Professional Documents
Culture Documents
Sample Specification For HVAC Equimpent & Materials
Sample Specification For HVAC Equimpent & Materials
FOR
HVAC EQUIPMENT AND MATERIALS
JPEP-0-1340-S-3110-Rev.0
This document is of a confidential nature and is the property of JGC CORPORATION, Tokyo, Japan, and shall not be traced,
photographed, photostated or reproduced in any manner, nor used for any purpose whatsoever except by written permission of
JGC CORPORATION.
TABLE OF CONTENTS
SHEET
1. GENERAL......................................................................................................................................................4
1.1 Scope ........................................................................................................................................................4
1.2 Referenced Documents .............................................................................................................................4
1.2.1 Project Specifications........................................................................................................................4
1.2.2 Codes/Standards................................................................................................................................4
1.2.3 Local Regulations..............................................................................................................................4
1.3 Environmental Constraints........................................................................................................................5
1.4 General Requirements for HVAC Equipment/Materials ...........................................................................5
1.5 Noise and Vibration ..................................................................................................................................5
4. AIR FILTERS...............................................................................................................................................12
7. HUMIDIFIERS ............................................................................................................................................14
FORM 799-2 3
JOB No. DOC. No. REV.
11. PIPING FOR REFRIGERANT, CHILLED WATER, STEAM AND CONDENSATE DRAINS ..............17
11.1 Refrigerant Piping...................................................................................................................................17
11.2 Chilled Water Piping...............................................................................................................................17
11.3 Steam Piping...........................................................................................................................................17
11.4 Condensate Drain Piping ........................................................................................................................17
FORM 799-2 3
JOB No. DOC. No. REV.
1. GENERAL
1.1 Scope
This specification covers the requirements for equipment, materials, products, items, etc. (hereinafter called
“Equipment/Materials”), to be used for HVAC (Heating, Ventilating and Air Conditioning) systems for
buildings in the ABC Project (hereinafter called “this Project”).
This specification defines a quality and/or performance level/grade of the Equipment/Materials which will/may
be used for buildings in this Project. Possibly some of the Equipment/Materials will not be used during detailed
engineering phase.
This specification is also intended to establish standard levels/grades of quality/performance and is not intended
to prevent the use of equivalents of the Equipment/Materials or ones of better or higher quality.
Where Equipment/Materials to be used or required are not specified in this specification, Project Specifications
listed in Section 1.2.1 below, codes/standards listed in ANNEX- A below, applicable local regulations, or
drawings, such Equipment/Materials to be used shall be commercially available ones of ordinary quality/grade.
When any of the provisions of this Specification cannot be complied with, JGC shall be consulted.
1.2.2 Codes/Standards
International codes/standards referenced in this specification shall be applied wholly or partially in conjunction
with this specification for the selection of the Equipment/Materials, and shall form integral parts of this
specification. The referenced international codes/standards are summarized in ANNEX - A below, in which
their editions applicable to this Project are also indicated.
Where any specific requirements are prescribed in this specification, they shall supersede those given in the
codes/standards.
Where two or more codes/standards are applicable to one (1) Equipment/Material, one of such codes/standards
that is the most appropriate in the light of the availability of the Equipment/Material in local market, etc., shall
be applied.
FORM 799-2 3
JOB No. DOC. No. REV.
shall prevail.
FORM 799-2 3
JOB No. DOC. No. REV.
FORM 799-2 3
JOB No. DOC. No. REV.
2.2.2 Water Chilling Units, Pumps, Expansion Tanks and Holding Tanks
(1) General Requirements for Water Chilling Units
Water Chilling Units shall be factory-assembled with compressors, drives, evaporators, condensers, control
systems, interconnecting piping and cabling and all other necessary equipment, devices and accessories.
The units shall be designed to function as a year-round air conditioning system. Where required in the
design, the outdoor units shall have a heat pump duty.
The chilling units shall be completely assembled and tested, complete with refrigerant charge and ready to
operate.
For refrigerant, refer to Section 2.1 above.
Cabinet of the chilling units shall make unit fully weatherproofed for outdoor installation, and shall have
suitable corrosion-resistant finish.
Removable safety guards shall be provided for equipment not to be housed in the cabinet.
The chilling units shall be provided with factory-wired self-contained control panel complete with all
necessary accessories for optimum operation, and with built-in protection system against overcurrent,
overload, high/low pressure and the like.
Recovering from the failure shall be by means of manual reset switch. An automatic reset is not permitted.
The chilling units shall contain indicator lights so designed as to make known type of failure, unless a
change to the standardized unit is required.
The chilling units shall transmit a failure alarm signal (as a common) to HVAC Panel as specified in
“Specification for Building Electrical Equipment and Materials (see Section 1.2.1 above)”. Control signal
interface between the unit and the HVAC Panel may be in accordance with the manufacturer’s standard
specification for the unit. It is preferable, however, that the HVAC Panel should power the signal circuit
with AC 24V, 1A max. for continuous signal (contact/close: alarm, break/open: normal condition), unless
noted otherwise.
(2) Compressors
A vapor compression system shall be one of the following types of compressors.
(a) Reciprocating Compressors:
Capacity control shall be by means of cylinder unloading in equal steps which shall determine the
design and operating temperatures of chilled water systems. Reciprocating compressors shall have
either hermetic, semi-hermetic or open drive motor configuration.
(b) Centrifugal Compressors:
They shall generally incorporate two stages of compression with an interstage economizer to improve
efficiency. Modulated control approaching 10% of full rated capacity shall be attainable, in
conjunction with condensing pressure control.
Centrifugal compressors may be direct driven or driven via a speed increasing gear train and may be
semi-hermetic (thereby eliminating the need for drive shaft seal) or open drive.
(c) Screw Compressors:
Capacity control, down to 10% output, shall be achieved by varying the compressors displacement by
means of a slide valve to retard the point at which compression commences.
Units incorporating a flooded evaporator require an oil recovery system to remove the small quantity
of lubricating and seal oil injected into the compressor, which will collect in the evaporator. Oil
coolers shall be provided on units which utilize the oil to remove some of the heat of compression.
Drives may be semi-hermetic or open in the same manner as centrifugal compressors. The machines
shall be suitable for use with both shell and tube water-cooled and air cooled condensers.
FORM 799-2 3
JOB No. DOC. No. REV.
(3) Evaporators
Evaporators shall be either of the following types in accordance with manufacturer’s standard:
Refrigerant direct expansion cooling coil type (the material comply with requirements in Section 2.1
above)
Flooded shell and tube type
(4) Condensers
Condensers shall be either of the following types, as required in the design:
(a) Water-Cooled Shell and Tube Type Condensers:
Condenser pressure control shall be maintained by controlling cooling water temperature. This shall
be achieved by by-passing the cooling tower to give constant flow through the condenser at varying
temperature, and prevents low water velocities through the tubes which could lead to increased
fouling. Throttling water flow through the condenser is not acceptable as this causes surging in the
compressor.
(b) Air-Cooled Type Condensers:
The large sized units shall generally be arranged with the coils in a flat horizontal configuration with
vertical air flow to present the lowest profile least affected by wind conditions.
The large units, condenser pressure control shall be achieved by varying the air flow over the tubes.
i.e., by fan speed control. In similar units, it shall be achieved by causing liquid refrigerant to
partially fill the tubes and thereby reduce the effective cooling surface. This method calls for a
receiver to store the additional refrigerant,
For refrigerants and coils, refer to Section 2.1 above.
(5) Chilled Water Pumps
Chilled water pumps shall be skid-mounted and assembled as an one-piece. They shall be completely
factory-assembled, tested and delivered so as to be ready to operate by the pump manufacturer under his
sole responsibility.
A cooling/heating water service pump associated with HVAC applications shall generally be of single stage
centrifugal type having a backward curved vaned impeller fitted in volute shaped casing to provide
maximum conversion of kinetic energy into pressure energy. A large capacity of the pump shall be of
“Split Casing” type.
The pumps shall be provided with mechanical seals and heavy duty ball bearings in combination with
sleeve bearings as applicable. All pump materials in contact with water shall be selected in accordance
with electro potential tables to avoid corrosive or electrolytic attack.
Pumps, motors and associated drives shall be readily accessible for operation, maintenance and repairs.
(6) Expansion Tanks
Expansion tank shall be of hermatic type and shall have diaphragm control. The expansion tank shall be
manufactured of carbon steel.
(7) Holding Tanks
Holding tank shall be provided for the chilled water circuit to avoid frequent switching on and off of the
water chilling unit. The holding tank shall be manufactured of carbon steel.
FORM 799-2 3
JOB No. DOC. No. REV.
FORM 799-2 3
JOB No. DOC. No. REV.
FORM 799-2 3
JOB No. DOC. No. REV.
FORM 799-2 3
JOB No. DOC. No. REV.
like.
Switches shall be furnished on the air conditioners to select on/off and room temperatures and cooling/heating
(if used for cooling and heating purposes) as a minimum.
Where shutdown control with a fire alarm signal is required by the design, it shall be by means of HVAC Panel
as specified in “Specification for Building Electrical Equipment and Materials (see Section 1.2.1 above)”.
4. AIR FILTERS
(1) Filters for Air Handling Units for the Central Air Conditioning Systems:
Prefilters shall be of approximately 75% dust weight arrestance per ASHRAE 52.1. The prefilters shall be
re-usable and washable.
Final filters shall be of 85% minimum of average dust spot efficiency per ASHRAE 52.1.
(2) Filters for Single Package Air Conditioners:
Prefilters shall be of approximately 75% dust weight arrestance per ASHRAE 52.1. The prefilters shall be
re-usable and washable.
(3) Filters for Ducted Split-System Air Conditioners:
Prefilters shall be of approximately 75% dust weight arrestance per ASHRAE 52.1. The prefilters shall be
re-usable and washable.
(4) Filters for Duct-Free Split-System Air Conditioners and Window Type Room Air Conditioners:
The filter shall be manufacturer’s standard prefilters associated with the air conditioners. The prefilters
shall be re-usable and washable and approximately 50% dust weight arrestance per ASHRAE 52.1.
FORM 799-2 3
JOB No. DOC. No. REV.
5. VENTILATION FANS
Ventilation fans shall be selected, considering suitable type, capacity, class, noise, etc. complying with the
requirements for the HVAC system.
Fan motor shall have at least 4 poles, except that 2-pole motor may be used only where specified room noise
limits can be maintained. Note that 6-(or more)pole motors will possibly be required for rooftop exhaust fans,
axial fans and other large fans in order to satisfy the room noise limits.
All fans shall be tested in accordance with the requirements of ASHRAE 51and AMCA 210, or the
manufacturer’s equivalent standards.
Each fan/motor unit shall be completely factory-assembled, tested and delivered so as to be ready to operate by
the fan manufacturer under his sole responsibility.
Centrifugal fans shall be skid-mounted assemblies, complete with suitable mounting steel channels and
appropriate vibration isolators for minimizing vibration and vibration-induced noise.
Belt guards shall be provided for all centrifugal fans.
Where the fans are installed in hazardous areas, they shall be suitable for applicable zone of the classification of
hazardous area.
Fans used for laboratory exhaust system shall have suitable resistance against corrosion, dissolution, melting,
etc., as applicable, due to the effluents, temperature, etc.
Rooftop exhaust fans shall be provided with an automatic shutter and bird screen.
Wall fan shall be provided with an automatic shutter and weather hood.
FORM 799-2 3
JOB No. DOC. No. REV.
Where required by the design, airflow interlocks shall be provided to keep the heater from operating with
extremely low or no airflow.
In addition, overcurrent protection short-circuit fuses or breakers shall be provided in the duct heaters.
Moisture-resistant type duct heaters shall be used, where they are used with humidifiers, or used with air
conditioners or other air-cooling equipment that may result in condensation of moisture shall be identified as
suitable for use with air conditioners.
7. HUMIDIFIERS
Humidifiers shall be selected, considering the quality of the supply water. Or, supply water shall be treated to
suit water type required by the humidifier. Humidifier manufacturer’s literature shall be consulted.
Where steam humidifiers are required by the design, they shall be of “Self-Contained Type” which is a
packaged steam generation unit separate from air handling unit.
9.1 Ductwork
Ductwork shall be permitted to be rigid or flexible and shall be constructed of materials that are reinforced and
sealed to satisfy the requirements for the use of the air duct system, and shall be constructed of steel or other
suitable materials permitted by NFPA 90A.
The material, thickness, construction and installation of ducts shall provide structural strength and durability in
conformance with ASHRAE Handbook - HVAC Systems and Equipment, and referenced standards invoked
therein.
Duct construction shall be in accordance with SMACNA HVAC Duct Construction Standards - Metal and
Flexible, or internationally recognized equivalent standards.
All ductwork shall be provided with suitable resistance to corrosion caused by environmental air, wind-borne
dust, airborne chemicals, galvanic attack and others that may be encountered. Air ducts for outdoor installation
shall be weathertight.
Galvanized steel sheets shall be G60 coated steel sheet (Z180 for SI unit) by hot-dip process conforming to
ASTM A 653, or its equivalent material.
Galvanized steel ducts need not be painted unless noted otherwise.
All ductwork (supply air, return air, exhaust air) that may result in condensation of moisture shall be properly
insulated with necessary thickness of suitable material.
As a minimum requirement, the insulation shall be of glasswool with a density of not less than 24 kg/m3 or
equivalent material.
The glasswool insulation and other blanket type insulation shall have a reflective aluminum foil vapor barrier
FORM 799-2 3
JOB No. DOC. No. REV.
9.3 Louvers
Blades and frames of louvers shall be made of tempered aluminum alloy extrusions. The surface of all
aluminum extrusions and assemblies shall be natural anodized to anodic coating thickness of not less than 15
microns.
Alternatively, steel louvers may be applied. The steel louvers shall be of, as a minimum requirement, nominal
1.0 mm thick (20 gage) galvanized steel blades and nominal 1.3 mm thick (18 gage) galvanized steel frame, and
shall be finished with suitable paints.
The color shall match that of the wall.
Free area through which air can pass shall be at least 35% of the louver face area (louver width x louver height
= area of the opening for installation of the louver on the wall).
External louvers shall be provided with bird screens of corrosion-resistant material.
Where required, air intake louver shall be provided with a filter specified in Section 4 (7) above.
For louvers on metal wall cladding and door louvers, refer to “Specification for Architectural Materials (see
Section 1.2.1 above)”.
10.1 Dampers
Volume dampers, back draft dampers, motorized dampers, pressure relief dampers and other dampers shall be in
accordance with the manufacturer’s standards, and be suitable for the requirements for HVAC system.
Volume dampers shall be of manually operated, opposed acting multiple blade type, and shall be suitable for
modulating control of airflow.
The damper shall be equipped with an adjustable operating quadrant/position indicator. Bushing/end-bearing for
blade end supports shall be of bronze, stainless steel or other suitable corrosion-resistant materials.
Motorized dampers shall be of multiple blade type, and shall be suitable for two positions of open-closed
control. The damper blades shall be provided with durable air seals with the damper in closed position.
Pressure relief dampers shall be of parallel acting multiple blade type having adjustable tension spring or
counterweight for pressure control set at specified relief pressure.
Dampers used for laboratory exhaust system shall have suitable resistance against corrosion, dissolution,
FORM 799-2 3
JOB No. DOC. No. REV.
All pressures above shall be assumed as triangular load pulse with zero rise time and decreasing linearly
with time.
FORM 799-2 3
JOB No. DOC. No. REV.
11. PIPING FOR REFRIGERANT, CHILLED WATER, STEAM AND CONDENSATE DRAINS
Note that requirements in this Section will not be applied to piping system installed inside equipment like air
conditioning unit, steam convectors. Origin country code/standard shall be applied in lieu in order to avoid
unnecessary change to the standardized equipment.
FORM 799-2 3
JOB No. DOC. No. REV.
ANNEX - A
REFERENCED CODES/STANDARDS
The following international codes/standards shall be applied wholly or partially in conjunction with this
specification for the selection of the Equipment/Materials to be used for HVAC systems for buildings, and shall
form integral parts of this specification including referenced ones invoked in the following codes/standards.
Years shown in (parentheses) denote editions of the codes/standards applicable to this Project.
ASME B16.22 : Wrought Copper and Copper Alloy Solder Joint Pressure Fittings (1995)
ASTM A653 : Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated
(Galvannealed) by the Hot-Dip Process (1998)
ASTM B88 : Specification for Seamless Copper Water Tube (1999)
ASTM B280 : Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field
Service (1998)
ASTM C534 : Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet
and Tubular Form (1999)
ASTM C591 : Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal
Insulation (1994)
NFPA 90A : Standard for the Installation of Air Conditioning and Ventilating Systems (1999)
JIS H3300 : Copper and Copper Alloy Seamless Pipes and Tubes (1997)
FORM 799-2 3