TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respective owners.
Revision History
Introduction ...................................................................................................................127
2PAA114623-600 7
Table of Contents
8 2PAA114623-600
About This User Manual
General
Any security measures described in this User Manual, for example, for user
access, password security, network security, firewalls, virus protection, etc.,
represent possible steps that a user of an 800xA System may want to consider
based on a risk assessment for a particular application and installation. This risk
assessment, as well as the proper implementation, configuration, installation,
operation, administration, and maintenance of all relevant security related
equipment, software, and procedures, are the responsibility of the user of the
800xA System.
The System 800xA is used for monitoring and controlling a process plant.
Information in this user manual is intended for the operators of a process plant. This
user manual describes the System Alarms that are generated when operating System
800xA.
Feature Pack
The Feature Pack content (including text, tables, and figures) included in this
User Manual is distinguished from the existing content using the following
two separators:
2PAA114623-600 9
Warning, Caution, Information, and Tip Icons About This User Manual
Warning icon indicates the presence of a hazard which could result in personal
injury.
Caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could
result in corruption of software or damage to equipment/property.
Information icon alerts the reader to pertinent facts and conditions.
Tip icon indicates advice on, for example, how to design your project or how to
use a certain function
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
fully comply with all Warning and Caution notices.
10 2PAA114623-600
About This User Manual Terminology
Terminology
A complete and comprehensive list of terms is included in System 800xA System
Guide Functional Description (3BSE038018*). The listing includes terms and
definitions that apply to the 800xA System where the usage is different from
commonly accepted industry standard definitions and definitions given in standard
dictionaries such as Webster’s Dictionary of Computer Terms. Terms that uniquely
apply to this User Manual are listed in the following table.
2PAA114623-600 11
Released User Manuals and Release Notes About This User Manual
12 2PAA114623-600
Section 1 System Alarm Messages
The most important system alarms are described in Table 1, Table 2, Table 3,
Table 4, Table 5, Table 6, Table 7,Table 8, Table 9 and Table 10 grouped based on
their functional areas:
• The Component column lists from where the system alarm originates.
(The corresponding function area is listed within parenthesis).
• The Priority of the Alarm lists the priority associated with the alarm.
• The Message Description column lists short descriptions of system alarms.
Text within % signs is replaced with the current data at run-time.
• The Extended description column explains system alarms further.
2PAA114623-600 13
Operations Section 1 System Alarm Messages
Operations
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
14 2PAA114623-600
Section 1 System Alarm Messages Operations
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
2PAA114623-600 15
800xA for AC 800M Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
16 2PAA114623-600
Section 1 System Alarm Messages Device Management Foundation Fieldbus
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
2PAA114623-600 17
Batch Management Section 1 System Alarm Messages
Batch Management
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Batch 2 Starting Batch The Batch Server application on the
Server as Primary indicated node is being started and will
act as the primary Batch Server.
Batch 2 Secondary Batch The indicated secondary Batch Server
Server Failed, has failed. Only the primary Batch
Primary Operation Server is still functioning so there is no
only redundancy.
Batch 2 Secondary Batch The indicated Batch Server application
Server Started is being started and it will function as a
secondary Batch Server.
Batch 2 Restart The identified process (process_name)
process_name is being restarted.
Batch 1 ERROR: task The identified task (task_name) has
task_name, hard failed in such a manner that it cannot
failure be restarted automatically.
18 2PAA114623-600
Section 1 System Alarm Messages 800xA History
800xA History
Short message
Long message
Priority Short description
Component Extended message of the system
Level of the system
alarm
alarm
AfwcPIMsSyncServi 1 Connection to The connection between 800xA History
ce RTDB Lost Sync Service and the History Data
Collector (RTDB) was lost.
AfwcPIMsSyncServi 1 RTDB status Any change in status of History Data
ce change Collector (RTDB) services will be
intimated through a System Alarm. The
message description will change
depending upon which service got
impacted.
2PAA114623-600 19
PC, Network Software and Monitoring (PNSM) Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended message of the system
Level of the system
alarm
alarm
Basic Computer 1 Resource Alarm The total computer free virtual memory
Asset as a percentage of the total available
virtual memory. An actual value less
than or equal to the configured limit will
cause an alarm.
Basic Computer 1 Resource Alarm The total non-paged pool for a
Asset computer in Megabytes. An actual
value greater than or equal to the
configured limit will cause an alarm.
20 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Priority Short description
Component Extended message of the system
Level of the system
alarm
alarm
Light Computer 1 Process Status Provides summaries of the state of
Process Alarm several key indicators within the
process.
Light Computer 1 Process Status Provides the values of several
Process Alarm indicators within the process.
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Dell Power Edge Device Connection Device disconnected
2600
System global System Global Status is not OK
Status
Overall Thermal System Thermal State problem.
System Status
Physical Memory Physical meory arrary problem
Array Status
Storage System Global Status of Storage system is not
Status Ok
2PAA114623-600 21
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Power Supply Power Supply system failure.
system status
Overall Cooling Cooling system problem.
system Status
Dell Power Edge Device Connection Device disconnected
28xx
System global System Global Status is not OK
Status
Overall Thermal System Thermal State problem.
System Status
Physical Memory Physical meory arrary problem
Array Status
Storage System Global Status of Storage system is not
Status Ok
Power Supply Power Supply system failure.
system status
Overall Cooling Cooling system problem.
system Status
Dell Power Edge Device Connection Device disconnected
29xx
System global System Global Status is not OK
Status
Overall Thermal System Thermal State problem.
System Status
Physical Memory Physical meory arrary problem
Array Status
22 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Storage System Global Status of Storage system is not
Status Ok
Power Supply Power Supply system failure.
system status
Overall Cooling Cooling system problem.
system Status
Dell Power Edge Device Connection Device disconnected
M600
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
M620
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
M1000e
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
R320
System global System Global Status is not OK
Status
Overall Thermal System Thermal State problem.
System Status
Physical Memory Physical meory arrary problem
Array Status
Storage System Global Status of Storage system is not
Status Ok
2PAA114623-600 23
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Power Supply Power Supply system failure.
system status
Overall Cooling Cooling system problem.
system Status
Dell Power Edge Device Connection Device disconnected
R710
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
R620
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
R720
System global System Global Status is not OK
Status
Dell Power Edge Device Connection Device disconnected
R730
System global System Global Status is not OK
Status
Cisco UCS C240 M3 Device Connection Device disconnected
Overall Thermal Systems Thermal environment
and Fan Status problem
HP Blade System Device Connection Device disconnected
C7000-3000
Enclosure Blade System Enclosure status is not
Condition Ok
24 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
HP ProLiant Bl460c Device Connection Device disconnected
G5
Memory System Memory System Board detected
board memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant Bl460c Device Connection Device disconnected
G7
Memory System Memory System Board detected
board memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant Bl460c Device Connection Device disconnected
G8
Memory System Memory System Board detected
board memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
2PAA114623-600 25
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
HP ProLiant DL380 Device Connection Device disconnected
G5
Memory System Memory System Board detected
board memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant DL380 Device Connection Device disconnected
G6
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant DL380 Device Connection Device disconnected
G7
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
26 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
System Health System Health Status Detected
Status problem
Raid Status System Raid Detected Problem
HP ProLiant DL380 Device Connection Device disconnected
G9
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
System Health System Health Status Detected
Status problem
Raid Status System Raid Detected Problem
HP ProLiant ML350 Device Connection Device disconnected
G5
Memory System Memory System Board detected
board memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
2PAA114623-600 27
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant ML350 Device Connection Device disconnected
G6
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
HP ProLiant ML350 Device Connection Device disconnected
G9
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller
Power Subsystem Power Subsystem failure
28 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
HP ProLiant ML370 Device Connection Device disconnected
G5
Memory System Memory System Board detected
board 1 memory problem
Memory System Memory System Board detected
board 2 memory problem
Overall Thermal Systems Thermal environment
and Fan Status problem
Drive Array Drive Array controller status is not Ok
controller-1
Drive Array Drive Array controller status is not Ok
controller-2
Power Subsystem Power Subsystem failure
IBM Blade Center Device Connection Device disconnected
HS22
System Health System Health Status Detected
Status problem
IBM Blade Center S Device Connection Device disconnected
System Health System Health Status Detected
Status problem
IBM X3650 Device Connection Device disconnected
System Health System Health Status Detected
Status problem
IBM X3650 M2 Device Connection Device disconnected or network
problem
System Health System Health Status Detected
Status problem
2PAA114623-600 29
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Stratus ft Server Device Connection Device disconnected
System Health System Health Status Detected
Status problem
ABB Power Server System global System Global Status is not OK
Status
Fan 1 Status Fan 1 Failure
Fan 2 Status Fan 2 Failure
Fan 3 Status Fan 3 Failure
Fan 4 Status Fan 4 Failure
Fan 5 Status Fan 5 Failure
Power Supply 1 Power Supply 1 failure
Status
Power Supply 2 Power Supply 2 failure
Status
Physical Merory Physical Memory Array 1 Failure
Array 1 Status
Physical Merory Physical Memory Array 2 Failure
Array 2 Status
Processor 1 Status Processor 1 Encountered problem
Processor 2 Status Processor 2 Encountered problem
30 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB Power Server System global System Global Status is not OK
Status
Fan 1 Status Fan 1 Failure
Fan 2 Status Fan 2 Failure
Fan 3 Status Fan 3 Failure
Fan 4 Status Fan 4 Failure
Fan 5 Status Fan 5 Failure
Fan 6 Status Fan 6 Failure
Fan 7 Status Fan 7 Failure
Fan 8 Status Fan 8 Failure
Power Supply 1 Power Supply 1 failure
Status
Power Supply 2 Power Supply 2 failure
Status
Physical Merory Physical Memory Array Failure
Array Status
Processor Status Processor Encountered problem
Generic Computer Device Connection Device disconnected
Node
Physical Drive Physical drive status is not Ok
Status
ProcessHealth The CPU Load is above warning Limit
2PAA114623-600 31
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Generic Computer ProcessHealth Computer Has Exceeded the VM
Node warning Limit
Computer Has Exceeded the VM Error
Limit
ProcessHealth Computer has Exceeded the VM trend
warning Limit
Computer has Exceeded the VM trend
Error Limit
ProcessHealth Computer has Exceeded the Handle
Count Warning Limit
Computer has Exceeded the Handle
Count Error Limit
ProcessHealth Computer has Exceeded the Thread
Count Warning Limit
Computer has Exceeded the Thread
Count Error Limit
ProcessHealth_EX Free Space of the physical memory is
below warning limit
Free Space of the physical memory is
below Error limit
ProcessHealth_EX Free Space of the Logical Disk is below
warning limit
Free Space of the Logical Disk is below
Error limit
32 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Remote Computer Device Connection Device disconnected
Node
ProcessHealth_SN Free Space of the physical memory is
MP below warning limit
Free Space of the physical memory is
below Error limit
Free Space of the Logical Disk is below
warning limit
Free Space of the Logical Disk is below
Error limit
Generic Network Device Connection Device disconnected
Interface
Device Status Device Encountered a problem
Network utilization Device Connection Device disconnected
Node to Node Device Connection Device disconnected
Utilization
Single Node Device Connection Device disconnected
utilization
Printer Device Connection Device disconnected
Device Status Device Encountered a problem
Remote Computer Device Connection Device disconnected
Process
Process Status Process is not running
2PAA114623-600 33
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Phoenix M-GUARD Device Connection Device disconnected
GT-GT
Signal Contact The Status of alarm contract is "open"
34 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
HP Workstation Device Connection Device disconnected
HP State CPU Fan Speed Reached CautionLimit
2PAA114623-600 35
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann Device Connection Device disconnected
EAGLE30
Signal Contact The Status of alarm contract is "open"
CISCO 12-24-48 Cisco switch port Monitors the connection between the
Port switch status node and device. Triggers an alarm
when device is disconnected from the
network.
36 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Cisco 3750 Power Supply Power Supply system failure.
system 1
Power Supply Power Supply system failure.
system 2
Overal Port Fault Status of one or mote port are not OK
Status
Fan and Fan and Temperature status is not OK
Temperature
Status
Cisco 3750 switch Monitors the connection between the
port status node and device. Triggers an alarm
when device is disconnected from the
network.
2PAA114623-600 37
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Dell Power Connect Device Connection Device disconnected
3524
Dell Port Status Individual Port Status
Source A Power Supply A is disconnected
Source B Power Supply B is disconnected
Dell Power Connect Device Connection Device disconnected
7024
Dell Port Status Individual Port Status
Source A Power Supply A is disconnected
Source B Power Supply B is disconnected
GarrettCom Magnm Device Connection Device disconnected
6k32T
Alarm Status One or more Alarm are present in the
switch
Harting HAVIS 3000 Harting Switch Monitors the connection between the
Port Status node and device. Triggers an alarm
when device is disconnected from the
network.
38 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann MACH Device Connection Device disconnected
104
Signal Contact The Status of alarm contract is "open"
2PAA114623-600 39
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann MAR Device Connection Device disconnected
1040
Signal Contact The Status of alarm contract is "open"
40 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann MSP30 Device Connection Device disconnected
Signal Contact 1 The Status of alarm contract 1 is
"open"
Signal Contact 2 The Status of alarm contract 2 is
"open"
Hirschmann Switch Individual Port Status
Port Status
Hirschmann RS2 Device Connection Device disconnected
power Supply-1 The Status of Power Supply 1 is not
Installed
power Supply-2 The Status of Power Supply 2 is not
Installed
Port-1 Operating The Status of Port 1 is "down"
Status
Port-2 Operating The Status of Port 2 is "down"
Status
Port-3 Operating The Status of Port 3 is "down"
Status
Port-4 Operating The Status of Port 4 is "down"
Status
Port-5 Operating The Status of Port 5 is "down"
Status
Port-6 Operating The Status of Port 6 is "down"
Status
2PAA114623-600 41
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann RS2 Port-7 Operating The Status of Port 7 is "down"
Status
Hirschmann RS20 Device Connection Device disconnected
RS30
Signal Contact The Status of alarm contract is "open"
42 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Hirschmann Device Connection Device disconnected
RSPS20
Signal Contact The Status of alarm contract is "open"
2PAA114623-600 43
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
MOXA EDS 408A Device Connection Device disconnected
Relay Contact The Status of relay contact is "Open"
44 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
MOXA EDS 516A Device Connection Device disconnected
Relay 1 Contact The Status of relay 1 contact is "Open"
2PAA114623-600 45
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
MOXA EDS G509 Device Connection Device disconnected
Relay 1 Contact The Status of relay 1 contact is "Open"
46 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Ruggedcom RS9000 Device Connection Device disconnected
RS 2100
Relay Contact Relay contact is energized
Status
Switch Port Status Individual Port Status
Sixnet SLX8MG Device Connection Device disconnected
Relay Contact Relay contact is off
Status
Switch Port Status Individual Port Status
Weidmuller IE SW Device Connection Device disconnected
16M
Switch Fault Status The Status of Switch is "fault"
Switch Port Status Individual Port Status
Weidmuller IE SW 6 Device Connection Device disconnected
2STM
Switch Fault Status The Status of Switch is "fault"
Switch Port Status Individual Port Status
Weidmuller IE SW Device Connection Device disconnected
PL08M
Relay Contact 1 The Status of relay contact 1 is "open"
2PAA114623-600 47
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Weidmuller IE SW Device Connection Device disconnected
PL09M
Relay Contact 1 The Status of relay contact 1 is "open"
48 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Westermo Lynx Device Connection Device disconnected
L+210
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
Westermo OnTime Device Connection Device disconnected
Lynx
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
Westermo OnTime Device Connection Device disconnected
R200
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
Westermo OnTime Device Connection Device disconnected
T200
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
WestermoRedFox Device Connection Device disconnected
RFI10P
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
2PAA114623-600 49
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
Westermo Viper X12 Device Connection Device disconnected
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
Westermo Wolverine Device Connection Device disconnected
DDW-25
SummaryAlarmSta Device Status is not OK
tus
Switch Port Status Individual Port Status
ABB DiMa 10P-2FG Device Connection Device disconnected
Port-1 Packets Packets Per Sec Alarm Limit Reached
50 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 10P-2FG Port-3 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 51
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 10P-2FG Port-6 Packets Packets Per Sec Warning Limit
Reached
Port-6 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-6 Input Error Input Error Rate Warning Limit
Rate Reached
Port-7 Packets Packets Per Sec Alarm Limit Reached
52 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 10P-2FG Port-9 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-9 Input Error Input Error Rate Warning Limit
Rate Reached
Port-10 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 53
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-1/2 Input Error Input Error Rate Alarm Limit Reached
7RG Rate
Port-1/2 Input Error Input Error Rate Warning Limit
Rate Reached
Port-1/3 Packets Packets Per Sec Alarm Limit Reached
54 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-2/2 Input Error Input Error Rate Warning Limit
7RG Rate Reached
Port-2/3 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 55
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-2/6 Packets Packets Per Sec Alarm Limit Reached
7RG
Port-2/6 Packets Packets Per Sec Warning Limit
Reached
Port-2/6 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-2/6 Input Error Input Error Rate Warning Limit
Rate Reached
Port-2/7 Packets Packets Per Sec Alarm Limit Reached
56 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-3/1 Packets Packets Per Sec Warning Limit
7RG Reached
Port-3/1 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-3/1 Input Error Input Error Rate Warning Limit
Rate Reached
Port-3/2 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 57
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-3/4 Input Error Input Error Rate Alarm Limit Reached
7RG Rate
Port-3/4 Input Error Input Error Rate Warning Limit
Rate Reached
Port-3/5 Packets Packets Per Sec Alarm Limit Reached
58 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB DiMa 19P-4FG- Port-3/7 Input Error Input Error Rate Warning Limit
7RG Rate Reached
Port-3/8 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 59
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-1/2 Input Error Input Error Rate Warning Limit
4FG-7RG Rate Reached
Port-1/3 Packets Packets Per Sec Alarm Limit Reached
60 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-2/3 Packets Packets Per Sec Alarm Limit Reached
4FG-7RG
Port-2/3 Packets Packets Per Sec Warning Limit
Reached
Port-2/3 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-2/3 Input Error Input Error Rate Warning Limit
Rate Reached
Port-2/4 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 61
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-2/6 Packets Packets Per Sec Warning Limit
4FG-7RG Reached
Port-2/6 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-2/6 Input Error Input Error Rate Warning Limit
Rate Reached
Port-2/7 Packets Packets Per Sec Alarm Limit Reached
62 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-3/1 Input Error Input Error Rate Alarm Limit Reached
4FG-7RG Rate
Port-3/1 Input Error Input Error Rate Warning Limit
Rate Reached
Port-3/2 Packets Packets Per Sec Alarm Limit Reached
2PAA114623-600 63
PNSM Device Libraries Section 1 System Alarm Messages
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-3/4 Input Error Input Error Rate Warning Limit
4FG-7RG Rate Reached
Port-3/5 Packets Packets Per Sec Alarm Limit Reached
64 2PAA114623-600
Section 1 System Alarm Messages PNSM Device Libraries
Short message
Long message
Short description
PNSM libraryt Extended message of the system
of the system
alarm
alarm
ABB RaMa 19P- Port-3/8 Packets Packets Per Sec Alarm Limit Reached
4FG-7RG
Port-3/8 Packets Packets Per Sec Warning Limit
Reached
Port-3/8 Input Error Input Error Rate Alarm Limit Reached
Rate
Port-3/8 Input Error Input Error Rate Warning Limit
Rate Reached
2PAA114623-600 65
800xA for Harmony Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
- 2 The RTD has been -
informed of a low
resource condition.
Consult syslog.log
for detailed info
66 2PAA114623-600
Section 1 System Alarm Messages 800xA for MOD 300
2PAA114623-600 67
800xA for AC 100 Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
AC 100 4 System Error RC1 Redund cable 1 failure
Communication - Redund cable 1
Module fail
AC 100 4 System Error RC2 Redund cable 2 failure
Communication - Redund cable 2
Module fail
AC 100 4 System Error VFI - Communication error reported
Communication Communicat.
Module Failure
AC 100 I/O Module 4 System Error PEE I/O device error occurred
- I/O device failure
AC 100 I/O Module 4 System Error PRE I/O process error occurred
- I/O process error
AC100 Processor 4 System Error ACT The application is stopped
Module - PC program
blocked
AC100 Processor 4 System Error SE - Fatal software error
Module Fatal SW error
AC100 Processor 4 System Error Nonfatal hardware error
Module HWE - Minor HW
error
AC100 Processor 4 System Error SWE Software error
Module - SW error
68 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 100
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
AC100 Processor 1 System Error PNA The module is not accessible
Module - PM not
accessible
AC100 Processor 4 System Error GE - General startion error
Module General error
AC100 Processor 4 System Error GW - General station warning
Module General warning
AC100 Processor 4 System Error TJ - Time synchronization failure
Module TimeSynch jitter
AC100 Processor 4 System Error The application in controller and BCD
Module AVC_AC - AVC: file is unequal
BCD unequal AC
AC100 Processor 4 System Error The application in OPC server and
Module AVC_BCD - AVC: BCD file is unequal. Restart the OPC
OPC uneq BCD Server
2PAA114623-600 69
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
AdvDsMasterAdapter 1 Failed to create The 800xA for Advant Master data
RTA Management service failed to connect to the RTA
Handler board Server. This indicates that no
data from the controller(s) will be
available through this Connectivity
Server Node.
AdvDsMasterAdapter 1 Failed to initialize Could not start the 800xA for Advant
Master data service due to severe
problems in the system. This indicates
that no data from the controller(s) will
be available through this Connectivity
Server Node.
AdvMbAeOPCServer 1 No nodes available No contact with the controller(s) on the
on MB300 network MB 300 network. This indicates that no
data from the controller(s) will be
available through this Connectivity
Server Node.
AdvMbTTDSrv 2 Failed to send data The 800xA for AC 400 TTD Server has
to client lost contact with a History Server. This
indicates that no history data from the
controller(s) will be logged from this
Connectivity Server Node.
RTA_ManagementSe 1 RTA Board failed The RTA Management Server has lost
rver (stall) or RTA contact with the RTA board. This
Board failed indicates that no data from the
(connection lost) controller(s) will be available through
this Connectivity Server Node.
70 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
RTA_ManagementSe 1 RTA Board startup This indicates that no data from the
rver failed controller(s) will be available through
this Connectivity Server Node.
RTA_ManagementSe 1 RTA Board startup This indicates that the Node and
rver failed (Network network address has not been
address not set) configured on the RTA Board. No data
from the controller(s) will be available
through this Connectivity Server Node
unless the address is set on the RTA
Board.
RTA_ManagementSe 1 RTA Board Server The RTA Management Server has
rver stopped stopped
RTA_ManagementSe 2 PU410 line 1 The connection to PU410 via Line 1 is
rver connection lost lost
RTA_ManagementSe 2 PU410 line 2 The connection to PU410 via Line 2 is
rver connection lost lost
Controller 3 CLOCKSYNCH - Clock synch channels not found
Channels not
found
Controller 3 CLOCKSYNCH - Failed to select clock master node
Failed to select
clock master
Controller 3 CLOCKSYNCH - There might be more than one backup
More than one node. Set time again!
clock master
Controller 3 CLOCKSYNCH - There might be more than one backup
Set time! node. Set time again!
2PAA114623-600 71
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 CPU STATUS - AC450 processor module redundancy
Auto CPU switch switch over. No redundancy!
Controller 3 CPU STATUS - AC450. The redundant processor
Error in CPU module has stopped. No redundancy!
Controller 3 DEV ST - nn Error in external device such as
printers
Controller 3 FAN for CPU faulty Fan in central rack is faulty
72 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 FIELDBUS - Cable Redundant field bus cable OK
x OK Bus y
Controller 3 FIELDBUS - Cable The I/O station reports that a cable is
x OK Bus y Stn z OK
Controller 3 FIELDBUS - The I/O station has one or more
Device error. Err=x system errors
Controller 3 FIELDBUS - Event Process events from fieldbus may have
queue full been lost due to full queue
Controller 3 FIELDBUS - Fatal Field bus fatal error, either modem or
bus error cable error
Controller 3 FIELDBUS - Field bus controller is missing
Missing controller
Bus x
Controller 3 FIELDBUS - The I/O module on bus x station y and
Module error bx sy position z is faulty
pz
Controller 3 FIELDBUS - The I/O module on bus x station y and
Module OK bx sy position z is OK again
pz
Controller 3 FIELDBUS - The I/O module on bus x station y and
Module warning bx position z has a warning
sy pz
Controller 3 FIELDBUS - New New primary redundant CI522 board
primary CI bx my
Controller 3 FIELDBUS - New Redundant I/O station changeover
primary station bx
sy
2PAA114623-600 73
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 FIELDBUS - No No contact with fieldbus station
access to Stn x
Bus y
Controller 3 FIELDBUS - Power The I/O station has reported a power
supply A/B error bx supply is OK again
sy
Controller 3 FIELDBUS - Power The I/O station has reported a power
supply A/B OK bx supply error
sy
Controller 3 FIELDBUS - The I/O station reports power supply
PowSupp x error error
Bus y Stn z
Controller 3 FIELDBUS - The I/O station reports power supply
PowSupp x OK OK
Bus y Stn z
Controller 3 FIELDBUS - Red. One or both redundant I/O stations
Stn Error bx sy (CI82x) are faulty
Controller 3 FIELDBUS - Red. The redundant I/O station is OK again
Stn OK bx sy
Controller 3 FIELDBUS - Stn x Error in field bus station
error bus y
Controller 3 FIELDBUS - Stn x Field bus station is OK
OK bus y
Controller 3 FPM - PU535 pos Module PU535 is out of order
x y error
Controller 3 FPM - PU535pos x Module PU535 is back in order
y working
74 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 LAN - Ch x cable MAC: Cable fault (distance in meter to
fault dist y m suspected cable fault)
Controller 3 LAN - MAC MAC: Checksum error i received frame
Checksum error ch
x
Controller 3 LAN - MAC MAC: Late collition while transmitting
Collition error ch x frame
Controller 3 LAN - MAC Init MAC controller failed to initialize
error ch x
Controller 3 LAN - MAC Loss of MAC: Loss of carrier in specified
carrier ch x channel
Controller 3 LAN - MAC MAC: Tranciever Hart beat error
Tranceiv error ch x
Controller 3 MFB STATUS - Both redundant field bus cables broken
Both cables broken
Bus x
Controller 3 MFB STATUS - Both redundant field bus cables OK
Both cables OK
Bus x
Controller 3 MFB STATUS - Bus Controller (CI570) error
Bus Controller
error Bus x
Controller 3 MFB STATUS - Bus Controller OK
Bus Controller OK
Bus x
2PAA114623-600 75
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 MFB STATUS - Redundant field bus cable broken
Cable x broken
Bus y
Controller 3 MFB STATUS - Redundant field bus cable OK
Cable x OK Bus y
Controller 3 MISC ST - DSDP Fatal error while accessing pulse
board failed counter board
Controller 3 MISC ST - DSDP Board OK
board working
Controller 3 MISC ST - FPB Error in Free Programmable Module,
board error PU535
Controller 3 MISC ST - FPB PU535 failed
board failed
Controller 3 MISC ST - FPB PU535 OK
board working
Controller 3 MISC ST - MISC No free DB elements "Misc Boards"
BOARDS full could be found
Controller 3 MISC ST - SEQ The PC element SEQ could not find its
database not found DB element
Controller 3 MN COMM - Board A communication board in specified
[not] working pos x position is faulty / not faulty
x
Controller 3 MN STATUS - Bus Master Field Bus communication is OK
x node y channel again
A/B OK
76 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 MN STATUS - Connection to a Master Net node is
Conn. Lost lost
netw/node x y
Controller 3 MN STATUS - A Master Net node is reconnected
Conn. With
netw/node x y
Controller 3 MN STATUS - Redundant Master Field Bus
Error bus x node y communication error
chan. A/B
Controller 3 MN STATUS - No No connection with a Master Net node
com with node x
Controller 3 MVI - Conn. With MVI node x,y is connected again
netw/node x, y
Controller 3 PCB STATUS - CI540 error
Bus extender error
Controller 3 PCB STATUS - CI540 is OK
Bus extender OK
Controller 3 PCFx error User defined errors. See DB element
AC450_1/AC410_1, section S4
Controller 3 PCFx signal OK User defined error is OK
2PAA114623-600 77
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 POW SUPP ST - 24V I/O power supply is OK
24V I/O supply A/B
working
Controller 3 POW SUPP ST - 24V power supply is faulty
24V supply A/B
faulty
Controller 3 POW SUPP ST - 24V power supply is OK
24V supply A/B
working
Controller 3 POW SUPP ST - Error on battery backup
Battery Backup x
faulty
Controller 3 POW SUPP ST - Battery backup OK
Battery Backup x
working
Controller 3 POW SUPP ST - Error in battery charger
Battery Charger x
faulty
Controller 3 POW SUPP ST - Battery charger OK
Battery Charger x
working
Controller 3 POW SUPP ST - Error in I/O voltage regulator
I/O Voltage
regulator missing
Controller 3 POW SUPP ST - Error in I/O voltage regulator
I/O Voltage
regulators faulty
78 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 POW SUPP ST - AC 400 I/O power supply is OK
I/O Voltage
regulators working
Controller 3 POW SUPP ST - Error found when accessing
TC520 error supervision unit TC520 board
Controller 3 POW SUPP ST - Error in voltage regulator
Voltage regulator
missing
Controller 3 POW SUPP ST - Error in voltage regulator
Voltage regulators
faulty
Controller 3 POW SUPP ST - AC 400 power supply is OK
Voltage regulators
present
Controller 3 POW SUPP ST - AC 400 power supply is OK
Voltage regulators
working
Controller 3 POW SUPPLY - Error found in FI/GI board
error FI/GI board
Controller 3 PROC I/O ST - XX Fatal error in process I/O board of type
board error "XX"
Controller 3 PROC I/O ST - XX I/O board is OK after preceding error
board working
Controller 3 PROC I/O ST - xx- "Function lost" reported from AX
function lost Redundant board
Controller 3 PROGRAM CARD The program card specified is OK
- Correct card x y
2PAA114623-600 79
800xA for Advant Master Section 1 System Alarm Messages
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 PROGRAM CARD The program card specified is faulty
- Memory error x y
Controller 3 PROGRAM CARD The program card specified is not
- Missing card x y accessible
Controller 3 PROGRAM CARD Wrong program card is inserted
- Wrong card x y
Controller 3 REF VOLT OK - FI/GI board is OK again
GI/FI board
Controller 3 REF VOLTAGE - Error found in FI/GI board
error GI/FI-board
Controller 3 REM I/O ST - Bus Communication is OK after preceding
x node y working error
Controller 3 REM I/O ST - Error Error in Master field bus module
in bus controller (CI570)
Controller 3 REM I/O ST - Error Error in Master Field Bus
in bus x node y communication to specified node
Controller 3 S100I/O BUS EXT Fatal error in S100 Bus extender
- BE x L/R Board DSBC174
Failure
Controller 3 S100I/O BUS EXT S100 Bus extender DSBC174 fan fail
- BE x L/R Fan
Failed
Controller 3 S100I/O BUS EXT S100 Bus extender DSBC174
- BE x L/R regulator failed
Regulator Failed
80 2PAA114623-600
Section 1 System Alarm Messages 800xA for Advant Master
Short message
Long message
Priority Short description
Component Extended description of the system
Level of the system
alarm
alarm
Controller 3 S100I/O BUS EXT S100 Bus extender DSBC174
- BE x L/R regulator is missing
Regulator Missing
Controller 3 S100I/O BUS EXT S100 Bus extender DSBC174 is OK
- BE x L/R Working
Controller 3 S100I/O BUS EXT The S100 Bus extender is OK again
- BE x y Working
Controller 3 S100I/O BUS EXT DSBC174 internal error, may cause a
- DSBC174 error CPU change-over
Controller 3 S100I/O BUS EXT No contact with S100 Bus extender
- Lost Contact with DSBC174
BE x R/L
Controller 3 S100I/O BUS EXT DSBC174 is manually stopped
- Manually
Stopped BE x L/R
Controller 3 TIME SYNCH - Time is not synchronized
Clock drift out of
range
Controller 3 TIME SYNCH - No There is no time synchronization
synch pulse master on the bus
available
Controller 3 User defined error User defined errors. See DB element
x AC450_1/AC410_1, section S4
2PAA114623-600 81
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
82 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 83
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody controller 3 Mon. of write- In a module there are certain data that
protected memory should not be modified during normal
failure program execution. These data are
saved in a memory area that is
prohibited for writing access. If a
program tries to write this prohibited
memory area then a special interrupt
will detect that. The CPU itself
cyclically checks the monitoring
function.
In this case the CPU detected that the
monitoring function failed. The module
is still OK but an important monitoring
function failed.
Melody controller 3 Max. number of The maximum number of Flash
flash-update programming cycles has been
achieved reached.
Melody controller 3 Exchange NV- The maximum number of NVRAM-
RAM of the module write-cycles has been reached. (In that
case a write cycle is a voltage
breakdown because only in that case
the non-volatile area will be written).
Melody controller 3 Interface failure The connection to the Engineering
SSx (frontpanel) system via front panel is disturbed.
Melody controller 3 Transmission The connection to the Engineering
failure SSx system via front panel interface is
(frontpanel) disturbed.
84 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 85
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
86 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 87
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
88 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 89
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
90 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 91
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
92 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody controller 1 Flash memory - The data in the Flash memory aren t
CRC error correct anymore. The access to the
Flash memory is blocked so that the
module might not boot again after
reset.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Task processing During the loading of a task an error
failure occurred.
Melody controller 1 Unknown OP- During the loading of a task an error
Code occurred.
Melody controller 1 Sys.-modul-prog Faulty or not-existing function module
processing failure has been detected. E.g. the
engineering system has loaded a
function block module into the unit that
is not supported by the software
version.
2PAA114623-600 93
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
94 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 95
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
96 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 97
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
98 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody controller 1 CPU-load > 90% The CPU load of the module has been
higher than 90% for a longer period.
Melody controller 1 Runtime error The system task that is named in the
system task message could not be executed in
time. Thus there was a runtime error of
this task. The cause may be a too high
CPU load or a disturbance in the
module tasking.
Melody controller 1 Runtime error The application task that is named in
system task the message could not be executed in
time. Thus there was a runtime error of
this task. The cause may be a too high
CPU load or a disturbance in the
module tasking.
Melody controller 1 Time The module has not received any time
synchronisation synchronization telegram for a longer
failed period.
Melody controller 2 system time delta The module has not yet received the
not balanced current time data (time zone, status
bits, ...). It is very likely that the time
synchronization is missing (see
message ID: 2101).
Melody controller 1 Multiple time The module has detected that there is
synchronisation more than one source for the time
synchronization.
Melody controller 3 Time of the master The master clock has been manually
clock was set changed.
2PAA114623-600 99
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
100 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 101
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
102 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Fnet 1 I/O module failed I/O module can t be accessed via Fnet.
Possible reason:
- Power supply failed CUW
- detected both Fnet-lines disturbed
Melody Fnet 2 Transmission I/O The Fnet-Master has three times
module/Controller unsuccessfully tried to request the I/O
(A) disturbed module on Fnet line A.
Possible reason:
- I/O module transmitter / Fnet line A
defective
- Fnet Master receiver / Fnet line A
defective
- Fnet line A defective
Melody Fnet 2 Transmission I/O The Fnet-Master has three times
module/Controller unsuccessfully tried to request the I/O
(B) disturbed module on Fnet line B.
Possible reason:
- I/O module transmitter / Fnet line B
defective
- Fnet Master receiver / Fnet line B
defective
- Fnet line B defective
Melody Fnet 1 Time The time synchronization is started
synchronisation with the linking of the first I/O module.
missing on Fnet The cause for this alarm is a failure of
the time synchronization, i.e. the Fnet-
Master has not received any time
synch telegrams for more than 10sec.
2PAA114623-600 103
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
104 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 105
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
106 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 107
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 2 Overflow of the In the third-party system a high number
event buffer of event messages occurred.
Melody Local I/O 1 Invalid Input-ZSP An invalid transfer memory address
memory in the has been entered in the event buffer.
event buffer
Melody Local I/O 3 Configuration fault: In the CCF 10 / CCF 10-P configuration
Init data errors occurred.
Melody Local I/O 3 Configuration fault: In the CCF 10 / CCF 10-P configuration
Read function errors occurred.
Melody Local I/O 3 Configuration fault: In the CCF 10 / CCF 10-P configuration
Write function errors occurred.
Melody Local I/O 3 Timeout for answer The requested subscriber on the
MODBUS has not responded in the
defined monitoring time.
Melody Local I/O 3 Answer with The subscriber on the MODBUS has
undefined fault answered with an unknown error code.
Melody Local I/O 1 Device disturbed The third-party system failed.
Melody Local I/O 3 FS- Module not Alarm text has been generated by
available (any third-party system.
more)
Melody Local I/O 3 FS- Max. Alarm text has been generated by
subscriber number third-party system.
(6) exceeded
Melody Local I/O 4 FS- Subscriber Alarm text has been generated by
cancelled/deleted third-party system.
108 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 FS- Incorrect Alarm text has been generated by
coupling mode third-party system.
Melody Local I/O 5 FS- Block no./block Alarm text has been generated by
name not found third-party system.
Melody Local I/O 3 FS- Reception Alarm text has been generated by
list/block disabled third-party system.
Melody Local I/O 2 FS- Reception Alarm text has been generated by
data block too third-party system.
small
Melody Local I/O 2 FS- Action against Alarm text has been generated by
write protection third-party system.
Melody Local I/O 2 FS- Data transfer Alarm text has been generated by
failed third-party system.
Melody Local I/O 1 FS- Bus failed Alarm text has been generated by
third-party system.
Melody Local I/O 2 FS- Bus coupler Alarm text has been generated by
failed/disturbed third-party system.
Melody Local I/O 2 FS- Bus coupler Alarm text has been generated by
(Transm. puffer full third-party system.
Melody Local I/O 2 FS- Bus coupler Alarm text has been generated by
(Reception puffer third-party system.
full)
Melody Local I/O 3 Incorrect The real data telegram length differs
measurement from the configured data telegram
telegram length length.
2PAA114623-600 109
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Monitoring time is The measuring value has not been
elapsed received within the monitoring time TU
(that has been adjusted within the
receive function block).
Melody Local I/O 3 Timeout in case of The establishment of the connection
announcing for a measuring value to the third-party
system is impossible.
Melody Local I/O 2 Doubled time If for the module 3964(R)/N-V.24
synchronization in T_SYN=1 and a time synchronization
FS telegram has simultaneously been
received from the Third-party system.
Melody Local I/O 3 Interface Within 5 seconds CCF 10 / CCF 10-P
overloaded could not reach a transmit release.
(STX/DLE).
Melody Local I/O 2 Interface failed CCF 10 / CCF 10-P hasn t received a
STX ('Start of Text') for at least 10
seconds.
Melody Local I/O 3 Send fifo : Frame An error in the FIFO of CCF 10 / CCF
too short 10-P has been detected.
Melody Local I/O 3 Send fifo : Frame An error in the FIFO of CCF 10 / CCF
too long 10-P has been detected.
Melody Local I/O 3 Send fifo : wrong An error in the FIFO of CCF 10 / CCF
frame checksum 10-P has been detected.
110 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 2 MODBUS There isn’t any stable data connection
disturbance between the MODBUS-subscribers.
- 20 % of the received frames are
defective.
- Bad cable quality,
- missing terminating resistors, etc.
Melody Local I/O 2 MBM Storage fault An hardware error has been detected
on the module.
Melody Local I/O 2 Voltage Uv has One voltage supply Uv 1, Uv2 or Uv3
failed failed
Melody Local I/O 3 Contact bias has A hardware error on the I/O module
failed regarding the generation of the
negative voltage has been detected.
Melody Local I/O 1 Error in The module CTI 20 has an error in the
configuration data configuration data.
Melody Local I/O 3 Line break Line break of field device or signal line.
transmitter/signal (The sum of device resistance and line
line resistance exceed the threshold value
that depends on the measuring value
and that is in the range of 3,5 kOhm up
to 1
Melody Local I/O 3 Short-circuit Short circuit of resistance or signal line
transmitter/signal connected to CTI 20. The sum of
line resistance and signal line resistance
has been fallen below the threshold of
50 Ohm.
2PAA114623-600 111
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Reference junction The channel with the measuring for the
disturbed reference junction temperature has
detected an error (invalid measuring of
the reference temperature) OR
The reference temperature measuring
is working correct but the measured
reference temperature differs more the
configured temperature difference
(TOLT) from the adjusted set value for
the reference temperature (REFT).
Melody Local I/O 2 Redundancy Disturbance of the CAC 10 partner in
balance disturbed redundancy (backup module).
Melody Local I/O 1 Unknown OP- A software error has been detected.
Code
Melody Local I/O 1 Data type error A software error has been detected.
Melody Local I/O 2 Stack error A software error has been detected.
Melody Local I/O 2 Division by 0 A software error has been detected.
Melody Local I/O 2 Arithmetic overflow A software error has been detected.
error
Melody Local I/O 2 Overflow of meas. The Fnet transfer capacity has been
value transmit temporarily exceeded, due to the high
buffer number of signals to be transferred.
(message bursts)
Melody Local I/O 3 Receive fifo: Frame An error in the FIFO of CCF 10 / CCF
too short 10-P has been detected.
112 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Receive fifo : An error in the FIFO of CCF 10 / CCF
Frame too long 10-P has been detected.
Melody Local I/O 3 Receive fifo : An error in the FIFO of CCF 10 / CCF
wrong frame 10-P has been detected.
checksum
Melody Local I/O 2 MBM not running Reaction on other errors (e.g. errors
during loading, wrong interface
parameter, ... ) Hardware error.
Melody Local I/O 3 Positioning loop Despite positioning commands sent,
AUT disturbance the actuator does not change the
position to the desired direction or not
with the required minimum speed.
Melody Local I/O 3 Positioning loop Despite a local operation has been
MAN disturbance done the actuator position does not
change to the desired direction or nor
with the required minimum speed.
Without operation the positioner
changes its position.
Melody Local I/O 3 Positioning loop Despite positioning commands sent,
AUT disturbance the actuator does not change the
position to the desired direction or not
with the required minimum speed.
2PAA114623-600 113
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
114 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Max value The signal coming from the transmitter
exceeded is higher than the configured maximum
value.
- Short circuit of the transmitter
- Transmitter is defective
Melody Local I/O 3 Fallen below min The signal coming from the transmitter
value is lower than the minimum value.
- Line break of the transmitter loop
- Short circuit of the transmitter loop to
ground/mass
- Transmitter is defective
Melody Local I/O 3 External release The fuse module of a 4-wire-transmitter
missing has detected a violation of the
admissible transmitter supply current
(too high / too low) and as a
consequence set the external release
signal to 0.
Melody Local I/O 3 Valence error The monitoring for the binary input of
CLOSED = the position feedback RM0 of the
N.CLOSED aggregate has detected an error:
- Valence monitoring (RM0=RM0/=0 or
1)
- Line break, mass connection or
connection to 24 V of the wiring.
2PAA114623-600 115
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Valence error The monitoring for the binary input of
OPEN = N.OPEN the position feedback RM1 of the
aggregate has detected an error:
- Valence monitoring (RM1=RM1/=0 or
1)
- Line break, mass connection or
connection to 24 V of the wiring.
Melody Local I/O 3 Valence error The valence monitoring has detected
OPEN=CLOSED an error RM0=RM1=0 or 1.
- Line break, mass connection or
connection to 24 V of the wiring.
- End position switch for OPEN/CLOSE
is defective.
- Inputs have not been wired yet.
Melody Local I/O 3 Val. err. of torque The valence monitoring has detected
sw. for an error DR0=DR1=0.
OPEN=CLOSED - Line break or M-connection of both
lines.
- Inputs have not been wired yet.
Melody Local I/O 3 External The binary input EXST has indicated a
disturbance EXST disturbance e.g. coming from
substation automation (switch gear).
Probable causes are:
- Overcurrent of the motors.
- The external fuse has blown.
116 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 117
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody Local I/O 3 Valence error ON = The monitoring for the binary inputs for
N.ON feedback signal RM1 of the aggregate
has detected an error.
- Valence monitoring (RM1=RM1/=0 or
1)
- Line break, mass connection or
connection to 24 V of the wiring.
Melody Local I/O 3 Valence error of Valence monitoring RM0=RM1=0 or 1.
acknowledgements - Line break, mass connection or
ON=OFF connection to 24 V of the wiring.
- The end switch for ON/OFF is
defective
- Inputs have not been wired yet.
Melody Local I/O 3 External The binary input EXST has indicated a
disturbance EXST disturbance e.g. coming from
substation automation (switch gear).
Probable causes are:
- Overcurrent of the motors.
- The external fuse has blown
Melody Local I/O 3 Disturbance of The power supply monitoring has
transmitter supply detected an error.
- Line break or M-connection
(connection to ground) of the power
supply lines
- temporary all inputs for drive related
transmitters on L-potential
118 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 119
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
120 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
Melody OPC Server 1 No Connection to The Melody OPC Server could not
%1 establish a connection to the CCO.
Melody OPC Server 1 No connection The CCO has been configured as
configured for %1 unavailable. No connections are
established.
Melody Profibus 1 Profibus: failure of The slave cannot be accessed via bus.
a subscriber The slave has not responded to a
repeated request of the master.
Melody Profibus 3 Profibus: Message of a slave after configuration,
parameter fault e.g.: identity number or user parameter
wrong. The last parameter telegram
that the slave received was faulty.
Melody Profibus 3 Profibus: Message of a slave after configuration.
configuration fault The last configuration data that the
slave has received differ from those
that the slave has identified, e.g.:
module structure is not matching to the
configuration data.
Melody Profibus 3 Profibus: diagnosis Slave diagnostic data are available
data exist which can not be analyzed by the
master because these data eventually
are not conform to the Profibus DP
standard or the master has is
overloaded.
Melody Profibus 1 Profibus: bus A bus address exists at least twice.
address available Two slaves in a Token Ring have the
twice same address.
2PAA114623-600 121
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
122 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 123
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
124 2PAA114623-600
Section 1 System Alarm Messages 800xA for AC 870P/Melody
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
2PAA114623-600 125
800xA for AC 870P/Melody Section 1 System Alarm Messages
Short message
Short description Long message
Priority
Component of the system Extended message of the system
Level
alarm alarm
126 2PAA114623-600
Revision History
Introduction
This section provides information on the revision history of this User Manual.
The following table lists the revision history of this User Manual.
Revision
Description Date
Index
- First version published for 800xA 6.0.1 October 2015
2PAA114623-600 127
Introduction
128 2PAA114623-600
Contact us
2PAA114623-600
www.abb.com/controlsystems All rights reserved.