TECHNICAL DATA SHEET

Product Description: 0.6/1kV 4C35SQ.MM CU/XLPE/PVC/SWA/PVC POWER CABLE

Construction : 1 Conductor Class 2, Plain annealed copper


2 Insulation XLPE(moisture crosslinking)
3 Filler Non-hygroscopic PP
4 Binding tape Non-hygroscopic
5 Inner sheath PVC (Type:ST2 BLACK)

6 Armored G. steel wire armored


7 Binding tape Non-hygroscopic
8 Outer sheath PVC (Type:ST2 BLACK)

No. ITEMS UNIT PARTICULARS


1 Name and Adress OF Manufacturer XCTY
2 Type of the cable CU/XLPE/PVC/SWA/PVC
3 Rated Voltage kV 0.6/1
4 Size 4X35
5 Standard Applied
Design guidelines IEC60502.1/ BS7889
Conductor IEC60228
Insulation and sheath IEC60502.1
Flame resistance IEC60332.3
Fault current carrying of conductor IEC 60949
6 Application
Max. continuous operation temperature ℃ 90
Max. temperature at short circuit(≤5s) ℃ 250
Lowest recommended temperature during installation ℃ 0
7 Core identification and mark as listed below, or as purchase order.
7.1 Identification of core: For 4 Conductors: Red, Yellow, Blue, Black.
7.2 Mark on outer sheath: MANUFACTURER ELECTRIC CABLE STANDARD SIZE VOLTAGE TYPE YEAR METER
A line of characters along the surface of outer sheath by printing.
Eg: XCTY IEC60502-1 IEC60332-3 POWER CABLE 0.6/1kV CU/XLPE/PVC/SWA/PVC 4C35 MM2 2022 xxxm
8 Dimension
8.1 Conductor
Cross sectional area mm2 35
Material Plain annealed copper
Shape of finished conductor Sector Compacted
No. of strands/single wire diameter of Phase No./mm 7/2.52
8.2 Insulation
Material XLPE
OVERSES SALES SUBSIDIARYS:
HENAN XINCHANGIMPORT AND EXPORT TRADE CO., LTD.,
#2 building of # 85 Jinshui Dong Road, Zhengzhou, Henan,P.R.China
INDUSTRIAL PARK,GONGYI,HENAN,P.R.CHINA Tel: 0086-15936206976 http://www.cncuxc.com 1209792977@qq.com

Nominal thickness of Phase mm 0.9


Minimum radial thickness mm 0.71
8.3 Fillers Binding tape
Material Non-Hygroscopic
8.4 Inner sheath
Material PVC
Nominal thickness mm 1.0
OD over bedding (Approx.) mm 24.40
8.5 Armored
Material G. steel wire
Diameter of armoring single wire mm 1.6
8.6 Out Sheath
Material PVC
Nominal thickness mm 2.0
Minimum radial thickness mm 1.40
8.7 OD of the finished cable (Approx.) mm 29.5
8.8 Weight of the finished cable (Approx.) Kg/km 2396
9 Electrical and Mechanical particulars
9.1 Max. D.C. Phase conductor resistance at 20℃ Ω/km 0.524
9.2 High Voltage test KV/(min) 3.5/5
The result No breakdown
9.3 Min. bending radius
During installation xD 12
Installed xD 10
9.4 Max. allowable pulling force of conductor KN 9.8
9.5 Fault current carrying of phase conductor (1s) KA 5.0
10 Current Carrying Capacity
Maximum conductor temperature ℃ 90
Ambient air temperature ℃ 40
Ground temperature ℃ 25
Depth of laying M 0.8
Thermal resistivity of soil C. m/W 1.2
In Air A 115
In Ground A 150
In Duct A 135
Note: these values are only for reference.
11 Environment temperature correction coefficient.
Environment temperature(℃)
Ambient Air Temperature Variation Ground Temperature Variation
20 25 35 40 45 50 55 10 15 20 25 30 35 40
1.18 1.14 1.05 1.00 0.95 0.89 0.84 1.11 1.07 1.04 1.00 0.96 0.92 0.88
12 Packing style Wooden Drum