HVF Type
HVG Type
Ensuring excellent switching capability and
high quality with various advantages
■ Retaining the high dielectric strength with the interrupter of the high vacuum
degree of 10-7mbar.
■ Providing reliable mechanical performance and long-life expectancy with
rigid structure of motor-spring energy stored mechanism.
■ Having excellent breaking capability with the special contact material
designed by the advanced vacuum technology.
■ Having rapid breaking time of 3 cycle.
■ Certified by New IEC publication 62271-100 and other related standards by
HYUNDAI in ISO9001/14001 and OHSAS18001 certified facilities.
HVF
Rigid structure to prove high reliability and long-life expectancy
– Wide 600 / 800mm switchgear available with small size & light weight
– Mechanical endurance of 30,000 operations
– (IEC) 7.2-17.5kV 25-50kA 630-4,000A
24/25.8kV 12.5-31.5kA 630-3,150A
36/40.5kV 25-31.5kA 1,250-3,150A
(ANSI) 4.76kV 50kA 1,200-4,000A
15kV 40kA 1,200-2,000A
38kV 31.5-40kA 1,200-3,000A
HVG
Compact structure to minimize the switchgear dimension
– Wide 600mm switchgear available with small size & light weight
– Mechanical endurance of 20,000 operations
– 7.2kV, 8-25kA, 400-1,250A
C O N T E N T S
Features
HVF type
HVF
◆ With rigid structure and minimized moving parts, HVF breaker operation mechanism features
reduced maintenance requirements providing high reliability and long-life expectancy.
◆ The breakers are more compactly designed in size with high performance vacuum interrupters, which
are made with the special contact material and advanced vacuum technology.
◆ This series are certified by New IEC publication 62271-100, ANSI C37.09 and other domestic standards.
Operating mechanism
<Fig.1> Front view of HVF type
HVF circuit breakers have motor-spring energy stored
mechanisms of a rigid structure. It consists of the
charging mechanism, the closing spring, the trip spring,
the motor, solenoids, auxiliary switches, spring charged Control jack
Shutter
and on/off indicators as shown in Fig.1.
Pole part
Manual
Depending on the intended protection functions, the Charging hole
operating mechanism can be supplemented by 2nd shunt Charged/ FS cradle
Discharged
release, under voltage release, lockout relay, cut-out indicator Close button
switch, limit switch, electrical local closing and so on. Close/Open Housing box
indicator
Open button
Cycle counter
The released closing spring is automatically recharged Name plate
Pole part
The pole parts are placed on the rear side of the Frame cap
operating mechanism. The internal parts of the pole are Upper pole support
well enclosed by the tubular type insulation frame as
shown in Fig.2. Vacuum interrupter
This prevents dust on the internal insulation material (Inside)
HVG type
HVG
◆ HVG Vacuum circuit-breakers are very compact, so it is possible to reduce the switchgear size
and to minimize its insulation space.
◆ This type of circuit breaker has a compact structure, which can be easily maintained, so it
requires minimal maintenance.
Operating mechanism
HVG vacuum circuit breakers have the simplified motor <Fig.3> Front view of HVG type
spring energy stored mechanism which consists of the
closing spring, the motor, link mechanisms solenoids,
Pole part
auxiliary switches and indicators as shown in Fig.3.
Pole part
Insulation frame
The pole parts are mounted on the rear side of the
Upper terminal
operating mechanism in the insulation frame.
Vacuum interrupter
Dash pot
The current conducting path consists of the plug-in
contacts, terminals, the vacuum interrupter and the Break shaft
flexible terminal.
VCB
6◀
Ratings
HVF
Model 1) HVF114 HVF115 HVF116 HVF117 HVF214 HVF215 HVF216 HVF217
Frequency (Hz) 50 / 60
4,000 4,000
tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
250 250
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) Power-frequency withstand voltage 42kV is available on request.
3) The value is with maintenance, 10,000 times without maintenance.
Vacuum Circuit Breaker ◀7
HVF
Model 1) HVF314 HVF315 HVF316 HVF611 HVF614 HVF714 HVF705
Frequency (Hz) 50 / 60
3,150
tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
200
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) Power-frequency withstand voltage 65kV is available on request.
3) The value is with maintenance, 10,000 times without maintenance.
VCB
8◀
Ratings
HVF
Model 1) HVF137 HVF336 HVF705 2)
HVF706 HVF105 HVF204 HVF606
Frequency (Hz) 50 / 60
3,150
4)
Rated short-circuit breaking current (kA) 50 40 31.5 40/44 31.5 25 40
Short-time withstand current (kA) 50 (2sec) 40 (2sec) 31.5 (3sec) 40 (3sec) 31.5 (3sec) 25 (3sec) 40 (3sec)
tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
3)
Operating Mechanical operation 10,000 20,000 20,000 30,000 20,000
life (times) Electrical operation 10,000 20,000 Refer to Table 2 (see page 14)
400
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) HVF705 type can be applicable to IEC 62271-100 standard.
3) The value is with maintenance, 10,000 times without maintenance.
4) Rated short-circuit breaking current 44kA is available on request.
Vacuum Circuit Breaker ◀9
HVF
Model 1) HVF224 HVF225 HVF226 HVF611 HVF614 HVF625 HVF725
Frequency (Hz) 50
3,150
Short-time withstand current for 3sec (kA) 25 31.5 40 12.5 25 31.5 31.5
tripping Supply voltage (V) DC48, 110, 125, 220 / AC110, 125, 220
control
Current (A) Refer to Table 3 (see page 15)
2)
Operating Mechanical operation 30,000 20,000
life (times) Electrical operation Refer to Table 2 (see page 14)
175
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) The value is with maintenance, 10,000 times without maintenance.
Vacuum Circuit Breaker ◀ 11
Type of Mounting
Hyundai vacuum circuit breakers offer various solutions for mounting with fixed and draw-out types.
The draw-out type breakers consist of truck, mechanical interlock, control terminal, and various
accessaries.
FS type Draw-out type VCB with FS cradle (Nonmetallic partition with shutter)
SF type Draw-out type VCB with FS cradle with screw type draw-in/out mechanism
GS type Draw-out type VCB with GS cradle (Metallic partition with shutter and bushing)
◆ CO - 15sec - CO
Switching unloaded transformer
◆ O - 0.3sec - CO - 3min - CO
◆ O - 15sec - CO - 3min - CO By the special contact materials, the chopping current of the
(O: Open, C: Close) vacuum circuit breakers is only 4A to 5A, so overvoltage is
limited when transformers are disconnected at no load
Current carring capacity condition.
1 - 630A
2- 1,250A
3 - 1,600A
4 - 2,000A
5 - 2,500A
6 - 3,150A
Vacuum Circuit Breaker ◀ 13
A metal-vapor arc discharge in the vacuum is initiated by If the metal vapor arc discharge can be maintained within a
the current to be interrupted as the contacts open. The certain level, the current is supposed to be chopped prior to
current flows through this metal-vapor plasma until the current zero.
next zero transition.
This chopping current must be controlled in order to
The arc extinguishes in the vicinity of the current zero, and prevent build-up of unduly high overvoltages when inductive
the conductive metal-vapor condenses within a few circuits are switched. The sintered CrCu contact limits the
microseconds on the metal surfaces. chopping current up to 4A to 5A.
As a result, the dielectric strength in the contact gap is
rapidly rebuilt. The geometry and size of the contact are designed
differently according to breaking current and interrupter
The rapid build-up of the dielectric strength at the contact type.
gap enables the arc to be safely extinguished even if contact
separation takes place shortly before a current zero
transition. The maximum arcing time for the last pole to
clear is therefore only up to 15ms.
1
2
5
6
7
10
11
<Table 1> Arc quenching medium
Service Life
HYUNDAI vacuum circuit breaker needs minimum maintenance due to the simple operating
mechanism and robust construction.
Vacuum circuit breaker shall be maintained periodically to ensure the perfect performance during
mechanical and/or electrical lifetime.
Please refer to the instruction manual for the detailed information.
HYUNDAI VCB adopts short-time duty charging motor, Closing solenoid and tripping solenoid operate latching
and the specification is stipulated on Table 3. mechanism for VCB springs, so the VCB can be
Since the motor operating time is short, the maximum controlled remotely.
value and inrush current are disregarded. The specification is mentioned on Table 3.
The solenoids unlatch the closing spring and opening
spring to close and open the VCB, respectively.
Auxiliary contacts
Standard Accessories
HVF type
<Fig.16>
GS cradle ES / FS cradle
Charging handle Control jack lead cable (2.5m, 1.5SQ) Control jack connector for C, D type
for A, B type control jack control jack
HVG type
<Fig.17>
Fixing plate (Fixed type) Control jack lead cable (2.5m, 1.5SQ)
Vacuum Circuit Breaker ◀ 17
Additional Options
HVF type
Mechanism operated cell switches (MOC) Earthing switch operation indicator contact
Additional Options
Vacuum checker
Control Circuits
Optional circuit
Control Circuits
XO
21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14 Y1 S1
A1 62 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1 K1
A2 K1 7
5 53 22 32 42 52
13 21
R S1 S8
A1 S5 21 31 41 51
54 14 22
Y9
22 24 34 44 54
A2
S22 S9
12 14 23 33 43 53
21
S8 S9
11 13
XO
1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43 50 51 39 16 53 54 58 56
※ The state of the breaker: spring released; open; the truck is in the test position
HVF 725
XO
21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14
Y1 S1
62
A1 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1
K1
A2 K1 7
5 53
13 21
R S1
A1 S5
54
Y9 14 22
22 A2
S22
21
XO
1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43
※ The state of the breaker: spring released; open; the truck is in the test position
M1: Motor S9: Aux. switch (working position) S1: Aux. switch
Y1: Tripping solenoid K1: Anti-pumping relay S8: Aux. switch (testing position)
R: Resistor S3, S5, S21, S22: Charging limit switch
X0: Plug connector Y9: Closing solenoid
Detail A
Model A C D E F G J B L K B L P
HVF1141 150 515 230 210 525 447 622 499 40 587 501 50 633
HVF1142 150 515 230 210 525 447 622 499 50 587 501 50 633
HVF1151 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1152 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1154 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF1161 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1162 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF1164 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF1166/7 210 612 245 310 630 450 738 550 90 587 549 90 633
HVF2172 210 667 245 310 734 450 738 - - - 549 50 610
HVF2176 275 831 245 310 788 450 738 - - - 768 109 613
HVF2177 275 831 245 310 788 450 738 - - - 768 109 613
HVF2178 275 831 245 310 788 450 780 - - - 768 109 613
HVF1372 165 535 234 254 645 447 - - - - - - -
HVF2141 150 515 230 210 525 447 622 499 40 587 501 50 633
HVF2141/2 150 515 230 210 525 447 622 499 50 587 501 50 633
HVF2151/2 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF2154 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF2161/2 165 515 234 275 592 447 675 499 50 587 501 50 633
HVF2164 165 515 234 275 592 447 675 499 60 587 501 60 633
HVF2166/7 210 612 245 310 630 450 738 550 90 587 549 90 633
HVF3141 150 510 230 210 525 447 610 499 40 587 501 50 673
HVF3142 150 510 230 210 525 447 610 499 50 587 501 50 673
HVF3151/2 165 515 234 275 592 447 675 499 50 587 501 50 673
HVF3154 165 515 234 275 592 447 675 499 60 587 501 60 673
HVF3161/2 165 515 234 275 592 447 675 499 50 587 501 50 673
HVF3164 165 515 234 275 592 447 675 499 60 587 501 60 673
HVF3166/7 210 610 249 310 630 450 738 550 90 587 549 90 673
HVF3362 254 813 234 275 592 447 - - - - - - -
HVF3364 254 813 235 275 592 447 - - - - - - -
HVF6111 210 560 298 310 688 450 774 550 40 587 549 50 784
HVF6112 210 560 298 310 688 450 774 550 50 587 549 50 784
HVF6141 210 560 298 310 688 450 774 550 40 587 549 50 784
HVF6142 210 560 298 310 688 450 774 550 50 587 549 50 784
HVF6144 210 560 298 310 688 450 774 550 60 587 549 60 784
HVF7142 275 845 457 403 984 595 - - - - 845 50 1007
HVF7144 275 845 457 403 984 595 - - - - 845 60 1007
HVF7146 275 845 457 403 984 595 - - - - 845 90 1007
HVF2241/2 210 588 234 275 582 447 - - - - - - -
HVF2252 210 588 234 275 582 447 - - - - - - -
HVF2254 275 786 249 310 630 447 - - - - - - -
HVF2262 210 588 234 275 582 447 - - - - - - -
HVF2264/6/7 275 786 249 310 630 447 - - - - - - -
HVF7252/4/6/7 300 908 583 533 1102 659 - - - - - - -
※ Dimensions may be revised without notice.
VCB
24 ◀
Dimensions
4-M10
55
80
19
40
60
786
275 275
310
169.6
711.5
80
150.5
490
34
301
34 10
176.3
189
11
112.5
4
57
838 850
376 838
10
220 786
130
94
275 275
A
B
310
780
770
345
126
71
B 35 49
838
850
376 10
838
786
A
275 275
B
310
780
770
345
126
71
B 79 109 109
HVF
(Unit: mm)
(Unit: mm)
Dimensions
W H L A B C D G I J K M N Terminal
Model
HVF1141/2 590 693 830 150 302 245 84 120 80 500 550 60 15 A
HVF1151/2 612 763 830 165 306 310 84 120 80 500 550 60 15 A
HVF1154 642 763 830 170 306 310 84 120 80 500 550 80 20 B
HVF1161/2 612 763 830 170 306 310 84 120 80 500 550 60 15 A
HVF1164 620 763 830 170 306 310 84 120 80 500 550 80 20 B
HVF1166/7 790 819 830 210 321 345 80 120 80 500 650 120 20 C
HVF2141/2 650 693 910 220 302 245 84 200 80 600 600 60 15 A
HVF2151/2 650 763 910 235 306 310 84 200 80 600 600 60 15 A
HVF2154 650 763 910 235 306 310 84 200 80 600 600 80 20 B
HVF2161/2 650 763 910 235 306 310 84 200 80 600 600 60 15 A
HVF2164 650 763 910 235 306 310 84 200 80 600 600 80 20 B
HVF2166/7 790 855 910 210 321 345 80 200 80 600 650 120 20 C
HVF3141/2 700 770 966 220 302 245 84 200 80 600 600 60 15 A
HVF3451/2 700 840 910 235 306 310 84 200 80 600 600 60 15 A
HVF3154 700 840 910 235 306 310 84 200 80 600 600 80 20 B
HVF3161/2 700 840 910 235 306 310 84 200 80 600 600 60 15 A
HVF3164 700 840 910 235 306 310 84 200 80 600 600 80 20 B
HVF6111/2 920 972 940 280(300) 370 345 84 230 100 670 650 60 15 A
HVF6141/2 920 972 940 280(300) 370 345 84 230 100 670 650 60 15 A
HVF6144 920 972 910 300 370 345 84 230 100 670 650 80 20 B
※ Dimensions may be revised without notice.
Vacuum Circuit Breaker ◀ 27
50 85
40
84 20
146
COVER PLATE
(OPTION: CA)
60
150
680 (VCB HEIGHT)
MANUAL CHARGING
210
245
HANDLE
693
150
15
2-
14
319
302
DRAW-OUT HANDLE
195
499
4
80 500
550
590 4- 14 BOTTOM 830
MOUNT HOLE
80 500
40
20
150
400
590
150
14
4- 14 MOUNTING HOLE
29
150 150 590
15
7
210
245
6
693.5
301.5
319
800
914
50 85
84 40
20
COVER PLATE
(OPTION: CA)
60
165
275
310
MANUAL CHARGING
680 (VCB HEIGHT)
HANDLE
763
14
165
2-
15
96
324
DRAW-OUT HANDLE
306
195
4
499 80 500
550 830
612 4- 14 BOTTOM
MOUNT HOLE
< for breakers manufactured before July 31, 2009 >
80 500
40
20
165
400
165
14
7
310
275
763
323.5
306
800
914
50 85
84 40
147
COVER PLATE 20
96
(OPTION: CA)
80
5
40
170
165
15
275
310
MANUAL CHARGING
680 (VCB HEIGHT)
HANDLE
763
165
170
20
4-
14
×
324
DRAW-OUT HANDLE
306
19
4
499 80 500
550 830
642 4- 14 BOTTOM
MOUNT HOLE
HVF1166, 1167
(Unit: mm)
50 85
80 40
153
50
COVER PLATE
120
(OPTION: CB)
210
345
310
775 (VCB HEIGHT)
MANUAL CHARGING
819
HANDLE
210
20
338
321
DRAW-OUT HANDLE 4-
14
195
550 80 500
4
650 830
790 4- 14 BOTTOM
MOUNT HOLE
CON. POSITION
547 (VCB WIDTH)
DIS. POSITION
515
(VCB PHASE TO PHASE)
150 150 10 200 587 (VCB DEPTH)
40
50 85
20
COVER PLATE 84
146
(OPTION: CA)
60
220
MANUAL CHARGING
210
245
680 (VCB HEIGHT)
HANDLE
693
220
15
320
DRAW-OUT HANDLE
302
2-
195
14
4
499 80 600
600 910
650 4- 14 BOTTOM
COVER PLATE
(OPTION: CA)
275
310
680 (VCB HEIGHT)
MANUAL CHARGING
HANDLE
763
A
DRAW-OUT HANDLE
324
306
195
80 600
4
499
910
600
650 4- 14 BOTTOM
MOUNT HOLE
(1250A) 40 (2000A) 40
20 20
60
80
40
235
235
Dimension A
235
235
HVF2152/2162 15mm
2- 4-
14 14
HVF2154/2164 20mm
189
23
120
COVER PLATE
(OPTION: CB)
210
50
310
345
775 (VCB HEIGHT)
855
MANUAL CHARGING
HANDLE
210
20
4-
14
338
321
DRAW-OUT HANDLE
195
120
550 80 600
4
HVF3141, 3142
40
(Unit: mm)
20
60
220
220
2-
14
50 85
223
COVER PLATE
(OPTION: CA)
MANUAL CHARGING
680 (VCB HEIGHT)
210
245
HANDLE
770
15
320
302
DRAW-OUT HANDLE
195
100
80 600
4
499
966
600
4- 14 BOTTOM
700
MOUNT HOLE
50 85
224
84
COVER PLATE
(OPTION: CA)
275
310
680 (VCB HEIGHT)
MANUAL CHARGING
840
HANDLE
A
324
DRAW-OUT HANDLE
306
195
499 80 600
4
600 906
700 4- 14 BOTTOM
MOUNT HOLE (630/1,250A) (2,000A) 40
40 20
20
80
60
40
235
235
Dimension A
HVF3151/3152/3161/3162 15mm
HVF3154/3164 20mm
235
235
2- 4-
14 14
HVF3166, 3167
(Unit: mm)
80
120
COVER PLATE
(OPTION: CB)
210
846 (VCB HEIGHT)
50
310
345
890
MANUAL CHARGING
HANDLE
210
20
4-
14
338
321
DRAW-OUT HANDLE
195
150
550 80 600
4
257
84 20
50 85
271
271
40
80
COVER PLATE
60
300
A
(OPTION: CB)
210
210
345
775 (VCB HEIGHT)
800
972
210
210
MANUAL CHARGING
HANDLE
210
210
300
A
B
271
271
370
DRAW-OUT
HANDLE
2-
126
181
195
14
4-
14
4
Dimension A Dimension B
(E3/F3) (ES/FS)
630/1250A 630/1250A 2000A
100 670
40
14
14 14
40
20
300
300
280
20 20
920
650
80
60
60
920
40 40
280
300
300
4- 14 MOUNTING HOLE
210 210
850 114 40
310
360
972
387.5
362.5
850
1024
40
30
150
400
60
150
2-
14
20
547 (VCB WIDTH)
515 CON. POSITION 4- 14 MOUNTING HOLE
(VCB PHASE TO PHASE) DIS. POSITION
150 150 40 115 587 (VCB DEPTH) 29
50 85
COVER PLATE
15
(OPTION: CA)
7
680 (VCB HEIGHT)
245
6
693.5
MANUAL CHARGING
HANDLE
DRAW-OUT 301.5
HANDLE
825
400
4
499 939
590
40
165
400
60
165
2-
547 (VCB WIDTH) 14
20
515
(VCB PHASE TO PHASE) CON. POSITION 4- 14 MOUNTING HOLE
165 165 DIS. POSITION
40 115 587 (VCB DEPTH)
50 85
147
15
COVER PLATE
(OPTION: CA) 7
310
680 (VCB HEIGHT)
MANUAL CHARGING
6
763
HANDLE
15
306
DRAW-OUT HANDLE
825
4
400
499 939
610
50 85
84 40
147
20
COVER PLATE
(OPTION: CA)
80
170
165
15
5
40
275
310
680 (VCB HEIGHT)
763
165
170
MANUAL CHARGING
HANDLE
20
4-
324
306
14
x1
9
DRAW-OUT HANDLE
4
80 500
499
855
550
642 4- 14 BOTTOM
MOUNT HOLE
HVF1166, 1167
(Unit: mm)
80 40
153
50
COVER PLATE
120
(OPTION: CB)
210
345
310
775 (VCB HEIGHT)
819
210
MANUAL CHARGING
20
HANDLE
338
321
4-
14
195
DRAW-OUT HANDLE
550 80 500
4
650 855
790 4- 14 BOTTOM
MOUNT HOLE
50 85
84
147
COVER PLATE
(OPTION: CA)
680 (VCB HEIGHT)
275
310
763
A
MANUAL CHARGING
HANDLE
140
324
306
DRAW-OUT 120
195
HANDLE
158
499 80 600
4
600 935
650 4- 14 BOTTOM
MOUNT HOLE (630/1,250A) 40 (2,000A)
40
20
60
20
80
40
235
235
Dimension A
235
235
HVF2151/2152/2161/2162 15mm
HVF2154/2164 20mm 2- 4-
14 14
50 85
224
84
COVER PLATE
(OPTION: CA)
680 (VCB HEIGHT)
275
310
840
A
MANUAL CHARGING
HANDLE
324
306
DRAW-OUT
195
HANDLE
499 80 600
4
600 935
700 4- 14 BOTTOM
MOUNT HOLE (1,250A) (2,000A) 40
40 20
20
80
60
40
235
235
Dimension A
235
235
HVF3152/3262 15mm
2- 4-
HVF3154/3164 20mm 14 14
647(VCB WIDTH)
612
515 CON. POSITION
(VCB PHASE TO PHASE)
DIS. POSITION
210 210
35 200 587 (VCB DEPTH)
76
50 85
40
224
23
80
120
COVER PLATE
(OPTION: CB)
50
775 (VCB HEIGHT)
310
345
890
MANUAL CHARGING
HANDLE
210
20
4-
14
338
321
195 150
DRAW-OUT HANDLE
550 80 600
4
50 85
COVER PLATE
(OPTION: CB)
775 (VCB HEIGHT)
345
972
MANUAL CHARGING
HANDLE
370
DRAW-OUT HANDLE
871
4
550 1049
650
920
125 670 2,000A 630/1,250A
40 40
40
30
300
280
650
80
60
280
300
Dimension B
HVF6111/6112/6141/6142 15mm 4-
2-
14
14
HVF6144 20mm 20 20
4- 14 MOUNTING HOLE
Order Information
4 4 4 C P2U4
Motor Closing Tripping Control jack
Code control Code control Code control Code Code Additional options
voltage voltage voltage Auxiliary switch Structure Application
2 DC48V 2 DC48V 2 DC48V A 4NO+4NC Fixed on VCB body P0 Cam for position switch HVF/HVG
3 DC60V 3 DC60V 3 DC60V B 7NO+7NC Fixed on VCB body U ✽ Under voltage release HVF
4 DC110V 4 DC110V 4 DC110V C 4NO+4NC 0.8m cable type R ✽ Second shunt release HVF
5 DC125V 5 DC125V 5 DC125V D 10NO+10NC 0.8m cable type L ✽ Lockout relay HVF
6 DC220V 6 DC220V 6 DC220V X Without control jack V ✽ Varistor module HVF/HVG
7 AC110V 7 AC110V 7 AC110V W Auto jack P21) Position switch HVF/HVG
9 AC220V 9 AC220V 9 AC220V KL1) Position padlock key HVF/HVG
L DC250V L DC250V L DC250V TP2) Trip padlock key HVF
EL Electrical local closing HVF
C0 Cut-out switch HVF
CP Closing padlock key HVF
S1 Spring charged signal (S41) HVF
C1 CT operated release 0.5A HVF
C2 CT operated release 1A HVF
EE Earthing switch operation indicator contact HVF
TC Trip coil supervision signal HVF
E9 BIL 38/95kV for 12kV VCB HVF
CA3) Cover plate / type A4) HVF
CB3) Cover plate / type B5) HVF
ZZ Special application HVF/HVG
※ ✽1: DC24V, 2: DC48V, 3: DC60V, 4: DC110V,
5: DC125V, 6: DC220V, 7: AC110V, 9: AC220V
1) Position switch and position padlock cannot be installed at same time.
2) Key is not supplied.
3) For the space between front cover of breaker and ES/FS/SF cradle.
4) Type A: for 7.2-17.5kV up to 31.5kA 2,000A
5) Type B: for 7.2-17.5kV 40/50kA 2,500-4,000A, 24/36kV
Spare parts for HVG type
Code Name Specification
HAFS-K1 Anti-pumping relay
1: DC24V, 2: DC48V, 3: DC60V
HVGS-M Charging motor
4: DC110V, 5: DC125V, 6: DC220V
HVGS-CS Closing solenoid
7: AC110V, 9: AC220V
HVGS-TS Tripping solenoid
HVFS-T4 Condensor trip device DC110V
HVFS-T6 Condensor trip device DC220V
HVFS-T7 Condensor trip device AC110V
HVFS-T9 Condensor trip device AC220V
HAFS-ASW4 Auxiliary switch 4NO+4NC
HAFS-ASW7 Auxiliary switch 7NO+7NC
HAFS-ASW10 Auxiliary switch 10NO+10NC
HAFS-L/S Limit switch (S1) 1NO+1NC
HVGS-P/S Position switch 1NO+1NC
HVGS-CAM Cam for position switch Attached in breaker body
HVGS-22JACK Control jack 4NO+4NC, fixed type, plug and socket only
HVGS-44JACK Control jack 7NO+7NC, fixed type, plug and socket only
HVGS-PL1099 Plug-in contact 8kA 400A
HVGS-PL1131-41 Plug-in contact 20/25kA 630A
HVGS-PL1011 Plug-in contact 12.5kA 630A
HVGS-PL1132-42 Plug-in contact 20/25kA 1,250A
HVGS-CHANDLE Charging handle
HVGS-DHANDLE Draw-out handle
HVFS-VC9 Vacuum checker AC220V
VCB
54 ◀
Order Information
진공차단기취급설명서
Vacuum Circuit BreakerlInstruction Manual
Notice
Read and understand these instructions before attempting any
unpacking, assembly, operation or maintenance of the circuit
breaker.
This instruction manual should be applied only to HVF Series
Vacuum Circuit Breakers.
This instruction manual does not include all items regarding
installation and maintenance procedures.
For more information, please contact authorized partners.
차단기를 포장해체, 조립, 동작, 유지보수를 하기 전 반드시 본 매뉴얼에
대해 숙지하시기 바랍니다.
본 매뉴얼은 HVF 시리즈 진공차단기에 한해 적용됨을 유의 바랍니다.
또한 본 매뉴얼은 모든 제품에 대한 정보를 포함하고 있지 않습니다.
따라서, 더 많은 정보를 원하실 경우, 현대중공업 또는 영업점으로 문의
바랍니다.
Safety Practices 안전 조항
Safety Practices 안전 조항
This instruction manual applies only to HVF series vacuum 본 취급 설명서는 HVF 시리즈 현대 진공차단기의 운전 및 안전에 관한
circuit breakers regarding installation and maintenance 중요한 내용을 기술하였습니다.
procedures. 제품을 부적절하게 설치하거나 유지∙보수시에는 치명적인 인명피해 및
Installing and maintaining these products IMPROPERLY may 재산 손실이 유발될 수 있으므로 포장해체, 조립, 작동, 혹은 유지∙보수를
result in serious personal injury, property damage, or 하시기 전에, 반드시 이 취급 설명서를 충분히 읽고 이해하시기 바랍니다.
death. Therefore this instruction manual must be read and 설치 및 유지 보수는 유자격자나 전문지식을 보유한 사람이 행하십시오.
understood at every step in unpacking, assembly,
operation, and maintenance of the breaker.
Only qualified persons who are familiar with installing and
maintaining circuit breakers are permitted to work on
breakers, and this instruction manual should be accessible
to those persons at all times.
Signal Words 기호 설명
Signal words used in this instruction manual are 본 취급설명서에서는 안전 주의사항을 위험 정도에 따라『위험』
,『경고』
,
DANGER, WARNING and CAUTION in descending order of 『주의』
로 구분하고 있습니다.
urgency.
Indicates an imminently hazardous situation which, if 회피되지 않으면, 사망 또는 중상을 입을 절박한 위험상태를 나타내며,
ignored, will result in death or serious injury. 가장 위험한 상황입니다.
Indicates a potentially hazardous situation, which, if 회피되지 않으면, 사망 또는 중상을 입을 수 있는 잠재적인 위험상태를
ignored, could result in death or serious injury. 나타냅니다.
Indicates a potentially hazardous situation, which, if 회피되지 않으면, 약한 상해나 경상이 발생할지 모르는 잠재적인 위험상태
ignored, may result in minor or moderate injury. This signal 를 나타냅니다. 또한 이 표시는 불안전한 행동에 대한 경고입니다.
also warns operators to take extra care in their work.
�Do not work on the breaker unless the �설치에 앞서 모든 전원을 차단하기 위해 앞단의
primary circuits are disconnected. 차단기나 그러한 종류의 제품을 반드시 Open
※ There is a damage of electric shock. 시키십시오. 감전의 위험이 있습니다.
�When connecting bus-bars, tighten �단자 Bolt는 표준체결 Torque로 확실하게
bolts using our standards. 조이십시오. 화재의 위험이 있습니다.
�The product should be installed and �본 제품은 수평하고 평평한 면에 단단하게
tighened on the plate area. 취부하여 고정시키십시오.
�Do not install the breaker in areas with �고온, 다습, 분진, 부식성가스, 진동, 충격 등
high temperature, high humidity, dust, 좋지 못한 환경에 설치하지 마십시오.
corrosive or vibrating conditions. 화재, 동작 불량이 발생할 수 있습니다.
�Concrete dust or any other dust should �먼지, 콘크리트 가루, 철분 등의 미물질 및
not be inside the product when it 빗물 등이 본제품의 내부에 들어가지 않도록
installed. It can cause fire or 시공하십시오.
malfunctions. 화재, 동작 불량이 발생할 수 있습니다.
�Connect the control jack tight, �Control Jack에 확실하게 접속하십시오.
otherwise it can cause malfunctions 오동작을 일으킬 수 있습니다.
�Do not touch the main and control �통전되고 있는 주회로 및 제어회로 단자부에는
circuit while the product is in operation. 접촉하지 마십시오.
The hazardous voltage can cause 감전의 위험이 있습니다.
electric shocks. �DISCONNECTION 위치(E, F2급인 경우)나
�Do not let the product stay in the 인출위치에서 UNLOCK 상태(G급인 경우)로
DISCONNECTION position with UNLOCK 제품을 방치하지 마십시오. 제품이 중량물이므
state. 로 낙하시 심각한 사고 및 제품 손상의 위험이
�If the heavy product dropped the 있습니다.
ground, it can cause the serious
accident or product damage.
�Before any maintenance, always open �작업은 앞단의 차단기를 반드시 Open시키고
the breaker and make sure that the 주회로, 제어회로가 모두 충전되어 있지 않은
main and control circuits are not 것을 확인한 후에 행하십시오.
charged. 감전의 위험이 있습니다.
The voltage can be hazardous. �내부 점검은 본 제품이 Open 상태인 것을
�Discharge the springs and open the 확인한 후 행하십시오. 손가락 및 공구가
breakers before performing any breaker 기구부에 끼여 다칠 위험이 있습니다.
maintenance, inspection or repair. �단자 Bolt는 정기적으로 표준 체결 Torque로
Charged closing or tripping spring can 조이십시오.
cause serious injury. Bolt 풀림은 화재 발생의 원인이 됩니다.
�Use the standard pressure torque to �부품의 교체는 반드시 당사 A/S 요원에 의하여
tighten the bolts. Loosening the bolts 작업이 될 수 있도록 하십시오.
can cause fire. �차단기의 개폐수명(당사 Catalogue 참조)을
�Replacing parts should be carried out 초과하여 사용하지 마십시오.
by our service agent.
�The breaker should not be used more
than its life time specified in catalogue.
>>
진공차단기 취급설명서 3
Contents 목차
Safety Practices 2 안전 조항 2
1. Production Scope 5 1. 제작 사양 5
Appendix 24 부록 24
Maintenance Recording 26 보수 점검 26
Rated Breaking Power Freq. Impulse Rated current per distance between phase to phase
상간거리별 정격전류 (A) Applied
Voltage Current Withstand Volt. Withstand Volt.
standard
정격전압 차단전류 상용주파 내전압 임펄스 내전압 630 1250 3150
2000 2500 4000 적용규격
(kV) (kA) (kV, 1 min) (kV) (600) (1200) (3000)
25 HVF1141 C HVF1142 C
25 HVF2141 C HVF2142 C
25 HVF7142 I HVF7144 I
36 70 170
31.5 HVF7052 I HVF7056 I HVF7057 I
A B C D E F G H I J K
130 140 150 165 178 210 250 254 275 300 350
- Type no. suffix in the ���� shall be listed as shown in - “����”안 빈칸은 정격 및 사양에 따라 상이하므로 표를
the column of the rated, specification. 참조하시어 작성바랍니다.
>>
진공차단기 취급설명서 5
02 Technical Data 기술적 데이터
CAUTION 주 의
Consideration of site altitude! 고도에 따른 전압 정정!
If the site altitude is higher than 1000 m, dielectric 1000m 이상에서 사용시에는 공기의 절연내력이 약화되므로
strength of the breaker will be reduced according to 차단기의 상용주파 내전압 및 충격 내전압치를 다음과 같이
the altitude. Therefore, the values of power frequency 보정하여 선택하여야 합니다.
withstand voltage and lightning impulse withstand ≥ 정격전압에 따른 상용주파 및 충격 내전압치 X k
voltage should be selected. (k : 표 3을 참조하십시오.)
≥Rated withstand voltage according to rated voltage
X k (k: Refer to table 2-1.)
For higher humidity, it is required to use a heater in the 습도가 보다 높은 곳에서 사용시는 절연물의 이슬 맺힘 및
switchgear to prevent dewdrops on the insulation 절연 내력 저하를 방지하기 위한 히터를 배전반에 반드시
material and the consecutive decrease in dielectric strength. 설치해야 합니다.
HVF VCB have motor-spring type stored-energy operating HVF VCB는 전동 스프링 방식의 에너지 저장형 기구부를 가지고
mechanism. The closing operation can be done only after 있으므로 투입 스프링이 완전히 차지된 후 투입 동작이 가능합니다.
the closing spring is charged. 표4에서 동작 중 모터의 전류 소비치를 나타내었으며, 돌입전류는
Consumption during the operation is shown in Table 4, and 아주 짧은 시간만 지속하므로 무시될 수 있습니다.
the inrush current may be disregarded since it lasts for only 표준회로 1, 2번 단자에 규정 전압이 인가되면 모터(M1)에 의해 투입
a brief period. 스프링이 인장되어 차지가 완료됩니다. 그리고 LINK에 의해 작동되는
The closing spring is fully tensioned by motor (M1) with the 리미트 위치 S21, S22에 의해 모터의 구동은 정지되고, 그림 1과 같이
rated voltage applied through terminal No.1 & 2 of standard 스프링 표시기는“SPRING CHARGED”
를 표시합니다.
control circuit. Then the limit switch (S21, S22) stops the 차지가 완료된 차단기는“트립-투입-트립”
의 동작을 연속적으로 할 수
motor, and the spring indicator shows "SPRING CHARGED" 있으며 트립 동작 후 지체 없이 다음 투입 및 트립 동작이 가능합니다.
by link activation as shown in Fig.1. The charged VCB can
� Fig. 2-1 State of Spring Charged / 그림 2-1 스프링이 차지된 상태
carry out the open-close-open sequential operation and
also the next close-open operation without delay.
9 11 13 15 17 19 21 23 25 27 29 31 33 35 1 3 5 7 9 11 13 15 17 19 21 23
10 23 21 33 31 43 41 63 51 53 61 73 71 83 81 93 91 103 101 113 111 123 121 73 71 83 81 93 91 103 101 113 111 123 121
S1 S1
19 24 22 34 32 44 42 64 52 54 62 74 72 84 82 94 92 104 102 114 112 124 122 74 72 84 82 94 92 104 102 114 112 124 122
10 12 14 16 18 20 22 24 26 28 30 32 34 36 2 4 6 8 10 12 14 16 18 20 22 24
Standard�
/�표준회로(DC) Extended�
circuit�
/�추가회로
13 21 13
1 S3 T6
S3 S6
S21 14
6
22 14
2 53
61 D1
S1 4
S1 S1
54 Y7
62 T8 D2 U1 Uc1
13
A1 E1
T1
M1 M F1 UVR�CONTROLLER S7
A2 1 E2 14
U2 Uc2
K1 8 1
5 K1 A1 R1 2
A1 13
2 T5 7 Y1 Y2 S41
A2 A2 14
S22 A1 10
1
Y9 R R2 S1
A2 19
T7
K1�CONTACT
X0 2 7 5
R1 Resistor Y4 C.T. operated release Limit switch supplied with the lockout
S5 (Prevents closing by electrical means when
X0 Plug Connector Y7 Under-voltage release
Lock-out effective)
Y9 Closing solenoid S6, S7 Cutout switches
Limit switches
S21, S22
(Interrupt motor circuit after spring charged)
S41, S42 Position switch (spring charged status signal)
Note - Extended circuit spec & connection line number are ※ 주의 - 추가 회로 및 접속은 고객 요구에 따라 변경될 수 있습니다.
defined by user's request. - AC 제어전원에 대해서는 정류기가 추가됩니다.
- For the AC control circuit, the rectifier should be - 추가 회로 요청 시, 표준 접점이 부족할 수도 있습니다.
attached on the standard circuit. - 전기적 Option을 1개 적용 시, A, B Jack은 21, 22번으로
- Standard contacts can be insufficient on the request of 인출을 하고, C, D Jack은 3, 8번으로 인출합니다.
the extended circuit.
- In case of 1 option applied, the numbers are 21, 22 for
A, B Jack and 3, 8 for C, D Jack.
>>
진공차단기 취급설명서 7
02 Technical Data 기술적 데이터
2.4 Interlock Mechanism of the Draw-Out Type Breaker 2.4 인출형 차단기의 인터록 장치
The draw-out type circuit breaker has an interlock 인출형 차단기는 오동작으로 인한 사고를 막기 위해 인터록 장치를
mechanism which prevents trouble due to misoperation. 구비하고 있습니다.
The sensing parts check the position of the circuit breaker 이 장치는 차단기의 위치를 파악하여 차단기가 안전한 위치에 있지
and prevent it from closing if the associated disconnector is 않을 때는 차단기의 투입이 불가능하게 합니다.
not allowed for safe operation.
CAUTION 주 의
2.5 Closing (Y9) and Anti-Pumping (K1) 2.5 투입(Y9)와 재투입방지 회로(K1)
When closing, authorization is applied through terminals 표준회로 6, 7번 단자에 규정 전압의 투입 신호가 인가되면,
6 & 7 Solenoid Y9 fress the closing spring, and thus closes 솔레노이드 Y9가 동작하여 차단기가 전기적으로 투입되게 됩니다.
the circuit breaker electrically. 차단기가 투입되자마자, 보조접점 S1은 투입회로를 개방시키고,
Immediately after the breaker closes, Aux. S/W, S1 opens 리미트스위치 S3과 재투입 방지 릴레이 K1은 연속 투입 지령이
the circuit of closing, and limit switch S3 and anti-pumping 끝날 때가지 Y9가 다시 동작되지 않도록 합니다.
relay K1 switch affect to Y9 so that they can not be 따라서 차단기는 IEC에서 요구하는 재투입 방지와 트립 방지 기능과
reactivated until the continuous closing command is 일치합니다.
interrupted. Thus the breaker can meet the IEC 동시에 Contact Pressure Spring은 차단기가 투입상태에서 진공 밸브의
requirements for anti-pumping and trip-free opeation. 가동접점에 적절한 접촉압력을 유지시키기 위해 압축되며, 트립 스프링도
At the same time, the contact pressure spring is 다음의 개극 동작을 위해 압축되게 됩니다.
compressed properly to maintain sufficient contact
pressure on the moving contact of the vacuum interrupters
while the breaker is in the closed position, and the tripping
spring is compressed for the opening operation.
Fixed Type Control Jack / 고정형 Control Jack(A/B Type) Draw-Out Control Jack / 인출형 Control Jack(C/D Type)
13 11 9 6 4 1 12 11 10 9 7 6 5 4 2 1
MOTOR
CLOSE
OPEN
NC NO CLOSE OPEN MOTOR
NO NC NO NC XA 24 23 22 21 20 19 18 17 16 15 14 13
NC NO NC NO NC NO
14 12 10 23 7 5 2
35 33 31 21 19 17 15 29 27 25 12 11 10 9 8 7 6 5 4 3 2 1
NC NO NC NO NC NO
E.NCE.NO E.NC NO NC NC NO NC E.NO E.NC E.NO XB 24 23 22 21 20 19 18 17 16 15 14 13
NC NO NC NO NC NO
36 34 32 22 20 24 18 16 30 28 26
CAUTION 주 의
This device maintains the voltage for 60 seconds 콘덴서 트립 장치는 정전시 차단기를 1회 트립시킬 수 있는
which can trip the breaker just one time. 전압을 60초 동안 유지할 수 있습니다.
It cannot be operated properly if used for other 이 장치를 다른 용도로 사용하거나 회로를 당사의 동의 없이
purposes or if the circuit is modified without the 변경하여 사용할 경우 동작하지 않을 수 있습니다.
agreement of the manufacturer.
72 80
1 2 3 4 5 6
CONDENSER TRIP DEVICE
WITH RECTIFIER
2-
∅ 6
22.2
66
72
지연선택 7 8 9 10 11 12
112
90
� Fig. 2-5 Circuit diagram of condenser trip device / 그림 2-5 콘덴서 트립 장치의 전기 회로도
1 6 C.T.D
3 4
7
R1
OPEN�
P/B
CLOSE�
P/B
SA RY R2 R3
1 6 4
SW C1 NL V.C.B
2 7 5
5
2
3 4
>>
진공차단기 취급설명서 9
02 Technical Data 기술적 데이터
� Fig. 2-6 Locked state / 그림 2-6 잠김 상태 � Fig. 2-7 Unlocked state / 그림 2-7 동작 가능 상태
CAUTION 주 의
Excessive weight will cause the serious injury, 과도한 무게가 나가는 제품은 중상, 재산파괴, 혹은 사망을
property damage, or even death. 일으킵니다.
To avoid this situation, do not transport a circuit 이 상황을 피하기 위해서는 절대로 제품을 높게 들어올린
breaker on a lift truck or other lifting facility in the 상황에서 운반하지 마십시오.
raised position.
When unloading from the vehicle, avoid turning it over. 수송용 차량에서 차단기를 내릴 때는 바른 위치에서 내려오게 하며,
Special care should be taken to avoid shocks. 충격을 주지 마십시오.
If vacuum circuit breakers must be stored prior to use, they 진공 차단기가 설치되기 전에 보관을 해야 한다면, 반드시 건조하고 먼지가
should be stored only in dry, dust-free and well ventilated 없으며 환기가 잘되는 실내장소에 보관하십시오. 이때 차단기는 트립
rooms, with the breakers in the open position and the (OPEN) 상태이며, 스프링은 압축되지 않은 상태이어야 합니다.
stored-energy spring mechanism in the released position.
3.2 Unpacking
When opening the package, also avoid turning it over and 3.2 포장해체
special care should be taken to not damage the breaker. 포장해체시 포장물을 바른 위치에 놓고 차단기에 손상을 주지 않도록
Carefully handle the insulated parts, vacuum interrupters, 주의해야 합니다. 특히 절연물, 진공튜브, Female Contact, Front Cover
main circuit, disconnecting unit, front panel and so on. 에 주의하십시오.
Spring Released
VCB Opened
3.4 Installation
Before installing the circuit breaker into the switchgear, 3.4 Switchgear에 설치
check the type rating and for any signs of damage again. 차단기를 배전반에 설치 전 차단기의 형식, 정격 및 손상여부를
Wipe the breaker with a dry cloth to remove dirt and dust. 재확인하고, 마른걸레로 먼지 및 더러운 부분을 닦아냅니다.
Mount the draw-out unit (if it is used) on a level floor by 인출형 차단기의 인출입 유니트는 수평상태가 유지되도록 설치되어야 하며,
means of screwing through the mounting holes on the 수평편차가 1mm을 초과할 경우, 깔판 등을 사용하여 수평편차를
bottom. The tolerance on the level should be within 조정하십시오.
1mm. If required, adjust the level using a liner.
>>
진공차단기 취급설명서 11
03 Handling and Installing the Breaker 취급설명
Wipe the connecting surface with a dry cloth to remove dirt 인출형 차단기 설치 후 부스 바(Bus bar) 연결 및 접지 작업을 하며,
and dust before connecting main circuit bus bars and earth 작업시 차단기에 무리한 힘이 가해지지 않도록 주의 하십시오.
terminal, and be careful not to shock the draw-out unit and
breaker.
Note Refer to our catalogue "HVF Vacuum Circuit Breaker" 주의 차단기 type별 인출입 유니트의 Mounting hole 치수, 주회로 접
for mounting hole sizes of the each draw-out unit and 지 단자부의 치수는 당사 카타로그“HVF Vacuum Circuit
earth terminal's size. Breaker”참조하십시오.
DANGER 위 험
Heavy weight! 과도한 무게가 나가는 제품은 중상, 재산파괴, 혹은 사망을 일으킵니다.
Please use lifter to remove or install the breaker in the 차단기를 Switchgear에 넣거나 꺼낼 경우에는 항상 Lifter를 사용
upper position of the switchgear. 하십시오.
Do not stand below the lifted breaker. 들려져있는 차단기의 아래에 서있지 마십시오.
DANGER 위 험
Charged closing or tripping spring can cause 차지된 투입, 트립 스프링은 중상을 일으킬 수 있습니다.
serious injury. 차단기와 관련해 작업을 하시기 전에, 항상 메카니즘 부품의
To avoid this situation, always be attentive to the 빠른 움직임에 주의하십시오.
mechanism of sudden movement before taking any 차단기의 보수, 검사를 하시기 전에 반드시 투입스프링 ⑫의
action on the circuit breaker. Discharge the springs ⑫ 차지를 해제하고 차단기는 트립된 상태에서 해야합니다.
and open the breakers before performing any breaker
maintenance, inspection or repair.
� Fig. 3-2 Charging the spring / � Fig. 3-3 Close operation / � Fig. 3-4 Open operation /
그림 3-2 스프링 차지 그림 3-3 Close 동작 그림 3-4 Open 동작
handle-crank
No. Item 항 목
14 Link ⑭ 링크
32
⑫ 33
15 Coupling Bar 커플링 바
�
34
16 Breaker Shaft 브레이크 샤프트
18 Counter � 카운터
23 Name Plate 명판
49
24 Hole for the charging handle 수동 차징핸들용 홀
31 Motor 모터
47
35 Anti-Pumping Contact (K1) 재투입 방지 접점(K1)
>>
진공차단기 취급설명서 13
04 Structure and Operation 구조 및 동작설명
1) Charging 1) 차징
11-1
When the charging mechanism is 수동적인 방법이나 모터(31)에 의해
activated by hand or motor (31), 11-2
Closing Spring(12)이 차지되면,
the charging shaft (11-1) turns by Charging Shaft(11-1)가 Gear나
11-3
the gears and the driver (11-2) so Driver(11-2)에 의해 돌아가서
that the closing spring (12) is 12 투입스프링을 압축합니다.
11
tensioned. When the closing 33
Closing Spring이 완전히 압축되면,
spring is fully tensioned, the Closing Pawl(11-3)은 Closing
31 25-1
closing pawl (11-3) latches Spring이 풀리지 않도록 고정시킵니다.
closing spring . 16
2) Closing
When closing command is Charging 2) 투입
49
applied, the closing spring is 투입지령이 들어오면, Closing Spring이
unlatched by the activation of Closing Pawl에 의해 압축을 풀게
the closing pawl. Through the 됩니다.
energy from the discharging of 이 에너지에 의해 Coupling Bar가
the closing spring, the coupling Charging Shaft와 Cam을 통하여
bar is powerfully pushed down 세게 아래로 내려가게 됩니다.
via the charging shaft and the 결과적으로, Breaker Shaft(16)는
cam. Moving Contact가 완전히 닿을 때까지
Consequently, the breaker shaft 회전하게 되며, Trip Pawl(25-1)에 의해
is turned until the moving 멈춰집니다.
contact is fully closed and 동시에 Contact Pressure Spring(49)은
latched by the trip pawl (25-1). 차단기가 투입상태에서 Moving
At the same time, the contact Closing Contact에 적정 압력을 주기 위해
pressure spring (49) is 알맞게 압축됩니다. Trip Spring(13)은
compressed to insure sufficient Opening 동작을 위해 압축됩니다.
contact pressure on the moving
contact while the breaker is in
the closed position, and the
tripping spring (13) is
compressed for the opening
operation.
3) Recharging 3) 재투입 대기
After the closing operation, the Recharging 투입동작 후에, Closing Spring이
closing spring can be 모터나 수동으로 다시 압축될 수
immediately recharged by a 있습니다. 이는 재투입 지령이 내려오면
motor (31) or hand so that the 다시 재투입하기 위해서 입니다.
breaker immediately re-closes
in case the closing authorization
re-close is applied.
4) Tripping 4) 트립
When opening command is 트립 지령이 내려지면,
applied, the tripping spring is Tripping Spring이 Trip Pawl에 의해
unlatched by the activation of 압축이 풀어지고, Breaker Shaft는
the trip pawl, and the breaker 개극 위치로 돌아오게 됩니다.
shaft is returned to the open
position. Tripping
4.3 Draw In & Out Operation of HVF VCB 4.3 HVF 차단기의 인출입 방법
HYUNDAI HVF Type Vacuum circuit breakers have several 현대 HVF Type 진공차단기의 인출입 장치는 고객의 요청에 따라
versions of draw-out mechanisms and the breaker types 여러 종류가 제작될 수 있습니다. 항 목
which were produced according to customer requests. The 다음은 당사에서 표준으로 사용하고 있는 모든 방식의 인출 장치에 대한
following procedure is for the circuit breaker of our standard 취급 설명입니다. 표준 Type이 아닌 경우에는 당사로 문의하십시오.
version having worm and wormgear type draw-out
mechanism. For instructions on nonstandard version, please
contact us.
DANGER 위 험
Hazardous High Voltage will cause serious injury, 고전압은 중상, 재산피해, 혹은 사망을 일으킵니다.
property damage, or death. 차단기를 인입, 인출시키기 전에 차단기는 반드시 트립(OPEN)
Before inserting or withdrawing, the breaker should be 상태이고, 인출입 핸들을 돌리기 전에 Interlock lever는
open. Before turning the handle, lift up the interlock 손으로 들어 올려진 상태이어야 합니다.
handle. If excessive power is applied to the handle 차단기가 투입상태이거나 인터록 핸들이 올라가 있지 않았을 때,
when the breaker is closed or the interlock handle is 무리하게 힘을 가하여 돌릴 시에는 제품의 파손을 가져올 수
not lifted up, it can cause damage to the breaker. 있습니다.
Make sure that the breaker and cradle have same 차단기와 크레들의 사양이 일치하는지 반드시 확인하여 주십시오.
rating when inserting and withdrawing the breaker. 크레들과 차단기에 제품의 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached on 반드시 확인 후 사양이 일치하도록 하십시오.
the product.
DANGER 위 험
Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, DO NOT transport the breaker 일으킬 수 있습니다.
on a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고, 절대 차단기
밑에 서있거나 지나가는 일이 없어야 합니다.
4.3.1. ES/FS Type � Fig. 4-5 Insertion of the ES/FS type(1) / 4.3.1. ES/FS Type
1) Check the condition of the breaker. 그림 4-5 ES/FS type VCB 인입방법(1) 1) VCB 상태점검
Check the breaker is opened before 배전반 또는 Cradle에 설치하기 전 VCB가
inserted into the switchgear or cradle. “OPEN”되었는지 반드시 확인하십시오.
>>
진공차단기 취급설명서 15
04 Structure and Operation 구조 및 동작
Wheels of the
breaker
DANGER 위 험
Hazardous high voltage will cause serious injury, 고전압은 중상, 재산피해, 혹은 사망을 일으킵니다.
property damage, or even death. 차단기를 인입, 인출시키기 전에 차단기는 반드시 트립(OPEN)
Before inserting or withdrawing, the breaker should be 상태이고, manual locker는 반드시 unlock position에
open, and also before turning the handle, the manual 있어야 합니다.
locker should be in the unlock position. 차단기가 투입상태이거나 manual locker가 unlock 상태가
If excessive power is applied to the handle when the 아닌 상황에서 무리한 힘으로 핸들을 돌리면 제품의 파손을
breaker is closed, it can cause damage to the product. 가져올수 있습니다.
DANGER 위 험
Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, do not transport the breaker on 일으킬 수 있습니다.
a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고,
절대 차단기 밑에 서있거나 지나가는 일이 없어야 합니다.
DANGER 위 험
Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여
same rating when inserting and withdrawing the 주십시오.
breaker. 크레들과 차단기에 제품 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached to 반드시 확인후 사양이 일치하도록 하십시오.
the product.
Sticker
4) Withdrawing the breaker � Fig. 4-10 Withdrawing the SF/GS type / 4) 차단기의 인출
After checking that the breaker is 그림 4-10. SF/GS type VCB 인출방법 차단기가“OPEN”상태인지 확인하십시오.
opened, insert the crank handle in the 인출입 핸들을 삽입하고 반시계방향으로
hole to draw in and out. 약 50회 돌려 차단기를 Disconnection 위치로
Rotate handle about 50 times 이동 시킵니다.
counterclockwise. 가운데 핸들을 잡아당기면 Interlock이
If operator pulls the center handle out, 해제 되면서 차단기를 Cradle로부터 완전히
interlock will be released and the breaker 분리시킬 수 있습니다.
will be fully separated from cradle.
Center
Handle
DANGER 위 험
Excessive weight can cause serious injury or damage. 과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
To avoid this situation, do not transport the breaker on 일으킬 수 있습니다.
a lifting facility in the raised position 높게 올려진 상태에서 차단기를 이동하지 마시고,
절대 차단기 밑에 서있거나 지나가는 일이 없어야 합니다.
DANGER 위 험
Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여
same rating when inserting and withdrawing the 주십시오.
breaker. 크레들과 차단기에 제품 사양이 표시되어 있습니다.
The sticker and name plate with rating are attached to 반드시 확인후 사양이 일치하도록 하십시오.
the product.
>>
진공차단기 취급설명서 17
04 Structure and Operation 구조 및 동작
DANGER 위 험
Excessive weight can cause serious injury or 과도한 무게가 나가는 제품은 심각한 인명 피해, 기타 사고를
damage. 일으킬 수 있습니다.
To avoid this situation, do not transport the breaker 높게 올려진 상태에서 차단기를 이동하지 마시고, 절대 차단기
on a lifting facility in the raised position 밑에 서있거나 지나가는 일이 없어야 합니다.
DANGER 위 험
Make sure that the breaker and cradle have the 차단기와 크레들의 사양이 일치하는지 반드시 확인하여 주십시오.
same rating when inserting and withdrawing the 크레들과 차단기에 제품 사양이 표시되어 있습니다.
breaker. 반드시 확인 후 사양이 일치하도록 하십시오.
The sticker and name plate with rating are attached to
the product.
4.3.4. MS Type � Fig. 4-12 Front view of MS Type VCB/Cradle / 4.3.4. MS Type
1) Checking before inserting the breaker in 그림 4-12. MS Type VCB/Cradle 정면사진 1) 설치전 VCB 상태 확인
to the switchgear 크래들이나 배전반에 차단기를 설치하기 전에
Before putting the breaker into the cradle 차단기의 상태는 다음과 같이 되어야 합니다.
or switchgear, check whether all parts of - 개폐 표시기 : "OPEN"
the breaker are in the right position as - 위치 표시기 :“DISCONNECTION"
follows. - Manual locker : UNLOCK 상태
- CLOSE/OPEN indicator :
displays "OPEN"
- Position indicator:
displays "DISCONNECTION"
- Manual locker :
in "UNLOCK" position
� Fig. 4-14 Set the breaker on the switchgear or cradle / � Fig. 4-15 Lock state in the disconnection position /
그림 4-14. 배전반이나 크레들에 차단기 올리기 그림 4-15. Disconnection 위치에서 Lock 상태
Position Indicator
Head of the
fixing screw
Manual Locker
Improper operation of the breaker can 차단기를 올바르게 조작하지 않을 시에는 제품의
cause product damage. 파손을 일으킬 수 있습니다.
The breaker can be withdrawn if the head 인입을 완료한 후 Head of fixing screw의 모양이
of the fixing screw isn't inserted in the 바르지 않으면 차단기가 인출될 우려가 있습니다.
proper position. 또한 인출을 완료 후 Disconnection위치에서
Also, after withdrawing the breaker into the Head of fixing screw의 모양이 바르지 않으면,
disconnection position, the head of the Manual locker가 Unlock이 되지 않아 차단기를
fixing screw must be in the proper position. 배전반이나 Cradle에서 분리시킬 수 없습니다.
Otherwise the manual locker cannot move 올바른 차단기의 동작을 위해 Head of fixing
to the unlock position. screw부분을 항상 바르게 하십시오.
Always check the location of fixing screw
for precise operation of the breaker.
>>
진공차단기 취급설명서 19
05 Maintenance and Inspection 보수∙점검
HYUNDAI HVF Vacuum Circuit Breakers require little 현대 HVF 진공차단기는 견고한 기구부를 가지고 있어 유지 보수가 매우
maintenance because of their simplified operating 간단합니다.
mechanisms and robust construction. 보다 신뢰성 있는 사용을 위해 정상 동작 중 마모나 노화가 될 수 있는
In fact, only the parts subject to normal wear and aging 부품에 대해서만 약간의 유지 보수가 필요한 정도입니다.
need be serviced to ensure fully reliable service. 유지 보수의 범위 및 점검 기간은 차단기의 상태, 주위환경 등 다음 사항에
The interval at which these jobs should be carried out and 따라 변할 수 있습니다.
the amount of work involved depend upon �단락전류 차단 횟수
�The number of short circuit interruptions �개폐 횟수
�The switching frequency �실사용 기간
�The actual service time �주위 환경
�Environmental conditions
The service intervals indicated below are only approximate 아래에 나타낸 점검주기는 대략적인 것이며, 특별한 동작이나 환경에 따라
and should be adjusted to suit particular operation or 변할 수 있습니다.
environmental conditions. 정상적인 동작상태에서 진공밸브는 유지보수가 필요없습니다.
Under normal conditions the vacuum interrupters need not
be serviced.
CAUTION 주 의
Failure to maintain the equipment could result in 부적절한 유지보수는 치명적인 인명피해, 재산손실과 제품의 오
death, serious injury or product failure and can 동작을 일으킬 수 있습니다.
prevent successful functioning of the connected 차단기를 "CONNECTION" 위치에서는 작업하지 마십시오.
apparatus. 스프링이 차지되었거나, 투입위치에서는 작업하지 마십시오.
Do not work on a breaker in the "CONNECTION" position. 차단기 주위에 공구를 놓아두지 마십시오.
Do not work on a breaker with springs charged or 보수 작업시에는 반드시 모든 제어전원은 공급되어서는
contacts closed. 안됩니다.
Do not leave maintenance tools around the breaker.
While the work is in progress, all auxiliary voltage
sources must also be disconnected.
� Table 5-2 The lists and interval of the periodical inspection / 표 5-2 정기검사항목과 검사사항
Inspection Interval 검사 간격
Description 검사사항
items remark 항목 비고
1. Clean the insulated surface with a 1. 절연물이나 절연체의 표면에 있는 먼지나 습기를
dry cloth to remove dust and
마른 천으로 닦아 깨끗이 합니다.
moisture.
Withstand 1. Test the breaker with power 내전압 1. 부록에 표시된 전압으로 상용주파 내전압 시험을
withstand voltage test according 3 years 매 3년
voltage test 시험 합니다.
to appendix.
�Check the grease condition and lubricate every 3 year or 5,000 operations �윤활유는 외부먼지에 의해 경화될 수 있으므로 매 3년 및 5,000회
because the grease harden. 동작마다 주유상태를 확인하시어 추가적으로 주유를 하십시오.
>>
진공차단기 취급설명서 21
05 Maintenance and Inspection 보수∙점검
Lubrication of the operating mechanism is necessary only 동작 메커니즘의 주유는 매 3년, 혹은 5,000회의 CLOSE/OPEN
every 3 years or every 5,000 operating cycles. 동작 후에 필요합니다.
In general, the circuit breaker requires only moderate 일반적으로 차단기는 주기적인 간격으로 조금의 주유를 필요로 하며,
lubrication at regular intervals and all excess must be 많이 주유가 되었을 때는 깨끗한 천으로 닦아서
removed with a clean cloth to prevent any accumulation of 그곳에 습기나 먼지가 축적되는 일을 막아야 합니다.
dust or dirt. Avoid any lubricant on insulation or other 주유시는 절연부위나 전기적인 부위는 피하십시오.
electrical parts. 움직이는 부위는 주유 후에 동작시킴으로서 주유가 골고루 퍼지게 하고,
Moving parts should then be moved slightly to let the 차단기를 수동으로 몇 회 동작하십시오. 사용되어지는 그리스는
grease penetrate and become properly distributed. Shell Albania NO.2를 추천합니다.
Now operate the breaker several times manually. 주유해야 할 부위는 그림 5-2에 나타내었습니다.
Our recommended grease for lubrication is
Shell Albania No. 2.
The points to be lubricated inside the mechanism housing
are shown in Fig. 5-2.
>>
진공차단기 취급설명서 23
Appendix 부록
Appendix. Basic Specification of HVF VCB Series 부록. HVF 진공차단기 기본사양
Appendix. Basic Specification of HVF VCB Series 부록. HVF 진공차단기 기본사양
>>
진공차단기 취급설명서 25
Maintenance Recording 보수 점검
Date The Substance of Service Service Agent Engineer Cost/Free Remarks Signature
일자 수리 내역 수리처 기사 성명 유상/무상 비고 서명
Memo
>>
진공차단기 취급설명서 27
HHIS-WZ-LKE-053-00, 2010. 8 Designed by ADPARK
www.hyundai-elec.com
Signal Signal Words If the ACB trips open automatically, remove the cause before closing the ACB.
Otherwise, a fire could occur.
A danger notice with this symbol indicates that neglecting the suggested procedure or practice could
For the ACB with the fixing block, be sure to loosen the block screws before drawing out the ACB.
be fatal or result in serious personal injury.
Otherwise, damage to the ACB may occur.
A caution notice with this symbol indicates that neglecting the suggested procedure or practice could
result in moderate to slight personal injury and/or property damage.
Note that failing to observe caution notices could result in serious injury/damage in some OCR Field Test Precautions
situations.
Because safety notices contain important information, be sure to read and observe them.
OCR field test must be performed by competent persons.
Never touch live terminal parts.
Otherwise, electric shock may occur.
Transportation Precaution
Never enter the area under the Air Circuit Breaker (ACB) when it is lifted or Maintenance and Inspection Precautions
suspended using a lifter or chain block. The ACB may suddenly drop.
The ACB is heavy. Entering such an area could cause serious injury.
ACB maintenance, inspection and/or parts replacement must be performed by competent persons.
Prior to commencing any work on the ACB, open an upstream breaker or the like to isolate all
sources of power/voltage from both the primary and auxiliary circuits.
Otherwise, electric shock may occur.
Prior to commencing ACB internal inspection, make sure that the ACB is open and the closing
Installation Precautions
spring is released.
Otherwise, fingers or tools could be pinched in the internal mechanism, causing an injury.
Installation work must be performed by competent persons. Retighten the terminal screws periodically to the specified torque.
Prior to commencing any installation work, open an upstream circuit breaker or the like to isolate Otherwise, a fire could occur.
all sources of power/voltage. Retighten the arcing contact mounting screws periodically to the specified torque.
Otherwise, electric shock may occur. Otherwise, a fire or malfunction could occur.
Tighten terminal screws securely to the specified torque. Be sure to reinstall the arc chute if removed.
Otherwise, a fire may occur. Failure to do so or incorrect installation of the arc chute may result in a fire and cause burns.
Fix the ACB (draw-out cradle) firmly on a flat lever surface using mounting screws. Do not touch ACB live parts (contacts in particular), or structural parts close to a live part,
Otherwise, draw-out operation may cause the ACB to fall. immediately after opening the ACB to stop supplying power.
Avoid blocking the arc gas vents of the ACB to ensure adequate arc space (insulation distance). Otherwise, remaining heat may cause burns.
Blocking the vents could result in failure of ACB tripping. Do not bring your hand or face close to the arc gas vent of the arc chute while the ACB is closed
Do not place the ACB in such an area that is subject to high temperature, high humidity, dusty air, or opened.
corrosive gas, strong vibration and shock, or other unusual conditions. Otherwise, burns may result from high-temperature arc gas blowing out of the arc gas vent.
Mounting in such areas could cause a fire, non-tripping, or malfunction.
Be careful to prevent foreign objects (debris, concrete powder, iron powder, etc.) and rainwater
from entering the ACB.
These materials inside the ACB could cause a fire or non-tripping.
For the ACB with four poles, connect the neutral wire of a 3-phase, 4-wire cable to the
N-phase pole (on the right end).
Otherwise, an overcurrent may cause non-tripping and a fire.
1. Receiving and Handling Upon receipt of your breaker, check the following.
1.1 Storage 5 If you have any questions or any problems, contact our agent nearest you.
1.2 Directions for Transportation 5 HiAN Series Air Circuit Breakers are completely assembled, inspected and tested both electrically and mechanically at the
factory, then shipped in fully guaranteed conditions in construction and operation.
2. Description of Various Parts 6
3. Operation
3.1 Manual Charging Type 7 1.1 Storage
3.2 Motor Charging Type 8 While it is recommended that the breaker be used as soon as you have received it, you may find it necessary to store the
breaker for some time before its installation. If so, please note the following for proper storage:
4. Draw-Out Mechanism 1) Store the breaker in a dry indoor location to prevent condensation due to a sudden change in temperature,
4.1 Moving the Breaker Body within Draw-Out Cradle 10 which is quite harmful to the breaker insulation.
4.2 Putting the Breaker Body Back into Draw-Out Cradle 11 2) Store the breaker in a clean place free of corrosive gases, dirt and dust.
In particular, a mixture of cement dust and moisture can cause corrosion in the various metal parts of the breaker.
5. Periodic Inspection and Parts Replacement Fully protect the breaker from such mixtures.
5.1 Arc Chamber 14 3) Place the breaker on a flat, level surface in its normal position.
5.2 Contacts 14 4) Do not place the breaker directly on the floor.
5.3 Operating Mechanism 16
5.4 Internal Accessories 17
1) Shunt Trip Device (SHT) 18
2) Undervoltage Trip Device (UVT) 19 1.2 Directions for Transportation
3) Latch Release Coil Device (LRC) 20 When transporting the breaker from one place to another, note the following:
4) Auxiliary Switch Unit 21
5) Motor Unit 22 1) When lifting up the breaker, apply wire ropes to the lifting plates (Fig. 1 ).
6) Direction of ACB Position Padlock Device 22 Take necessary care to ensure that the tightened wire ropes may not touch the arc chambers and
multi-protective device (Fig. 1 ).
6. Over-Current Protective Device When lifting up the breaker, be sure to lift it up slowly.
6.1 Base Current [I ] of APR Multifunction Protective Device Type
0 25 2) Lower the breaker onto a flat, level surface.
6.2 Protective Functions and Setting Ranges of APR Multifunction Protective Device Type 25 3) Avoid impacts and shocks to the breaker during transportation
6.3 APR Characteristic Curve 27
6.4 Method of Changing Protective Function Settings 28
6.5 Operation Indication Functions of APR Multifunctions Protective Device Type 30
6.6 Field Test Method of APR Multifunction Protective Device Type 31
6.7 Configuration of APR Tester 32
6.8 Characteristic Check Method for Each Protective Function 35
6.9 General Directions for Testing at Primary Current Levels 37
6.10 Instruction Manual of APR-1D-GM Type 38
8. Troubleshooting Points 43
HiAN series Air Circuit Breakers are available either in manual charging type or in motor charging type.
Fig. 1 Description of Various Parts
2) Closing Operation
Before closing the breaker, check the following items:
Closing springs should be charged.
The shutter of the draw-out handle insertion hole (Fig. 3 ) should be completely closed.
Specified voltage should be applied to the undervoltage trip device (option).
See the description of the undervoltage trip device for the procedure in detail.
Upon satisfactory confirmation of the above items, press the PUSH TO CLOSE button (Fig. 3 ).
The breaker is closed. The CLOSE-OPEN indicator (Fig. 3 ) shows “CLOSED”, and the spring charged indicator (Fig. 3 )
shows “DISCHARGED”.
3) Opening Operation
Press the PUSH TO OPEN button (Fig. 3 ) This opens the breaker, and the CLOSE-OPEN indicator (Fig. 3 ) shows “OPEN”.
3.2 Motor Charging Type The draw-out mechanism permits one to draw out and remove the breaker body from the draw-out cradle and to put the
In this type, a motor-operated mechanism automatically charges the closing springs. breaker body back into the cradle, which facilitates the inspection and parts replacement.
Means for remote electrical close-open control of the breaker are also fitted. The draw-out mechanism permits one to move the breaker body to any of the following three positions in the draw-out cradle.
Complete manual operations are also possible for the same procedures described in above Manual Charging Type section. The switchboard panel door can be shut with the breaker body drawn out to the TEST or ISOLATED position.
The auxiliary switch assembly mounted on the body works in the CONN, TEST and ISOLATED positions.
In this position, the main circuit and the control circuits (of the breaker) are connected to the external
CONN POSITION
circuits for normal service.
2) Closing Operation
Before closing the breaker, check the following items:
In this position, the main circuit is isolated, and the control circuits are connected.
Closing springs are charged. TEST POSITION
This position permits close-open test, control circuit function test, etc.
The shutter of the draw-out handle insertion hole (Fig. 3 ) is completely closed.
Specified voltage is applied to the undervoltage trip device (option).
In this position, the main circuit and the control circuits are isolated.
Upon satisfactory confirmation of the above items, press the CLOSE button. ISOLATED POSITION
The breaker is completely de-energized in this position.
This energizes the latch release coil, which, in turn, releases the charged closing springs and the breaker is immediately closed.
The spring charged indicator shows DISCHARGED”.
With the closing springs discharged the charging motor is immediately turned to charge the closing springs. CONN POSITION TEST POSITION ISOLATED POSITION
Even when item 2) is not satisfied, the breaker will not be placed in a closed state.
Be sure to perform closing operation according item 2).
3) Opening Operation
The shunt trip device (SHT) or undervoltage trip device (UVT) is used for remote electrical opening operation.
Press the OPEN button. This opens the breaker via the SHT or UVT.
When close-open operations are repeated with the charging motor ON, limit the number of successive
close-open cycles to 10 times. If the open-close cycle is repeated more than 10 times, allow a cooling
period of at least 10 minutes between the 10th cycle and the 11th cycle.
04 Draw-Out Mechanism
4.1 Moving the Breaker Body Within Draw-out Cradle 3) Further Withdrawal and Removal of Breaker Body from ISOLATED Position
The draw-out handle (Fig. 4 ) is used to move the breaker body to one of the three positions (CONN, TEST, and ISOLATED) The breaker body may be further drawn out from the ISOLATED position to remove it from the draw-out cradle for
in the draw-out cradle. Attached draw-out handle (installed externally to the breaker) is to be used. inspection, maintenance or parts replacement purposes.
If the breaker is in charged condition, perform close-open operation once, and release the closing spring.
Slowly draw out the breaker body from the draw-out cradle until the draw-out dragger stops (Fig. 1 )
When the fixing blocks (optional) are fitted, be sure to loosen the right and left screws of the fixing
blocks before drawing out the breaker body.
Otherwise, a malfunction may occur.
Do not leave the breaker body as it is. When the above operation is made in as-received condition to
separate the breaker body from the cradle, take necessary measures to prevent the possible turnover
due to a change in the center of gravity.
Fig. 4
Never enter under the breaker.
The breaker weight will cause serious injuries in the event that it drops.
This process should be performed slowly.
At this process, be sure to install crane or rope to breaker’s body.
Fig. 5
Press the PUSH TO OPEN button and open the shutter of the draw-out handle insertion hole (Fig. 4 ) at the same time.
Engage the draw-out handle with the draw-out mechanism shaft and turn the handle counterclockwise to move the
breaker body. The position indicator moves to the test position.
When the draw-out handle is inserted in the draw-out mechanism shaft, the breaker is prevented
from being closed. For close-open test, remove the draw-out handle and close the shutter of the
draw-out handle insertion hole. (Fig. 4
Lift up the breaker body or use a special lifter. Attach the body extention rail to roller of the cradle and push in the breaker Frequency of Periodic Inspection
body slightly, at this time the body coil be stopped by stopper. It is most appropriate that the user works out his or her own inspection plan for the breakers according to the switching
frequency, the values of normal making and breaking currents, the magnitude of fault current interrupted, service conditions
Never enter under the breaker. and environmental conditions.
The breaker weight will cause serious injuries in the event that it drops. Otherwise it is recommended to perform a simplified inspection once every 6 months and a full inspection once a year.
Be sure to draw out the breaker to the ISOLATED position or to remove the breaker body from the draw-out cradle for
inspection or parts replacement purposes.
To release the stopper, lift up the body’s front part and push in again until the extention rails are locked.
This position is “ISOLATED”.
Press the PUSH TO OPEN button and to open the shutter of the draw-out handle insertion hole at the same time,
and engage the draw-out handle with the draw-out mechanism shaft (Fig. 6 ).
Mechanical Durability of the Breaker
Turn the draw-out handle clockwise to send the breaker body into the draw-out cradle.
The following table shows the mechanical durability of the breaker in terms of the number of switching cycles.
The position indicator (Fig. 4 ) now shows “TEST”.
When the breaker switching cycles exceed those shown in the table, the possibility of failure may increase.
Turn the draw-out handle clockwise to send the breaker into the CONN position.
For renewal or thorough inspection of the breaker, contact HHI.
Mating of the primary disconnect device starts just before the CONN position, and the draw-out handle will become heavy,
but continue to turn the handle. When the breaker is sent into the CONN position, further turning effort on the draw-out Frame Size 1600 A or smaller 2000 A or larger
handle will be stopped. No. of switching cycles 10000 5000
The position indicator now shows “CONN”. Remove the draw-out handle (Fig. 6 ).
When you try to move the breaker body to the CONN position, the draw-out handle operating force
will increase. This is because the primary circuit contacts in the breaker begin to close and
Frequency of Periodic Inspection
the insertion friction increases; an increase in handle operating force does not show the CONN While it is most appropriate that the user works out his or her own inspection plan for the breakers according to the
position has been reached, is not a failure sign. Further rotate the draw-out handle 2 or 2.5 switching frequency, the values of normal making and breaking currents, the magnitude of fault current interrupted,
turns to move the breaker body to the CONN position.
service conditions and environmental conditions, it is recommended to perform a simplified inspection
Rely on a change of position indicator in order to check if the intended breaker position is reached.
once every 6 months and a full inspection once a year.
When the handle is locked and impossible to be turned anyway, the breaker has reached the
intended position. Do not force-turn the draw-out handle while it is locked.
Inspection interval based on switching cycles
Doing so may cause a malfunction. Switching Conditions of ACB
Below 630 Frame (A) 1250 Frame (A) - 2500 Frame (A) Over 3200 (A)
When the breaker is sent into the “CONN” position, remove the draw handle and close the shutter of Switching operation in the rated
1000 500 100
insertion hole after confirming the position indication “CONN”. current region
Be sure to draw out the breaker to the ISOLATED position or to remove the breaker body from the
draw-out cradle for inspection or parts replacement purposes.
Make sure that live parts have cooled down before performing inspection work.
Trip button
Shutter of the draw-out
handle insertion hole
Draw-out mechanism shaft
Draw-out handle
When dressing contact tips, Be careful so as to not let dust fall into the breaker mechanism.
After dressing, be sure to wipe and clean the tips.
mounting
screw 2) Replacement
Stationary Arcing Contact (see Fig. 8)
Fig. 9
nut
Do not perform on-off operation with the nut installed after removing arc chamber.
Otherwise the nut will slip into contact unit. Mounting bolts
Fig. 8 Remove the two mounting screws (Fig. 9) and remove the stationary arcing contact (Fig. 9).
Set a new stationary arcing contact in position and firmly tighten the two mounting screws.
At the time of removing or mounting, must not drop any washer into pole inside.
Fig. 10
Safety Precautions:
1) Do not place your finger or a tool in the gap between the PUSH TO CLOSE button
and the CLOSED-OPEN indicator (Fig. 12 ) since this gap is closed when the breaker is closed.
2) Never attempt to put your hand or a tool into the breaker when the closing springs are charged.
Be sure to discharge the closing springs prior to internal inspection.
1) Periodic Maintenance
Check the operating mechanism in detail to a possible extent. If there are detail parts that seem to require a check
but are hard to check, please contact HHI.
INSPECTION ITEMS METHODS / CRITERIA / DISPOSITIONS LRC (latch release coil) Charging motor
MHT (magnetic hold trigger) Draw-out shaft
Operation Open and close the breaker through manual control to check the mechanical parts for normal operation. Type APR over current release Closed-open indicator
Open lever for draw-out Charged-discharged indicator
Add a small amount of grease to each of the pins, shafts and their bearings. Fixing block Auxiliary switch unit
Lubrication
Avoid excessive oiling as such will result in accumulation of dirt and dust. Shunt trip coil Auxiliary switch fixing bolt
Screws, Bolts Check screws and bolts on each part for signs of loosening. Tighten them if loose.
and Springs Check each spring for proper engagement and damage. Correct problem by repair or replacement.
Dirt and dust Latching parts should be free of dirt and dust. Wipe them with a clean cloth.
Push the moving core of SHT with a pointed tool, such as screwdriver tip, then slowly release the core.
(1) General View of Undervoltage Trip Device
The result is acceptable if the core returns lightly.
Slowly push in the moving core after closing the breaker.
Operation Fig. 14 UVT Control Device
The result is acceptable if breaker trips open.
If the breaker trips open at less than 70% of the rated voltage after closing the breaker,
the result is acceptable.
UVT controller
Terminals and Check terminals and mounting screws for loosening.
UVT control device mounting
Mounting Screws Tighten them if loose.
bolt (3-M6 x 10)
Wire terminals (fasten terminal)
Fig. 13
Never apply voltage to the UVT terminals Nos.”9” and ”10”. when the UVT function is locked.
Doing so may cause burn-out of the equipment.
Never loosen nor tighten the ADJ nut.
Doing so may cause a malfunction.
Fig. 15
4) Auxiliary Switch Unit
(1) Replacement of Auxiliary Switch Unit (See Fig. 17)
The auxiliary switch unit is an assembly of 10 switch elements (4 a-contacts and 4 b-contacts).
Replace the whole switch unit even if a defect is partial.
- Remove the M5 bolt and remove the auxiliary switch unit with wiring.
- Remove the two M4 R/H auxiliary bolts which hold auxiliary switches in line.
- Replace the fault auxiliary switch.
Yoke
- Fix it again as it was.
Yoke mounting screw
Moving core - Check the switch movement.
Coil (2) Periodic Inspection
Terminal
INSPECTION ITEMS METHODS / CRITERIA
Take the breaker body out of the draw-out cradle.
Connect the ohmmeter or alarm (buzzer) to each switch element.
Operation
Check that a-contact is ON and b-contact is OFF when breaker is CLOSED, and that a-contact is OFF and
b-contact is ON when breaker is OPEN.
(2) Periodic Inspection
Check each contact for surface roughness (removing laminated phenolics plate from unit permits a visual check of contacts).
Contact Surface
INSPECTION ITEMS METHODS / CRITERIA If contact is excessively worn or rough, replace whole switch unit.
Push the moving core with a pointed tool, such as screwdriver tip, then slowly release the core. Terminals and Check terminals and mounting screws for loosening. Tighten them if loose.
Mounting Screws
The result is acceptable if the core returns lightly.
Operation Charge the closing springs and push the moving core.
The result is acceptable if the closing springs are discharged. Fig. 17 Fig. 18
If the breaker can be closed at 85% of the rated voltage, the result is acceptable.
Terminals and Check terminals and mounting screws for loosening. AUX. SW SUP/A
Mounting Screws Tighten them if they are loose.
Mounting bolt
(2-M4 75L)
AUX. switch