RE-R1 Example Renewable Energy Balance

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Line 1: Please enter under Options

Line 2: Please enter under Options


DRE IT/ITE
Variant1

14 x AOSP-240
Total Gross Surface Area: 35.28 m²
Azimuth: 0°
Incl.: 20°

4.62 m³/Day
60 °C

Electric
18 kW

IT1500 DRE 120 vessel


Vol : 1550 l Vol : 480 l

Results of Annual Simulation


Installed Collector Power: 24.70 kW
Installed Gross Solar Surface Area: 35.28 m²
Collector Surface Area Irradiation (Active Surface): 66.41 MWh 2,136.67 kWh/m²
Energy Produced by Collectors: 43.55 MWh 1,401.32 kWh/m²
Energy Produced by Collector Loop: 42.40 MWh 1,364.38 kWh/m²

DHW Heating Energy Supply: 71.69 MWh


Solar Contribution to DHW: 41.54 MWh
Energy from Auxiliary Heating: 40.24 MWh

Electricity Savings: 48,875.8 kWh


CO2 Emissions Avoided: 32,551.30 kg
DHW Solar Fraction: 50.8 %
Fractional Energy Saving (EN 12976): 51.9 %
System Efficiency: 62.6 %

T*SOL Expert 4.5 Page 1 13/02/2013


Line 1: Please enter under Options
Line 2: Please enter under Options
DRE IT/ITE
Variant1

Basic Data
Climate File
Location: ABU DHABI
Climate Data Record: ABU DHABI INTL
Total Annual Global Radiation: 2031.66 kWh
Latitude: 24.43 °
Longitude: -54.65 °
.

Domestic Hot Water


Average Daily Consumption: 4.62 m³
Desired Temperature: 60 °C
Load Profile: Shower peaks 3 x pd 9am till 4pm
7 days per week
Cold Water Temperature: February:23 °C / August:23 °C
Circulation: Yes

System Components
Collector Loop
Manufacturer: AO Smith
Type: AOSP-240
Number: 14.00
Total Gross Surface Area: 35.28 m²
Total Active Solar Surface Area: 31.08 m²
Tilt Angle: 20 °
Azimuth: 0°
.

DHW Standby Tank


Manufacturer: AO Smith
Type: DRE 120 vessel
Volume: 480 l
Solar Preheating Tank
Manufacturer: AO Smith
Type: IT1500
Volume: 1550 l
.

Auxiliary Heating
Manufacturer: T*SOL Database
Type: Electric
Nominal Output: 18 kW

Legend
Original T*SOL Database
With Test Report
Solar Keymark

T*SOL Expert 4.5 Page 2 13/02/2013


Line 1: Please enter under Options
Line 2: Please enter under Options
DRE IT/ITE
Variant1

Solar Energy Consumption as Percentage of Total Consumption

1,700
1,600
1,500
1,400
[ kWh ] per week

1,300
1,200
1,100
1,000
900
800
700
600
500
Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Solar Contribution 41,544 kWh Total Energy Consumption 81,785 kWh

Daily Maximum Collector Temperature

72
70
68
66
64
62
60
58
[ °C ]

56
54
52
50
48
46
44
42
40

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

These calculations were carried out by T*SOL Expert 4.5 - the Simulation Programme for Solar
Thermal Heating Systems. The results are determined by a mathematical model calculation with
variable time steps of up to 6 minutes. Actual yields can deviate from these values due to
fluctuations in climate, consumption and other factors.The system schematic diagram above does
not represent and cannot replace a full technical drawing of the solar system.

T*SOL Expert 4.5 Page 3 13/02/2013


Line 1: Please enter under Options
Line 2: Please enter under Options
DRE IT/ITE
Variant1

Energy Balance Schematic

Legend
1 Collector Surface Area Irradiation (Active Surface) 66 MWh
1.1 Optical Collector Losses 17,459 kWh
1.2 Thermal Collector Losses 5,396 kWh
2 Energy from Collector Array 44 MWh
2.2 Solar Energy to Preheating Tank 42 MWh
2.5 Internal Piping Losses 894 kWh
2.6 External Piping Losses 254 kWh
3.1 Tank Losses 1,105 kWh
3.2 Circulation Losses 8,990 kWh
3.3 Preheating Tank to Tank 42 MWh
4.1 Tank Losses (S) 865 kWh
6 Final Energy 47 MWh
6.1 Supplementary Energy to Tank 40 MWh
6.5 Heating Element 0 kWh
9 DHW Energy from Tank 72 MWh

T*SOL Expert 4.5 Page 4 13/02/2013


Line 1: Please enter under Options
Line 2: Please enter under Options
DRE IT/ITE
Variant1

Glossary
1 Collector Surface Area Irradiation (Active Surface)
Energy Irradiated onto Tilted Collector Area (Active Solar Surface)
1.1 Optical Collector Losses
Reflection and Other Losses
1.2 Thermal Collector Losses
Heat Conduction and Other Losses
2 Energy from Collector Array
Energy Output at Collector Array Outlet (i.e. Before the Piping)
2.2 Solar Energy to Preheating Tank
Collector Array Energy Minus Piping Losses
2.5 Internal Piping Losses
Internal Piping Losses
2.6 External Piping Losses
External Piping Losses
3.1 Tank Losses
Heat Losses via Surface Area
3.2 Circulation Losses
Circulation Piping Losses
3.3 Preheating Tank to Tank
Heat from Preheating Tank to Tank
4.1 Tank Losses (S)
Heat Losses via Surface Area
6 Final Energy
Final Energy Current into System. This can flow in as natural gas, oil or electricity (not
including solar energy) taking efficiency levels into account
6.1 Supplementary Energy to Tank
Supplementary Energy (e.g. Boiler) to Tank
6.5 Heating Element
Energy from Heating Element
9 DHW Energy from Tank
Heat for DHW Appliances from Tank (Exluding Circulation)

T*SOL Expert 4.5 Page 5 13/02/2013