FIRE FIGHTING FOAM TEST REPORT

Customer : Aito Firework (Malkraine Sdn Bhd) Laboratory Ref. No. : 100857
Customer Ref. No. : PO23/10-657 No. Of Samples : 1/1
Sample Location : Pail C Sample No. : 100857(1)
Foam Brand : Safeguard Date : 25-Oct-23
Foam Type : 6% AFFF Next Test Date : Immediate

FOAM CONCENTRATE TEST RESULTS


Physical Characteristic Test Results Range
Appearance Slight Viscous Pale Amber Liquid
Specific Gravity at 20ᵒC 0.992 1.00-1.04
pH at 20ᵒC 7.61 7-8
Sediment % v/v None
Viscosity at 20ᵒC (Spindle 64, 60RPM) 150 cPs
Surface Tension at 20ᵒC 0.0325 N/m

Foam Properties
25% Drainage Time 3mins 43secs
Expansion Rate 7.66

Fire Extinguishment Test


Fire Extinguishment Test (Heptane) Unsatisfactory

CONCLUSION & RECOMMENDATION


The sample was tested as a 6%AFFF and was found to be in unsatisfactory condition due to poor
fire extinguishment performance. We would like to draw your attention to the low specific
gravity, high viscosity and high surface tension. We recommend immediate re-testing.

Sign on Behalf of Foamlab Fire Technologies

Laboratory Manager (Tel: +60 85 658284)

Satisfactory
Marginal Error
Unsatisfactory
(Please note that the conclusions drawn in this report are based solely on the samples submitted with assumption
that samples are representative of parent stock. We are not responsible for the subsequent performance of the
foam when used beyond our control.)