G7M-0010-23 - CT Ratio Test
G7M-0010-23 - CT Ratio Test
ELECTRICAL G7M-0010-23
GLOBAL 14-JAN-2008
Page 1 of 2
i
CT RATIO TEST
ii
Special Equipment 1. Calibrated Current Transformer Test Set or the equipment listed below:
3. Calibrated (within one year) ammeters (2) with a range that will give
approximately 1/2 scale readings of the primary and secondary
currents.
iii
Procedure
Step Action
4
Inject and record a primary current in the CT. This current should
be approximately in the upper 1/3 of the CT primary current rating.
It may be necessary to install several wraps of primary wire
through the core of the CT primary to obtain the desired secondary
current on CT’s with high ratios.
5 Divide the primary current by the secondary and record this ratio.
i
14-JAN-2008; MOC N/A; By: Karl Beaty; Supersedes Issue Date 19-JAN-2005; Corrected table
format for STEPS 1 – 3. Added hyperlink to referenced practice. No technical update.
ii
19-JAN-2004, MOC 2005_02571, By: Walter Selle, Supercedes Issue Date 05-MAR-1999, SPECIAL
EQUIPMENT – Added new 1 and 2. Renumbered
iii
19-JAN-2004, MOC 2005_02571, By: Walter Selle, Supercedes Issue Date 05-MAR-1999,
PROCEDURE – Added new STEPS 1, 2 and 3. Modified STEP 4. Renumbered