Professional Documents
Culture Documents
10-Division 15-Section 15080 Odour Control-Version 4
10-Division 15-Section 15080 Odour Control-Version 4
10-Division 15-Section 15080 Odour Control-Version 4
(ADSSC)
DIVISION 15 MECHANICAL
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 1 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
01 April 2008
First Issue.
05
06
07
08
09
10
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 2 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
TABLE OF CONTENTS
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 3 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
1. ODOUR CONTROL
1.1 GENERAL
a) All items described within this section shall comply with the provisions of
Section 15001: General M&E Requirements.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 4 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
k) H2S can cause corrosion of concrete and mortar fixtures when oxidised
to sulphuric acid, e.g. on moist walls of sewers and manholes.
Metalwork and electrical equipment is also vulnerable to H2S corrosion.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 5 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 6 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 7 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
Do not locate tanker discharge point near a sensitive Connect tanker vents to OCU
boundary. if air mixing employed.
Grit Removal Do not select aerated grit channels. Do not select aerated grit Aerated grit channels can lead to a
channels significant release of odours
Cover unit
Ensure grit is washed once removed. Ensure grit is washed once
removed.
Enclose grit conveyor and
classifier.
Inlet screens and Provide local covers and minimise turbulence as far House screens in a building
screenings as possible. actively vented to OCU.
handling Ensure materials below covers are resistant to Provide local covers and
hydrogen sulphide/sulphate attack. minimise turbulence as far as
possible.
Wash screenings. Ensure materials below covers
are resistant to hydrogen
sulphide/sulphate attack.
Provide a gas alarm system,
as high levels of H2S could
accumulate if the ventilation
system fails.
Discharge washed screenings
to enclosed skips.
Do not store full skips on site.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 8 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 9 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
Desludge frequently and remove sludges at a low Ensure materials below covers
concentration to avoid excessive retention. are resistant to
sulphide/sulphate attack
Design arrangement so that tanks can be removed
from operation at times of low flow to avoid excessive
retention of sewage.
Minimise the height of drop over weirs to reduce
splashing.
Lamella separators Minimise need for manual cleaning of plates. Provide covers vented to The level of septicity and odours developing
odour control. is in proportion to the retention time.
Do not select systems that incorporate sludge Ensure materials below covers
thickening within the unit. are resistant to
sulphide/sulphate attack.
Activated Sludge/ Ensure adequate aeration and mixing. Fine bubble Cover distribution chambers, At normal loadings, activated sludge has a
MBRs/SBR aeration systems are preferred to mechanical surface inlet channels and anoxic zone low odour level, decreasing as the loading
aeration systems. areas. rate decreases.
Use submerged or non-turbulent inlet and outlet Minimise the loading rate. FBDA systems release less aerosol and
arrangements odours than mechanical surface aerators.
There also is less risk of septic pockets
developing.
Conventional Ensure correct operation. Can be a cause of odours if overloaded and
biological filters ponding.
Minimise the height of drop between distributor and
media surface.
Use recirculation if signs of ponding.
Ensure adequate ventilation.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 10 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
Submerged Fluidised media preferred to fixed media Cover and vent to odour Septic areas can develop, particularly in
biological aerated control fixed media systems.
filters fixed or Avoid turbulence at inlet and during backwashing
fluidised media
High-rate biological Cover and vent filter and effluent sump to odour Replace with an alternative Can be a significant source of odour due to
filters treatment system. system, or: the development of thick biofilms with
Draw air from the base of the filter. Cover and vent by drawing air release of odour from the top of the filter in
down to the base, i.e. in the the ventilation.
same direction and the
sewage flow.
Do not co-settle sludge Treat the vented air.
Ensure materials below covers
are resistant to hydrogen
sulphide/sulphate attack.
Final Recycle backwash waters from sand filters without
Sedimentation, storage
Tertiary sand filter,
UV treatment
Picket fence Cover and vent tanks to OCU, passive may be Replace with mechanical Odour in sludges and sludge liquor strength
thickeners and raw sufficient. thickeners increase with storage.
sludge storage
Toxic levels of hydrogen sulphide will develop below
covers.
Do not locate near a sensitive boundary. Active venting to OCU PFTs can be a significant source of odour
formation with release of odours from: the
surface of the PFT, the overflow weir, the
sludge liquor drainage system and from
subsequent handling of the sludge.
Non-turbulent low-level inlet, outlet and supernatant
discharge.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 11 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 12 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
Cover tanks, feed, mixing and take-off points Digester gases can contain significant
levels of H2S which is oxidised by flaring or
burning.
Ensure the gas handling system is fully operational.
If gas is not required for heating or engines it should
be flared.
Aerobic digestion Ensure that there is more than sufficient capacity. Cover tanks and ventilate to Odours will be released during aeration of
OCU. raw and secondary sludges.
Cover feed, mixing and take-off points
Thermal treatment Odour control, possibly by thermal oxidation. Volatilisation of a range of organic
processes and compounds may occur due to the high
drying temperature.
Tall stack.
ADSSC/GSMW Division 15 Section 15080 Odour Control Rev: 04 Feb. 2016 Page 13 of 38
General Specification for Mechanical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
c) The design of the ventilation and odour control system shall take in to
account the handling of potentially hazardous gases, and the zone
requirements of the area in which it is installed.
i. 25 - 35ºC sewage.
ii. 0 - 55ºC ambient.
iii. 90ºC maximum radiating temperature (surfaces).
iv. Up to 30ºC air vented from the sewerage system to an OCU.
1.4 MATERIALS
c) Choice of materials for covers will need to take into account: strength,
thickness, durability, weight, cost, aesthetics, supplier and operational
requirements.
g) Materials for covers and supports, and any equipment below the cover
shall be resistant to corrosion. Where possible, motors, etc., shall be
located outside the cover.
j) Where possible, design shall be such that equipment below covers can
be easily and quickly removable.
g) The Tenderer shall state the expected life of the activated carbon and
guarantee sufficient supplies for the first year of operation. The cost of
the activated carbon shall be entered in the appropriate schedule.
i) Fan motors shall be direct coupled and suitable for installation within a
Zone 1 potentially explosive hazardous area and shall comply with
Section 16000: Electric Motors.
j) Where the odour control system is fan-assisted all parts exposed to the
fumes shall be non-metallic or stainless steel construction, heavy gauge
and resistant to attack, and the motor and drive shall be sealed from the
exhaust gas path.
l) Suitable flap valves shall be provided to allow the circulation of fresh air
into the well as necessary, so that the deodoriser can operate.
a) Biofilters shall utilise peat media for the bio-oxidation of H2S. Peat is a
typical lignitic material which is capable of absorbing large quantities of
water and has with good compaction resistance. Alternatives may be
offered as options for consideration at the tender stage.
b) The filter shall be manufactured from GRP with rigid polyethelylene foam
infill, boltable sectional panels, removable cover and base.
Polyethelylene foam (25mm thickness) shall be fully-encapsulated and
provide thermal insulation for site conditions.
h) Final effluent shall be utilised for the wetting of the media, where
available. Alternatively, potable water with necessary pH chemical
dosing control shall be provided.
m) Condensate shall be drained from all low points within the system and
adequately sized inspection hatches shall be provided wherever access
is required for periodic maintenance of internals.
o) The chimney shall be fitted with eddy shedders and shall be restrained
by steel guy wires. The chimney design shall be approved by the
ADSSC.
The odour control system shall design to remove all the pollutant inclusive of
hydrogen sulphide, organic reduced sulphur compounds (RSCs) and other
odorous compounds from the foul air stream from the municipal wastewater
odour sources using a biotrickling filter operating in a counter-current
manner. Co-current systems shall not be allowed.
The foul air shall enter the system from the bottom of each reactor and flow
upward through each of the media layers installed in series. The media bed
shall be intermittently or continually watered from top of rector using suitable
reclaimed plant effluent or potable water as per the manufacturer
recommendations. The water trickles through the media and is collected in a
sump at the bottom of the reactor. The drain water from the system will pass
from the sump in the bottom of the reactor vessel and be piped to a
discharge point as designed. It shall be the manufacturer responsibility to
select the right system (single / recirculation type) as appropriate to treat the
odorous gas to comply the ADSSC emission standards
3.2.2 PRODUCTS
3.2.2.1 GENERAL
The odour control equipment supplied under this section must be provided
by a single manufacturer who will be solely responsible for the design,
delivery and entire performance of the system. The equipment must be new
and unused and meet the specifications and warranty requirements as per
ADSSC terms & conditions.
The biotrickling filter manufacturer is responsible for the coordination with all
the equipment suppliers to complete the system inclusive of FRP towers, air
blowers, nutrients system, pipelines, ducts, instrumentations, panels, etc....
The Contractor shall not be allowed for any substitutions. The biological
odour control system manufacturer shall be experienced in the design,
manufacturing, installation and operation of biotrickling filters designed to
remove hydrogen sulphide and all the organic RSCs from municipal
wastewater odour sources. The system manufacturer shall have a minimum
of five (5) years of experience of producing similar system, and shall show
evidence of at least five (5) systems in satisfactory operation for that at least
three (3) systems in the Gulf Regions. Any manufacturer whose main
business is FRP manufacturing will not be accepted as a supplier for the
odour control system specified herein.
Duty Continuous
Location Out Door
Surface temperature 90 degree Centigrade (expose direct to sunlight)
Inlet air temperature from the sewage at 25 - 35 degree Centigrade
Inlet relative humidity up to 100%
Contaminants Hydrogen sulphide, organic RSC's, ammonia,
methyl mercaptan, Dimethyl sulphide and similar
organic sulphides, amines and any other odour as
identified during the odour investigation.
The manufacture shall submit the proposal in way to provide all the details in
a below mentioned order but all to comply with the overall requirement of this
specification:
Number of vessels _______ No
Model _______ No
Air Flow rate _______ m3/s
Gas retention time _______ sec
Maximum pressure drop across vessel _______ W.C
Contaminant concentration:
Average hydrogen sulfide concentration _______ ppmv
Peak hydrogen sulfide concentration _______ ppmv
Average odour concentration _______OU/m3
Peak odour concentration _______ OU/m3
Average ammonia concentration _______ ppmv
Peak ammonia concentration _______ ppmv
Spray water flow _______ lit./min
Spray water pressure (dynamic) _______ psi
Performance requirements:
Average Hydrogen sulfide removal > 99.5 % at discharge or < 0.10 ppmv *
The Biotrickling filter vessel shall be free standing vertical "tower" type
configuration operating in a counter-current manner. Each vessel shall
consist of one (1) or more modules containing structured media and one (1)
top piece shall be structured to confirm the quality of air release to the
atmosphere to meet the contract requirements. Each vessel shall be
constructed of Fiberglass Reinforced Plastic (FRP) and be designed with
adequate strength to support the number of required modules. Each vessel
shall contain internally as a minimum of 1.5 mm vinyl ester resin corrosion
barrier. The structural layer shall consist of isophthalic resin with chop strand
and continuous glass. The exterior top coat shall be isophthalic resin with UV
resistant pigment (minimum service life of 15 years). The exterior colour shall
be white enamel.
Biotrickling filter vessels shall not provide access to any area beneath the
media or any location within the vessel where there is a chance for dripping
acidic filtrate or hydrogen sulphide gas. The reactor vessels shall be
provided with 316 stainless steel hold down lugs to account for all the
anticipated loads to comply with local wind code requirements.
B. Media
Media shall resist compaction or swelling due to varying moisture levels and
shall not degrade when subjected to low pH (i.e. pH <2) conditions.
The uniform structure of the media shall minimize the potential for short
circuiting and encourage a uniform water and air flow pattern over the entire
media cross-sectional area.
The manufacturer shall provide evidence that the airflow through the media
is uniform from the bottom of the media is homogeneous at the average
airflow rate. Sufficient media shall be provided to ensure that all the
performance shall meet to the contract requirements as minimum.
Media shall be pre-installed in the FRP module (s) and tested in verification
of all the designed parameters as mentioned in the contract shall need to be
accepted by the ADSSC / Engineer; prior to the shipment to the job site,
C. Recirculation System
i. The recirculation system shall consist of a spray nozzle assembly above
the biotrickling filter media, and centrifugal recirculation pump. pipe shall
be schedule 80 PVC. Spray nozzles shall be PVC.
ii. Motors are 3 Phase/ 50Hz/415V, TEFC, rated for Class 1, Division 2.
iii. Pump to be constructed of corrosion resistant materials, as suitable for
the intended service.
iv. The recirculation system shall be designed to operate continuously for
entire life of odour control system
v. Each spray nozzle shall be tested by the Manufacturer and a certificate
of conformity supplied with the shop drawings to show that the nozzle
has been tested and meets the specified standards for uniform
distribution.
vi. Spray nozzle array systems with multiple nozzles may be used as per
the design requirements
vii. As applicable, the spray system shall be supplied with a nutrient addition
system to provide the macro and micronutrients required by the bacteria
for optimal metabolism of the odorous compounds being treated.
D. Control System
The ECP enclosure shall be NEMA 4X and constructed of FRP, and the
panel shall come with a 316SS panel stand. The ECP shall house with all
the necessary electronic components, PLC with Panel View Component,
HMI, etc. for the control and monitoring of the complete system. Volt free /
Dry contacts shall be provided for all the external notification of alarm status
and any other notification as require under the contract, not to limited to for
the followings:
- low spray water flow,
- high spray water flow,
- no nutrient flow (as applicable) and
- blower fail.
After the odor control system has been satisfactorily started-up and switched
to normal operation, the Contractor shall, in the presence of the Engineer,
demonstrate that the system will perform as specified in section 3.2.2.4 of
this specification.
The Contractor shall provide the Engineer with a written test protocol and the
performance test may not be conducted until the test protocol has been
reviewed and approved by the Engineer.
The manufacturer shall present during the performance test and, at its own
discretion, may conduct a parallel performance test as long as they do not
interfere with the performance test being conducted by the Contractor.
The Contractor shall supply, install and operate all equipment, sensors and
instrumentation required to complete the performance test.
1- Measure airflow into each unit and, if necessary, adjust to the design
airflow of +/- 10%. Airflow balancing can be conducted by manufacturer
and witnessed by the Engineer. Airflow shall be measured at the
beginning of the test period. The set position on the damper(s) and / or
blower VFD(s) will be marked or noted.
3. Measure temperature and relative humidity of the inlet, outlet and ambient
air.
4. Performance test period to begin at a noted time and last for four (4)
hours. H2S data from the common inlet location and from the outlet of
each odour control system will be measured and logged once every 10
minutes to demonstrate performance during test period.
a) The inlet H2S data will be logged with a pre-calibrated and approved
gas data logger with appropriate range and accuracy for the inlet air
stream (0-1000 ppmv or 0 - 200 ppmv range, 1 ppmv display
resolution or 0.0 - 50 .0 ppmv range, 0.1 ppmv display resolution) as
appropriate to match with the system requirement
b) The outlet H2S data will be logged with a pre-calibrated and
approved gas data logger with appropriate range and accuracy for
the outlet air stream. (0.0 - 2.00 ppmv range, 0.01 ppmv display
resolution or 0.0 - 50.0 ppmv range, 0.1 ppmv display resolution) as
appropriate to match with the system requirement
1. Measure airflow into each unit and, if necessary, adjust to the design
airflow of +/- 10%. Airflow balancing can be conducted by manufacturer
and witnessed by the Engineer. Airflow shall be measured at the
beginning of the test period. The set position on the damper(s) and/or
VFD(s) will be marked or noted.
3. Measure temperature and relative humidity of the inlet, outlet and ambient
air.
4. One (1 ) set of air samples, each consisting of one (1) inlet air sample and
one (1) outlet air sample from each odor control system, will be collected
in 10 L Tedlar bags with air sampling chamber. (In the event that there is
more than one odor control system, a separate inlet air sample will be
taken for each outlet air sample as near simultaneously as possible.)
Each set of samples shall be collected in duplicate to minimize the risk of
sample loss during shipping. One (1) set of bag samples per biotrickling
filter shall be analysed for odours if the results found stable and
satisfactory in comply to the standard. Bag samples will be shipped to an
In all case the system shall be design to assure the avoidance of any odour
nuisance, the site shall remain under the strict vigilance for any odour
complaint for the duration as agreed by the ADSSC and Engineer
2- The following type procedure shall be followed for the testing of the
water spray system or the manufacturer to propose their own system
of testing for the ADSSC approval.
c- In between the cycles, while the valve is CLOSED, set the target
flow rate to the proper design irrigation flow rate. Demonstrate that
the valve will automatically close in order to reach the design flow
rate within permissible time of the spray operation as set for each
cycle.
e- Set the target flow rate to the normal target irrigation flow rate.
Partially close at least one valve upstream of the modulating ball
valve and demonstrate that the irrigation valve will automatically
adjust to a more open position in order to reach the design flow rate
(as set) for the next spray cycle.
The biotrickling filter manufacturer shall warranty the structural media against
all the defects in material and workmanship for fifteen (15) years from media
delivery. In addition, the manufacturer shall also warranty the media against
shrinking, swelling, plugging and further against any increase in pressure
drop across the complete media beyond 5% form the initial reading for a
period of fifteen (15) years. In the event that it is determined that a defect
exists, at the manufacturer's shall replace the defective section in a manner
the system operation shall not be suffered in any way and all works shall no
cost to ADSSC.
4.1 GENERAL
b) Scrubber towers:
b) Gases shall be extracted and ducted to the inlet of the first stage
scrubbing tower passing vertically through a packed bed section
complete with a recirculation system set above the packing elements.
d) In the packed bed section, the gas constituents shall be dissolved and
diffused into the scrubbing liquid by means of the large liquid/fume
interfacial surface contact area provided by the packing elements.
e) The treated gas air stream shall then flow through the knitted pad type
mist eliminator. The entrained liquid droplets removed from the air
f) Liquid to the spray headers shall be recirculated from the base tank with
evaporation losses and a continuous overflow, from the discharge side
of the duty pump, replaced by water make up via a ball float valve. The
bleed off rate will be determined by site operating conditions.
b) Treated gases shall then pass from the side exit of the scrubber to the
inlet of the adjacent second stage scrubbing tower.
a) Here a similar course of events to the first stage shall occur, but an
additional Redox probe shall be provided in the sump to control the
addition of sodium hypochlorite.
b) The pH probe in this secondary tower shall control the addition of 20%
sodium hydroxide solution.
c) The final treated gases shall then be ducted to the inlet of the
duty/standby extraction fans for discharge via the exhaust stack, or via
suitable louvres if the extract fans are fitted on the scrubber inlet.
a) The scrubbing towers shall include conductive resin strips behind weld
lines, nozzle fitting joints in vessel shell, etc. to enable a full spark test to
be carried out. This will permit checks to be made on the integrity of the
inner thermoplastic shell after installation and at any time during the
lifetime of the vessel.
c) The sump section of the units shall hold recirculating scrubbing liquor
pumps and be complete with internal baffle, flanged connections and
water level measurement.
i. Overflow.
ii. Make-up water inlet, incorporating float valve,
iii. Drain outlet.
iv. Chemical dosing points.
o) The filter thickness shall be 50mm minimum with a free open area of
96%.
p) The chemical filter section shall contain media in vertical beds which
shall be suitable for horizontal air flows. Overall bed depth shall be
adjustable from 200mm minimum up to 750mm in 250m increments.
q) The air flow rate shall be designed in order to achieve a dwell time of two
seconds over the media section.
r) The media shall be capable of providing adequate odour control for peak
loadings of hydrogen sulphide up to 500 ppm whilst the average loading
is anticipated to be 5 ppm.
b) They shall be suitably rated for their duty and be selected to operate at
or near their best efficiency point.
d) Fans and their drive systems shall be securely fixed to rigid supports.
e) Where the odour control system is fan-assisted all parts exposed to the
fumes shall be non-metallic or stainless steel construction, heavy gauge
and resistant to attack.
f) The impeller shall be secured to the impeller shaft and shall be secured
against circumferential movement. The impeller shall not be pinned to
the shaft nor shall shaft movement be relied on to ensure that the
impellor is locked in position.
h) The motor and drive shall be sealed from the exhaust gas path.
i) Substantial outlet and inlet plenums with external stiffeners and flanges
shall be provided for connection to the external ductwork.
k) Panels for access shall be designed to enable manual lift-off for general
maintenance and access doors shall be provided with quarter turn quick
release fasteners, which shall be of a lockable type.
a) The Chemical Dosing pumps shall be of the double diaphragm type and
have as a minimum standard:
v. The softener shall use a fine bead resin bed in conjunction with a
brine solution.
vi. The softener shall be rated for 28 days use without the salt storage
being replenished.
vii. Flow regulating ball type valves.
viii. Flow indicator sensors, variable with adjustable high and low
sensor.
a) The storage tanks shall conform to BS 4994 and each incorporate the
following features, as a minimum:
4.12 INSTRUMENTATION
a) pH transmitters shall be provided with 110V high and low alarm contacts,
range 0-14 pH, fully programmable complete with electrodes and dip
probes.
b) Redox transmitters shall be provided with 110V high and low alarm
contacts, range 0-14 pH, fully programmable complete with electrodes
and dip probe.
c) One conductivity type level measurement device of the 24V rod type
shall be provided in each scrubbing tower.
d) One recirculation flowmeter with 110V magnetic low flow switch shall be
provided.
f) One differential air pressure switch for extract fans shall be provided.
g) One pump pressure gauge and switch shall be provided for each pair of
dosing pumps.
5. HOSES
a) In each area where chemicals are dosed or stored and there is the
possibility of chemical spillage, hose reels shall be provided as a
minimum standard.
b) They shall comply with BS 5274, BSEN 671-3 and BS 5306 part 1.
c) Each hose end shall be fitted with an adjustable jet spray shut-off of high
impact nylon, and a separate isolating valve.
6. DRENCH SHOWERS
c) Drench showers shall not be fed directly from the mains, unless a heater
is incorporated to reduce any thermal shock to the user.
END OF SECTION