Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

Customer: Date:

Protocol №:
Object:
Job title: Chromatographic analysis of 80 MVA Transformer oil №1

Device: Transport X 2

Standard: ASTM D 1533

Voltage Production
Type of oil Factory № On inspection
kV year
Results Allowed values
Gases in an oil
sample: <5 ppm 100 ppm
-Hydrogen 344 ppm 2500 ppm
-Carbon dioxide 203 ppm 350 ppm
-Carbon monoxide <2 ppm 50 ppm
-Ethylene 1LFI4367722612 110 2012 <2 ppm 65 ppm
-Ethane <2 ppm 120 ppm
-Methane <0,5 ppm 35 ppm
-Acetylene
Humidity(ppm): 6 ppm 10 ppm

Feedback: The dimensions are within the norm. The oil is usable.
Note: The measured parameters were measured according to the customer's order.

Conductor of the test:

Deputy Director of the


Laboratory Center

You might also like