) are not
exceeded. All connections to other apparatus or Special Conditions of Safe Use (x):
associated apparatus shall have control over this voltage
and current equivalent to a category “ib” circuit 1.) The apparatus must be installed in an enclosure that
according to EN 60079-11:2007. provides a degree of protection of at least IP20.
Non-metallic enclosures must be suitable to prevent
2.) Component approved Ex e cable entries must be electrostatic hazards and light alloy or zirconium
used which maintain the ingress protection of the enclosures must be protected from impact and friction
enclosure to at least IP66. when installed.
3.) Any unused cable entry holes must be filled with 2.) The apparatus is not capable of withstanding the
component approved Ex e blanking plugs. 500 V isolation test required by IEC 60079-11: 2006
clause 6.3.12. This must be taken into account when
4.) The ambient temperature range of use shall be the
installing the apparatus.
most restrictive of the apparatus, cable gland, or
blanking plug. N7 IECEx Type n Approval
Certificate No.” IECExBAS09.0032X
Ex Na nL IIC T5 (Tamb = – 40 to 65 °C)
15
February 2013 Rosemount 848T Family
1.) The component must be housed in a suitable 1.) Only when temperature transmitter is installed in IP
component certified enclosure that provides a degree of 20(GB4208-2008) housing, it could be used in hazardous
protection of at least IP54 and meets the relevant location. The metallic housing should observe the
material and environmental requirements of IEC requirements of GB3836.1-2000 Clause 8. The
60079-0: 2004 & IEC 60079-15: 2005. non-metallic housing should observe the requirements
of GB3836.1-2000 Clause 7.3. This apparatus is not
2.) Provision must be made, external to the component, capable of withstanding the 500V rms insulation test
to ensure the rated voltage of the component supply is required by Clause 6.4.12 of GB3836.4-2000.
not exceeded by transient disturbances of more than
40%. 2.) The ambient temperature range is:
Output T code Ambient temperature
3.) The electrical circuit is connected directly to earth;
this must be taken into account when installing the F T4 -50 °C < Ta < + 60 °C
component.
3.) Parameters:
NJ IECEx Type n COMPONENT Approval
Terminals of power/loop (1-2):
Certification Number: IECExBAS09.0031U
Maximu
EEx nA nL IIC T4 (Tamb = -50 to 85 °C) Maximum Maximum
m Maximum
EEx nA nL IIC T5 (Tamb = -50 to 70 °C) Output Output
Output Output external
Current: Power:
Voltage: parameters
Io (mA) Po (mW)
Uo (V)
NOTE: Co (F) Lo (H)
NJ is valid with S001 and S002 Input Types F 30 300 1.3 2.1 0
F(FISCO) 17.5 380 5.32 2.1 0
16
Rosemount 848T Family February 2013
Terminals of sensor:
Maximum Maximum Maximum Maximum
Terminals Output Output Output external
Output
Voltage: Current: Power: parameters
Uo (V) Io (mA) Po (mW) :
Co Lo
(F) (H)
F 1-8 12.5 4.8 15 1.2 1
WirelessHART
FISCO model, FISCO parameters of this product are as
above.
Japanese certifications
17
February 2013 Rosemount 848T Family
Dimensional drawings
Junction Boxes with no entries (option codes JP1, JA1, and JS1) – external dimensions are the same as those outlined for the other
junction box materials in this section.
Rosemount 848T
6.7
(170)
3.7
(93)
Removable Wiring
Connection
Ground Screw
Side View
Front View
2.44 (62) 7.84 (199.2)
1.57 (40)
1.73 (44) 6.30 (160)
4.41 (112)
2.28 (58)
3.78 (96)
1.10 (28)
18
Rosemount 848T Family February 2013
7.7 (196)
WirelessHART
Ground Screw
4.0 (102)
2.4 (62)
1.8 (47)
1.2 (30)
3.5 (89)
1.7 (42)
Five Plugged 0.86-in. diameter
holes suitable for installing 1/2-in.
NPT fittings
Dimensions are in inches (millimeters)
19
February 2013 Rosemount 848T Family
Ground Screw
WirelessHART
Front View
1.4 (35) Side View
1.1 (27) 2.8 (70) 1.2 (30)
4.0 (102)
2.4 (62)
1.6 (42) 1.8 (4.7)
0.06 (1.5)
Five Plugged 0.86-in. diameter holes suitable for installing 1/2-in. NPT
Dimensions are in inches (millimeters)
Mounting options
Aluminum/Plastic Junction Box Stainless Steel Junction Box
(styles JA and JP) (style JS)
Front View Side View Front View Side View
10.2 4.7
5.1 6.6 (167) fully
(260) (119)
assembled
7.5 (190) fully
assembled
20
Rosemount 848T Family February 2013
WirelessHART
Thermocouples
0-1000 mV and 0-10 V
2-, 3-, and 4-wire ohm
4-20mA
Intrinsically safe, long lasting Power Module, which utilizes Emerson’s
SmartPower™ Technology
Configurable high and low alerts to improve process performance
Easy to use Device Dashboard, used to configure, monitor, and troubleshoot the
848T Wireless
Table 19. Rosemount 848T Wireless Transmitter Ordering Table
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model Product Description
848T High Density Temperature Measurement Family
Transmitter Output
Standard Standard
X Wireless ★
Product Certifications
Standard Standard
I1 ATEX Intrinsic Safety ★
I5 FM Intrinsically Safe ★
I6 CSA Intrinsically Safe ★
I7 IECEx Intrinsic Safety ★
N5 FM Class I, Division 2, and Dust Ignition-proof (enclosure required) ★
N6 CSA Class I, Division 2 ★
NA No Approval ★
Input Type
Standard Standard
S001 RTD, Thermocouple, mV, Ohm Inputs ★
S002(1) RTD, Thermocouple, mV, Ohm and 4–20 mA Inputs ★
S003 RTD, Thermocouple, Ohm, mV, and 2 - dual channel voltage adapters ★
S004(2) RTD, Thermocouple, Ohm, mV, and 1 - dual channel voltage adapters ★
21
February 2013 Rosemount 848T Family
Standard Standard
HA1(5) Aluminum with Cable Glands (5 x 1/2-in. NPT for 7.5 - 11.9 mm) ★
HA2(5) Aluminum with Conduit Entries (5 plugged holes, suitable for installing 1/2-in. NPT fittings) ★
Software Configuration
Standard Standard
C1 Custom Configuration of Date, Descriptor, Message and Wireless Parameters (Required CDS with order) ★
Line Filter
Standard Standard
F5 50 Hz Line Voltage Filter ★
5-Point Calibration
Expanded
C4 5-Point Calibration (Requires Q4 option code to generate a Calibration Certificate)
Calibration Certificate
Standard Standard
Q4 Calibration Certificate (3-Point Calibration) ★
Typical Model Number: 848T X I5 S001 WA3 WK1 B6 HA1
(1) Only available with product certifications NA and N5. Stable resistors included.
22
Rosemount 848T Family February 2013
WirelessHART
Supports both star and mesh topologies
Self-Healing Network
If an obstruction is introduced into the mesh network,
devices will automatically find the best alternate
communication path
This allows the network to instantly change to the new
path without any loss in data
23
February 2013 Rosemount 848T Family
Specifications
Functional specifications Physical specifications
Self calibration
The analog-to-digital measurement circuitry automatically
self-calibrates for each temperature update by comparing the
dynamic measurement to extremely stable and accurate
internal reference elements.
Vibration effect
Tested to high pipeline vibration specifications per IEC
60770-1 1999 with no effect on performance.
(1) Reference conditions are 68 °F (20 °C), and routing data for three
additional network devices.
24
Rosemount 848T Family February 2013
Sensor connections
1 1
2 +
WirelessHART
2
3 3
-
4 4
5 5
25
February 2013 Rosemount 848T Family
Accuracy
Table 20. Input Options/Accuracy
Accuracy Over
Input Ranges
Sensor Option Range(s)
Sensor Reference °C °F °C °F
2-, 3-, and 4-Wire RTDs
Pt 50 ( = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.57 ± 1.03
Pt 100 ( = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.28 ± 0.50
Pt 100 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.30 ± 0.54
Pt 100 ( = 0.003916) JIS 1604, 1981 –200 to 645 –328 to 1193 ± 0.30 ± 0.54
WirelessHART
Pt 200 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.54 ± 0.98
PT 200 ( = 0.003916) JIS 1604, 1981 ( = 0.003916) –200 to 645 –328 to 1193 ± 0.54 ± 0.98
Pt 500 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 850 –328 to 1562 ± 0.38 ± 0.68
Pt 1000 ( = 0.00385) IEC 751; = 0.00385, 1995 –200 to 300 –328 to 572 ± 0.40 ± 0.72
Ni 120 Edison Curve No. 7 –70 to 300 –94 to 572 ± 0.30 ± 0.54
Edison Copper Winding No.
Cu 10 –50 to 250 –58 to 482 ± 3.20 ± 5.76
15
Cu 100 (a=428) GOST 6651-94 -185 to 200 -301 to 392 ± 0.48 ±0.86
Cu 50 (a=428) GOST 6651-94 -185 to 200 -301 to 392 ± 0.96 ±1.73
Cu 100 (a=426) GOST 6651-94 -50 to 200 -58 to 392 ± 0.48 ±0.86
Cu 50 (a=426) GOST 6651-94 -50 to 200 -58 to 392 ± 0.96 ±1.73
Thermocouples—Cold Junction Adds + 0.5 °C to Listed Accuracy
NIST Type B (Accuracy varies 100 to 300 212 to 572 ± 6.00 ± 10.80
NIST Monograph 175
according to input range) 301 to 1820 573 to 3308 ± 1.54 ± 2.78
NIST Type E NIST Monograph 175 –200 to 1000 –328 to 1832 ± 0.40 ± 0.72
NIST Type J NIST Monograph 175 –180 to 760 –292 to 1400 ± 0.70 ± 1.26
NIST Type K NIST Monograph 175 –180 to 1372 –292 to 2502 ± 1.00 ± 1.80
NIST Type N NIST Monograph 175 –200 to 1300 –328 to 2372 ± 1.00 ± 1.80
NIST Type R NIST Monograph 175 0 to 1768 32 to 3214 ± 1.50 ± 2.70
NIST Type S NIST Monograph 175 0 to 1768 32 to 3214 ± 1.40 ± 2.52
NIST Type T NIST Monograph 175 –200 to 400 –328 to 752 ± 0.70 ± 1.26
DIN L DIN 43710 –200 to 900 –328 to 1652 ± 0.70 ± 1.26
DIN U DIN 43710 –200 to 600 –328 to 1112 ± 0.70 ± 1.26
w5Re/W26Re ASTME 988-96 0 to 2000 32 to 3632 ± 1.60 ± 2.88
Type L GOST R.8.585-2001 –200 to 800 –328 to 1472 ±0.71 ±1.28
Terminal Temperature -50 to 85 -58 to 185 ±3.50 ±6.30
Input Units
Ohm Input 0 to 2000 ohms ±0.90 ohms
Millivolt Input -10 to 100 mV ±0.05 mV
1000 mV input -10 to 1000 mV ±1.0 mV
greater of ±10 mV or
1000 mV input 0 to 10 V
0.2% of span
4–20 mA (Rosemount)(1) 4–20 mA ±0.01 mA
4–20 mA (NAMUR)1 4–20 mA ±0.01 mA
26
February 2013 Rosemount 848T Family
(1) Change in ambient is in reference to the calibration temperature of the transmitter (20 °C (68 °F) typical from the factory).
Product certifications
Approved Manufacturing Locations Hazardous Locations certificates
Rosemount Inc. – Chanhassen, Minnesota, USA
North American Certifications
Emerson Process Management GmbH & Co. - Karlstein,
Factory Mutual (FM) Approvals
Germany
Emerson Process Management Asia Pacific Private Limited - I5 FM Intrinsic Safety and Non-incendive
Singapore Intrinsically Safe for Class I, Division 1, Groups A, B, and C.
Zone Marking: Class I, Zone 0, AEx ia llC
European Union Directive Information
Temperature Codes T4 (Tamb = -50 to 70 °C)
The EC declaration of conformity for all applicable European Non-incendive for Class I, Division 2, Groups A, B, C, and D.
directives for this product can be found at Intrinsically Safe and non-incendive when installed in
www.rosemount.com. A hard copy may be obtained by accordance with Rosemount drawing 00849-1000.
contacting an Emerson Process Management representative. For use with Rosemount power module P/N
ATEX Directive (94/9/EC) 753-9220-0001 only.
Enclosure Type 4X / IP66
Emerson Process Management complies with the
ATEX Directive. N5 FM Class 1, Division 2, and Dust
Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II/III, Division 1, Groups E, F,
Electro Magnetic Compatibility (EMC) (2004/108/EC)
and G.
EN 61326-1:2006
Ambient Temperature Limits -50 to 85 °C
EN 61326-2-3:2006 Non-incendive when installed in accordance with
Radio and Telecommunications Terminal Equipment Rosemount drawing 00849-1000.
Directive (R&TTE) (1999/5/EC) For use with Rosemount power module P/N
753-9220-0001 only.
Emerson Process Management complies with the
Enclosure Type 4X / IP66
R&TTE Directive.
Telecommunication compliance CSA - Canadian Standards Association
All wireless devices require certification to ensure that they I6 CSA Intrinsic Safety
adhere to regulations regarding the use of the RF spectrum. Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
Nearly every country requires this type of product certification. D.
Emerson is working with governmental agencies around the Temp Code T3C
world to supply fully compliant products and remove the risk of Non-incendive for Class I, Division 2, Groups A, B, C, and D.
violating country directives or laws governing wireless device Enclosure Type 4X / IP66
usage. For use with Rosemount power module P/N
753-9220-0001 only.
FCC and IC Intrinsically Safe and non-incendive when installed in
This device complies with Part 15 of the FCC Rules. Operation is accordance with Rosemount drawing 00849-1016.
subject to the following conditions: This device may not cause
harmful interference, this device must accept any interference N6 CSA Class 1, Division 2
received, including interference that may cause undesired Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
operation. Enclosure Type 4X / IP66.
This device must be installed to ensure a minimum antenna For use with Rosemount power module P/N
separation distance of 20 cm from all persons. 753-9220-0001 only.
Non-incendive when installed per Rosemount drawing
Ordinary Location Certification for FM 00849-1016.
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical,
and fire protection requirements by FM, a nationally recognized
testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
28 www.rosemount.com
February 2013 Rosemount 848T Family
I1 ATEX Intrinsic Safety 1.) The surface resistivity of the antenna is greater than
Certificate No.: Baseefa09ATEX0022X II 1G 1GÙ . To avoid electrostatic charge build-up, it must not be
Ex ia IIC T5 (Ta = -60 °C to 40 °C) rubbed or cleaned with solvents or a dry cloth.
Ex ia IIC T4 (Ta = -60 °C to 70 °C) 2.) The power module may be replaced in a hazardous
IP66 area. The power module has surface resistivity greater
For use with Rosemount power module P/N 753-9220-0001 than 1GÙ and must be properly installed in the wireless
only. device enclosure. Care must be taken during
1180 transportation to and from the point of installation to
prevent electrostatic charge build-up.
IECEx certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 09.0004X
www.rosemount.com 29
Rosemount 848T Family February 2013
Dimensional drawings
Rosemount 848T Wireless Dimensional Drawings
5.55
(141,1)
2.20
(55,8)
7.0
(177,8)
3.00
(76,3)
6.38
(162)
10.22
(259,7)
6.81
(173)
3.46
(87,8)
3.978
(101)
30 www.rosemount.com
February 2013 Rosemount 848T Family
www.rosemount.com 31
Rosemount 848T Family Product Data Sheet
00813-0100-4697 Rev LB February 2013