Table 05-05: Clearances of SEC U/G Cables & Other Utilities lines
8.3.1 Warning posts shall be installed along the center line of the trench at not over
50 m intervals on congested areas and not over 90 m intervals on open areas
and at all locations where the trench changes direction.
8.3.2 On straight route, the warning post shall have a two-arrow sign to indicate
cable route direction.