DISYUNTOR

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 78

We build a better future!

HVF Type

HVG Type
Ensuring excellent switching capability and
high quality with various advantages
■ Retaining the high dielectric strength with the interrupter of the high vacuum
degree of 10-7mbar.
■ Providing reliable mechanical performance and long-life expectancy with
rigid structure of motor-spring energy stored mechanism.
■ Having excellent breaking capability with the special contact material
designed by the advanced vacuum technology.
■ Having rapid breaking time of 3 cycle.
■ Certified by New IEC publication 62271-100 and other related standards by
HYUNDAI in ISO9001/14001 and OHSAS18001 certified facilities.

HVF
Rigid structure to prove high reliability and long-life expectancy
– Wide 600 / 800mm switchgear available with small size & light weight
– Mechanical endurance of 30,000 operations
– (IEC) 7.2-17.5kV 25-50kA 630-4,000A
24/25.8kV 12.5-31.5kA 630-3,150A
36/40.5kV 25-31.5kA 1,250-3,150A
(ANSI) 4.76kV 50kA 1,200-4,000A
15kV 40kA 1,200-2,000A
38kV 31.5-40kA 1,200-3,000A

HVG
Compact structure to minimize the switchgear dimension
– Wide 600mm switchgear available with small size & light weight
– Mechanical endurance of 20,000 operations
– 7.2kV, 8-25kA, 400-1,250A

C O N T E N T S

Features 4 Power Consumption & Rated Current 15


Ratings 6 Standard Accessories 16
Type of Mounting 11 Additional Options 17
Technical Data 12 Control Circuits 19
Arc Quenching System 13 Dimensions 22
Service Life 14 Order Information 52
VCB
4◀

Features

HVF type
HVF
◆ With rigid structure and minimized moving parts, HVF breaker operation mechanism features
reduced maintenance requirements providing high reliability and long-life expectancy.
◆ The breakers are more compactly designed in size with high performance vacuum interrupters, which
are made with the special contact material and advanced vacuum technology.
◆ This series are certified by New IEC publication 62271-100, ANSI C37.09 and other domestic standards.

Operating mechanism
<Fig.1> Front view of HVF type
HVF circuit breakers have motor-spring energy stored
mechanisms of a rigid structure. It consists of the
charging mechanism, the closing spring, the trip spring,
the motor, solenoids, auxiliary switches, spring charged Control jack
Shutter
and on/off indicators as shown in Fig.1.
Pole part
Manual
Depending on the intended protection functions, the Charging hole
operating mechanism can be supplemented by 2nd shunt Charged/ FS cradle
Discharged
release, under voltage release, lockout relay, cut-out indicator Close button
switch, limit switch, electrical local closing and so on. Close/Open Housing box
indicator
Open button
Cycle counter
The released closing spring is automatically recharged Name plate

by the charging motor, and capable of the operating Draw-in/


out hole
sequences “open-close-open” which is required when
unsuccessful auto-reclosing operation is attempted.

<Fig.2>Rear view of HVF type

Pole part

The pole parts are placed on the rear side of the Frame cap

operating mechanism. The internal parts of the pole are Upper pole support
well enclosed by the tubular type insulation frame as
shown in Fig.2. Vacuum interrupter
This prevents dust on the internal insulation material (Inside)

which is highly resistant to tracking.


Lower contact

The vacuum interrupters are mounted rigidly in the


insulation frame, so they can withstand forces arising Insulation frame
from switching operation and contact pressure.

In the closed state, the necessary contact pressure is


established by the contact pressure spring and the
atmospheric pressure. The contact pressure spring
automatically compensates the arc erosion which is very
small.
Vacuum Circuit Breaker ◀5

HVG type
HVG
◆ HVG Vacuum circuit-breakers are very compact, so it is possible to reduce the switchgear size
and to minimize its insulation space.
◆ This type of circuit breaker has a compact structure, which can be easily maintained, so it
requires minimal maintenance.

Operating mechanism

HVG vacuum circuit breakers have the simplified motor <Fig.3> Front view of HVG type
spring energy stored mechanism which consists of the
closing spring, the motor, link mechanisms solenoids,
Pole part
auxiliary switches and indicators as shown in Fig.3.

Manual Control jack


The closing spring can be charged manually or charging hole
electrically, and released mechanically with the manual Housing box Close button
closing push button or electrically through the remote
Open button
electrical control.
Charged/
Close/Open Discharged
indicator indicator
The released closing spring is automatically recharged Cycle counter
by the charging motor, and capable of the operating
Draw-in/out Draw-in/out
sequences“open-close-open”which is required when interlock holder mechanism
unsuccessful auto-reclosing operation is attempted.

<Fig.4> Rear view of HVG type

Pole part
Insulation frame
The pole parts are mounted on the rear side of the
Upper terminal
operating mechanism in the insulation frame.
Vacuum interrupter

The vacuum interrupter is mounted rigidly in the Lower terminal


insulation frame, so that it withstands forces arising
Insulation rod
from switching operation and contact pressure.
Contact press spring

Dash pot
The current conducting path consists of the plug-in
contacts, terminals, the vacuum interrupter and the Break shaft
flexible terminal.
VCB
6◀

Ratings

HVF
Model 1) HVF114 HVF115 HVF116 HVF117 HVF214 HVF215 HVF216 HVF217

Standard IEC 62271-100

Rated voltage (kV) 7.2 12

Frequency (Hz) 50 / 60

630 630 630 1,250 630 630 630 1,250

1,250 1,250 1,250 2,000 1,250 1,250 1,250 2,000

2,000 2,000 2,500 2,000 2,000 2,500


Rated current (A)
2,500 3,150 2,500 2,500 3,150

3,150 4,000 3,150 4,000

4,000 4,000

Rated short-circuit breaking current (kA) 25 31.5 40 50 25 31.5 40 50

Rated short-circuit making current (kA) 65 82 104 130 65 82 104 130

Short-time withstand current for 3sec (kA) 25 31.5 40 50 25 31.5 40 50

Power-frequency withstand voltage (kV, 1mim) 20 28 / 42 2)

Impulse withstand voltage (kV, 1.2×50㎲) 60 75

Operating duty O - 0.3sec - CO - 3min - CO / CO - 15sec - CO

Closing time (ms, at DC110V) 55 54 55 54

Opening time (ms, at DC110V) 32 36 32 36

Breaking time (cycles) 3

System Motor spring stored energy


Closing
Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
operation
Current (A) Refer to Table 3 (see page 15)

Closing & Tripping system Shunt trip

tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)

Operating Mechanical operation3) 30,000


life (times) Electrical operation Refer to table 2 (see page 14) 20,000 Refer to table 2 (see page 14) 20,000

Auxiliary contacts 4NO+4NC, 7NO+7NC (Max. 10NO+10NC+1W)

110 110 115 200 110 110 115 200

110 110 115 110 110 115

Weight (kg) 130 130 250 130 130 250


(Main-body) 200 250 200 250

200 250 200 250

250 250

※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) Power-frequency withstand voltage 42kV is available on request.
3) The value is with maintenance, 10,000 times without maintenance.
Vacuum Circuit Breaker ◀7

HVF
Model 1) HVF314 HVF315 HVF316 HVF611 HVF614 HVF714 HVF705

Standard IEC 62271-100

Rated voltage (kV) 17.5 24 / 25.8 36 36

Frequency (Hz) 50 / 60

630 630 630 630 630 1,250 1,250

1,250 1,250 1,250 1,250 1,250 2,000 2,500

Rated current (A) 2,000 2,000 2,000 2,000 2,500 3,150

2,500 2,500 2,500

3,150

Rated short-circuit breaking current (kA) 25 31.5 40 12.5 25 25 31.5

Rated short-circuit making current (kA) 65 82 104 32.5 65 65 82

Short-time withstand current for 3sec (kA) 25 31.5 40 12.5 25 25 31.5


2)
Power-frequency withstand voltage (kV, 1mim) 38 50 / 65 70 70

Impulse withstand voltage (kV, 1.2×50㎲) 95 125 170 170

Operating duty O - 0.3sec - CO - 3min - CO / CO - 15sec - CO

Closing time (ms, at DC110V) 52 68 75 62

Opening time (ms, at DC110V) 32 45 42

Breaking time (cycles) 3 5 5

System Motor spring stored energy


Closing
Supply voltage (V) DC48, 110, 125 / AC110, 125, 220
operation
Current (A) Refer to Table 3 (see page 15)

Closing & Tripping system Shunt trip

tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)

Operating Mechanical operation3) 30,000 20,000


life (times) Electrical operation Refer to Table 2 (see page 14)

Auxiliary contacts 4NO+4NC, 7NO+7NC (Max. 10NO+10NC+1W)

110 110 115 110 110 130 340

110 110 115 110 130 145 400


Weight (kg)
130 130 145 180 400
(Main-body)
200

200
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) Power-frequency withstand voltage 65kV is available on request.
3) The value is with maintenance, 10,000 times without maintenance.
VCB
8◀

Ratings

HVF
Model 1) HVF137 HVF336 HVF705 2)
HVF706 HVF105 HVF204 HVF606

ANSI C37.09 IEC 60056 IEC 60056 IEC 60056


Standard (KR, GL) (KR, GL)
Rated voltage (kV) 4.76 15 38 7.2 12 24

Frequency (Hz) 50 / 60

1,200 1,200 1,200 1,200 630 630 1,250

4,000 2,000 2,000 2,000 1,250 1,250 2,000


Rated current (A)
3,000 3,000 2,000 2,000 2,500

3,150
4)
Rated short-circuit breaking current (kA) 50 40 31.5 40/44 31.5 25 40

Rated short-circuit making current (kA) 130 104 82 104 82 65 104

Short-time withstand current (kA) 50 (2sec) 40 (2sec) 31.5 (3sec) 40 (3sec) 31.5 (3sec) 25 (3sec) 40 (3sec)

Power-frequency withstand voltage (kV, 1mim) 19 36 80 80 20 28 50

Impulse withstand voltage (kV, 1.2×50㎲) 60 95 150 150 60 75 150


O - 15sec - CO O - 0.3sec - CO - 3min - CO
Operating duty - 3min - CO
Closing time (ms, at DC110V) 75 75 75 75 75 75 75

Opening time (ms, at DC110V) 60 60 50 50 60 60 60

Breaking time (cycles) 5

System Motor spring stored energy


Closing
Supply voltage (V) DC48, 110, 125 / AC110, 125, 220
operation
Current (A) Refer to Table 3 (see page 15)

Closing & Tripping system Shunt trip

tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
3)
Operating Mechanical operation 10,000 20,000 20,000 30,000 20,000
life (times) Electrical operation 10,000 20,000 Refer to Table 2 (see page 14)

Auxiliary contacts 4NO+4NC, 7NO+7NC (Max. 10NO+10NC+1W)

200 160 340 340 150 150 340

Weight (kg) 300 160 365 365 160 160 360


(Main-body) 400 400 160 160 400

400
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) HVF705 type can be applicable to IEC 62271-100 standard.
3) The value is with maintenance, 10,000 times without maintenance.
4) Rated short-circuit breaking current 44kA is available on request.
Vacuum Circuit Breaker ◀9

HVF
Model 1) HVF224 HVF225 HVF226 HVF611 HVF614 HVF625 HVF725

Standard GOST-R 52565-06 / IEC 62271-100

Rated voltage (kV) 12 24 24 40.5

Frequency (Hz) 50

630 1,250 1,250 630 630 630 1,250

1,250 2,000 2,000 1,250 1,250 1,250 2,000

Rated current (A) 2,500 2,000 2,000 2,500

3,150 2,500 3,150

3,150

Rated short-circuit breaking current (kA) 25 31.5 40 12.5 25 31.5 31.5

Rated short-circuit making current (kA) 65 82 104 32.5 65 80 81.9

Short-time withstand current for 3sec (kA) 25 31.5 40 12.5 25 31.5 31.5

Power-frequency withstand voltage (kV, 1mim) 42 65 65 95

Impulse withstand voltage (kV, 1.2×50㎲) 75 125 125 190

Operating duty O - 0.3sec - CO - 3min - CO / CO - 15sec - CO O - 0.3sec - CO O - 0.3 sec - CO - 3min


- 3min - CO - CO / CO - 15sec - CO
Closing time (ms, at DC110V) 55 68 45-60 70

Opening time (ms, at DC110V) 32 32 35-45 40

Breaking time (cycles) 3 3 3 5

System Motor spring stored energy


Closing
Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
operation
Current (A) Refer to Table 3 (see page 15)

Closing & Tripping system Shunt trip

tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
2)
Operating Mechanical operation 30,000 20,000
life (times) Electrical operation Refer to Table 2 (see page 14)

Auxiliary contacts 4NO+4NC, 7NO+7NC (Max. 10NO+10NC+1W) 6NO+6NC 4NO+4NC, 7NO+7NC


(Max. 10NO+10NC+1W)
110 110 115 110 110 145 280

110 130 130 110 130 150 300


Weight (kg)
200 145 170 340
(Main-body)
200 175 360

175
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) The value is with maintenance, 10,000 times without maintenance.
Vacuum Circuit Breaker ◀ 11

Type of Mounting

Hyundai vacuum circuit breakers offer various solutions for mounting with fixed and draw-out types.
The draw-out type breakers consist of truck, mechanical interlock, control terminal, and various
accessaries.

XA type Fixed type VCB without cradle

ES type Draw-out type VCB with ES cradle (Without shutter)

FS type Draw-out type VCB with FS cradle (Nonmetallic partition with shutter)

SF type Draw-out type VCB with FS cradle with screw type draw-in/out mechanism

GS type Draw-out type VCB with GS cradle (Metallic partition with shutter and bushing)

GE type Draw-out type VCB with GS cradle with earthing switch


※ Besides the standard version of draw-out circuit breakers, specially designed breakers like those for are available on
request, such as ANSI standards or retrofit.

<Fig.5> XA type (HVF) <Fig.6> ES type (HVF)

<Fig.7> FS type (HVF) <Fig.8> GS type (HVF)


VCB
12 ◀

Technical Data [ Application ]

Applicable standards Switching of overload


transmission lines and cables
HYUNDAI vacuum circuit breakers meet IEC 62271-100,
IEC 60056, and ANSI C37.09 standards. The relatively small capacitive currents of overload
transmission lines and cables under no load condition can be
Rapid load transfer & Operating duty safely interrupted without restrike and overvoltage
development.
With its consistent short closing and operating times,
Hyundai vacuum circuit breakers are especially beneficial in
Switching of capacitors
load transfer from one circuit to another without interruption
of service. HYUNDAI vacuum circuit breakers are the solution for
This high speed operation performs synchronizing of the capacitive applications by switching the circuit without
systems to be paralleled at the instant of contact closure as well. restrike and over voltage. VCB above 7.2kV 20kA can switch
According to the relevant standards and breaker types, tests ON/OFF up to 400A capacitive load. For the higher than 400A
were carried out for the following operating duties. circuit, it shall be informed in advance.

◆ CO - 15sec - CO
Switching unloaded transformer
◆ O - 0.3sec - CO - 3min - CO
◆ O - 15sec - CO - 3min - CO By the special contact materials, the chopping current of the
(O: Open, C: Close) vacuum circuit breakers is only 4A to 5A, so overvoltage is
limited when transformers are disconnected at no load
Current carring capacity condition.

HYUNDAI vacuum circuit breakers may be operated at


Switching of motors
ambient temperatures between -25℃ and +40℃. The rated
normal currents are determined according to IEC standards Long electrical lifetime at rated current lets HYUNDAI
at an ambient temperature of 40℃. vacuum circuit breakers be the excellent solution for high
When the breakers are operated at different termperatures, voltage motors.
the correction on the operating current must be considered. A surge absorber is recommended on these motors, which
Fig.9 shows appropriate operating currents at different have less insulation level or less than 600A starting current.
ambient temperatures. Even though low surge occurrence is the feature of HYUNDAI
However, the diagram applies only to open type switchgear, vacuum circuit breakers, the motor and the circuit itself can
so metal enclosed switchgear load currents should be be further protected by the surge absorber.
reduced accordingly.

Interruption of transient recovery voltage


<Fig.9> Load characteristic curve
HYUNDAI vacuum circuit breakers can break the accident
current properly at down steam of transformers, generators,
and current limit chokes, whose rising rates of transient
recovery voltage are higher than IEC Standard, even up to
10kV/㎲.

1 - 630A
2- 1,250A
3 - 1,600A
4 - 2,000A
5 - 2,500A
6 - 3,150A
Vacuum Circuit Breaker ◀ 13

Arc Quenching System

A metal-vapor arc discharge in the vacuum is initiated by If the metal vapor arc discharge can be maintained within a
the current to be interrupted as the contacts open. The certain level, the current is supposed to be chopped prior to
current flows through this metal-vapor plasma until the current zero.
next zero transition.
This chopping current must be controlled in order to
The arc extinguishes in the vicinity of the current zero, and prevent build-up of unduly high overvoltages when inductive
the conductive metal-vapor condenses within a few circuits are switched. The sintered CrCu contact limits the
microseconds on the metal surfaces. chopping current up to 4A to 5A.
As a result, the dielectric strength in the contact gap is
rapidly rebuilt. The geometry and size of the contact are designed
differently according to breaking current and interrupter
The rapid build-up of the dielectric strength at the contact type.
gap enables the arc to be safely extinguished even if contact
separation takes place shortly before a current zero
transition. The maximum arcing time for the last pole to
clear is therefore only up to 15ms.

<Fig.10> Section view of VI <Fig.11> Arcing time-breaking current curve

1
2

5
6
7

10

11
<Table 1> Arc quenching medium

Breaker type Arc voltage (V)


Vacuum circuit breaker 20-200
SF6 gas circuit breaker 500-1,000

1 End flange 7 Act chamber


Oil circuit breaker 1,500-3,000
2 Ceramic insulator 8 Bellows shield Magnetic blaster circuit breaker 1,500-3,000
3 Fixed stem 9 Bellows
4 Middle flange 10 Bearing cap
5 Contact base 11 Movable stem
6 Contact trip
VCB
14 ◀

Service Life

HVF / HVG type

HYUNDAI vacuum circuit breaker needs minimum maintenance due to the simple operating
mechanism and robust construction.
Vacuum circuit breaker shall be maintained periodically to ensure the perfect performance during
mechanical and/or electrical lifetime.
Please refer to the instruction manual for the detailed information.

<Fig.12> <Fig.13> <Fig.14>

<Table 2> Electrical endurance curve number depending on VCB type


Model HVF HVG
Rated voltage kV 4.76 7.2 12 15 17.5 24/25.8 36/40.5 38 7.2
Rated breaking current kA 50 25 31.5 40 25 31.5 40 40 25 31.5 40 12.5 25 25 31.5 31.5 40 8 12.5 20 25
400A 8
630A 1 2 3 1 2 4 1 2 5 6 8 9 9
1,250A 11 1 2 3 1 2 4 10 1 2 4 5 6 6 2 2 4 9 9
Curve number 2,000A 2 3 2 4 10 2 4 6 6 2 2 4
2,500A 3 4 4 2 2 4
3,150A 3 4 4 2 2 4
4,000A 11 4
Vacuum Circuit Breaker ◀ 15

Power Consumption & Rated Current

Charging motor Solenoids

HYUNDAI VCB adopts short-time duty charging motor, Closing solenoid and tripping solenoid operate latching
and the specification is stipulated on Table 3. mechanism for VCB springs, so the VCB can be
Since the motor operating time is short, the maximum controlled remotely.
value and inrush current are disregarded. The specification is mentioned on Table 3.
The solenoids unlatch the closing spring and opening
spring to close and open the VCB, respectively.
Auxiliary contacts

The following versions are available:


◆ X: Without control jack
◆ A: Double control jack mounted on the breaker body, 4NO+4NC
◆ B: Double control jack mounted on the breaker body, 7NO+7NC
◆ C: Single control jack leaded out from the breaker body with a 0.8m cable, 4NO+4NC
◆ D: Double control jack leaded out from the breaker body with two 0.8m cables, 10NO+10NC

Rating of auxiliary contacts


◆ Operating voltage: Max. 250V AC, DC
◆ Continuous thermal current: 10A
◆ Making current: 30A
◆ Switching capacity: 2A at DC220V, T=20ms

Power consumption & control voltage <Table 3>

Control current (A)


Control
Motor Closing solenoid Tripping solenoid Voltage range
voltage
HVF HVG HVF HVG HVF HVG
DC24V 21 - 4.0 - 12.4 -
DC48V 10.5 4.8 2.7 10.3 6.2 10.3
DC60V 8 3.8 1.7 8.4 5.0 8.4 Motor: 85-110%
DC110V 4.5 2.4 1.3 3.3 2.7 3.3 Close: 85-110%
DC125V 4.5 2.8 1.5 3.5 2.4 3.5 Open: 85-110%
DC220V 2.3 1.2 0.7 2.4 1.4 2.4
AC110V 6.4 3.6 1.3 3.3 2.7 3.3
AC220V 3.2 2.5 0.7 2.4 1.4 2.4
VCB
16 ◀

Standard Accessories

HVF type

<Fig.16>

GS cradle ES / FS cradle

< Draw-out handle >

Charging handle Control jack lead cable (2.5m, 1.5SQ) Control jack connector for C, D type
for A, B type control jack control jack

HVG type

<Fig.17>

Charging handle Draw-out handle

Fixing plate (Fixed type) Control jack lead cable (2.5m, 1.5SQ)
Vacuum Circuit Breaker ◀ 17

Additional Options

HVF type

2nd shunt release Under voltage release

Auto secondary jack Earthing switch

Lockout relay Truck operated cell switches (TOC)

Mechanism operated cell switches (MOC) Earthing switch operation indicator contact

CT operated release Spring charged signal

HAFS-CT1 HAFS-CT2 Using the auxiliary switches operated by the


Order code
closing spring, the spring charged status can be
Rated current 0.5A 1.0A
displayed for visual checking.
Operation current above 0.45A above 0.8A
Coil registance 20Ω 11Ω
VCB
18 ◀

Additional Options

HVF / HVG type

Varistor module Position switch

Vacuum checker

Order code HAFS-VC9


Rated input voltage AC220V
Rated output voltage AC11kV / 22kV
Dimension W200×L350×H176

Condenser trip device

Order code HVFS-T7 HVFS-T9 HVFS-T4 HVFS-T6


Rated input voltage AC110V AC220V DC110V DC220V
Charging voltage DC145V DC290V DC110V DC220V
Ordinary current DC2A
Time delay within 1.5sec
Frequency 50 / 60Hz -
Vacuum Circuit Breaker ◀ 19

Control Circuits

HVF type ◆ IEC 62271-100


HVF
Standard circuit

Optional circuit

F1: Lockout relay Y1: Tripping solenoid S3: Limit switch


HA: Manual tripping Y7: Under voltage release S41, S42: Limit switch (spring charged signal)
HE: Manual closing Y9: Closing solenoid S6, S7: Cutout switch
K1: Anti-pumping relay R1: Resistor V1, V2, V3: Varistor module
M1: Motor S1: Aux. switch X0: Plug / Socket
P: Stored energy mechanism S21, S22: Limit switch

※ Diagram may be revised without notice.


VCB
20 ◀

Control Circuits

HVF type ◆ GOST-R 52565-06 / IEC 62271-100


HVF
HVF 224 , 225 , 226 , 625

Motor Closing and Shunt Closing Spring Aux. Switch /


Anti-pumping Release Charged Signal Position Switch
25 4 31 24 26 8 7 23 3 28 5 46 9 2 27 21 44 22 32 29 6 52 42 57 55

XO
21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14 Y1 S1
A1 62 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1 K1
A2 K1 7
5 53 22 32 42 52
13 21
R S1 S8
A1 S5 21 31 41 51
54 14 22
Y9
22 24 34 44 54
A2
S22 S9
12 14 23 33 43 53
21
S8 S9
11 13

XO

1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43 50 51 39 16 53 54 58 56

※ The state of the breaker: spring released; open; the truck is in the test position

HVF 725

Motor Closing and Shunt Closing Spring Aux. Switch /


Anti-pumping Release Charged Signal Position Switch
25 4 31 24 26 8 7 23 3 28 5 46 9 2 27 21 44

XO

21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14
Y1 S1
62
A1 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1
K1
A2 K1 7
5 53
13 21
R S1
A1 S5
54
Y9 14 22
22 A2
S22
21

XO

1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43

※ The state of the breaker: spring released; open; the truck is in the test position

M1: Motor S9: Aux. switch (working position) S1: Aux. switch
Y1: Tripping solenoid K1: Anti-pumping relay S8: Aux. switch (testing position)
R: Resistor S3, S5, S21, S22: Charging limit switch
X0: Plug connector Y9: Closing solenoid

※ Diagram may be revised without notice.


VCB
22 ◀

Dimensions [ HVF fixed type & draw-out type body only ]

HVF fixed type (XA) HVF


(Unit: mm)

Rated Current 630A / 1,250A / 2,000A 2,500A / 3,150A

Detail A

HVF draw-out type body only (EA, FA, SA, GA)


(Unit: mm)

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 23

HVF (Unit: mm)


Dimensions XA/EA/FA/GA EA/FA/GA EA/FA GA

Model A C D E F G J B L K B L P
HVF1141 150 515 230 210 525 447 622 499 40 587 501 50 633
HVF1142 150 515 230 210 525 447 622 499 50 587 501 50 633
HVF1151 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1152 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1154 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF1161 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1162 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1164 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF1166/7 210 612 245 310 630 450 738 550 90 587 549 90 633
HVF2172 210 667 245 310 734 450 738 - - - 549 50 610
HVF2176 275 831 245 310 788 450 738 - - - 768 109 613
HVF2177 275 831 245 310 788 450 738 - - - 768 109 613
HVF2178 275 831 245 310 788 450 780 - - - 768 109 613
HVF1372 165 535 234 254 645 447 - - - - - - -
HVF2141 150 515 230 210 525 447 622 499 40 587 501 50 633
HVF2141/2 150 515 230 210 525 447 622 499 50 587 501 50 633
HVF2151/2 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF2154 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF2161/2 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF2164 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF2166/7 210 612 245 310 630 450 738 550 90 587 549 90 633
HVF3141 150 510 230 210 525 447 610 499 40 587 501 50 673
HVF3142 150 510 230 210 525 447 610 499 50 587 501 50 673
HVF3151/2 165 515 234 275 592 447 675 499 50 587 501 50 673
HVF3154 165 515 234 275 592 447 675 499 60 587 501 60 673
HVF3161/2 165 515 234 275 592 447 675 499 50 587 501 50 673
HVF3164 165 515 234 275 592 447 675 499 60 587 501 60 673
HVF3166/7 210 610 249 310 630 450 738 550 90 587 549 90 673
HVF3362 254 813 234 275 592 447 - - - - - - -
HVF3364 254 813 235 275 592 447 - - - - - - -
HVF6111 210 560 298 310 688 450 774 550 40 587 549 50 784
HVF6112 210 560 298 310 688 450 774 550 50 587 549 50 784
HVF6141 210 560 298 310 688 450 774 550 40 587 549 50 784
HVF6142 210 560 298 310 688 450 774 550 50 587 549 50 784
HVF6144 210 560 298 310 688 450 774 550 60 587 549 60 784
HVF7142 275 845 457 403 984 595 - - - - 845 50 1007
HVF7144 275 845 457 403 984 595 - - - - 845 60 1007
HVF7146 275 845 457 403 984 595 - - - - 845 90 1007
HVF2241/2 210 588 234 275 582 447 - - - - - - -
HVF2252 210 588 234 275 582 447 - - - - - - -
HVF2254 275 786 249 310 630 447 - - - - - - -
HVF2262 210 588 234 275 582 447 - - - - - - -
HVF2264/6/7 275 786 249 310 630 447 - - - - - - -
HVF7252/4/6/7 300 908 583 533 1102 659 - - - - - - -
※ Dimensions may be revised without notice.
VCB
24 ◀

Dimensions

HVF6251, 6252, 6254, 6256, 6257 fixed type HVF


(Unit: mm)

4-M10

55
80
19
40
60

786
275 275

310
169.6
711.5

80
150.5

490

34

301
34 10
176.3
189

11
112.5

4
57

40.5 512 126.5 275 60.5 780


720 585.5
780

HVF6251, 6252 draw-out type body only


(Unit: mm)

838 850

376 838
10

220 786
130
94

275 275
A
B
310
780
770

345
126
71

852 300 320


885 383
458
744

Type 630A 1,250A


A 74 87

B 35 49

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 25

HVF6254, 6256, 6257 draw-out type body only HVF


(Unit: mm)

838
850
376 10
838
786

A
275 275

B
310
780
770

345
126
71

852 300 320


885 383
458
737

Type 2,000A 2,500A 3,150A


A 117 147 147

B 79 109 109

※ Dimensions may be revised without notice.


VCB
26 ◀

Dimensions [ HVF draw-out type with ES/FS cradle ]

HVF
(Unit: mm)

Main Circuit Terminal


A B C

(Unit: mm)
Dimensions
W H L A B C D G I J K M N Terminal
Model
HVF1141/2 590 693 830 150 302 245 84 120 80 500 550 60 15 A
HVF1151/2 612 763 830 165 306 310 84 120 80 500 550 60 15 A
HVF1154 642 763 830 170 306 310 84 120 80 500 550 80 20 B
HVF1161/2 612 763 830 170 306 310 84 120 80 500 550 60 15 A
HVF1164 620 763 830 170 306 310 84 120 80 500 550 80 20 B
HVF1166/7 790 819 830 210 321 345 80 120 80 500 650 120 20 C
HVF2141/2 650 693 910 220 302 245 84 200 80 600 600 60 15 A
HVF2151/2 650 763 910 235 306 310 84 200 80 600 600 60 15 A
HVF2154 650 763 910 235 306 310 84 200 80 600 600 80 20 B
HVF2161/2 650 763 910 235 306 310 84 200 80 600 600 60 15 A
HVF2164 650 763 910 235 306 310 84 200 80 600 600 80 20 B
HVF2166/7 790 855 910 210 321 345 80 200 80 600 650 120 20 C
HVF3141/2 700 770 966 220 302 245 84 200 80 600 600 60 15 A
HVF3451/2 700 840 910 235 306 310 84 200 80 600 600 60 15 A
HVF3154 700 840 910 235 306 310 84 200 80 600 600 80 20 B
HVF3161/2 700 840 910 235 306 310 84 200 80 600 600 60 15 A
HVF3164 700 840 910 235 306 310 84 200 80 600 600 80 20 B
HVF6111/2 920 972 940 280(300) 370 345 84 230 100 670 650 60 15 A
HVF6141/2 920 972 940 280(300) 370 345 84 230 100 670 650 60 15 A
HVF6144 920 972 910 300 370 345 84 230 100 670 650 80 20 B
※ Dimensions may be revised without notice.
Vacuum Circuit Breaker ◀ 27

HVF1141, 1142 HVF


(Unit: mm)

547 (VCB WIDTH) CON. POSITION


515 DIS. POSITION
(VCB PHASE TO PHASE)
150 150 10 120 587 (VCB DEPTH)

50 85
40

84 20

146
COVER PLATE
(OPTION: CA)

60

150
680 (VCB HEIGHT)

MANUAL CHARGING

210
245
HANDLE

693

150
15
2-
14

319
302
DRAW-OUT HANDLE

195
499
4

80 500
550
590 4- 14 BOTTOM 830

MOUNT HOLE

< for breakers manufactured before July 31, 2009 >

80 500

40

20
150
400

590
150

14

4- 14 MOUNTING HOLE

29
150 150 590
15

7
210

245
6

693.5
301.5
319

800
914

< for breakers manufactured from August 1, 2009 >

※ Dimensions may be revised without notice.


VCB
28 ◀

Dimensions [ HVF draw-out type with ES/FS cradle ]

HVF1151, 1152, 1161, 1162 HVF


(Unit: mm)

547 (VCB WIDTH)


CON. POSITION
515
DIS. POSITION
(VCB PHASE TO PHASE)
165 165 10 120 587 (VCB DEPTH)

50 85

84 40
20

COVER PLATE
(OPTION: CA)

60
165
275
310
MANUAL CHARGING
680 (VCB HEIGHT)

HANDLE

763

14

165
2-
15

96
324
DRAW-OUT HANDLE

306
195
4

499 80 500
550 830
612 4- 14 BOTTOM
MOUNT HOLE
< for breakers manufactured before July 31, 2009 >

80 500

40

20
165
400

165

14

165 165 4- 14 MOUNTING HOLE 29 610


15

7
310
275

763
323.5

306

800
914

< for breakers manufactured from August 31, 2009 >

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 29

HVF1154, 1164 HVF


(Unit: mm)

547 (VCB WIDTH)


CON. POSITION
515
DIS. POSITION
(VCB PHASE TO PHASE)
165 165 10 120 587 (VCB DEPTH)

50 85
84 40

147
COVER PLATE 20

96
(OPTION: CA)

80
5
40

170
165

15
275
310
MANUAL CHARGING
680 (VCB HEIGHT)

HANDLE

763

165

170
20
4-
14
×

324
DRAW-OUT HANDLE

306
19
4

499 80 500
550 830
642 4- 14 BOTTOM
MOUNT HOLE

HVF1166, 1167
(Unit: mm)

647 (VCB WIDTH)


CON. POSITION
515
DIS. POSITION
(VCB PHASE TO PHASE)
210 210 15 120 587 (VCB DEPTH)

50 85
80 40
153

50

COVER PLATE
120

(OPTION: CB)
210
345
310
775 (VCB HEIGHT)

MANUAL CHARGING
819

HANDLE
210
20

338
321

DRAW-OUT HANDLE 4-
14
195

550 80 500
4

650 830
790 4- 14 BOTTOM
MOUNT HOLE

※ Dimensions may be revised without notice.


VCB
30 ◀

Dimensions [ HVF draw-out type with ES/FS cradle ]

HVF2141, 2142 HVF


(Unit: mm)

CON. POSITION
547 (VCB WIDTH)
DIS. POSITION
515
(VCB PHASE TO PHASE)
150 150 10 200 587 (VCB DEPTH)
40
50 85
20
COVER PLATE 84

146
(OPTION: CA)

60

220
MANUAL CHARGING

210
245
680 (VCB HEIGHT)

HANDLE

693

220
15

320
DRAW-OUT HANDLE

302
2-

195
14
4

499 80 600
600 910
650 4- 14 BOTTOM

HVF2152, 2154, 2162, 2164


(Unit: mm)
547 (VCB WIDTH)
515 CON. POSITION
(VCB PHASE TO PHASE) DIS. POSITION
165 165
10 200 587 (VCB DEPTH)
50 85
84
147

COVER PLATE
(OPTION: CA)
275
310
680 (VCB HEIGHT)

MANUAL CHARGING
HANDLE
763
A

DRAW-OUT HANDLE
324
306
195

80 600
4

499
910
600
650 4- 14 BOTTOM
MOUNT HOLE
(1250A) 40 (2000A) 40
20 20
60

80
40
235

235

Dimension A
235

235

HVF2152/2162 15mm
2- 4-
14 14
HVF2154/2164 20mm

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 31

HVF2166, 2167 HVF


(Unit: mm)

647 (VCB WIDTH)


CON. POSITION
612
515 DIS. POSITION
(VCB PHASE TO PHASE)
210 210 10 200 587 (VCB DEPTH)
76
50 85
80 40

189
23

120
COVER PLATE
(OPTION: CB)

210
50
310
345
775 (VCB HEIGHT)

855
MANUAL CHARGING
HANDLE

210
20
4-
14

338
321
DRAW-OUT HANDLE

195
120

550 80 600
4

650 4- 14 BOTTOM 910


790 MOUNT HOLE

HVF3141, 3142
40
(Unit: mm)

20
60
220
220

2-
14

547 (VCB WIDTH)


515
(VCB PHASE TO PHASE) CON. POSITION
150 150
DIS. POSITION
84
10 200 643 (VCB DEPTH)

50 85
223

COVER PLATE
(OPTION: CA)

MANUAL CHARGING
680 (VCB HEIGHT)

210
245

HANDLE
770
15

320
302

DRAW-OUT HANDLE
195

100

80 600
4

499
966
600
4- 14 BOTTOM
700
MOUNT HOLE

※ Dimensions may be revised without notice.


VCB
32 ◀

Dimensions [ HVF draw-out type with ES/FS cradle ]

HVF3151, 3152, 3154, 3161, 3162, 3164 HVF


(Unit: mm)
547 (VCB WIDTH)
CON. POSITION
515
(VCB PHASE TO PHASE) DIS. POSITION
165 165 587 (VCB DEPTH)
10 200

50 85

224
84
COVER PLATE
(OPTION: CA)

275
310
680 (VCB HEIGHT)

MANUAL CHARGING

840
HANDLE

A
324
DRAW-OUT HANDLE

306
195
499 80 600
4

600 906

700 4- 14 BOTTOM
MOUNT HOLE (630/1,250A) (2,000A) 40
40 20
20

80
60

40
235

235
Dimension A

HVF3151/3152/3161/3162 15mm

HVF3154/3164 20mm
235

235
2- 4-
14 14

HVF3166, 3167
(Unit: mm)

647 (VCB WIDTH)


612
CON. POSITION
515
(VCB PHASE TO PHASE) DIS. POSITION
210 210 587 (VCB DEPTH)
10 200
76
50 85
40
23
224

80
120

COVER PLATE
(OPTION: CB)
210
846 (VCB HEIGHT)

50
310
345
890

MANUAL CHARGING
HANDLE
210
20

4-
14
338
321

DRAW-OUT HANDLE
195

150

550 80 600
4

650 4- 14 BOTTOM 910


850 MOUNT HOLE

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 33

HVF6111, 6112, 6141, 6142, 6144 HVF


(Unit: mm)
647 (VCB WIDTH)
560
(VCB PHASE TO PHASE)
515
210 210
CON. POSITION INSULATION SHUTTER
(ONLY F2 CLASS) (1,250A) (2,000A)
DIS. .POSITION 40
40 20
35 230 587 (VCB DEPTH)

257
84 20
50 85

271

271

40
80
COVER PLATE

60

300
A
(OPTION: CB)

210

210
345
775 (VCB HEIGHT)

800

972

210

210
MANUAL CHARGING
HANDLE

210

210

300
A
B

271

271
370
DRAW-OUT
HANDLE

2-
126
181
195

14
4-
14
4

550 100 670


650 940
920
4- 14 BOTTOM < for breakers manufactured before July 31, 2009 >
MOUNT HOLE

Dimension A Dimension B

ES/FS type 280mm HVF6111-6142 ES/FS/E3/F3 type 15mm


HVF6111-6142
E3/F3 type 300mm HVF6144 ES/FS type 20mm

(E3/F3) (ES/FS)
630/1250A 630/1250A 2000A
100 670
40
14
14 14
40

20
300

300
280

20 20
920
650

80
60

60
920

40 40
280
300

300

4- 14 MOUNTING HOLE

210 210
850 114 40
310

360

972
387.5

362.5

850
1024

< for breakers manufactured from August 1, 2009 >

※ Dimensions may be revised without notice.


VCB
34 ◀

Dimensions [ HVF draw-out type with SF cradle ]

HVF1141, 1142 HVF


(Unit: mm)
105 500

40

30
150
400

60
150
2-
14
20
547 (VCB WIDTH)
515 CON. POSITION 4- 14 MOUNTING HOLE
(VCB PHASE TO PHASE) DIS. POSITION
150 150 40 115 587 (VCB DEPTH) 29
50 85

COVER PLATE

15
(OPTION: CA)

7
680 (VCB HEIGHT)

245
6

693.5
MANUAL CHARGING
HANDLE

DRAW-OUT 301.5
HANDLE

825
400
4

499 939
590

HVF1151, 1152, 1161, 1162


(Unit: mm)
105 500

40
165
400

60
165

2-
547 (VCB WIDTH) 14
20
515
(VCB PHASE TO PHASE) CON. POSITION 4- 14 MOUNTING HOLE
165 165 DIS. POSITION
40 115 587 (VCB DEPTH)

50 85
147
15

COVER PLATE
(OPTION: CA) 7
310
680 (VCB HEIGHT)

MANUAL CHARGING
6

763

HANDLE
15

306

DRAW-OUT HANDLE
825
4

400
499 939
610

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 35

HVF1154, 1164 HVF


(Unit: mm)

547 (VCB WIDTH)


515 CON. POSITION
(VCB PHASE TO PHASE) DIS. POSITION
165 165
40 115 587 (VCB DEPTH)

50 85
84 40

147
20
COVER PLATE
(OPTION: CA)

80
170
165

15
5

40
275

310
680 (VCB HEIGHT)

763

165

170
MANUAL CHARGING
HANDLE

20
4-

324

306
14
x1
9

DRAW-OUT HANDLE
4

80 500
499
855
550
642 4- 14 BOTTOM
MOUNT HOLE

HVF1166, 1167
(Unit: mm)

647 (VCB WIDTH) CON. POSITION

515 DIS. POSITION


(VCB PHASE TO PHASE)
40 120 587 (VCB DEPTH)
210 210
50 85 80

80 40
153

50

COVER PLATE
120

(OPTION: CB)
210
345
310
775 (VCB HEIGHT)

819

210

MANUAL CHARGING
20

HANDLE
338
321

4-
14
195

DRAW-OUT HANDLE
550 80 500
4

650 855
790 4- 14 BOTTOM
MOUNT HOLE

※ Dimensions may be revised without notice.


VCB
36 ◀

Dimensions [ HVF draw-out type with SF cradle ]

HVF2151, 2152, 2154, 2161, 2162, 2164 HVF


(Unit: mm)
547 (VCB WIDTH)
CON.POSITION
515
(VCB PHASE TO PHASE) DIS.POSITION
165 165 587 (VCB DEPTH)
35 200

50 85
84

147
COVER PLATE
(OPTION: CA)
680 (VCB HEIGHT)

275
310
763
A
MANUAL CHARGING
HANDLE

140
324
306
DRAW-OUT 120

195
HANDLE

158
499 80 600
4

600 935
650 4- 14 BOTTOM
MOUNT HOLE (630/1,250A) 40 (2,000A)
40
20
60
20

80
40
235

235
Dimension A
235

235
HVF2151/2152/2161/2162 15mm

HVF2154/2164 20mm 2- 4-
14 14

HVF3152, 3154, 3162, 3164


547 (VCB WIDTH) (Unit: mm)
515 CON. POSITION
(VCB PHASE TO PHASE) DIS. POSITION
165 165 587 (VCB DEPTH)
35 200

50 85
224

84
COVER PLATE
(OPTION: CA)
680 (VCB HEIGHT)

275
310
840
A

MANUAL CHARGING
HANDLE
324
306

DRAW-OUT
195

HANDLE

499 80 600
4

600 935
700 4- 14 BOTTOM
MOUNT HOLE (1,250A) (2,000A) 40
40 20
20
80
60

40
235

235

Dimension A
235

235

HVF3152/3262 15mm
2- 4-
HVF3154/3164 20mm 14 14

※ Dimensions may be revised without notice.


Vacuum Circuit Breaker ◀ 37

HVF3166, 3167 HVF


(Unit: mm)

647(VCB WIDTH)
612
515 CON. POSITION
(VCB PHASE TO PHASE)
DIS. POSITION
210 210
35 200 587 (VCB DEPTH)
76
50 85
40

224
23
80

120
COVER PLATE
(OPTION: CB)

50
775 (VCB HEIGHT)

310
345
890
MANUAL CHARGING
HANDLE

210
20
4-
14

338
321
195 150
DRAW-OUT HANDLE
550 80 600
4

650 4- 14 BOTTOM 935


850 MOUNT HOLE

HVF6111, 6112, 6141, 6142, 6144


647 (VCB WIDTH) (Unit: mm)
560
515
(VCB PHASE TO PHASE)
210 210 114 40
CON. POSITION
DIS. POSITION
15T 630/1250A
20T 2000A

35 230 587 (VCB DEPTH)


257

50 85

COVER PLATE
(OPTION: CB)
775 (VCB HEIGHT)

345
972

MANUAL CHARGING
HANDLE
370

DRAW-OUT HANDLE
871
4

550 1049
650
920
125 670 2,000A 630/1,250A
40 40
40

30
300

280
650

80

60
280
300

Dimension B

HVF6111/6112/6141/6142 15mm 4-
2-

14
14

HVF6144 20mm 20 20
4- 14 MOUNTING HOLE

※ Dimensions may be revised without notice.


VCB
52 ◀

Order Information

HVF 111) 41) 11) C1) ES1)


Rated Rated Rated current Pole Mounting
Code Type Code Code breaking Code Code distance of Code
voltage current IEC ANSI VCB body Structure
HVG HVG 10 7.2kV 9 8kA 9 400A 400A A 130mm XA Body Fixed type
HVF HVF 11 7.2kV 1 12.5kA 1 630A 600A B 140mm EA Body part of ES cradle
21 12kV 4 25kA 2 1,250A 1,200A C 150mm ES ES cradle (without shutter)
31 17.5kV 5 31.5kA 4 2,000A 2,000A D 165mm FA Body part of FS cradle
61 24kV 6 40kA 6 2,500A 2,500A E 178mm FS FS cradle (nonmetallic partition with shutter)
70 36/38kV 7 50kA 7 3,150A 3,000A F 210mm SA Body part of SF cradle
71 36kV 8 4,000A 4,000A G 250mm FS cradle (nonmetallic partition with shutter)
SF
※ 1) For correct application, please refer to page 54 and 55. H 254mm with screw type draw-in/out mechanism)
I 275mm GA Body part of GS cradle Draw-out
J 300mm GS GS cradle (metallic partition with shutter and bushing) type
K 350mm GE GS cradle with earthing switch
CS GS cradle for marine application (HVF 7.2/12kV)
E3 ES cradle for 300mm pole distance (HVF 24kV 630/1250A)
F3 FS cradle for 300mm pole distance (HVF 24kV 630/1250A)
MA for HHI standard switchgear
MS GS cradle for 38kV ANSI type
WA GS cradle for 4.76kV ANSI type

Spare parts for HVF type


Code Name Specification
HAFS-K1 Anti-pumping relay
HAFS-M Charging motor
1: DC24V, 2: DC48V, 3: DC60V
HAFS-L0 Lockout relay
4: DC110V, 5: DC125V, 6: DC220V
HAFS-SOL Closing solenoid
7: AC110V, 9: AC220V
HVFS-SOL Tripping solenoid
HVFS-UV Under voltage release
HVFS-UVE UVT operating mechanism
HVFS-T4 Condensor trip device DC110V
HVFS-T6 Condensor trip device DC220V
HVFS-T7 Condensor trip device AC110V
HVFS-T9 Condensor trip device AC220V
HAFS-ASW4 Auxiliary switch 4NO+4NC
HAFS-ASW7 Auxiliary switch 7NO+7NC
HAFS-ASW10 Auxiliary switch 10NO+10NC
HAFS-L/S Limit switch (S1) 1NO+1NC
HVFS-P/S Position switch 1NO+1NC
HAFS-C/ME Closing mechanism
HAFS-T/ME Tripping mechanism
HAFS-CT1 CT operated release 0.5A
HAFS-CT2 CT operated release 1A
HAFS-22JACK Control jack 4NO+4NC, fixed type, plug and socket only
HAFS-44JACK Control jack 4NO+4NC, cable type, plug and socket only
HAFS-HANDLE Charging handle
HVFS-EFHANDLE Draw-out handle ES, FS, SF cradle
HVFS-MGHANDLE Draw-out handle GS, CS, MS cradle
HVFS-VC9 Vacuum checker AC220V
Vacuum Circuit Breaker ◀ 53

4 4 4 C P2U4
Motor Closing Tripping Control jack
Code control Code control Code control Code Code Additional options
voltage voltage voltage Auxiliary switch Structure Application
2 DC48V 2 DC48V 2 DC48V A 4NO+4NC Fixed on VCB body P0 Cam for position switch HVF/HVG
3 DC60V 3 DC60V 3 DC60V B 7NO+7NC Fixed on VCB body U ✽ Under voltage release HVF
4 DC110V 4 DC110V 4 DC110V C 4NO+4NC 0.8m cable type R ✽ Second shunt release HVF
5 DC125V 5 DC125V 5 DC125V D 10NO+10NC 0.8m cable type L ✽ Lockout relay HVF
6 DC220V 6 DC220V 6 DC220V X Without control jack V ✽ Varistor module HVF/HVG
7 AC110V 7 AC110V 7 AC110V W Auto jack P21) Position switch HVF/HVG
9 AC220V 9 AC220V 9 AC220V KL1) Position padlock key HVF/HVG
L DC250V L DC250V L DC250V TP2) Trip padlock key HVF
EL Electrical local closing HVF
C0 Cut-out switch HVF
CP Closing padlock key HVF
S1 Spring charged signal (S41) HVF
C1 CT operated release 0.5A HVF
C2 CT operated release 1A HVF
EE Earthing switch operation indicator contact HVF
TC Trip coil supervision signal HVF
E9 BIL 38/95kV for 12kV VCB HVF
CA3) Cover plate / type A4) HVF
CB3) Cover plate / type B5) HVF
ZZ Special application HVF/HVG
※ ✽1: DC24V, 2: DC48V, 3: DC60V, 4: DC110V,
5: DC125V, 6: DC220V, 7: AC110V, 9: AC220V
1) Position switch and position padlock cannot be installed at same time.
2) Key is not supplied.
3) For the space between front cover of breaker and ES/FS/SF cradle.
4) Type A: for 7.2-17.5kV up to 31.5kA 2,000A
5) Type B: for 7.2-17.5kV 40/50kA 2,500-4,000A, 24/36kV
Spare parts for HVG type
Code Name Specification
HAFS-K1 Anti-pumping relay
1: DC24V, 2: DC48V, 3: DC60V
HVGS-M Charging motor
4: DC110V, 5: DC125V, 6: DC220V
HVGS-CS Closing solenoid
7: AC110V, 9: AC220V
HVGS-TS Tripping solenoid
HVFS-T4 Condensor trip device DC110V
HVFS-T6 Condensor trip device DC220V
HVFS-T7 Condensor trip device AC110V
HVFS-T9 Condensor trip device AC220V
HAFS-ASW4 Auxiliary switch 4NO+4NC
HAFS-ASW7 Auxiliary switch 7NO+7NC
HAFS-ASW10 Auxiliary switch 10NO+10NC
HAFS-L/S Limit switch (S1) 1NO+1NC
HVGS-P/S Position switch 1NO+1NC
HVGS-CAM Cam for position switch Attached in breaker body
HVGS-22JACK Control jack 4NO+4NC, fixed type, plug and socket only
HVGS-44JACK Control jack 7NO+7NC, fixed type, plug and socket only
HVGS-PL1099 Plug-in contact 8kA 400A
HVGS-PL1131-41 Plug-in contact 20/25kA 630A
HVGS-PL1011 Plug-in contact 12.5kA 630A
HVGS-PL1132-42 Plug-in contact 20/25kA 1,250A
HVGS-CHANDLE Charging handle
HVGS-DHANDLE Draw-out handle
HVFS-VC9 Vacuum checker AC220V
VCB
54 ◀

Order Information

Slection table for rating, pole distance and mounting


Specification Applicable mounting
Rated Rated Rated Pole Order
Type distance of Model Fixed
voltage breaking current code Draw-out type cradle
VCB body type
(kV) current (kV) (kV) (mm)
1. IEC62271-100
8 400 130 HVG1099 HVG1099 A XA EA, ES, FA, FS GA, GS
12.5 630 130 HVG1011 HVG1011 A XA EA, ES, FA, FS GA, GS
630 140 HVG1131 HVG1131 B XA EA, ES, FA, FS GA, GS
HVG 7.2 20
1,250 140 HVG1132 HVG1132 B XA EA, ES, FA, FS GA, GS
630 140 HVG1141 HVG1141 B XA EA, ES, FA, FS GA, GS
25
1,250 140 HVG1142 HVG1142 B XA EA, ES, FA, FS GA, GS
630 150 HVF1141 HVF1141 C XA EA, ES, FA, FS, SF GA, GS GE
25
1,250 150 HVF1142 HVF1142 C XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF1151 HVF1151 D XA EA, ES, FA, FS, SF GA, GS GE
31.5 1,250 165 HVF1152 HVF1152 D XA EA, ES, FA, FS, SF GA, GS GE
2,000 165 HVF1154 HVF1154 D XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF1161 HVF1161 D XA EA, ES, FA, FS, SF GA, GS GE
165 HVF1162 D XA EA, ES, FA, FS, SF GA, GS GE
1,250 HVF1162
210 HVF1162 F ✽non-standard, please ask to HHI.
165 HVF1164 D XA EA, ES, FA, FS, SF GA, GS GE
2,000 210 HVF1164 HVF1164 F ✽non-standard, please ask to HHI.
7.2 40 275 HVF1164 I ✽non-standard, please ask to HHI.
210 HVF1166 F XA EA, ES, FA, FS, SF GA, GS GE
2,500 HVF1166
275 HVF1166 I ✽non-standard, please ask to HHI.
210 HVF1167 F XA EA, ES, FA, FS, SF GA, GS GE
3,150 HVF1167
275 HVF1167 I ✽non-standard, please ask to HHI.
4,000 275 HVF1168 HVF1168 I XA EA, ES, FA, FS, SF GA, GS GE
1,250 210 HVF1172 HVF1172 F XA EA, ES, FA, FS, SF GA, GS GE
2,000 275 HVF1174 HVF1174 I XA EA, ES, FA, FS, SF GA, GS GE
50 2,500 275 HVF1176 HVF1176 I XA EA, ES, FA, FS, SF GA, GS GE
3,150 275 HVF1177 HVF1177 I XA EA, ES, FA, FS, SF GA, GS GE
4,000 275 HVF1178 HVF1178 I XA EA, ES, FA, FS, SF GA, GS GE
HVF 630 150 HVF2141 HVF2141 C XA EA, ES, FA, FS, SF GA, GS GE
25
1,250 150 HVF2142 HVF2142 C XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF2151 HVF2151 D XA EA, ES, FA, FS, SF GA, GS GE
1,250 165 HVF2152 HVF2152 D XA EA, ES, FA, FS, SF GA, GS GE
31.5
2,000 165 HVF2154 HVF2154 D XA EA, ES, FA, FS, SF GA, GS GE
2,500 210 HVF2156 HVF2156 F XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF2161 HVF2161 D XA EA, ES, FA, FS, SF GA, GS GE
165 HVF2162 D XA EA, ES, FA, FS, SF GA, GS GE
1,250 HVF2162
210 HVF2162 F ✽non-standard, please ask to HHI.
165 HVF2164 D XA EA, ES, FA, FS, SF GA, GS GE
2,000 210 HVF2164 HVF2164 F ✽non-standard, please ask to HHI.
12
40 275 HVF2164 I ✽non-standard, please ask to HHI.
210 HVF2166 F XA EA, ES, FA, FS, SF GA, GS GE
2,500 HVF2166
275 HVF2166 I ✽non-standard, please ask to HHI.
210 HVF2167 F XA EA, ES, FA, FS, SF GA, GS GE
3,150 HVF2167
275 HVF2167 I ✽non-standard, please ask to HHI.
4,000 275 HVF2168 HVF2168 I XA EA, ES, FA, FS, SF GA, GS GE
1,250 210 HVF2172 HVF2172 F XA EA, ES, FA, FS, SF GA, GS GE
2,000 275 HVF2174 HVF2174 I XA EA, ES, FA, FS, SF GA, GS GE
50 2,500 275 HVF2176 HVF2176 I XA EA, ES, FA, FS, SF GA, GS GE
3,150 275 HVF2177 HVF2177 I XA EA, ES, FA, FS, SF GA, GS GE
4,000 275 HVF2178 HVF2178 I XA EA, ES, FA, FS, SF GA, GS GE
✽For models and codes not listed, please ask to HHI.
Vacuum Circuit Breaker ◀ 55

Specification Applicable mounting


Rated Rated Rated Pole Order
Type distance of Model Fixed
voltage breaking current code Draw-out type cradle
VCB body type
(kV) current (kV) (kV) (mm)
630 150 HVF3141 HVF3141 C XA EA, ES, FA, FS, SF GA, GS GE
25
1,250 150 HVF3142 HVF3142 C XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF3151 HVF3151 D XA EA, ES, FA, FS, SF GA, GS GE
1,250 165 HVF3152 HVF3152 D XA EA, ES, FA, FS, SF GA, GS GE
31.5
2,000 165 HVF3154 HVF3154 D XA EA, ES, FA, FS, SF GA, GS GE
2,500 210 HVF3156 HVF3156 F XA EA, ES, FA, FS, SF GA, GS GE
630 165 HVF3161 HVF3161 D XA EA, ES, FA, FS, SF GA, GS GE
17.5
165 HVF3162 D XA EA, ES, FA, FS, SF GA, GS GE
1,250 HVF3162
210 HVF3162 F ✽non-standard, please ask to HHI.
165 HVF3164 D XA EA, ES, FA, FS, SF GA, GS GE
40 2,000 HVF3164
210 HVF3164 F ✽non-standard, please ask to HHI.
2,500 210 HVF3166 HVF3166 F XA EA, ES, FA, FS, SF GA, GS GE
210 HVF3167 F XA EA, ES, FA, FS, SF GA, GS GE
3,150 HVF3167
HVF 275 HVF3167 I ✽non-standard, please ask to HHI.
630 210 HVF6111 HVF6111 F XA EA, ES, FA, FS, SF GA, GS GE
12.5 1,250 210 HVF6112 HVF6112 F XA EA, ES, FA, FS, SF GA, GS GE
2,000 210 HVF6114 HVF6114 F XA EA, ES, FA, FS, SF GA, GS GE
24 630 210 HVF6141 HVF6141 F XA EA, ES, FA, FS, SF GA, GS GE
1,250 210 HVF6142 HVF6142 F XA EA, ES, FA, FS, SF GA, GS GE
25
2,000 210 HVF6144 HVF6144 F XA EA, ES, FA, FS, SF GA, GS GE
2,500 210 HVF6146 HVF6146 F XA EA, ES, FA, FS, SF GA, GS GE
1,250 275 HVF7142 HVF7142 I XA EA, ES, FA, FS GA, GS GE
25 2,000 275 HVF7144 HVF7144 I XA EA, ES, FA, FS GA, GS GE
2,500 275 HVF7146 HVF7146 I XA EA, ES, FA, FS GA, GS GE
36
1,250 275 HVF7052 HVF7052 I XA EA, ES, FA, FS GA, GS GE
31.5 2,500 275 HVF7056 HVF7056 I XA EA, ES, FA, FS GA, GS GE
3,150 275 HVF7057 HVF7057 I XA EA, ES, FA, FS GA, GS GE
2. ANSI
50 1,200 178 HVF1372 HVF1372 E XA EA, ES, FA, FS GA, GS GE
4.76
4,000 275 HVF1378 HVF1378 I XA EA, ES, FA, FS GA, GS GE
1,200 254 HVF3362 HVF3362 H XA EA, ES, FA, FS GA, GS GE
15 40
2,000 254 HVF3364 HVF3364 H XA EA, ES, FA, FS GA, GS GE
1,200 275 HVF7052 HVF7052 I XA EA, ES, FA, FS GA, GS GE
HVF
31.5 2,000 275 HVF7054 HVF7054 I XA EA, ES, FA, FS GA, GS GE
3,000 275 HVF7057 HVF7057 I XA EA, ES, FA, FS GA, GS GE
38
1,200 275 HVF7062 HVF7062 I XA EA, ES, FA, FS GA, GS GE
40 2,000 275 HVF7064 HVF7064 I XA EA, ES, FA, FS GA, GS GE
3,000 275 HVF7067 HVF7067 I XA EA, ES, FA, FS GA, GS GE
3. IEC60056
630 165 HVF1051 HVF1051 D XA EA, ES, FA, FS GA, GS GE
7.2 31.5 1,250 165 HVF1052 HVF1052 D XA EA, ES, FA, FS GA, GS GE
2,000 210 HVF1054 HVF1054 F XA EA, ES, FA, FS GA, GS GE
630 165 HVF2041 HVF2041 D XA EA, ES, FA, FS GA, GS GE
12 25 1,250 165 HVF2042 HVF2042 D XA EA, ES, FA, FS GA, GS GE
HVF
2,000 210 HVF2044 HVF2044 F XA EA, ES, FA, FS GA, GS GE
1,250 275 HVF6062 HVF6062 I XA EA, ES, FA, FS GA, GS GE
2,000 275 HVF6064 HVF6064 I XA EA, ES, FA, FS GA, GS GE
24 40
2,500 275 HVF6066 HVF6066 I XA EA, ES, FA, FS GA, GS GE
3,150 275 HVF6067 HVF6067 I XA EA, ES, FA, FS GA, GS GE
✽For models and codes not listed, please ask to HHI.
HHIS-WC-LE-B45-04, 2010.5 Designed by MERMONT
www.hyundai-elec.com

Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea


Tel: 82-52-202-8101~8 Fax: 82-52-202-8100
Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea
(Sales & Marketing) Tel: 82-2-746-8519, 7510 Fax: 82-2-746-7647
Orlando 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A.
Tel: 1-407-249-7350 Fax: 1-407-275-4940
New Jersey 300 Sylvan Avenue, Englewood Cliffs, NJ, 07632, U.S.A.
Tel: 1-201-816-0286 Fax: 1-201-816-4083
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK
Tel: 44-20-8741-0501 Fax: 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan
Tel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093
Osaka I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818
Dubai Level 2, Unit 205, Emaar Square-Bldg.4, Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E.
Tel: 971-4-425-7995 Fax: 971-4-425-7996
Sofia 1271, Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200, 3220 Fax: 359-2-803-3203
Yangzhong No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231
HVF Series (IEC62271-100)

진공차단기취급설명서
Vacuum Circuit BreakerlInstruction Manual

Notice
Read and understand these instructions before attempting any
unpacking, assembly, operation or maintenance of the circuit
breaker.
This instruction manual should be applied only to HVF Series
Vacuum Circuit Breakers.
This instruction manual does not include all items regarding
installation and maintenance procedures.
For more information, please contact authorized partners.
차단기를 포장해체, 조립, 동작, 유지보수를 하기 전 반드시 본 매뉴얼에
대해 숙지하시기 바랍니다.
본 매뉴얼은 HVF 시리즈 진공차단기에 한해 적용됨을 유의 바랍니다.
또한 본 매뉴얼은 모든 제품에 대한 정보를 포함하고 있지 않습니다.
따라서, 더 많은 정보를 원하실 경우, 현대중공업 또는 영업점으로 문의
바랍니다.
Safety Practices 안전 조항

Safety Practices 안전 조항
This instruction manual applies only to HVF series vacuum 본 취급 설명서는 HVF 시리즈 현대 진공차단기의 운전 및 안전에 관한
circuit breakers regarding installation and maintenance 중요한 내용을 기술하였습니다.
procedures. 제품을 부적절하게 설치하거나 유지∙보수시에는 치명적인 인명피해 및
Installing and maintaining these products IMPROPERLY may 재산 손실이 유발될 수 있으므로 포장해체, 조립, 작동, 혹은 유지∙보수를
result in serious personal injury, property damage, or 하시기 전에, 반드시 이 취급 설명서를 충분히 읽고 이해하시기 바랍니다.
death. Therefore this instruction manual must be read and 설치 및 유지 보수는 유자격자나 전문지식을 보유한 사람이 행하십시오.
understood at every step in unpacking, assembly,
operation, and maintenance of the breaker.
Only qualified persons who are familiar with installing and
maintaining circuit breakers are permitted to work on
breakers, and this instruction manual should be accessible
to those persons at all times.

Signal Words 기호 설명
Signal words used in this instruction manual are 본 취급설명서에서는 안전 주의사항을 위험 정도에 따라『위험』
,『경고』
,
DANGER, WARNING and CAUTION in descending order of 『주의』
로 구분하고 있습니다.
urgency.

Indicates an imminently hazardous situation which, if 회피되지 않으면, 사망 또는 중상을 입을 절박한 위험상태를 나타내며,
ignored, will result in death or serious injury. 가장 위험한 상황입니다.

Indicates a potentially hazardous situation, which, if 회피되지 않으면, 사망 또는 중상을 입을 수 있는 잠재적인 위험상태를
ignored, could result in death or serious injury. 나타냅니다.

Indicates a potentially hazardous situation, which, if 회피되지 않으면, 약한 상해나 경상이 발생할지 모르는 잠재적인 위험상태
ignored, may result in minor or moderate injury. This signal 를 나타냅니다. 또한 이 표시는 불안전한 행동에 대한 경고입니다.
also warns operators to take extra care in their work.

Safety Practices During Moving 이동시 주의사항

�When the breaker need to be moved on �바닥에서 차단기를 수평 이동시 핸들을 잡고


a flat area, grab the handle and move 이동하는 것이 안전합니다.
the breaker. �로프를 이용하여 차단기를 들어올릴 경우 무게
�When the breaker is lifted by a rope, it 중심의 이동으로 차단기가 접속단자부 쪽으로
may lean to the terminal side. Take the 기울어질 수 있으므로 인체와 제품의 피해가
necessary precautions to prevent 없도록 주의바랍니다.
damage to the unit and injury to
personnel.

2 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

Safety Practices During Installation 설치(취부, 접속)시의 주의사항

�Do not work on the breaker unless the �설치에 앞서 모든 전원을 차단하기 위해 앞단의
primary circuits are disconnected. 차단기나 그러한 종류의 제품을 반드시 Open
※ There is a damage of electric shock. 시키십시오. 감전의 위험이 있습니다.
�When connecting bus-bars, tighten �단자 Bolt는 표준체결 Torque로 확실하게
bolts using our standards. 조이십시오. 화재의 위험이 있습니다.
�The product should be installed and �본 제품은 수평하고 평평한 면에 단단하게
tighened on the plate area. 취부하여 고정시키십시오.
�Do not install the breaker in areas with �고온, 다습, 분진, 부식성가스, 진동, 충격 등
high temperature, high humidity, dust, 좋지 못한 환경에 설치하지 마십시오.
corrosive or vibrating conditions. 화재, 동작 불량이 발생할 수 있습니다.
�Concrete dust or any other dust should �먼지, 콘크리트 가루, 철분 등의 미물질 및
not be inside the product when it 빗물 등이 본제품의 내부에 들어가지 않도록
installed. It can cause fire or 시공하십시오.
malfunctions. 화재, 동작 불량이 발생할 수 있습니다.
�Connect the control jack tight, �Control Jack에 확실하게 접속하십시오.
otherwise it can cause malfunctions 오동작을 일으킬 수 있습니다.

Safety Practices During Operation 동작시 주의사항

�Do not touch the main and control �통전되고 있는 주회로 및 제어회로 단자부에는
circuit while the product is in operation. 접촉하지 마십시오.
The hazardous voltage can cause 감전의 위험이 있습니다.
electric shocks. �DISCONNECTION 위치(E, F2급인 경우)나
�Do not let the product stay in the 인출위치에서 UNLOCK 상태(G급인 경우)로
DISCONNECTION position with UNLOCK 제품을 방치하지 마십시오. 제품이 중량물이므
state. 로 낙하시 심각한 사고 및 제품 손상의 위험이
�If the heavy product dropped the 있습니다.
ground, it can cause the serious
accident or product damage.

Safety Practices During Maintenance 유지�보수시 주의사항

�Before any maintenance, always open �작업은 앞단의 차단기를 반드시 Open시키고
the breaker and make sure that the 주회로, 제어회로가 모두 충전되어 있지 않은
main and control circuits are not 것을 확인한 후에 행하십시오.
charged. 감전의 위험이 있습니다.
The voltage can be hazardous. �내부 점검은 본 제품이 Open 상태인 것을
�Discharge the springs and open the 확인한 후 행하십시오. 손가락 및 공구가
breakers before performing any breaker 기구부에 끼여 다칠 위험이 있습니다.
maintenance, inspection or repair. �단자 Bolt는 정기적으로 표준 체결 Torque로
Charged closing or tripping spring can 조이십시오.
cause serious injury. Bolt 풀림은 화재 발생의 원인이 됩니다.
�Use the standard pressure torque to �부품의 교체는 반드시 당사 A/S 요원에 의하여
tighten the bolts. Loosening the bolts 작업이 될 수 있도록 하십시오.
can cause fire. �차단기의 개폐수명(당사 Catalogue 참조)을
�Replacing parts should be carried out 초과하여 사용하지 마십시오.
by our service agent.
�The breaker should not be used more
than its life time specified in catalogue.

>>
진공차단기 취급설명서 3
Contents 목차

Safety Practices 2 안전 조항 2

1. Production Scope 5 1. 제작 사양 5

2. Technical Data 6 2. 기술적 데이터 6


2.1 Service Conditions 2.1 사용 조건
2.2 Motor Drive 2.2 모터 동작
2.3 Multiple Auto-Reclosing 2.3 다중 재투입
2.4 Interlock Mechanism of the Draw-Out Type Breaker 2.4 인출형 차단기의 인터록 장치
2.5 Closing (Y9) and Anti-Pumping (K1) 2.5 투입(Y9)와 재투입방지 회로(K1)
2.6 Open Solenoid (Y1) 2.6 트립 솔레노이드(Y1)
2.7 Auxiliary Switch (S1) 2.7 보조 스위치(S1)
2.8 Condenser Trip Device 2.8 콘덴서 트립 장치
2.9 Under Voltage Release (Y7) 2.9 부족전압 Release(Y7)
2.10 2nd Open Solenoid (Y2) 2.10 2차 트립 솔레노이드(Y2)
2.11 Cutout Switch 2.11 컷아웃 스위치
2.12 Closing Spring Charge Signal 2.12“투입스프링 차지”신호

3. Handling and Installing the Breaker 11 3. 취급설명 11


3.1 Unloading and Storage 3.1 운송 및 보관
3.2 Unpacking 3.2 포장해체
3.3 Inspection After Unpacking 3.3 포장해체 후 점검 사항
3.4 Installation 3.4 Switchgear에 설치
3.5 Inspection Before Operation 3.5 운전 전 점검사항
3.6 Manual Operation 3.6 차단기의 수동 조작 설명

4. Structure and Operation 13 4. 구조 및 동작 13


4.1 Component List of HVF VCB 4.1 HVF 차단기의 구조 및 부품표
4.2 Operation Mode 4.2 동작 설명
4.3 Draw In & Out Operation of HVF VCB 4.3 HVF 차단기의 인출입 방법

5. Maintenance and Inspection 20 5. 보수∙점검 20


5.1 Visual Inspection 5.1 외관 점검
5.2 Periodical Inspection 5.2 정기 점검
5.3 Contact Erosion 5.3 접점 마모 한계
5.4 Trouble Shooting Guide 5.4 문제 해결 가이드
5.5 Lubrication 5.5 주유

Appendix 24 부록 24

Maintenance Recording 26 보수 점검 26

4 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series
01 Product Scope 제작 사양

● HVF Type (HVF ����)


� Table 1-1 / 표 1-1

Rated Breaking Power Freq. Impulse Rated current per distance between phase to phase
상간거리별 정격전류 (A) Applied
Voltage Current Withstand Volt. Withstand Volt.
standard
정격전압 차단전류 상용주파 내전압 임펄스 내전압 630 1250 3150
2000 2500 4000 적용규격
(kV) (kA) (kV, 1 min) (kV) (600) (1200) (3000)

25 HVF1141 C HVF1142 C

31.5 HVF1151 D HVF1152 D HVF1154 D


7.2 20 60
40 HVF1162 D HVF1164 D HVF1166 F/I HVF1167F/I HVF1168 I

50 HVF1172 F HVF1176 I HVF1177 I HVF1178 I

25 HVF2141 C HVF2142 C

31.5 HVF2151 D HVF2152 D HVF2154 D


12 28 75
40 HVF2162 D HVF2164 D/F HVF2166 F/I HVF2167 F/I HVF2168 F/I
IEC62271-
50 HVF2172 F HVF2176 I HVF2177 I HVF2178 I
100
25 HVF3141 C HVF3142 C

17.5 31.5 38 95 HVF3151 D HVF3152 D HVF3154 D HVF3156 F

40 HVF3162 D/F HVF3164 D/F HVF3166 F/I HVF3167 F/I HVF3168 I

12.5 HVF6111 F HVF6112 F


24 50 125
25 HVF6141 F HVF6142 F HVF6144 F/I HVF6146 I HVF6147 I

25 HVF7142 I HVF7144 I
36 70 170
31.5 HVF7052 I HVF7056 I HVF7057 I

4.76 40 19 60 HVF1372 E HVF1374 E HVF1377 H HVF1378 H

15 50 36 95 HVF3362 H HVF3364 H HVF3367 H


ANSI C.37
31.5 HVF7052 I HVF7054 I HVF7057 I
38 80 150
40 HVF7062 I HVF7064 I HVF7067 I

- Indicating process of the distance / 상간거리 내용 (Unit : mm)

A B C D E F G H I J K

130 140 150 165 178 210 250 254 275 300 350

- Type no. suffix in the ���� shall be listed as shown in - “����”안 빈칸은 정격 및 사양에 따라 상이하므로 표를
the column of the rated, specification. 참조하시어 작성바랍니다.

>>
진공차단기 취급설명서 5
02 Technical Data 기술적 데이터

2.1 Service Condition 2.1 사용 조건


1) Site altitude: Less than 1000 m 1) 사용 고도 : 1000m 이하
2) Relative humidity: Less than 95% 2) 상대 습도 : 95% 이하
3) Ambient temperature: MAX 40°C / MIN -5°C 3) 주위 온도 : MAX 40℃ / MIN -5℃

CAUTION 주 의
Consideration of site altitude! 고도에 따른 전압 정정!
If the site altitude is higher than 1000 m, dielectric 1000m 이상에서 사용시에는 공기의 절연내력이 약화되므로
strength of the breaker will be reduced according to 차단기의 상용주파 내전압 및 충격 내전압치를 다음과 같이
the altitude. Therefore, the values of power frequency 보정하여 선택하여야 합니다.
withstand voltage and lightning impulse withstand ≥ 정격전압에 따른 상용주파 및 충격 내전압치 X k
voltage should be selected. (k : 표 3을 참조하십시오.)
≥Rated withstand voltage according to rated voltage
X k (k: Refer to table 2-1.)

For higher humidity, it is required to use a heater in the 습도가 보다 높은 곳에서 사용시는 절연물의 이슬 맺힘 및
switchgear to prevent dewdrops on the insulation 절연 내력 저하를 방지하기 위한 히터를 배전반에 반드시
material and the consecutive decrease in dielectric strength. 설치해야 합니다.

� Table 2-1 Correction factor as a function of site altitude / 표 2-1 고도에 따른 정정 계수


Applied Altitude / 적용 고도 1000 m 1500 m 2000 m 2500 m 3000 m
Correction Factor (k) / 보정 계수 1.0 1.05 1.1 1.15 1.2

2.2 Motor Drive 2.2 모터 동작

� Table 2-2 Specifications for motor operation / 표 2-2 투입 조작용 모터 특성


Rate voltage Operating voltage (V) Power consumption Current For motor protection MCCB
정격 전압 동작 전압 전력 소비 전류 rated current (A)
(V) Max. Min. (W) (VA) (A) 모터 보호용 MCCB 정격전류
24 DC 25.6 20 500 - 25 30
48 DC 53 41 500 - 15 20
(60 DC) (66) (51) (500) - (12) (15)
110 DC 121 93.5 500 - 7.5 10
220 DC 242 187 500 - 3.5 5
110 AC 121 93.5 - 700 8.5 10
220 AC 242 187 - 700 4.5 10

HVF VCB have motor-spring type stored-energy operating HVF VCB는 전동 스프링 방식의 에너지 저장형 기구부를 가지고
mechanism. The closing operation can be done only after 있으므로 투입 스프링이 완전히 차지된 후 투입 동작이 가능합니다.
the closing spring is charged. 표4에서 동작 중 모터의 전류 소비치를 나타내었으며, 돌입전류는
Consumption during the operation is shown in Table 4, and 아주 짧은 시간만 지속하므로 무시될 수 있습니다.
the inrush current may be disregarded since it lasts for only 표준회로 1, 2번 단자에 규정 전압이 인가되면 모터(M1)에 의해 투입
a brief period. 스프링이 인장되어 차지가 완료됩니다. 그리고 LINK에 의해 작동되는
The closing spring is fully tensioned by motor (M1) with the 리미트 위치 S21, S22에 의해 모터의 구동은 정지되고, 그림 1과 같이
rated voltage applied through terminal No.1 & 2 of standard 스프링 표시기는“SPRING CHARGED”
를 표시합니다.
control circuit. Then the limit switch (S21, S22) stops the 차지가 완료된 차단기는“트립-투입-트립”
의 동작을 연속적으로 할 수
motor, and the spring indicator shows "SPRING CHARGED" 있으며 트립 동작 후 지체 없이 다음 투입 및 트립 동작이 가능합니다.
by link activation as shown in Fig.1. The charged VCB can
� Fig. 2-1 State of Spring Charged / 그림 2-1 스프링이 차지된 상태
carry out the open-close-open sequential operation and
also the next close-open operation without delay.

6 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

� Fig. 2-2 Standard circuit diagram / 그림 2-2 표준 내부 회로도

Auxiliary�Switch Auxiliary�Switch Auxiliary�Switch

For�A,�C�Type For�B�Type For�D�Type

표준접점 표준접점 추가접점


(4NO+4NC) (7NO+7NC) (10NO+10NC)
STANDARD EXTENDED EXTENDED

9 11 13 15 17 19 21 23 25 27 29 31 33 35 1 3 5 7 9 11 13 15 17 19 21 23

10 23 21 33 31 43 41 63 51 53 61 73 71 83 81 93 91 103 101 113 111 123 121 73 71 83 81 93 91 103 101 113 111 123 121

S1 S1
19 24 22 34 32 44 42 64 52 54 62 74 72 84 82 94 92 104 102 114 112 124 122 74 72 84 82 94 92 104 102 114 112 124 122

10 12 14 16 18 20 22 24 26 28 30 32 34 36 2 4 6 8 10 12 14 16 18 20 22 24

Standard�
/�표준회로(DC) Extended�
circuit�
/�추가회로

Closing�and Undervoltage 2nd�Open Closing�spring


Motor�drive anti-pumping Open�solenoid Lock�out release solenoid Cutout�switch charged�signal
X0 1 6 4

13 21 13
1 S3 T6
S3 S6
S21 14
6
22 14
2 53
61 D1
S1 4
S1 S1
54 Y7
62 T8 D2 U1 Uc1
13
A1 E1
T1
M1 M F1 UVR�CONTROLLER S7
A2 1 E2 14
U2 Uc2
K1 8 1
5 K1 A1 R1 2
A1 13
2 T5 7 Y1 Y2 S41
A2 A2 14
S22 A1 10
1
Y9 R R2 S1
A2 19
T7
K1�CONTACT

X0 2 7 5

M1 Motor operating mechanism Y1 Open solenoid S1 Auxiliary switch

K1 Anti-pumping contactor Y2 2nd open solenoid S3 Limit switch (K1 Control)

R1 Resistor Y4 C.T. operated release Limit switch supplied with the lockout
S5 (Prevents closing by electrical means when
X0 Plug Connector Y7 Under-voltage release
Lock-out effective)
Y9 Closing solenoid S6, S7 Cutout switches
Limit switches
S21, S22
(Interrupt motor circuit after spring charged)
S41, S42 Position switch (spring charged status signal)

Note - Extended circuit spec & connection line number are ※ 주의 - 추가 회로 및 접속은 고객 요구에 따라 변경될 수 있습니다.
defined by user's request. - AC 제어전원에 대해서는 정류기가 추가됩니다.
- For the AC control circuit, the rectifier should be - 추가 회로 요청 시, 표준 접점이 부족할 수도 있습니다.
attached on the standard circuit. - 전기적 Option을 1개 적용 시, A, B Jack은 21, 22번으로
- Standard contacts can be insufficient on the request of 인출을 하고, C, D Jack은 3, 8번으로 인출합니다.
the extended circuit.
- In case of 1 option applied, the numbers are 21, 22 for
A, B Jack and 3, 8 for C, D Jack.

>>
진공차단기 취급설명서 7
02 Technical Data 기술적 데이터

2.3 Multiple Auto-Reclosing 2.3 다중 재투입


HVF circuit breakers are capable of auto-reclosing and HVF 차단기는 재투입 기능이 있으며, 또한 다음의 동작 스퀀스에 따라
can also be used for multiple reclosing for the following 다중 재투입으로도 사용될 수 있습니다.
operating sequence O-0.3s-CO-3min-CO-15s-CO..... (O; 트립, C; 투입)
O-0.3s-CO-3min-CO-15s-CO..... (O: tripping; C: closing)

2.4 Interlock Mechanism of the Draw-Out Type Breaker 2.4 인출형 차단기의 인터록 장치
The draw-out type circuit breaker has an interlock 인출형 차단기는 오동작으로 인한 사고를 막기 위해 인터록 장치를
mechanism which prevents trouble due to misoperation. 구비하고 있습니다.
The sensing parts check the position of the circuit breaker 이 장치는 차단기의 위치를 파악하여 차단기가 안전한 위치에 있지
and prevent it from closing if the associated disconnector is 않을 때는 차단기의 투입이 불가능하게 합니다.
not allowed for safe operation.

CAUTION 주 의

Misoperation or carelessness may result in 오조작, 또는 부주의가 중상 혹은 재산피해을 일으킬 수 있습니다.


serious injury or property damage. 차단기가 투입된 상태에서는 인입이나 인출이 불가능합니다.
With the breaker closed, the draw in & out operation is 잘못된 방법에서 차단기의 인입과 인출을 무리한 힘으로 동작
impossible. Do not push too hard on the breaker under 시키지 마십시오.
improper condition.

2.5 Closing (Y9) and Anti-Pumping (K1) 2.5 투입(Y9)와 재투입방지 회로(K1)
When closing, authorization is applied through terminals 표준회로 6, 7번 단자에 규정 전압의 투입 신호가 인가되면,
6 & 7 Solenoid Y9 fress the closing spring, and thus closes 솔레노이드 Y9가 동작하여 차단기가 전기적으로 투입되게 됩니다.
the circuit breaker electrically. 차단기가 투입되자마자, 보조접점 S1은 투입회로를 개방시키고,
Immediately after the breaker closes, Aux. S/W, S1 opens 리미트스위치 S3과 재투입 방지 릴레이 K1은 연속 투입 지령이
the circuit of closing, and limit switch S3 and anti-pumping 끝날 때가지 Y9가 다시 동작되지 않도록 합니다.
relay K1 switch affect to Y9 so that they can not be 따라서 차단기는 IEC에서 요구하는 재투입 방지와 트립 방지 기능과
reactivated until the continuous closing command is 일치합니다.
interrupted. Thus the breaker can meet the IEC 동시에 Contact Pressure Spring은 차단기가 투입상태에서 진공 밸브의
requirements for anti-pumping and trip-free opeation. 가동접점에 적절한 접촉압력을 유지시키기 위해 압축되며, 트립 스프링도
At the same time, the contact pressure spring is 다음의 개극 동작을 위해 압축되게 됩니다.
compressed properly to maintain sufficient contact
pressure on the moving contact of the vacuum interrupters
while the breaker is in the closed position, and the tripping
spring is compressed for the opening operation.

2.6 Open Solenoid (Y1) 2.6 트립 솔레노이드(Y1)


When the opening command is applied, the tripping spring 개극 신호가 인가되면 트립 솔레노이드, Y1은 트립 스프링의 랫치를
is unlatched by the trip solenoid Y1 and the force turns the 해지함으로 Breaker Shaft가 회전하여 차단기가 개극 되도록 합니다.
torque to rotate the brake shaft to make the opening 차단기가 개극되면 개폐표시기는 Open 상태를 표시하고 보조접점 S1은
position. Immediately after the breaker is open, the 개극회로를 개로시킵니다.
indicator displays the open state and Aux. S/W, S1 open
the opening circuit.

2.7 Auxiliary Switch (S1) 2.7 보조 스위치(S1)


The standard auxiliary contacts for external connection are 외부의 연결을 위한 표준 보조접점은 4NO + 4NC로 되어 있으며,
composed of 4NO+4NC. These contacts are wired to the 이 접점들은 플러그 컨넥션(XO)에 연결되어 있습니다.
control jack (XO). �정격절연전압 : AC/DC 250V
�Rated Insulation Voltage: AC/DC 250 V �연속전류 : 10A
�Continuous Current: 10 A �투입전류 : 30A
�Making Current: 30 A �개폐전류 : 2A (DC220V, τ=20ms에서)
�Switching Current: 2 A at DC 220 V, τ=20 ms �추가 접점이 요구되는 경우 최대 10NO+10NC까지 가능합니다.
�The maximum connection 10NO+10NC is available on request.

8 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

� Fig. 2-3 Arrangement of control jack / 그림 2-3 제어회로 결선

Fixed Type Control Jack / 고정형 Control Jack(A/B Type) Draw-Out Control Jack / 인출형 Control Jack(C/D Type)

13 11 9 6 4 1 12 11 10 9 7 6 5 4 2 1

MOTOR
CLOSE

OPEN
NC NO CLOSE OPEN MOTOR
NO NC NO NC XA 24 23 22 21 20 19 18 17 16 15 14 13
NC NO NC NO NC NO
14 12 10 23 7 5 2

35 33 31 21 19 17 15 29 27 25 12 11 10 9 8 7 6 5 4 3 2 1
NC NO NC NO NC NO
E.NCE.NO E.NC NO NC NC NO NC E.NO E.NC E.NO XB 24 23 22 21 20 19 18 17 16 15 14 13
NC NO NC NO NC NO
36 34 32 22 20 24 18 16 30 28 26

2.8 Condenser Trip Device 2.8 콘덴서 트립 장치


It is recommended to employ the capacitor trip unit for a 트립 제어전압을 AC로 사용할 경우 트립 제어용 전압은 정전에 대비하기
trip operation of the breaker when the control source is 위해 일반 정류기를 사용하지 않고 콘덴서 트립 장치를 사용할 수 있습니다.
lost in the AC control system. 보조릴레이 Ry의 접점 B1, B2를 그림과 같이 트립용 푸시버튼 등과 병렬로
The contacts B1, B2 of auxiliary relay are connected with 연결시키면 정전시 차단기를 자동으로 트립시킬 수 있습니다.
tripping push button as shown below. The breaker can be
opened automatically in case of power failure and
terminals 5, 7 can be used as AC power supply connecting
to the motor or closing circuit.

CAUTION 주 의

This device maintains the voltage for 60 seconds 콘덴서 트립 장치는 정전시 차단기를 1회 트립시킬 수 있는
which can trip the breaker just one time. 전압을 60초 동안 유지할 수 있습니다.
It cannot be operated properly if used for other 이 장치를 다른 용도로 사용하거나 회로를 당사의 동의 없이
purposes or if the circuit is modified without the 변경하여 사용할 경우 동작하지 않을 수 있습니다.
agreement of the manufacturer.

� Fig. 2-4 Condenser trip device / 그림 2-4 콘덴서 트립 장치

72 80

1 2 3 4 5 6
CONDENSER TRIP DEVICE
WITH RECTIFIER
2-
∅ 6
22.2
66
72

지연선택 7 8 9 10 11 12

112
90

� Fig. 2-5 Circuit diagram of condenser trip device / 그림 2-5 콘덴서 트립 장치의 전기 회로도

1 6 C.T.D
3 4
7
R1
OPEN�
P/B

CLOSE�
P/B
SA RY R2 R3
1 6 4
SW C1 NL V.C.B
2 7 5
5
2

3 4

>>
진공차단기 취급설명서 9
02 Technical Data 기술적 데이터

2.9 Under Voltage Release (Y7) 2.9 부족전압 Release(Y7)


The UVR (Y7) having a spring-energy storing mechanism, is 스프링 에너지 저장 방식 메커니즘을 가진 부족전압 Release(Y7)은
used for the continous monitoring of circuits, and can open 계통을 연속적으로 감시하여 제어 전압이 Drop-out전압보다 낮으면
the circuit breaker automatically when the control voltage 차단기를 자동 트립시킵니다.
drops lower than the drop-out voltage. 제어전압이 Pick-up 전압보다 높을 경우, 이 Release의 래치 메커니즘이
The latching mechanism of the release can be excited to 여기되어 투입상태를 유지할 수 있습니다.
hold the closing condition of the circuit breaker when the ● Drop-out voltage: 정격전압의 35~60%
control voltage rises above the pick-up voltage. ● Pick-up voltage: 정격전압의 75~85%
● Drop-out voltage: 35~60% of rated control voltage
점검 등을 위해서 필요한 경우, 이 Release의 Lock-screw를
● Pick-up voltage: 75~85% of rated control voltage
그림 2-6과 같이 윗쪽으로 위치시킴으로 차단기가 낮은 전압에서
If it is necessary to lock the automatic tripping function of 트립되지 않도록 할 수 있으며, 그림 2-7과 같이 나사를 아래쪽으로
the release at the lower control voltage, you can place the 위치시키면 Lock기능이 해지됩니다.
lock-screw as shown in Fig. 2-6.
The release can be operated again by shifting the screw
down as shown in Fig. 2-7.

� Fig. 2-6 Locked state / 그림 2-6 잠김 상태 � Fig. 2-7 Unlocked state / 그림 2-7 동작 가능 상태

2.10 2nd Open Solenoid (Y2) 2.10 2차 트립 솔레노이드(Y2)


The 2nd trip solenoid (Y2) can be attached to the HYUNDAI 현대 HVF형 진공차단기는 제1트립 솔레노이드(개극회로, Trip)외에
HVF circuit breaker putting aside the 1st trip solenoid (Y1), 2차 트립 솔레노이드를 추가로 부착하여 차단기를 트립 시킴으로서
so that the circuit breaker can be opened safely. 더 안정된 동작을 추구할 수 있습니다.

2.11 Cutout Switch 2.11 컷아웃 스위치


The cutout switch consists of two limit switches, which are 보조스위치 S1에 준비된 Impulse접점은 차단기의 개폐순간 Close 된 후
connected in series with the impulse contact of the 다시 Open 되는 접점입니다. 이 접점을 이용하여 차단기의 전기적인
auxiliary switch in the alarm circuit. 트립시에 경고음 등을 발생시킬 수 있도록 연결하여 사용할 수 있는
When the VCB is opened locally, the cutout switch 스위치입니다. 리미트 스위치 S6, S7은 차단기의 수동 조작시 신호를
interrupts the tripping signal. 방지하기 위한 것입니다.
�Closing time of impulse contact is more than 10 ms. �impulse 접점의 Close 시간은 10ms 이상임.

2.12 "Closing Spring Charge" Signal 2.12“투입 스프링 차지”신호


Using the auxiliary switches S41, S42 operated by the 차단기의 차지상태에 따라 동작하는 리미트 스위치 S41, S42를 이용하여
closing spring, the spring charged indicator is displayed for 외부에서 스프링 차지 상태를 알 수 있도록 합니다.
visual checking.

10 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series
03 Handling and Installing the Breaker 취급설명

3.1 Unloading and Storage 3.1 운송 및 보관

CAUTION 주 의

Excessive weight will cause the serious injury, 과도한 무게가 나가는 제품은 중상, 재산파괴, 혹은 사망을
property damage, or even death. 일으킵니다.
To avoid this situation, do not transport a circuit 이 상황을 피하기 위해서는 절대로 제품을 높게 들어올린
breaker on a lift truck or other lifting facility in the 상황에서 운반하지 마십시오.
raised position.

When unloading from the vehicle, avoid turning it over. 수송용 차량에서 차단기를 내릴 때는 바른 위치에서 내려오게 하며,
Special care should be taken to avoid shocks. 충격을 주지 마십시오.
If vacuum circuit breakers must be stored prior to use, they 진공 차단기가 설치되기 전에 보관을 해야 한다면, 반드시 건조하고 먼지가
should be stored only in dry, dust-free and well ventilated 없으며 환기가 잘되는 실내장소에 보관하십시오. 이때 차단기는 트립
rooms, with the breakers in the open position and the (OPEN) 상태이며, 스프링은 압축되지 않은 상태이어야 합니다.
stored-energy spring mechanism in the released position.

3.2 Unpacking
When opening the package, also avoid turning it over and 3.2 포장해체
special care should be taken to not damage the breaker. 포장해체시 포장물을 바른 위치에 놓고 차단기에 손상을 주지 않도록
Carefully handle the insulated parts, vacuum interrupters, 주의해야 합니다. 특히 절연물, 진공튜브, Female Contact, Front Cover
main circuit, disconnecting unit, front panel and so on. 에 주의하십시오.

� Fig. 3-1 HVF VCB / 그림 3-1 HVF VCB

Spring Released

VCB Opened

3.3 Inspection After Unpacking


1) Check the type rating and quantities with the 3.3 포장해체 후 점검사항
specification sheet. (1) 포장 List에 따라 형식, 정격, 대수를 확인합니다.
2) Check the circuit breaker for any damage or missing (2) 외관상의 손상, 파손 및 변형을 점검하고, 각 부분의 Bolt들의 이완을
materials 점검합니다.
3) Check all accessories and spares supplied. Also, check to (3) 표준부속품, 예비품이 있을 경우 수량을 점검하고 파손 여부를
see if these parts are damaged. 점검합니다.

3.4 Installation
Before installing the circuit breaker into the switchgear, 3.4 Switchgear에 설치
check the type rating and for any signs of damage again. 차단기를 배전반에 설치 전 차단기의 형식, 정격 및 손상여부를
Wipe the breaker with a dry cloth to remove dirt and dust. 재확인하고, 마른걸레로 먼지 및 더러운 부분을 닦아냅니다.
Mount the draw-out unit (if it is used) on a level floor by 인출형 차단기의 인출입 유니트는 수평상태가 유지되도록 설치되어야 하며,
means of screwing through the mounting holes on the 수평편차가 1mm을 초과할 경우, 깔판 등을 사용하여 수평편차를
bottom. The tolerance on the level should be within 조정하십시오.
1mm. If required, adjust the level using a liner.

>>
진공차단기 취급설명서 11
03 Handling and Installing the Breaker 취급설명

Wipe the connecting surface with a dry cloth to remove dirt 인출형 차단기 설치 후 부스 바(Bus bar) 연결 및 접지 작업을 하며,
and dust before connecting main circuit bus bars and earth 작업시 차단기에 무리한 힘이 가해지지 않도록 주의 하십시오.
terminal, and be careful not to shock the draw-out unit and
breaker.
Note Refer to our catalogue "HVF Vacuum Circuit Breaker" 주의 차단기 type별 인출입 유니트의 Mounting hole 치수, 주회로 접
for mounting hole sizes of the each draw-out unit and 지 단자부의 치수는 당사 카타로그“HVF Vacuum Circuit
earth terminal's size. Breaker”참조하십시오.

DANGER 위 험

Heavy weight! 과도한 무게가 나가는 제품은 중상, 재산파괴, 혹은 사망을 일으킵니다.
Please use lifter to remove or install the breaker in the 차단기를 Switchgear에 넣거나 꺼낼 경우에는 항상 Lifter를 사용
upper position of the switchgear. 하십시오.
Do not stand below the lifted breaker. 들려져있는 차단기의 아래에 서있지 마십시오.

3.5 Inspection Before Operation 3.5 운전 전 점검사항


(1) Check to see if the breaker is installed properly. (1) 차단기가 바르게 설치되었는지 확인합니다
(2) Operate the breaker a few times manually to ensure that (2) 먼저 수동으로 조작하고 이상이 없을시, 제어회로에 전원을 공급하고
the breaker is closed and opened smoothly. Then, operate 동작시킵니다.
the breaker using the motor operating mechanism with (3) 최종 점검을 하고 설치에 사용한 공구, 자재가 남겨져 있는지
the auxiliary power, and check the CLOSE/OPEN indicator 확인합니다.
and charged state of the closing spring. (4) 차단기의 모든 접지부분을 접지합니다.
(3) Check that no tools and materials are left near the breaker.
(4) Ground all possible parts of circuit breaker.

DANGER 위 험

Charged closing or tripping spring can cause 차지된 투입, 트립 스프링은 중상을 일으킬 수 있습니다.
serious injury. 차단기와 관련해 작업을 하시기 전에, 항상 메카니즘 부품의
To avoid this situation, always be attentive to the 빠른 움직임에 주의하십시오.
mechanism of sudden movement before taking any 차단기의 보수, 검사를 하시기 전에 반드시 투입스프링 ⑫의
action on the circuit breaker. Discharge the springs ⑫ 차지를 해제하고 차단기는 트립된 상태에서 해야합니다.
and open the breakers before performing any breaker
maintenance, inspection or repair.

3.6 Manual Operation 3.6 차단기의 수동 조작 설명


(1) Insert the handle-crank in the hole and turn it clockwise 1) 수동핸들을 그림과 같이 차단기 전면 수동핸들용 홀에 넣고 시계방향으로
until the indicator displays spring charged " ". 돌려 스프링이 차지된 후, Spring Charged Indicator가 동작합니다.
(2) Press the "CLOSE" button. Be sure to check that the breaker 2) 투입 버튼을 손으로 누르면 차단기가 투입된 후 CLOSE/OPEN
is closed and the CLOSE/OPEN indicator displays close " I ". Indicator가 동작합니다.
(3) Press the "OPEN" button. And be sure to check that the 3) 다음 트립 버튼을 손으로 누르면 차단기가 트립되고 CLOSE/OPEN
breaker is opened and the CLOSE/OPEN indicator Indicator가 동작합니다.
displays open " " 4) 상시개폐동작을 2~3회 반복하여 차단기의 이상이 없음을 확인합니다.
(4) Finally, check that no tools and materials are left near
the breaker.

� Fig. 3-2 Charging the spring / � Fig. 3-3 Close operation / � Fig. 3-4 Open operation /
그림 3-2 스프링 차지 그림 3-3 Close 동작 그림 3-4 Open 동작

hole for handle


Push the button Push the button

handle-crank

12 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series
04 Structure and Operation 구조 및 동작

4.1 Component List of HVF VCB 4.1 HVF 차단기의 구조 및 부품표

No. Item 항 목

10 Housing Box Fig. 4-1 / 그림 4-1 조작기구부 외함


�⑩
11 Closing Mechanism 투입조작 기구부

12 Closing Spring 투입 스프링


⑪ 35

13 Trip Spring 트립 스프링


� 36

14 Link ⑭ 링크
32
⑫ 33
15 Coupling Bar 커플링 바

34
16 Breaker Shaft 브레이크 샤프트

17 Dash Pot � 데쉬 포트 (완충기)


18 Counter � 카운터

19 CLOSE/OPEN Indicator 31 �⑬⑮ � 개폐 표시기

20 Spring Charged Indicator 스프링 상태 표시기


Fig. 4-2 / 그림 4-2
21 Closing Button 투입버튼

22 Trip Button 트립버튼

23 Name Plate 명판

49
24 Hole for the charging handle 수동 차징핸들용 홀

31 Motor 모터

32 Closing Solenoid 투입 솔레노이드


48
33 Trip Solenoid 23
트립 솔레노이드

34 Limit Switch (S3, S21, S22) 리미트 스위치(S3, S21, S22)

47
35 Anti-Pumping Contact (K1) 재투입 방지 접점(K1)

36 Auxiliary Switch (S1) 보조 스위치(S1)

41 Upper Female Arm Fig. 4-3 / 그림 4-3 상부 접속 연결

42 Lower Female Arm 하부 접속 연결부


45

43 Tulip Contact 접속 단자부 콘택


41
44 Insulation Frame 절연 프레임

45 Insulation Frame Cap 43 절연커버 덮개

46 Rear Silicon Cover 44 후단부 실리콘 절연커버


50
42
47 Truck for moving VCB 차단기 이동장치
46
48 Warning Sticker for Draw-Out 인출입 경고 스티커

49 Front Cover 차단기 전면부 덮개

Vacuum Interruptor covered 진공밸브


50
with the Insulation Frame (절연프레임에 덮혀 있음)

>>
진공차단기 취급설명서 13
04 Structure and Operation 구조 및 동작설명

4.2 Operation Mode 4.2 동작 설명

� Fig. 4-4 / 그림 4-4 항 목

1) Charging 1) 차징
11-1
When the charging mechanism is 수동적인 방법이나 모터(31)에 의해
activated by hand or motor (31), 11-2
Closing Spring(12)이 차지되면,
the charging shaft (11-1) turns by Charging Shaft(11-1)가 Gear나
11-3
the gears and the driver (11-2) so Driver(11-2)에 의해 돌아가서
that the closing spring (12) is 12 투입스프링을 압축합니다.
11
tensioned. When the closing 33
Closing Spring이 완전히 압축되면,
spring is fully tensioned, the Closing Pawl(11-3)은 Closing
31 25-1
closing pawl (11-3) latches Spring이 풀리지 않도록 고정시킵니다.
closing spring . 16

2) Closing
When closing command is Charging 2) 투입
49
applied, the closing spring is 투입지령이 들어오면, Closing Spring이
unlatched by the activation of Closing Pawl에 의해 압축을 풀게
the closing pawl. Through the 됩니다.
energy from the discharging of 이 에너지에 의해 Coupling Bar가
the closing spring, the coupling Charging Shaft와 Cam을 통하여
bar is powerfully pushed down 세게 아래로 내려가게 됩니다.
via the charging shaft and the 결과적으로, Breaker Shaft(16)는
cam. Moving Contact가 완전히 닿을 때까지
Consequently, the breaker shaft 회전하게 되며, Trip Pawl(25-1)에 의해
is turned until the moving 멈춰집니다.
contact is fully closed and 동시에 Contact Pressure Spring(49)은
latched by the trip pawl (25-1). 차단기가 투입상태에서 Moving
At the same time, the contact Closing Contact에 적정 압력을 주기 위해
pressure spring (49) is 알맞게 압축됩니다. Trip Spring(13)은
compressed to insure sufficient Opening 동작을 위해 압축됩니다.
contact pressure on the moving
contact while the breaker is in
the closed position, and the
tripping spring (13) is
compressed for the opening
operation.

3) Recharging 3) 재투입 대기
After the closing operation, the Recharging 투입동작 후에, Closing Spring이
closing spring can be 모터나 수동으로 다시 압축될 수
immediately recharged by a 있습니다. 이는 재투입 지령이 내려오면
motor (31) or hand so that the 다시 재투입하기 위해서 입니다.
breaker immediately re-closes
in case the closing authorization
re-close is applied.

4) Tripping 4) 트립
When opening command is 트립 지령이 내려지면,
applied, the tripping spring is Tripping Spring이 Trip Pawl에 의해
unlatched by the activation of 압축이 풀어지고, Breaker Shaft는
the trip pawl, and the breaker 개극 위치로 돌아오게 됩니다.
shaft is returned to the open
position. Tripping

14 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

4.3 Draw In & Out Operation of HVF VCB 4.3 HVF 차단기의 인출입 방법
HYUNDAI HVF Type Vacuum circuit breakers have several 현대 HVF Type 진공차단기의 인출입 장치는 고객의 요청에 따라
versions of draw-out mechanisms and the breaker types 여러 종류가 제작될 수 있습니다. 항 목

which were produced according to customer requests. The 다음은 당사에서 표준으로 사용하고 있는 모든 방식의 인출 장치에 대한
following procedure is for the circuit breaker of our standard 취급 설명입니다. 표준 Type이 아닌 경우에는 당사로 문의하십시오.
version having worm and wormgear type draw-out
mechanism. For instructions on nonstandard version, please
contact us.

DANGER 위 험

Hazardous High Voltage will cause serious injury, 고전압은 중상, 재산피해, 혹은 사망을 일으킵니다.
property damage, or death. 차단기를 인입, 인출시키기 전에 차단기는 반드시 트립(OPEN)
Before inserting or withdrawing, the breaker should be 상태이고, 인출입 핸들을 돌리기 전에 Interlock lever는
open. Before turning the handle, lift up the interlock 손으로 들어 올려진 상태이어야 합니다.
handle. If excessive power is applied to the handle 차단기가 투입상태이거나 인터록 핸들이 올라가 있지 않았을 때,
when the breaker is closed or the interlock handle is 무리하게 힘을 가하여 돌릴 시에는 제품의 파손을 가져올 수
not lifted up, it can cause damage to the breaker. 있습니다.

Make sure that the breaker and cradle have same 차단기와 크레들의 사양이 일치하는지 반드시 확인하여 주십시오.
rating when inserting and withdrawing the breaker. 크레들과 차단기에 제품의 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached on 반드시 확인 후 사양이 일치하도록 하십시오.
the product.

DANGER 위 험

Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, DO NOT transport the breaker 일으킬 수 있습니다.
on a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고, 절대 차단기
밑에 서있거나 지나가는 일이 없어야 합니다.

4.3.1. ES/FS Type � Fig. 4-5 Insertion of the ES/FS type(1) / 4.3.1. ES/FS Type
1) Check the condition of the breaker. 그림 4-5 ES/FS type VCB 인입방법(1) 1) VCB 상태점검
Check the breaker is opened before 배전반 또는 Cradle에 설치하기 전 VCB가
inserted into the switchgear or cradle. “OPEN”되었는지 반드시 확인하십시오.

2) Insertion to the disconnection position Interlock Lever 2) Disconnection(또는 Test) 위치로 장착


Insert the breaker to the cradle at 차단기를 Cradle의 Disconnection(또는 Test)
disconnection (or test) position. 위치에 밀어 넣습니다. 이때 Interlock Lever를
At this time, push down the interlock 충분히 눌러 삽입이 원활히 이루어 지도록
lever fully for easy insertion. Check that 합니다. 또한, 그림 4-8과 같이 Truck Wheel이
the wheels of the breaker are 정확히 안착되었는지 확인하여야 합니다.
inserted into the cradle as fig 4-8. Wheels of the
breaker
3) Insertion to the connection position 3) Connection 위치로 장착
After checking to see if the breaker is 차단기가 개극 되었는지 확인한 후,
opened at the disconnection position, 수동 인출입 핸들을 삽입하십시오.
� Fig. 4-6 Insertion of the ES/FS type(2) /
insert the crank handle to the hole to Interlock Lever를 충분히 누르고 차단기가
그림 4-6 ES/FS type VCB 삽입방법(2)
draw in and out. Push the interlock down Connection 위치로 이동하도록 인출입 핸들을
a
fully. Then, push up the crank handle to 차단기 방향으로 밀어 삽입합니다.
the breaker so that the breaker moves to 그림 4-6 하부 사진과 같이, 차단기가
the connection position. Crank Handle Connection 위치에 정확히 장착되면
If the breaker is in the connection Interlock Pin이 자동으로 떨어지면서
position as in fig 4-6b, the interlock pin Interlock Lever가 원위치로 복귀합니다.
drops down into the lock hole and 이때 Interlock이 적절히 이루어지면
interlock lever comes back to the initial b Locking 되는 소리(부딪히는 소리)가
position. 발생하오니 반드시 확인하십시오.
At this time, check that interlock pin 또한, Interlock Lever를 2~3회 이상 눌러
Interlock Lever
makes the locking sound 자연스럽게 동작하는지 반드시 확인하십시오.
"knocking or click".
Finally, push the interlock lever times to
check the movement.

>>
진공차단기 취급설명서 15
04 Structure and Operation 구조 및 동작

4) Withdrawing the breaker 4) 차단기의 인출


After checking that the breaker is 차단기가“Open" 상태인지 확인하십시오.
opened, insert the crank handle in the � Fig. 4-7 Withdrawing the ES/FS type / 인출입 핸들을 삽입하고 Interlock lever를
hole and push the interlock lever down 그림 4-7. ES/FS type VCB 인출방법 누르십시오.
fully. 그림 4-7과 같이 인출입 핸들을 차단기와
Then, push the crank handle down 반대 방향으로 누르고, 차단기를 Disconnection
against the breaker so that the breaker 위치로 이동 시킵니다.
goes to the disconnection position.

4.3.2. SF/GS Type 4.3.2. SF/GS Type


� Fig. 4-8 Insertion of the SF/GS type(1) /
1) Check the condition of the breaker 1) VCB 상태점검
그림 4-8. SF/GS type VCB 인입방법(1)
Check the breaker is open before 배전반 또는 Cradle에 설치하기 전 VCB가
inserted to the switchgear or cradle. “Open”되었는지 반드시 확인하십시오.

2) Insertion to the disconnection position 2) Disconnection(또는 Test) 위치로 장착


Insert the breaker to the cradle at 차단기를 Cradle의 Disconnection(또는 Test)
Close button
disconnection (or test) position. 위치에 밀어 넣습니다.
At this time, push down the close button 이때 투입버튼을 눌러 정확한 위치에
fully for the breaker insertion. 삽입되었는지 확인 합니다.
Check that the wheels of the breaker is Sticker 또한, 그림 4-8과 같이 Truck wheel이
exactly inserted to the cradle as in fig 4-8. 정확히 안착되었는지 확인하여야 합니다.

Wheels of the
breaker

DANGER 위 험

Hazardous high voltage will cause serious injury, 고전압은 중상, 재산피해, 혹은 사망을 일으킵니다.
property damage, or even death. 차단기를 인입, 인출시키기 전에 차단기는 반드시 트립(OPEN)
Before inserting or withdrawing, the breaker should be 상태이고, manual locker는 반드시 unlock position에
open, and also before turning the handle, the manual 있어야 합니다.
locker should be in the unlock position. 차단기가 투입상태이거나 manual locker가 unlock 상태가
If excessive power is applied to the handle when the 아닌 상황에서 무리한 힘으로 핸들을 돌리면 제품의 파손을
breaker is closed, it can cause damage to the product. 가져올수 있습니다.

DANGER 위 험

Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, do not transport the breaker on 일으킬 수 있습니다.
a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고,
절대 차단기 밑에 서있거나 지나가는 일이 없어야 합니다.

DANGER 위 험

Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여
same rating when inserting and withdrawing the 주십시오.
breaker. 크레들과 차단기에 제품 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached to 반드시 확인후 사양이 일치하도록 하십시오.
the product.

16 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

3) Insertion to the connection position 3) Connection 위치로 장착


After checking to see if the breaker is 차단기가 개극 되었는지 확인한 후,
opened at the disconnection position, � Fig. 4-9 Insertion of the SF/GS type(2) / 수동 인출입 핸들을 삽입하십시오.
insert the crank handle to the hole to 그림 4-9. SF/GS type VCB 인입방법(2) 시계방향으로 약 40~50회 핸들을 돌리면
draw in and out. After rotating handle Connection 위치로 이동합니다.
about 40~50 times clockwise, the breaker 이때, Cradle 바닥면에 부착된 스티커를
goes to the connection position. 확인하고, 투입버튼을 눌러 정확한 위치에
At this time, check the sticker at the 삽입되었는지 확인 합니다.
cradle base and push the close button for 차단기가 충분히 삽입되어도 별도의 소리가
VCB insertion. 나지 않으므로 무리한 힘으로 회전을
The circuit breakers does not make any 시키지 않습니다.
rattling noise so the operate does not
have to rotate the crank with force.

Sticker

4) Withdrawing the breaker � Fig. 4-10 Withdrawing the SF/GS type / 4) 차단기의 인출
After checking that the breaker is 그림 4-10. SF/GS type VCB 인출방법 차단기가“OPEN”상태인지 확인하십시오.
opened, insert the crank handle in the 인출입 핸들을 삽입하고 반시계방향으로
hole to draw in and out. 약 50회 돌려 차단기를 Disconnection 위치로
Rotate handle about 50 times 이동 시킵니다.
counterclockwise. 가운데 핸들을 잡아당기면 Interlock이
If operator pulls the center handle out, 해제 되면서 차단기를 Cradle로부터 완전히
interlock will be released and the breaker 분리시킬 수 있습니다.
will be fully separated from cradle.
Center
Handle

DANGER 위 험

Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, do not transport the breaker on 일으킬 수 있습니다.
a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고,
절대 차단기 밑에 서있거나 지나가는 일이 없어야 합니다.

DANGER 위 험

Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여
same rating when inserting and withdrawing the 주십시오.
breaker. 크레들과 차단기에 제품 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached to 반드시 확인후 사양이 일치하도록 하십시오.
the product.

>>
진공차단기 취급설명서 17
04 Structure and Operation 구조 및 동작

4.3.3. Special GS Type 4.3.3. 특수형 GS Type


1) Check the condition of the breaker 1) VCB 상태점검
Check the breaker is opened before � Fig. 4-11 Insertion of the special GS type(1) /
배전반 또는 Cradle에 설치하기 전 VCB가
그림 4-11. Special GS type VCB 인입방법(1)
inserting into the switchgear or cradle. “OPEN”되었는지 반드시 확인하십시오.

2) Insertion into the disconnection position 2) Disconnection(또는 Test) 위치로 장착


After lifting the center handle, the 가운데 핸들을 들어올리고 Locking 소리가
operator can push the breaker to the 날 때까지 차단기를 밀어 넣습니다.
cradle until it makes a locked sound.

3) Insertion into the connection position 3) Connection 위치로 장착


Same as the SF/GS type method. SF/GS Type과 동일한 방법으로 인입을
시도합니다.

4) Withdrawing the breaker 4) 차단기의 인출


After checking that the breaker is Center Handle 차단기가“OPEN" 상태인지 확인하십시오.
opened, insert the crank handle in the 인출입 핸들을 삽입하고 반시계방향으로
hole to draw in and out. � Fig. 4-11 Withdrawing of the special GS type(2)/ 약 40~50회 돌려 차단기를 Disconnection
After rotating handle about 40~50 times 그림 4-11. Special GS type VCB 인출방법(2) 위치로 이동 시킵니다.
counterclockwise the operator can pull 가운데 핸들을 위로 올리면 Interlock이
the center handle out. 해제되면서 차단기를 Cradle로부터
Interlock will be released and the breaker 완전히 분리시킬 수 있습니다.
will be fully separated from the cradle.

DANGER 위 험

Excessive weight can cause serious injury or 과도한 무게가 나가는 제품은 심각한 인명 피해, 기타 사고를
damage. 일으킬 수 있습니다.
To avoid this situation, do not transport the breaker 높게 올려진 상태에서 차단기를 이동하지 마시고, 절대 차단기
on a lifting facility in the raised position 밑에 서있거나 지나가는 일이 없어야 합니다.

DANGER 위 험

Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여 주십시오.
same rating when inserting and withdrawing the 크레들과 차단기에 제품 사양이 표시되어 있습니다.
breaker. 반드시 확인 후 사양이 일치하도록 하십시오.
The sticker and name plate with rating are attached to
the product.

4.3.4. MS Type � Fig. 4-12 Front view of MS Type VCB/Cradle / 4.3.4. MS Type
1) Checking before inserting the breaker in 그림 4-12. MS Type VCB/Cradle 정면사진 1) 설치전 VCB 상태 확인
to the switchgear 크래들이나 배전반에 차단기를 설치하기 전에
Before putting the breaker into the cradle 차단기의 상태는 다음과 같이 되어야 합니다.
or switchgear, check whether all parts of - 개폐 표시기 : "OPEN"
the breaker are in the right position as - 위치 표시기 :“DISCONNECTION"
follows. - Manual locker : UNLOCK 상태
- CLOSE/OPEN indicator :
displays "OPEN"
- Position indicator:
displays "DISCONNECTION"
- Manual locker :
in "UNLOCK" position

18 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

2) Inserting into the disconnection position 2) Disconnection 위치로 장착


Put the breaker to the switchgear or 차단기를 배전반이나 크래들 위에 놓고
cradle and push it slowly until it stops. � Fig. 4-13 Side view of MA type VCB /
멈출 때까지 천천히 밉니다. 차단기가 멈추면,
When it stops, set the manual lock handle 그림 4-13. MS type VCB 측면사진
manual lock handle을 LOCK 위치로 놓습니다.
to the LOCK position. This is the 이 위치가 disconnection 위치입니다.
disconnection position.
3) Connection 위치로 인입
3) Inserting into the connection position Disconnection 위치에서 차단기가
After checking that the breaker is open in OPEN 상태임을 다시 한번 확인 후,
the disconnection position, insert the 인출입용 핸들을 the Head of the Fixing Screw
handle into the head of the fixing screw 에 넣고 시계방향으로 돌리면 차단기가
and turn it in a clockwise direction so that connection 위치로 이동하게 됩니다.
the breaker moves to the connection 차단기가 connection 위치에 도달하게 되면,
position. 위치 표시기는“CONNECTION” 을 표시합니다.
When the breaker is in the connection
position check that the position indicator 4) 차단기의 인출
displays "CONNECTION." 우선 차단기를 OPEN시킨 후 인출입용 핸들을
the head of the fixing screw에 넣고 반시계
4) Withdrawing the breaker 방향을 돌리면 차단기가 인출을 하기 시작합니다.
First of all, open the breaker and put the 차단기가 Disconnection 위치에 오면
handle into the head of the fixing screw 위치 표시기는“DISCONNECTION” 를 표시합니다.
and turn in a anticlockwise direction to 차단기를 크레들이나 배전반에서 완전히
withdraw the breaker. 인출시키기 위해서는 Manual Locker를
The position indicator will display UNLOCK위치에 놓고 차단기를 서서히 꺼냅니다.
"DISCONNECTION" when the breaker
reaches the disconnection position.
To withdraw the breaker fully from the
cradle, put the manual locker to the
unlock state and pull the breaker out
slowly.

� Fig. 4-14 Set the breaker on the switchgear or cradle / � Fig. 4-15 Lock state in the disconnection position /
그림 4-14. 배전반이나 크레들에 차단기 올리기 그림 4-15. Disconnection 위치에서 Lock 상태

Position Indicator

Head of the
fixing screw
Manual Locker

Unlock Position Lock Position

CAUTION The Head of Fixing Screw 주 의

Improper operation of the breaker can 차단기를 올바르게 조작하지 않을 시에는 제품의
cause product damage. 파손을 일으킬 수 있습니다.
The breaker can be withdrawn if the head 인입을 완료한 후 Head of fixing screw의 모양이
of the fixing screw isn't inserted in the 바르지 않으면 차단기가 인출될 우려가 있습니다.
proper position. 또한 인출을 완료 후 Disconnection위치에서
Also, after withdrawing the breaker into the Head of fixing screw의 모양이 바르지 않으면,
disconnection position, the head of the Manual locker가 Unlock이 되지 않아 차단기를
fixing screw must be in the proper position. 배전반이나 Cradle에서 분리시킬 수 없습니다.
Otherwise the manual locker cannot move 올바른 차단기의 동작을 위해 Head of fixing
to the unlock position. screw부분을 항상 바르게 하십시오.
Always check the location of fixing screw
for precise operation of the breaker.

>>
진공차단기 취급설명서 19
05 Maintenance and Inspection 보수∙점검

HYUNDAI HVF Vacuum Circuit Breakers require little 현대 HVF 진공차단기는 견고한 기구부를 가지고 있어 유지 보수가 매우
maintenance because of their simplified operating 간단합니다.
mechanisms and robust construction. 보다 신뢰성 있는 사용을 위해 정상 동작 중 마모나 노화가 될 수 있는
In fact, only the parts subject to normal wear and aging 부품에 대해서만 약간의 유지 보수가 필요한 정도입니다.
need be serviced to ensure fully reliable service. 유지 보수의 범위 및 점검 기간은 차단기의 상태, 주위환경 등 다음 사항에
The interval at which these jobs should be carried out and 따라 변할 수 있습니다.
the amount of work involved depend upon �단락전류 차단 횟수
�The number of short circuit interruptions �개폐 횟수
�The switching frequency �실사용 기간
�The actual service time �주위 환경
�Environmental conditions

The service intervals indicated below are only approximate 아래에 나타낸 점검주기는 대략적인 것이며, 특별한 동작이나 환경에 따라
and should be adjusted to suit particular operation or 변할 수 있습니다.
environmental conditions. 정상적인 동작상태에서 진공밸브는 유지보수가 필요없습니다.
Under normal conditions the vacuum interrupters need not
be serviced.

CAUTION 주 의

Failure to maintain the equipment could result in 부적절한 유지보수는 치명적인 인명피해, 재산손실과 제품의 오
death, serious injury or product failure and can 동작을 일으킬 수 있습니다.
prevent successful functioning of the connected 차단기를 "CONNECTION" 위치에서는 작업하지 마십시오.
apparatus. 스프링이 차지되었거나, 투입위치에서는 작업하지 마십시오.
Do not work on a breaker in the "CONNECTION" position. 차단기 주위에 공구를 놓아두지 마십시오.
Do not work on a breaker with springs charged or 보수 작업시에는 반드시 모든 제어전원은 공급되어서는
contacts closed. 안됩니다.
Do not leave maintenance tools around the breaker.
While the work is in progress, all auxiliary voltage
sources must also be disconnected.

5.1 Visual Inspection 5.1 외관 점검


The purpose of visual inspection is to check the exterior of 외관 점검은 차단기의 운전 상태에서 외관의 이상 유무를 수시로 점검하는
the breaker in usual operation. Once a year, a general 것입니다. 특히 먼지가 많은 곳에서 사용시에는 매년 절연물 등에 먼지의
visual inspection is to be carried out. The outer insulation 부착 상태를 점검하여 이를 청소해야 합니다.
parts should be wiped with a rag more frequently if the 표 5-1은 외관 점검사항을 나타냅니다.
breakers are exposed to dust.

� Table 5-1 The visual inspection list / 표 5-1 외관 점검사항


Inspection Description 검 사 내 용

CLOSE/OPEN 지시계가 제대로 작동하는지 검사한다.


Check if CLOSE/OPEN indicator is normal
Circuit 차단기 주위 먼지나 습기 등의 여부를 검사한다.
Check for the presence of dust or moisture 차단기
breaker 차단기 주의 이상한 소리, 냄새, 변색 등의
Check for unusual noise, smell or discoloration
여부를 검사한다.

Check inside of the switchgear for normal


Temperature temperature.
온도상승 스위치기어(Switchgear) 내부온도가 정상적인지 검사한다.
rise Check main-circuit terminals for discoloration
or traces of overheating.

Control Check the operating voltage and the control


제어전압 전압계를 이용하여 조작전압과 제어전압을 검사한다.
voltage voltage with voltmeter.

20 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

5.2 Periodical Inspection 5.2 정기 점검


Periodical inspection is generally made once every 3 years 정기점검은 차단기의 동작조건에 따라 다르지만, 일반적으로 3년에 한번씩
though it depends on the operating conditions of the circuit 해야합니다.
breaker. 동작 메카니즘은 매 3년마다, 혹은 5,000회 CLOSE/OPEN 동작 후에는
The operating mechanisms should be oiled and lubricated 특정 부위에 윤활유를 발라주고, 주유해야 합니다.
in specific parts or every 3 years or after 5,000 break 표2는 정기점검사항과 점검 주기를 나타냅니다.
operations. Table 2 shows items and intervals of the
periodical inspection.

� Table 5-2 The lists and interval of the periodical inspection / 표 5-2 정기검사항목과 검사사항
Inspection Interval 검사 간격
Description 검사사항
items remark 항목 비고
1. Clean the insulated surface with a 1. 절연물이나 절연체의 표면에 있는 먼지나 습기를
dry cloth to remove dust and
마른 천으로 닦아 깨끗이 합니다.
moisture.

2. Check the exterior for damage. 2. 외부 파손 여부를 검사하십시오.



General 3. Check for loose bolts and nuts in 반 3. 작동 메커니즘 부위 및 외부에 있는 볼트나
the operating mechanism and the 3 years 매 3년
check 사 너트가 느슨해지지 않았는지 점검합니다.
external parts.

4. Check stop ring and stop retainer 4. 스탑 링(stop ring)과 스탑 리테이너 (stop
for damage. retainer)의 손상 여부를 확인합니다.

5. Check the connections between 5. 터미널과 도체 간의 접속 상태를 점검합니다.


terminals and conducts.

1. Operate a few times manually and 1. 전기적∙수동적으로 몇 차례의 동작으로 이상


electrically and check each part for 2,000 여부를 확인하며, 또한 각 부품들이 올바르게
proper function. operations 동작하는지 점검합니다.
동 매 2,000회
or 10
Operation 2. Check CLOSE/OPEN indicator and 작 2. CLOSE/OPEN 지시계나 카운터가 올바르게 동작시,
operations
test counter. 시 동작하는지 점검합니다. 혹은 매 단락
of short
험 10회 차단시
3. Check the compressed length of circuit
3. 접촉압력 스프링의 수축 거리가 부록의
contact press spring according to currents
appendix. 표시된 값이 되는지 확인합니다.

1. Measure insulation resistance


between phases and between 1. 1000V Megger로 상간, 극대지간의
pole-earth with 1000 V megger, 절연 저항을 측정하여 500MΩ 이하로 나오면
if the measured value is less than 절 원인분석이 필요 합니다.
Insulation 500 MΩ, check the cause. 연
3 years 매 3년
resistance 2. Check insulation resistance 저
between control circuit and earth 항 2. 500V Megger로 제어회로 간의 절연 저항을
500V megger.If the measured 측정하여 2MΩ이하로 나오면 원인분석이
value is less than 2MΩ, 필요합니다.
check the cause.

Withstand 1. Test the breaker with power 내전압 1. 부록에 표시된 전압으로 상용주파 내전압 시험을
withstand voltage test according 3 years 매 3년
voltage test 시험 합니다.
to appendix.

1. Lubricate each part of operating 1. 동작 각 부위에 주유를 합니다.


mechanism.
3 years 매 3년, 혹은
주 2. 터미널 도체를 마른 천으로 깨끗이 닦아내고
Lubrication 2. Clean disconnection unit with a or 5,000 매 5,000회
유 적은 양의 도전성 그리스를 바릅니다.
dry cloth and a small amount of operations 동작시
grease (conductive grease: lithium (도전성 그리스(grease) :
soap-based grease). Lithium soap-based grease)

1. Check for contact erosion. 1. 접점 마모 정도를 확인하십시오.


(In closed condition, VI should be 진 차단기가 투입된 상태에서 VI Stem의 White
replaced if half of the white mark is
Vacuum 10,000 공 Mark가 1/2정도 보이면 교체해야 합니다.) 매 10,000회
visible.)
interrupter operations 밸 동작시
2. With the circuit opened, check 브 2. 차단기가 개극된 상태에서 Vacuum Checker를
vacuum degree. 이용하여 진공도를 점검하십시오.

�Check the grease condition and lubricate every 3 year or 5,000 operations �윤활유는 외부먼지에 의해 경화될 수 있으므로 매 3년 및 5,000회
because the grease harden. 동작마다 주유상태를 확인하시어 추가적으로 주유를 하십시오.

>>
진공차단기 취급설명서 21
05 Maintenance and Inspection 보수∙점검

5.3 Contact Erosion 5.3 접점 마모 한계


In case of the HVF VCB, the Vacuum Interrupters are HVF VCB는 진공밸브가 절연 프레임 안에 설치되어 있어 깨끗하게
covered with the insulation frame so they remain clean and 유지되므로 사용기간 동안 별도 보수가 필요하지 않습니다.
require no maintenance.

� Fig. 5-1 Structure of the insulation frame / 그림 5-1 절연 프레임 구조

5.4 Trouble Shooting Guide 5.4 문제 해결 가이드

� Table 5-3 / 표 5-3

Symptom / 증상 Cause / 원인 Action / 조치

Motor switch off Check the Cable of Motor Line 모터 케이블 결선 확인

No control power Breaker in Disconnection Position 차단기가 Disconnection 위치


Breaker will not CHARGE
스프링이 차지가 되지 않음
Motor will not run Replace the Motor 모터 교체

Spring charged Check the Spring Charge Indicator 스프링 상태 표시기 점검

Closing spring not


Charge Closing Spring 투입 스프링을 차지시킴
charged

Breaker closed Check the CLOSE/OPEN Indicator 개폐 표시기 점검


Breaker will not CLOSE
차단기가 투입되지 않음 Breaker is not in Set to the Disconnect, Test or Disconnect, Test 또는
proper position Connect Position Connection에 차단기를 위치시킴
Verify Control Power Available 제어전원 확인,
No electrical close signal
Check Close Solenoid 투입 솔레노이드 확인

Breaker open Check the CLOSE/OPEN Indicator 개폐 표시기 점검


Breaker will not OPEN
차단기가 개극되지 않음 Verify Control Power Available 제어전원 확인,
No electrical open signal
Check the Open Solenoid 투입 솔레노이드 확인

22 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

5.5 Lubrication 5.5 주유

� Fig. 5-2 Lubrication points / 그림 5-2 주유위치

Lubrication of the operating mechanism is necessary only 동작 메커니즘의 주유는 매 3년, 혹은 5,000회의 CLOSE/OPEN
every 3 years or every 5,000 operating cycles. 동작 후에 필요합니다.
In general, the circuit breaker requires only moderate 일반적으로 차단기는 주기적인 간격으로 조금의 주유를 필요로 하며,
lubrication at regular intervals and all excess must be 많이 주유가 되었을 때는 깨끗한 천으로 닦아서
removed with a clean cloth to prevent any accumulation of 그곳에 습기나 먼지가 축적되는 일을 막아야 합니다.
dust or dirt. Avoid any lubricant on insulation or other 주유시는 절연부위나 전기적인 부위는 피하십시오.
electrical parts. 움직이는 부위는 주유 후에 동작시킴으로서 주유가 골고루 퍼지게 하고,
Moving parts should then be moved slightly to let the 차단기를 수동으로 몇 회 동작하십시오. 사용되어지는 그리스는
grease penetrate and become properly distributed. Shell Albania NO.2를 추천합니다.
Now operate the breaker several times manually. 주유해야 할 부위는 그림 5-2에 나타내었습니다.
Our recommended grease for lubrication is
Shell Albania No. 2.
The points to be lubricated inside the mechanism housing
are shown in Fig. 5-2.

>>
진공차단기 취급설명서 23
Appendix 부록

Appendix. Basic Specification of HVF VCB Series 부록. HVF 진공차단기 기본사양

Power Frequency Control Circuit Withstand Compressed Length of


Standard Withstand Voltage Voltage VI GAP Contact Sp.
Type VI Type
사용규격 상용주파 내전압 보조회로 내전압 (± 2mm) Contact SP.
(kV/1min) (kV/1min) 압축거리(mm)

HVF1141/2 IEC62271-100 20 2 HVS01725 12 4~7

HVF1151/2 IEC62271-100 20 2 HVS01745 10 4~7

HVF1154 IEC62271-100 20 2 HVS01745 10 4~7

HVF1162 IEC62271-100 20 2 HVS01746 10 4~7

HVF1164 IEC62271-100 20 2 HVS01746 10 4~7

HVF1167 IEC62271-100 20 2 HVS01746 12 4~7

HVF1168 IEC62271-100 20 2 HVS01753 12 4~7

HVF1172 IEC62271-100 20 2 HVS01753 12 4~7

HVF1177 IEC62271-100 20 2 HVS01753 12 4~7

HVF1178 IEC62271-100 20 2 HVS01753 12 4~7

HVF2141/2 IEC62271-100 28 2 HVS01726 12 4~7

HVF2151/2 IEC62271-100 28 2 HVS01745 10 4~7

HVF2154 IEC62271-100 28 2 HVS01745 10 4~7

HVF2162 IEC62271-100 28 2 HVS01746 10 4~7

HVF2164 IEC62271-100 28 2 HVS01746 10 4~7

HVF2167 IEC62271-100 28 2 HVS01747 12 4~7

HVF2168 IEC62271-100 28 2 HVS01753 12 4~7

HVF2172 IEC62271-100 28 2 HVS01753 12 4~7

HVF2177 IEC62271-100 28 2 HVS01753 12 4~7

HVF2178 IEC62271-100 28 2 HVS01753 12 4~7

HVF3141/2 IEC62271-100 38 2 HVS01726 12 4~7

HVF3151/2 IEC62271-100 38 2 HVS01745 10 4~7

HVF3154 IEC62271-100 38 2 HVS01745 10 4~7

HVF3156 IEC62271-100 38 2 HVS01745 10 4~7

HVF3162 IEC62271-100 38 2 HVS01746 10 4~7

HVF3164 IEC62271-100 38 2 HVS01746 10 4~7

HVF3167 IEC62271-100 38 2 HVS01747 10 4~7

24 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

Appendix. Basic Specification of HVF VCB Series 부록. HVF 진공차단기 기본사양

Power Frequency Control Circuit Withstand Compressed Length of


Standard Withstand Voltage Voltage VI GAP Contact Sp.
Type VI Type
사용규격 상용주파 내전압 보조회로 내전압 (± 2mm) Contact SP.
(kV/1min) (kV/1min) 압축거리(mm)

HVF3168 IEC62271-100 38 2 HVS01753 10 4~7

HVF6111/2 IEC62271-100 50 2 HVS02421 13 4~7

HVF6141/2 IEC62271-100 50 2 HVS02421 13 4~7

HVF6144 IEC62271-100 50 2 HVS02421 13 4~7

HVF6146/7 IEC62271-100 50 2 HVS02435 13 4~7

HVF7142 IEC62271-100 70 2 HVS03626 20 4~7

HVF7144 IEC62271-100 70 2 HVS03626 20 4~7

HVF7052 IEC62271-100 70 2 HVS03640 20 4~7

HVF7054 IEC62271-100 70 2 HVS03640 20 4~7

HVF7057 IEC62271-100 70 2 HVS03640 20 4~7

HVF1372 ANSI C37 19 2 HVS01750 12 4~7

HVF1374 ANSI C37 19 2 HVS01750 12 4~7

HVF3362 ANSI C37 36 2 HVS01750 12 4~7

HVF3364 ANSI C37 36 2 HVS01746 12 4~7

HVF7052 ANSI C37 80 2 HVS03640 20 4~7

HVF7054 ANSI C37 80 2 HVS03640 20 4~7

HVF7057 ANSI C37 80 2 HVS03640 20 4~7

HVF7062 ANSI C37 80 2 HVS03642 20 4~7

HVF7064 ANSI C37 80 2 HVS03642 20 4~7

HVF7067 ANSI C37 80 2 HVS03642 20 4~7

>>
진공차단기 취급설명서 25
Maintenance Recording 보수 점검

Maintenance Recording Sheet 보수 점검표

Date The Substance of Service Service Agent Engineer Cost/Free Remarks Signature
일자 수리 내역 수리처 기사 성명 유상/무상 비고 서명

26 << Vacuum Circuit Breaker Instruction Manual


VCB | HVF Series

Memo

>>
진공차단기 취급설명서 27
HHIS-WZ-LKE-053-00, 2010. 8 Designed by ADPARK
www.hyundai-elec.com

Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea 본 사 울산광역시 동구 전하동 1번지


Tel. 82-52-202-8101~8 Fax. 82-52-202-8100
설계: TEL. (052)202-8452~7 FAX. (052)202-8450
Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea A/S: TEL. (052)202-8474 FAX. (052)202-8450
(Sales & Marketing) Tel. 82-2-746-7510, 8519 Fax. 82-2-746-7647 울산영업: TEL. (052)202-8101~8 FAX. (052)202-8100
Orlando 4700 Millenia Blvd., Suite 370, Orlando,
Florida 32839, U.S.A. 서울사무소 서울특별시 종로구 계동 140-2번지 현대B/D
Tel. 1-407-249-7350 Fax. 1-407-275-4940 (산전기기영업) TEL. (02)746-7446, 7498, 8410 FAX. (02)746-7647
New Jersey 300 Sylvan Avenue, Englewood Cliffs, NJ, 07632, U.S.A. A / S 센 터 인천광역시 중구 항동 7가 104-2번지
Tel. 1-201-816-0286 Fax. 1-201-816-4083 TEL. (032)888-4483 FAX. (032)881-0086
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove,
London, W6 0LG, UK 부 산 지 사 부산광역시 동구 수정동 3번지 우리아비바생명B/D 12층
Tel. 44-20-8741-0501 Fax. 44-20-8741-5620 TEL. (051)463-4382 FAX. (051)463-8843
Tokyo 8th Fl., Yurakucho Denki Bldg., 1-7-1, Yuraku-cho, 광 주 지 사 광주광역시 서구 농성동 415-12번지 현대B/D(별관) 3층
Chiyoda-gu, Tokyo, 100-0006, Japan TEL. (062)368-9097 FAX. (062)366-9097
Tel. 81-3-3212-2076, 3215-7159 Fax. 81-3-3211-2093
Osaka l-Room 5th Fl., Nagahori-Plaza Bldg., 2-4-8, Minami Senba, 대 구 지 사 대구광역시 수성구 범어2동 223-5번지 동일산업B/D 6층
Chuo-ku, Osaka, 542-0081, Japan TEL. (053)746-0555, 1530 FAX. (053)746-0557
Tel. 81-6-6261-5766, 5767 Fax. 81-6-6261-5818
창 원 지 사 경상남도 창원시 신촌동 20번지 현대자동차B/D 3층
Dubai 205, Building 4, Emaar Square, Sheikh Zayed Road, TEL. (055)286-4351 FAX. (055)286-4350
Pobox 252458, Dubai, UAE
Tel. 971-4-425-7995 Fax. 971-4-425-7996 대 전 지 점 대전광역시 동구 성남동 503-2번지 현대자동차B/D 3층
Sofia 1271, Sofia 41, Rojen Blvd., Bulgaria TEL. (042)622-4100 FAX. (042)625-4175
Tel. 359-2-803-3200, 3220 Fax. 359-2-803-3203
Yangzhong No. 9 Xiandai Road, Xinba Scientific and Technologic Zone,
Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel. 86-511-8842-0666, 0212 Fax. 86-511-8842-0668, 0231
HHIS-WZ-LE-013-01 2002.8 Printed by designtomato
HiAN Series
Air Circuit Breakers
Instruction Manual

HEAVY INDUSTRIES CO., LTD.


www.hhi.co.kr
ELECTRO ELECTRIC SYSTEMS

HEAD OFFICE 1 JEONHA-DONG, DONG-GU, ULSAN, KOREA


TEL. 82-52-230-8101~8 FAX. 82-52-230-8100
Notice
SEOUL HYUNDAI B/D, 140-2, GYE-DONG, JONGNO-GU, SEOUL, KOREA
TEL. 82-2-746-7522, 7589 FAX. 82-2-746-7648 Read and understand these instructions before attempting any
unpacking, assembly, operation or maintenance of the circuit
ORLANDO 3452 LAKE LYNDA DRIVE, SUITE 110, ORLANDO, FLORIDA, 32817 U.S.A. breaker.
TEL. 1-407-249-7350 FAX. 1-407-275-4940
This instruction manual should be applied only to HiAN
LONDON 11TH FL., ST. MARTIN’S HOUSE 1 HAMMERSMITH GROVE, LONDON W6 ONB, U.K. air circuit breakers.
TEL. 44-20-8600-7127 FAX. 44-20-8741-5620 This instruction booklet does not include all items regarding
TOKYO 8TH FL. YURAKUCHO DENKI BLDG.1-7-1, YURAKU-CHO, CHIYODA-GU, TOKYO, JAPAN 100-0006 installation and maintenance procedures.
TEL. 81-3-3212-2076, 3215-7159 FAX. 81-3-3211-2093 For more information, please contact HYUNDAI Heavy Industries
Co., Ltd. or one of our partners.
CAIRO APARTMENT NO. 503, 5TH FL., BLDG. NO. 7 BLOCK 2, 9TH DIVISION, EL-NASR ROAD, NEW MAADI, CAIRO, EGYPT
TEL. 20-2-520-0148~9 FAX. 20-2-754-7528 This instruction manual is changable without any pre-notice
for the quality upgrade.
SOFIA 41, ROJEN BLDG., 1271 SOFIA BULGARIA
TEL. 359-2-938-1068, 936-0300 FAX. 359-2-936-0742
These specification are subject to change without notice. HEAVY INDUSTRIES CO.,LTD.
ACB | HiAN Series

For operational safety of Air Circuit Breakers

Safety Notices Operation Precautions


Thank you for purchasing a HHI’s Air Circuit Breaker.
These safety notices are followed by important safety information. Never touch live terminal parts.
Be sure to read these notices, the product instruction manual, and other associated documents accompanying the product Otherwise, electric shock may occur.
thoroughly to familiarize yourself with product handling, safety information and all other precautions before installing, Do not leave the ACB in the draw-out position.
The ACB is heavy. Dropping the ACB could cause serious injury.
operating, or inspecting the product.
The safety notices are divided into “DANGER” and “CAUTION” according to the hazard level:

Signal Signal Words If the ACB trips open automatically, remove the cause before closing the ACB.
Otherwise, a fire could occur.
A danger notice with this symbol indicates that neglecting the suggested procedure or practice could
For the ACB with the fixing block, be sure to loosen the block screws before drawing out the ACB.
be fatal or result in serious personal injury.
Otherwise, damage to the ACB may occur.

A caution notice with this symbol indicates that neglecting the suggested procedure or practice could
result in moderate to slight personal injury and/or property damage.
Note that failing to observe caution notices could result in serious injury/damage in some OCR Field Test Precautions
situations.
Because safety notices contain important information, be sure to read and observe them.
OCR field test must be performed by competent persons.
Never touch live terminal parts.
Otherwise, electric shock may occur.

Transportation Precaution

Never enter the area under the Air Circuit Breaker (ACB) when it is lifted or Maintenance and Inspection Precautions
suspended using a lifter or chain block. The ACB may suddenly drop.
The ACB is heavy. Entering such an area could cause serious injury.
ACB maintenance, inspection and/or parts replacement must be performed by competent persons.
Prior to commencing any work on the ACB, open an upstream breaker or the like to isolate all
sources of power/voltage from both the primary and auxiliary circuits.
Otherwise, electric shock may occur.
Prior to commencing ACB internal inspection, make sure that the ACB is open and the closing
Installation Precautions
spring is released.
Otherwise, fingers or tools could be pinched in the internal mechanism, causing an injury.
Installation work must be performed by competent persons. Retighten the terminal screws periodically to the specified torque.
Prior to commencing any installation work, open an upstream circuit breaker or the like to isolate Otherwise, a fire could occur.
all sources of power/voltage. Retighten the arcing contact mounting screws periodically to the specified torque.
Otherwise, electric shock may occur. Otherwise, a fire or malfunction could occur.
Tighten terminal screws securely to the specified torque. Be sure to reinstall the arc chute if removed.
Otherwise, a fire may occur. Failure to do so or incorrect installation of the arc chute may result in a fire and cause burns.
Fix the ACB (draw-out cradle) firmly on a flat lever surface using mounting screws. Do not touch ACB live parts (contacts in particular), or structural parts close to a live part,
Otherwise, draw-out operation may cause the ACB to fall. immediately after opening the ACB to stop supplying power.
Avoid blocking the arc gas vents of the ACB to ensure adequate arc space (insulation distance). Otherwise, remaining heat may cause burns.
Blocking the vents could result in failure of ACB tripping. Do not bring your hand or face close to the arc gas vent of the arc chute while the ACB is closed
Do not place the ACB in such an area that is subject to high temperature, high humidity, dusty air, or opened.
corrosive gas, strong vibration and shock, or other unusual conditions. Otherwise, burns may result from high-temperature arc gas blowing out of the arc gas vent.
Mounting in such areas could cause a fire, non-tripping, or malfunction.
Be careful to prevent foreign objects (debris, concrete powder, iron powder, etc.) and rainwater
from entering the ACB.
These materials inside the ACB could cause a fire or non-tripping.
For the ACB with four poles, connect the neutral wire of a 3-phase, 4-wire cable to the
N-phase pole (on the right end).
Otherwise, an overcurrent may cause non-tripping and a fire.

2 << Air Circuit Breakers Instruction Manual >>


3
ACB | HiAN Series

Contents 01 Receiving and Handling

1. Receiving and Handling Upon receipt of your breaker, check the following.
1.1 Storage 5 If you have any questions or any problems, contact our agent nearest you.
1.2 Directions for Transportation 5 HiAN Series Air Circuit Breakers are completely assembled, inspected and tested both electrically and mechanically at the
factory, then shipped in fully guaranteed conditions in construction and operation.
2. Description of Various Parts 6

3. Operation
3.1 Manual Charging Type 7 1.1 Storage
3.2 Motor Charging Type 8 While it is recommended that the breaker be used as soon as you have received it, you may find it necessary to store the
breaker for some time before its installation. If so, please note the following for proper storage:
4. Draw-Out Mechanism 1) Store the breaker in a dry indoor location to prevent condensation due to a sudden change in temperature,
4.1 Moving the Breaker Body within Draw-Out Cradle 10 which is quite harmful to the breaker insulation.
4.2 Putting the Breaker Body Back into Draw-Out Cradle 11 2) Store the breaker in a clean place free of corrosive gases, dirt and dust.
In particular, a mixture of cement dust and moisture can cause corrosion in the various metal parts of the breaker.
5. Periodic Inspection and Parts Replacement Fully protect the breaker from such mixtures.
5.1 Arc Chamber 14 3) Place the breaker on a flat, level surface in its normal position.
5.2 Contacts 14 4) Do not place the breaker directly on the floor.
5.3 Operating Mechanism 16
5.4 Internal Accessories 17
1) Shunt Trip Device (SHT) 18
2) Undervoltage Trip Device (UVT) 19 1.2 Directions for Transportation
3) Latch Release Coil Device (LRC) 20 When transporting the breaker from one place to another, note the following:
4) Auxiliary Switch Unit 21
5) Motor Unit 22 1) When lifting up the breaker, apply wire ropes to the lifting plates (Fig. 1 ).
6) Direction of ACB Position Padlock Device 22 Take necessary care to ensure that the tightened wire ropes may not touch the arc chambers and
multi-protective device (Fig. 1 ).
6. Over-Current Protective Device When lifting up the breaker, be sure to lift it up slowly.
6.1 Base Current [I ] of APR Multifunction Protective Device Type
0 25 2) Lower the breaker onto a flat, level surface.
6.2 Protective Functions and Setting Ranges of APR Multifunction Protective Device Type 25 3) Avoid impacts and shocks to the breaker during transportation
6.3 APR Characteristic Curve 27
6.4 Method of Changing Protective Function Settings 28
6.5 Operation Indication Functions of APR Multifunctions Protective Device Type 30
6.6 Field Test Method of APR Multifunction Protective Device Type 31
6.7 Configuration of APR Tester 32
6.8 Characteristic Check Method for Each Protective Function 35
6.9 General Directions for Testing at Primary Current Levels 37
6.10 Instruction Manual of APR-1D-GM Type 38

7. Insulation Resistance Test and Dielectric Withstand Test


7.1 Main Circuit 42
7.2 Control Circuit (to earth) 42

8. Troubleshooting Points 43

4 << Air Circuit Breakers Instruction Manual >>


5
ACB | HiAN Series

02 Description of Various Parts 03 Operation

HiAN series Air Circuit Breakers are available either in manual charging type or in motor charging type.
Fig. 1 Description of Various Parts

3.1 Manual Charging Type


In the manual charging type, charging the closing springs and open-close control of the breaker
are all done manually. The breaker is able to close only when the closing springs are charged.

Do not force down the charging handle after completion of charging.


Doing so may cause a malfunction.

1) Spring Charging Operation


Follow the procedure given below to charge the closing springs.
Pump the charging handle (about 4~5 cycles)(Fig. 2)
When the closing springs are fully charged, a metallic “click” will be heard and no further pumping of the charging handle
will be possible. When the charging handle is pumped with its maximum stroke (approx. 105°), about four pumping cycles
will complete the charging. Check that the spring charged indicator (Fig. 3 ) now shows “CHARGED”.

2) Closing Operation
Before closing the breaker, check the following items:
Closing springs should be charged.
The shutter of the draw-out handle insertion hole (Fig. 3 ) should be completely closed.
Specified voltage should be applied to the undervoltage trip device (option).
See the description of the undervoltage trip device for the procedure in detail.

Upon satisfactory confirmation of the above items, press the PUSH TO CLOSE button (Fig. 3 ).
The breaker is closed. The CLOSE-OPEN indicator (Fig. 3 ) shows “CLOSED”, and the spring charged indicator (Fig. 3 )
shows “DISCHARGED”.

3) Opening Operation
Press the PUSH TO OPEN button (Fig. 3 ) This opens the breaker, and the CLOSE-OPEN indicator (Fig. 3 ) shows “OPEN”.

Fig. 2 Fig. 3 Front view of breaker

Draw-out cradle Type APR multifunction protective device (optional)


Name plate Charging handle
Front cover Disconnect device for control circuit (body side)
Close/open indicator Disconnect device for control circuit (cradle side)
Charge/discharge indicator Hole for lifting lug
Close button Draw-out handle Close/open indicator
Open button Key-lock device (optional) Charge/discharge indicator
ACB dragger for draw-out Handle clip Push to close button
Position indicator Draw-out handle insertion hole shutter Push to open button
Fixing blocks Position indicator
Draw-out handle insertion
hole shutter

6 << Air Circuit Breakers Instruction Manual >>


7
ACB | HiAN Series

03 Operation 04 Draw-Out Mechanism

3.2 Motor Charging Type The draw-out mechanism permits one to draw out and remove the breaker body from the draw-out cradle and to put the
In this type, a motor-operated mechanism automatically charges the closing springs. breaker body back into the cradle, which facilitates the inspection and parts replacement.
Means for remote electrical close-open control of the breaker are also fitted. The draw-out mechanism permits one to move the breaker body to any of the following three positions in the draw-out cradle.
Complete manual operations are also possible for the same procedures described in above Manual Charging Type section. The switchboard panel door can be shut with the breaker body drawn out to the TEST or ISOLATED position.
The auxiliary switch assembly mounted on the body works in the CONN, TEST and ISOLATED positions.

1) Spring Charging Operation


Supply the specified control power voltage to the charging motor circuit. OPERATIONAL PRECAUTIONS
In case of AC MOTOR, check whether the UVT is applied to specified voltage.
As soon as the closing springs are discharged, the charging motor is turned on to charge the closing springs. Open the breaker before working with the draw-out mechanism.
Be sure to loosen the screws of the fixing blocks (Fig. 1 )before drawing out the breaker body.
The charging motor is automatically stopped when the closing springs are fully charged, and the spring charged indicator
if provided otherwise, a malfunction may occur.
(Fig. 3 ) shows “CHARGED”. When you try to move the breaker body to the CONN position, the operating force will increase.
While the charging time varies depending on the rated control voltage and the type of breaker, it is normally within a range Further rotate the draw-out handle to move the breaker body to the CONN position. Typical operating force is about 25 kgf.
of 3 to 10 seconds. When the breaker is in connect position, stop turning the draw-out handle.
Otherwise, a malfunction may occur.
Make sure the shutter (Fig. 1 ) is closed after the draw-out handle is removed.
The permissible control voltage range for the charging motor is 85 to 110% of the rated voltage. Only at the exact position (ISOLATED, TEST, CONN) the shutter (Fig. 1 ) can be closed.
It is strongly recommended to supply the control power at the rated voltage.
When dielectric withstand voltage test is carried out, the dielectric withstand voltage of motor
for DC, AC110 and 220 V is 1500 V but motor for DC24 and 48 V is 500 V.

In this position, the main circuit and the control circuits (of the breaker) are connected to the external
CONN POSITION
circuits for normal service.
2) Closing Operation
Before closing the breaker, check the following items:
In this position, the main circuit is isolated, and the control circuits are connected.
Closing springs are charged. TEST POSITION
This position permits close-open test, control circuit function test, etc.
The shutter of the draw-out handle insertion hole (Fig. 3 ) is completely closed.
Specified voltage is applied to the undervoltage trip device (option).
In this position, the main circuit and the control circuits are isolated.
Upon satisfactory confirmation of the above items, press the CLOSE button. ISOLATED POSITION
The breaker is completely de-energized in this position.
This energizes the latch release coil, which, in turn, releases the charged closing springs and the breaker is immediately closed.
The spring charged indicator shows DISCHARGED”.
With the closing springs discharged the charging motor is immediately turned to charge the closing springs. CONN POSITION TEST POSITION ISOLATED POSITION

Even when item 2) is not satisfied, the breaker will not be placed in a closed state.
Be sure to perform closing operation according item 2).

3) Opening Operation
The shunt trip device (SHT) or undervoltage trip device (UVT) is used for remote electrical opening operation.
Press the OPEN button. This opens the breaker via the SHT or UVT.

When close-open operations are repeated with the charging motor ON, limit the number of successive
close-open cycles to 10 times. If the open-close cycle is repeated more than 10 times, allow a cooling
period of at least 10 minutes between the 10th cycle and the 11th cycle.

8 << Air Circuit Breakers Instruction Manual >>


9
ACB | HiAN Series

04 Draw-Out Mechanism

4.1 Moving the Breaker Body Within Draw-out Cradle 3) Further Withdrawal and Removal of Breaker Body from ISOLATED Position
The draw-out handle (Fig. 4 ) is used to move the breaker body to one of the three positions (CONN, TEST, and ISOLATED) The breaker body may be further drawn out from the ISOLATED position to remove it from the draw-out cradle for
in the draw-out cradle. Attached draw-out handle (installed externally to the breaker) is to be used. inspection, maintenance or parts replacement purposes.
If the breaker is in charged condition, perform close-open operation once, and release the closing spring.
Slowly draw out the breaker body from the draw-out cradle until the draw-out dragger stops (Fig. 1 )
When the fixing blocks (optional) are fitted, be sure to loosen the right and left screws of the fixing
blocks before drawing out the breaker body.
Otherwise, a malfunction may occur.
Do not leave the breaker body as it is. When the above operation is made in as-received condition to
separate the breaker body from the cradle, take necessary measures to prevent the possible turnover
due to a change in the center of gravity.

1) Moving to TEST Position


When the fixing blocks are fitted, loosen and free the right and left screws.
Lift the breaker body’s front part to release stopper and pull out again.
Check that the breaker is OPEN. If it is CLOSED, press the PUSH TO OPEN button (Fig. 4 ) to open the breaker.

Fig. 4
Never enter under the breaker.
The breaker weight will cause serious injuries in the event that it drops.
This process should be performed slowly.
At this process, be sure to install crane or rope to breaker’s body.

Charge / discharge indicator


Draw-out handle
Position indicator 4.2 Putting the Breaker Body Back into Draw-out Cradle
Close-open indicator
Follow the procedure given below to put the removed breaker body back into the draw-out cradle.
Push to open button
Draw-out handle insertion
Check that the breaker is OPEN, then check that the position indicator (Fig. 4 ) showing “ISOLATED.”
Shutter of the draw-out Check that the spring charged indicator (Fig. 4 ) shows “DISCHARGED”, indicating the closing springs are discharged.
handle insertion hole

Fig. 5

Press the PUSH TO OPEN button and open the shutter of the draw-out handle insertion hole (Fig. 4 ) at the same time.
Engage the draw-out handle with the draw-out mechanism shaft and turn the handle counterclockwise to move the
breaker body. The position indicator moves to the test position.

When the draw-out handle is inserted in the draw-out mechanism shaft, the breaker is prevented
from being closed. For close-open test, remove the draw-out handle and close the shutter of the
draw-out handle insertion hole. (Fig. 4

2) Moving to ISOLATED Position


Press the PUSH TO OPEN button and open the shutter of the draw-out handle insertion hole (Fig. 4 ) at the same time.
The breaker body has been drawn out to the TEST position.
Turn the draw-out handle counterclockwise to move the breaker body. The position indicator (Fig. 4 )
now shows “ISOLATED”.

10 << Air Circuit Breakers Instruction Manual >>


11
ACB | HiAN Series

04 Draw-Out Mechanism 05 Periodic Inspection and Parts Replacement

Lift up the breaker body or use a special lifter. Attach the body extention rail to roller of the cradle and push in the breaker Frequency of Periodic Inspection
body slightly, at this time the body coil be stopped by stopper. It is most appropriate that the user works out his or her own inspection plan for the breakers according to the switching
frequency, the values of normal making and breaking currents, the magnitude of fault current interrupted, service conditions
Never enter under the breaker. and environmental conditions.
The breaker weight will cause serious injuries in the event that it drops. Otherwise it is recommended to perform a simplified inspection once every 6 months and a full inspection once a year.
Be sure to draw out the breaker to the ISOLATED position or to remove the breaker body from the draw-out cradle for
inspection or parts replacement purposes.
To release the stopper, lift up the body’s front part and push in again until the extention rails are locked.
This position is “ISOLATED”.
Press the PUSH TO OPEN button and to open the shutter of the draw-out handle insertion hole at the same time,
and engage the draw-out handle with the draw-out mechanism shaft (Fig. 6 ).
Mechanical Durability of the Breaker
Turn the draw-out handle clockwise to send the breaker body into the draw-out cradle.
The following table shows the mechanical durability of the breaker in terms of the number of switching cycles.
The position indicator (Fig. 4 ) now shows “TEST”.
When the breaker switching cycles exceed those shown in the table, the possibility of failure may increase.
Turn the draw-out handle clockwise to send the breaker into the CONN position.
For renewal or thorough inspection of the breaker, contact HHI.
Mating of the primary disconnect device starts just before the CONN position, and the draw-out handle will become heavy,
but continue to turn the handle. When the breaker is sent into the CONN position, further turning effort on the draw-out Frame Size 1600 A or smaller 2000 A or larger
handle will be stopped. No. of switching cycles 10000 5000
The position indicator now shows “CONN”. Remove the draw-out handle (Fig. 6 ).

When you try to move the breaker body to the CONN position, the draw-out handle operating force
will increase. This is because the primary circuit contacts in the breaker begin to close and
Frequency of Periodic Inspection
the insertion friction increases; an increase in handle operating force does not show the CONN While it is most appropriate that the user works out his or her own inspection plan for the breakers according to the
position has been reached, is not a failure sign. Further rotate the draw-out handle 2 or 2.5 switching frequency, the values of normal making and breaking currents, the magnitude of fault current interrupted,
turns to move the breaker body to the CONN position.
service conditions and environmental conditions, it is recommended to perform a simplified inspection
Rely on a change of position indicator in order to check if the intended breaker position is reached.
once every 6 months and a full inspection once a year.
When the handle is locked and impossible to be turned anyway, the breaker has reached the
intended position. Do not force-turn the draw-out handle while it is locked.
Inspection interval based on switching cycles
Doing so may cause a malfunction. Switching Conditions of ACB
Below 630 Frame (A) 1250 Frame (A) - 2500 Frame (A) Over 3200 (A)

Switching operation in the state


When the fixing blocks (Fig. 1 ) are fitted, fully tighten the right and left fixing screws using the draw-out handle. 1000 1000 1000
of nearly no-carrying current

When the breaker is sent into the “CONN” position, remove the draw handle and close the shutter of Switching operation in the rated
1000 500 100
insertion hole after confirming the position indication “CONN”. current region

Switching operation in overload


region (about 2-3 times the 25 25 10
Failing to firmly tighten these screws may cause a breaker malfunction, particularly rated current)
when the breaker is installed in such an area that is subject to strong vibration.
Switching operation in current
Each time Each time Each time
interruption region
Fig. 6

Be sure to draw out the breaker to the ISOLATED position or to remove the breaker body from the
draw-out cradle for inspection or parts replacement purposes.
Make sure that live parts have cooled down before performing inspection work.
Trip button
Shutter of the draw-out
handle insertion hole
Draw-out mechanism shaft
Draw-out handle

12 << Air Circuit Breakers Instruction Manual >>


13
ACB | HiAN Series

05 Periodic Inspection and Parts Replacement

5.1 Arc Chamber 1) Periodic Inspection


Check each arc chamber during the periodic inspection and also after a fault current was interrupted. Arcing Contacts
A cracked arc chamber cover or deionized grid side plate, or a heavy, hard-to-remove molten contact or deionized grid pieces INSPECTION ITEMS METHODS / CRITERIA
inside of the arc chamber, requires replacement of the arc chamber unit.
Check visually.
1) Periodic Inspection Blackening of contact tip surfaces is due to oxidation and subformation,
and will not lead to any problems since it is wiped off in closing operation.
INSPECTION ITEM METHOD / CRITERIA
Contact tip surfaces Remove dirt, dust, grease, etc.
Check visually. Inside must be clean, free of foreign matter and dust. Dress roughened surfaces with fine emery paper (#200).
Dirt, dust, foreign matter
Blow off foreign matter and dust with a jet of compressed air. If thickness of contact tip is reduced to of original value after a number of dressing
operations, replace both the moving and stationary arcing contacts.
Check visually. There should be no cracks or other damage.
Cracks
Replace arc chamber if cracked or damaged.
Check each moving arcing contact for loosening of mounting bolts (Fig. 9).
Mounting conditions Tighten screws as necessary.
2) Removal and Mounting
Check each contact tip pair for proper alignment in the closed position.
Loosen the one-mounting screws captivated on an arc chamber until they are free, then remove the arc chamber & nut.
To mount the arc chamber, set nut & arc chamber in position and tighten the one-mounting screws. Main Contacts
Fig. 7 It the main contacts were toughened wear, clean their surfaces at the time of a periodic inspection.

When dressing contact tips, Be careful so as to not let dust fall into the breaker mechanism.
After dressing, be sure to wipe and clean the tips.

mounting
screw 2) Replacement
Stationary Arcing Contact (see Fig. 8)
Fig. 9

nut

Do not perform on-off operation with the nut installed after removing arc chamber.
Otherwise the nut will slip into contact unit. Mounting bolts

Fix arc chute


5.2 Contacts Stationary arcing contact
The pole contact assemblies are visible and accessible when the arc chutes are removed.
Check them during a periodic inspection and after a short-circuit fault current was interrupted.

Fig. 8 Remove the two mounting screws (Fig. 9) and remove the stationary arcing contact (Fig. 9).
Set a new stationary arcing contact in position and firmly tighten the two mounting screws.

At the time of removing or mounting, must not drop any washer into pole inside.

Fig. 10

Stationary arcing contact


Stationary main contact
Molded base
Moving arc/main contact
Move contact fix base
Crossbar link
Low terminal
Terminal cover

14 << Air Circuit Breakers Instruction Manual >>


15
ACB | HiAN Series

05 Periodic Inspection and Parts Replacement

5.3 Operating Mechanism 5.4 Internal Accessories


Remove the front panel (Fig. 1 ) to gain access to the internal accessories.
Fig. 11
To remove the front panel, remove the two front panel mounting screws.

Safety Precautions:
1) Do not place your finger or a tool in the gap between the PUSH TO CLOSE button
and the CLOSED-OPEN indicator (Fig. 12 ) since this gap is closed when the breaker is closed.
2) Never attempt to put your hand or a tool into the breaker when the closing springs are charged.
Be sure to discharge the closing springs prior to internal inspection.

Fig. 12 Location of internal accessories, motor charging type

Terminal spacer CT Trip latch lever


Up terminal Terminal cover Crossbar unit
Low terminal Closing cam Crossbar support
Arc chute Close link unit Closing spring
Move contact fix base Co-latch Co-latch
Crossbar link Co-trip latch unit Co-indicator
Mold base Co-trip latch unit

1) Periodic Maintenance
Check the operating mechanism in detail to a possible extent. If there are detail parts that seem to require a check
but are hard to check, please contact HHI.

INSPECTION ITEMS METHODS / CRITERIA / DISPOSITIONS LRC (latch release coil) Charging motor
MHT (magnetic hold trigger) Draw-out shaft
Operation Open and close the breaker through manual control to check the mechanical parts for normal operation. Type APR over current release Closed-open indicator
Open lever for draw-out Charged-discharged indicator
Add a small amount of grease to each of the pins, shafts and their bearings. Fixing block Auxiliary switch unit
Lubrication
Avoid excessive oiling as such will result in accumulation of dirt and dust. Shunt trip coil Auxiliary switch fixing bolt

Screws, Bolts Check screws and bolts on each part for signs of loosening. Tighten them if loose.
and Springs Check each spring for proper engagement and damage. Correct problem by repair or replacement.

Dirt and dust Latching parts should be free of dirt and dust. Wipe them with a clean cloth.

16 << Air Circuit Breakers Instruction Manual >>


17
ACB | HiAN Series

05 Periodic Inspection and Parts Replacement

1) Shunt Trip Device (SHT) (2) Replacement of SHT


(1) Periodic Inspection - Take out the breaker body from the draw-out cradle.
- Remove the two wires from the SHT terminals (Fig. 13 ).
RATED VOLTAGE (V) COIL RESISTANCE ( ) - Remove the two support mount screws (Fig. 13 ) and take out the SHT.
- Remove the two mount screws (Fig. 13 ).
421 ~ 480 472
380 ~ 420 352 - After checking the light movement of the moving core of new SHT, mount it in the breaker as it was.
AC
180 ~ 250 101 At mounting, be sure to confirm the trip lever (Fig. 13 ) as it was.
100 ~ 150 25 - Connect the two wires to the SHT terminals (Fig. 13 ).
- Test the SHT both electrically and mechanically for normal operation.
150 ~ 230 161
90 ~ 125 36
DC
48 9.7
24 2.7
2) Undervoltage Trip Device (UVT)
The coil of undervoltage trip device (UVT) uses only DC rating.
This undervoltage trip device includes instantaneous trip type IANS-U and time delay trip type IANS-T having 500 ms and
INSPECTION ITEMS METHODS / CRITERIA / DISPOSITIONS 1 sec time delay characteristics.

Push the moving core of SHT with a pointed tool, such as screwdriver tip, then slowly release the core.
(1) General View of Undervoltage Trip Device
The result is acceptable if the core returns lightly.
Slowly push in the moving core after closing the breaker.
Operation Fig. 14 UVT Control Device
The result is acceptable if breaker trips open.
If the breaker trips open at less than 70% of the rated voltage after closing the breaker,
the result is acceptable.

Measure the coil resistance with an ohmmeter.


Coil
If it is much lower than the value shown in Table or there is no continuity, replace the SHT.

UVT controller
Terminals and Check terminals and mounting screws for loosening.
UVT control device mounting
Mounting Screws Tighten them if loose.
bolt (3-M6 x 10)
Wire terminals (fasten terminal)

Fig. 13

(2) Periodic Inspection

INSPECTION ITEMS METHODS / CRITERIA / DISPOSITIONS

Shunt (SHT) The breaker is trip-free when the UVT is de-energized.


SHT support Because of this, when the PUSH TO CLOSE button is depressed, the closing springs are discharged,
Dish screw M4 for mounting (2EA) but if the breaker is not closed, the result is acceptable.
Charging handle Operation
If the breaker can be closed at more than 85% of the rated voltage, the result is acceptable.
SHT terminal If the breaker can be tripped at 70 to 35% of the rated voltage after
Dish screw M5 for SHT closing breaker, the result is acceptable.
Trip lever
Rated Voltage (V) Coil Resistance (ohms)
Measure the coil resistance with an ohmmeter.
Coil Resistance If the measured resistance is much lower than the value 100 - 470 V AC
shown in the right or there is no continuity, replace the UVT. 160 16
100 - 200 V DC

Terminals and Check terminals and mounting screws for loosening.


Mounting Screws Retighten them if loose.

18 << Air Circuit Breakers Instruction Manual >>


19
ACB | HiAN Series

05 Periodic Inspection and Parts Replacement

(3) Replacement of UVT (3) Replacement of LRC


When it is necessary to replace the UVT, replace the whole UVT unit. - Remove the wires from the LRC terminals (Fig. 15 ).
- Remove the UVT coil and the wire terminal (Fig. 14 . - Remove one M4 LRC mounting screw (Fig. 16 ), and take out the LRC from the breaker body.
- Remove two UVT control device mounting bolt (Fig. 14 M6 10). Take out the UVT controller. - After checking the light movement of the new LRC moving core, mount it in the breaker as it was.
- Install UVT control device as it was on the breaker with UVT mounting screws (Fig. 14 ). - Connect the wires to the LRC terminals (Fig. 15 ).
- Connect the wire terminals with fasten terminals at the same time. - Test the device both electrically and mechanically for normal operation in the same manner described in periodic inspection table.
- Test the UVT both electrically and mechanically for normal operation in the same manner.
Fig. 16

Never apply voltage to the UVT terminals Nos.”9” and ”10”. when the UVT function is locked.
Doing so may cause burn-out of the equipment.
Never loosen nor tighten the ADJ nut.
Doing so may cause a malfunction.

Dish screw M4 for mounting


3) Latch Release Coil Device (LRC)
Terminal
(1) General View of Latch Release Device

Fig. 15
4) Auxiliary Switch Unit
(1) Replacement of Auxiliary Switch Unit (See Fig. 17)
The auxiliary switch unit is an assembly of 10 switch elements (4 a-contacts and 4 b-contacts).
Replace the whole switch unit even if a defect is partial.
- Remove the M5 bolt and remove the auxiliary switch unit with wiring.
- Remove the two M4 R/H auxiliary bolts which hold auxiliary switches in line.
- Replace the fault auxiliary switch.
Yoke
- Fix it again as it was.
Yoke mounting screw
Moving core - Check the switch movement.
Coil (2) Periodic Inspection
Terminal
INSPECTION ITEMS METHODS / CRITERIA
Take the breaker body out of the draw-out cradle.
Connect the ohmmeter or alarm (buzzer) to each switch element.
Operation
Check that a-contact is ON and b-contact is OFF when breaker is CLOSED, and that a-contact is OFF and
b-contact is ON when breaker is OPEN.
(2) Periodic Inspection
Check each contact for surface roughness (removing laminated phenolics plate from unit permits a visual check of contacts).
Contact Surface
INSPECTION ITEMS METHODS / CRITERIA If contact is excessively worn or rough, replace whole switch unit.

Push the moving core with a pointed tool, such as screwdriver tip, then slowly release the core. Terminals and Check terminals and mounting screws for loosening. Tighten them if loose.
Mounting Screws
The result is acceptable if the core returns lightly.
Operation Charge the closing springs and push the moving core.
The result is acceptable if the closing springs are discharged. Fig. 17 Fig. 18
If the breaker can be closed at 85% of the rated voltage, the result is acceptable.

Measure the coil resistance with an ohmmeter.


Coil Resistance
If it were much lower than the value shown in Table 1 or there is no continuity, replace the LRC.

Terminals and Check terminals and mounting screws for loosening. AUX. SW SUP/A
Mounting Screws Tighten them if they are loose.

Mounting bolt
(2-M4 75L)

AUX. switch

20 << Air Circuit Breakers Instruction Manual >>


21