TDS - 1600kva Oil Type Transformer

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2



Technical Specification
Characteristic
Liquid-Filled Groundmount Transformer; 3PH,
Product name
1600 kVA, HV 11000D , LV 433yn
Country of origin Turkey
Rated power [kVA] 1600
Insulation Liquid Mineral Oil
High voltage [V] 11000
High voltage tappings (DETC) +2 -2 2.5%
Low voltage at no load [V] 433
High voltage insulation level [kV] LI 75 / AC 28 / Um 12
Low voltage insulation level [kV] LI - / AC 3 / Um 1.1
Frequency [Hz] 50
Number of phases 3
Vector group Dyn11
Ambient temperature
°C 55 / 45 / 35
max./monthly/annual average
Max. average temperature rise
[C/C] 45 / 50
(Oil/Winding)
Surface treatment Painted, Dark Admiral Grey (C5M)
Altitude (a.s.l.) [m] <1000
Location Indoor/Outdoor
The transformer is not compliant with the
EcoDesign Requirement prevailing regulation and is intended for export
outside Europe only (no CE marking)

Performance values
Standards IEC 60076
Impedance [%] 6(+-10%)
No load losses [W] 1360(+0%)
Load losses at 75 °C [W] 15300(+0%)

Preliminary dimensions and weight


Length [mm] 2150
Width [mm] 1300
Height [mm] 2300
Roller distance (c/c) [mm] 820 x 820
Oil Weight [kg] 1215
Core Steel Weight [kg] 1331
Windings Weight [kg] 856
Total weight [kg] 5580

Type of design
Tank construction Corrugated Wall, Hermetically sealed
Cooling ONAN
Core Steel Type RGO
High voltage winding conductor material Cu
Low voltage winding conductor material Cu

ABB ELEKTRİK SANAYİ A.Ş.

Yukarı Dudullu, Organize Sanayi Bölgesi Fax: +90.216.365 29 21


2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY Phone:+90.216.528 22 00
3/4

Standard Features/Accessories
Wheels
Terminal Box
Off-Circuit Tap Changer
HV&LV Bushings
HV&LV Cable Boxes
Pressure Relief Valve
Dial-Type Thermometer
Oil Level Indicator

General Comments and Exceptions


- Junction box - standard type aluminum cast terminal box will be given, steel box is not possible with small
dimensions.
- Any CTs, surge arresters, resistors, NERs; etc are not included.
- Dimensions given preliminary and cannot be used for civil works.
- Type of the transformer will be hermetically sealed with corrugated wall tank.
- All conditions are according to our standard, if we did not indicate in our offer.
- Painting will be carried out according to TRABB painting procedure.

ABB ELEKTRİK SANAYİ A.Ş.

Yukarı Dudullu, Organize Sanayi Bölgesi Fax: +90.216.365 29 21


2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY Phone:+90.216.528 22 00
4/4

You might also like