Option A12 Longi LR7 HGD 590Wp PCS 90 MWP - VD7-Report
Option A12 Longi LR7 HGD 590Wp PCS 90 MWP - VD7-Report
Project: 240218 Option A12 Longi LR7 HGD 590Wp PCS 90 MWp
Variant: 240218 Option A12 Longi LR7 HGD 590Wp PCS 90 MWp
Ground system (tables) on a hill
System power: 90.00 MWp
Botley_West - United Kingdom
Author
PVDP (Germany)
Project: 240218 Option A12 Longi LR7 HGD 590Wp PCS 90
MWp
PVsyst V7.4.5
Variant: 240218 Option A12 Longi LR7 HGD 590Wp PCS 90 MWp
VD7, Simulation date:
19/02/24 19:51 PVDP (Germany)
with v7.4.5
Project summary
Geographical Site Situation Project settings
Botley_West Latitude 51.80 °N Albedo 0.20
United Kingdom Longitude -1.35 °W
Altitude 90 m
Time zone UTC
Meteo data
Woodstock
SolarGISv2.2.37 - TMY
System summary
Grid-Connected System Ground system (tables) on a hill
System information
PV Array Inverters
Nb. of modules 145158 units Nb. of units 20 units
Pnom total 90.00 MWp Pnom total 60.00 MWac
Pnom ratio 1.500
Results summary
Produced Energy 85341469 kWh/year Specific production 948 kWh/kWp/year Perf. Ratio PR 83.01 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Horizon definition 5
Near shading definition - Iso-shadings diagram 6
Main results 7
Loss diagram 8
Predef. graphs 9
Single-line diagram 15
General parameters
Grid-Connected System Ground system (tables) on a hill
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Nb. of sheds 5583 units Transposition Perez
Tilt/Azimuth 15 / -1.1 ° Sizes Diffuse Imported
Sheds spacing 6.63 m Circumsolar separate
Collector width 4.78 m
Ground Cov. Ratio (GCR) 72.2 %
Shading limit angle
Limit profile angle 31.7 °
PV Array Characteristics
PV module Inverter
Manufacturer Longi Solar Manufacturer SMA
Model LR7-72HGD-620M Model Sunny Central 3000 EV
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 620 Wp Unit Nom. Power 3000 kWac
Number of PV modules 145158 units Number of inverters 20 units
Nominal (STC) 90.00 MWp Total power 60000 kWac
Modules 5583 string x 26 In series Operating voltage 956-1425 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.50
Pmpp 83.77 MWp
U mpp 1060 V
I mpp 79005 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 1.0 % Module temperature according to irradiance Global array res. 0.26 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 1.8 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 1.0 % Loss Fraction -0.8 % Loss Fraction 2.0 % at MPP
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 655 Vac tri
Loss Fraction 0.08 % at STC
Inverter: Sunny Central 3000 EV
Wire section (20 Inv.) Copper 20 x 3 x 2500 mm²
Average wires length 10 m
MV line up to Injection
MV Voltage 33 kV
Wires Copper 3 x 1000 mm²
Length 12000 m
Loss Fraction 1.83 % at STC
AC losses in transformers
MV transfo
Medium voltage 33 kV
Transformer parameters
Nominal power at STC 88.36 MVA
Iron Loss (24/24 Connexion) 67.15 kVA
Iron loss fraction 0.08 % at STC
Copper loss 671.50 kVA
Copper loss fraction 0.76 % at STC
Coils equivalent resistance 3 x 0.04 mΩ
Horizon definition
Horizon from PVGIS website API, Lat=51°48"15', Long=-1°21"2', Alt=90m
Horizon profile
Azimuth [°] -180 -150 -143 -128 -120 -113 -105 -90 -83 -75 -38 -30
Height [°] 2.3 2.3 1.5 1.5 0.4 0.4 0.0 0.0 0.4 0.0 0.0 0.8
Azimuth [°] -23 -15 -8 8 60 68 98 105 113 120 128 180
Height [°] 1.1 1.1 0.8 0.0 0.0 0.4 0.4 0.8 1.1 1.1 2.3 2.3
Iso-shadings diagram
Orientation #1
Main results
System Production
Produced Energy 85341469 kWh/year Specific production 948 kWh/kWp/year
Perf. Ratio PR 83.01 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
1024 kWh/m² Global horizontal irradiation
+11.5% Global incident in coll. plane
Predef. graphs
Referenzenergieeinstrahlung in auf Zelloberfläche
Predef. graphs
Incident Irradiation Distribution
Predef. graphs
Array Temperature vs. Effective Irradiance
Predef. graphs
Daily System Output Energy
Predef. graphs
System-Ausgangsleistungsverteilung
Predef. graphs
Array Voltage Distribution