Professional Documents
Culture Documents
2 1933 Clark F. M. - The Role of Dissolved Gases in Determining The Behavior of Mineral Insulating Oils
2 1933 Clark F. M. - The Role of Dissolved Gases in Determining The Behavior of Mineral Insulating Oils
2 1933 Clark F. M. - The Role of Dissolved Gases in Determining The Behavior of Mineral Insulating Oils
F. M. CLARK,
General Electric Company. Pittsfield, Mass.
ABSTRACT.
Method of Test.
FIG. I.
Gas Co//ector
Apparatus
used to determine the kind and amount of dissolved gas in mineral oil.
Per cent. air reduced to 25” C., 760 millimeters pressure dis-
solved in 100” C. oil whose volume has been corrected
to 29 C.-I I .3.
Air Solubility in Mineral Oil.
Tempera f we “C
The effect of temperature on gas solubility in transformer oil.
Oil temperatureas stated.
Barometer--corrected to 760 mm.
Gas volume--corrected to z.sO C.
Oil conditionins- hours at temperature given.
Oil volume-3 :” deep. 36 sq. ins. surface area.
Phenomena of De-&ration.
34
32
30
28
FIG.4.
JO 0 IO 20 30 40 50 60 70 80 90 IO0 /IO20
Temperature ‘C
Relative amounts of dissolved oxygen and nitrogen taken up by oil exposed
to air at temperature shown. Based on Fig. 2.
FIG. 5.
_
0 100 aJo 300 400 5-00 600 700 800
FIG. 6.
amount remained in the oil was evident from the fact that
the gas over the oil showed no tendency to increase amounts of
oxygen even after standing at room temperature for periods
of approximately one week.
THE RATE OF RE-SOLUTION OF AIR BY DE-AhATED OIL.
From the fact that air is difficult to remove from still oil,
it is frequently concluded that its resolution is likewise a
slow and difficult process. The contrary is true. The re-
solution of air by de-aerated oil is rapid, the exact rate being
dependent on the ratio of oil depth to volume, oil agitation
and other testing factors.
FIG. 7.
0 r02030404v60wC7ww//0&0
Hours Exposure @S”C>
Rate of re-solution of air in transformer oil at 2 j” C.
Oil surface--8/Io sq. ins.
Oil depth-1 I inches.
Temperature-So C.
Barometer-760 mm. mercury.
Figure 7 shows the rate of re-solution at 25'C. for a body
of still oil, .8 sq. in. surface area, and II in. deep (surface to
depth ratio of .07).
Figure 8 shows the speed of air re-solution at 80” C. for a
body of still oil, 36 sq. in. in surface area, and 31 in. deep
(ratio of surface to depth of I I .o).
0 2 4 6 8 IO 12 I4 16 18 20 22 24
Hours at8o"C
Gas sohbility increase in 80’ C. oil as a function of time exposure.
Oil-transformer oil at 80~ C.
No circulation of oil.
Gasvolume comsnonding to 2s’ C.-y60 mm.
Oil volume-3 !” deep, 36 sq. in. area.
FIG.9.
6
I I I
0 2 4 6 8 io 12 /4 16 I8 20 22 24
f?afio Oil Area to Oil Depth
The effect of surface area to depth on gas re-solution in degassed transformer oil.
Oil heated one-half hour at moo C. No circulation.
TABLE II.
The Dielectric Strength of Transformer Oil as a Function of Its Gas
Content at Atmospheric Pressure.
--~-___ __
_
Average 60 Cycle Di-
electric Strength of Oil
Minimum Gas-Saturated at At-
Sparking Voluqe mospheric Pressure.
Gas Used to Saturate Oil. Potential v;b;‘.;y pF,y:
of Gas.
Rapidly Ap- Minute
plied Test. Test.
._
Air.................... 341 10.8% 25 34.8 34x5
Hydrogen . 302 5.070 2.5 31.8 32.4
Carbon Dioxide. 4’9 99.0% 25 36. I 31.2
_
TABLE III.
Relation of Minimum Sparking Potential of Gas to Dielectric Strength of Oil
Saturated with the Gas at Atmospheric Pressure.
FIG. IO.
FIG. 12.
The dependence of the “critical pressure” value of the dielectric strength of transformer oil on the
type of test and the type of oil dissolved gas.
Gap-I/IO” (horizontal).
Electrodes-r” brass discs.
Ja11.9
1933.1 Drssor,v~n G.\sEs.
5s
TABLE I\‘.
The Effect of the Testing Procedure and the Type of Gas Dissolved in Mineral Oil
on the Gas Pressure Corresponding to Minimum Oil Breakdown.
Pressure Corresponding to Minimum Oil Breakdown.
Gas. Rapidly Applied Test. Minute Test.
Air........................ 4oomicrons I000 microns
Carbon Dioxide. Less than 150 microns 600 microns
Hydrogen. .. . . Less than ISO microns 600 microns
KV=mP+n
the value of m agrees well with that already given for air.
Sufficient data are not available, however, to permit the
conclusion that for all gases or even for air, the value
of m is always .45 as illustrated in previous paragraphs.
Data are at hand, however, to show the linear decrease in oil
dielectric strength as the pressure of the gas, either carbon
dioxide, hydrogen or air, is decreased.
F. M. CLARK. [J.F. I.
56
Further Illustration of the Importance of Dissolved Gases in Determining the
I Dielectric Strength of Mineral Oil.
FIG. 13.
0 /OOZfW3#4W5~6&7 ?Vt98do%O/.O
Gas Pressure in Microns of Mercury
The dielectric strength of transformer oil as a function of its air content tested at
(hydrostatic) atmospheric pressure.
Testing gap-r/m”.
Electrodes-standard I” brass discs.
Gap-horizontal.
Voltage-rapidly applied.
Jan., 1933.1 DISSOLVED GASES. 57
FIG. 14.
50
48
II I I I I I I I I I II
0 10 20 30 40 50 60 70 80 90 /m II0 I20 IJO 140 /m I60 I70 I80
44
1 42
k
-40
l/l I I I I I I I I I I I I I I I I
FIG. 16.
FIG.17.
than 500 microns, and (3) that the rate of re-sol ion of air in
de-aerated oil is rapid and practically complet in 25 to 30
minutes of air exposure under atmospheric cond ‘ons.
The Effect of Temperature on the Dielectric Strength.
/ I
I
tiorizor7tal
--t-
FIG.21.
E/e&-odes Vertical
.I .2 .3 ? .5 .6 r/.8.9
I.0 2.0
inches Distance Between E/et tredes
Logarithmic expression for the A.C. strength thickness relation in transformer oil.
Electrodes-m” brass discs.
Test procedure--rapidly applied.
Gap setting-s shown.
Condition of oil between tests-well stirred.
(Points are average of ten tests.)
66 I;. M. CLARK. [J.F. I.
FIG. 22.
Electrodes krtical
(KVMT-97)
ZOO
E/ectfodes
10. .
.I .2 .3 9 .5 .6 7.8.9l.o 2.0
Distance Between E/ectfodes--inches
The logarithmic expression of the A.C. strength thickness relation in transformer oil
Electrodes-brass discs IO” in diam.
Test procedure-minute.
Gap settingas shown.
Condition of oil between tests-well stirred.
(Points are average of five tests.)
Jan., 1933.1 DISSOLVED GASES. 67
BIBLIOGRAPUY.