GRUNDFOS DATA BOOKLET

S pumps, range 70
80 to 140 kW
60 Hz
S pumps, range 70

1. Introduction 4
Table of contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Main constructional features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. Performance range 5
Performance range overview, S pumps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Performance range, S pumps, range 70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
List of pump curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3. Identification 7
Type key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pump nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ex approval plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable entry approval plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4. Selection of product 9
Ordering the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5. Product range 10
Standard pumps - cast iron, 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Explosion-proof pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

6. Variants 14
List of variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7. Construction 15
Sectional drawing, motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Components and material specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

8. Product description 26
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Motor range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Explosion-proof pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Level controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

9. Curve charts and technical data 34


How to read the curve charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Curve conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Pump performance testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Performance-test types for end-suction pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Specifying acceptance grades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Witness test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

10. Performance curves and technical data 40


Low pressure - 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Low pressure - 3 x 460 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Medium pressure - 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Medium pressure - 3 x 460 V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Medium pressure - 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Medium pressure - 3 x 460 V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
High pressure - 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
High pressure - 3 x 460 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
High pressure - 3 x 380/660 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
High pressure - 3 x 460 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

11. Accessories 60
Accessories (for installation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

12. Dimensions 63
Recommendation for pump foundations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

2
S pumps, range 70

Basic pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Table of contents
Installation on auto-coupling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Dry, vertical installation on concrete foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Dry, horizontal installation on base stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

13. Weights 74

14. Flange forces 75

15. Grundfos Product Center 76

3
1 S pumps, range 70

1. Introduction
Introduction

Introduction Applications
This data booklet deals with Grundfos heavy-duty S pumps are designed for applications, such as these:
sewage pumps, type S, range 70. • raw-water intake
• wastewater treatment plants
• municipal pumping stations
• public buildings
• blocks of flats
• industries
• garages
• underground car parks
• car-wash areas
• restaurants and hotels.
The pumps are suitable for both temporary and
permanent installation. The lifting bracket fitted on the
pumps facilitates easy transportation as well as
installation at the installation site.

Main constructional features


TM07 0831 0718

• Leak-proof connection on auto coupling via the


Grundfos SmartSeal sealing system
• double mechanical shaft seal system for reliable
Fig. 1 S pump, range 70 sealing between pumped liquid and motor
S pumps, range 70, are a range of free-flow channel • watertight cable entry of corrosion-resistant
impeller pumps specifically designed for pumping polyamide
sewage and wastewater in a wide range of municipal, • moisture switch for continuous monitoring of motor
private and industrial applications. housing and terminal box ensuring automatic cut-off
The pumps are made of resistant materials, such as of power in case of ingress of liquid
cast iron and stainless steel. These materials ensure a • self-cleaning channel impeller with long vanes
proper operation. reducing the risk of jamming or clogging or
The pumps are fitted with motors from 80 kW up to 140 SuperVortex impeller with high pumping efficency
kW. The motors are either 4-, 6- or 8-pole motors, and less downtime
depending on the motor size. • SmartTrim system allowing easy adjustment of
The free passage in the pumps is 90 to 145 mm. impeller clearance and maintaining maximum pump
efficiency over pump lifetime
The pumps are available for these types of installation:
• motor in insulation class F (155 °C), enclosure class
• submerged installation on auto-coupling system
IP68 with three thermal sensors in stator windings
• submerged installation, free-standing
• shaft seal condition monitoring via water-in-oil
• dry installation, vertical sensor (optional)
• dry installation, horizontal. • explosion-proof motors for applications involving
potential risk of explosion
• two stainless steel versions for use in corrosive or
aggressive liquids:
– stainless steel impeller, cast iron pump and motor
housing
– stainless steel pump housing, flange and impeller,
cast iron motor housing made entirely of
corrosion-resistant stainless steel.

4
S pumps, range 70
2

2. Performance range

Performance range
Performance range overview, S pumps

+
>P@
 +]



 




 

 


 


                  

TM03 9286 0515


4>OV@

          


   4>PñK@

5
2 S pumps, range 70

Performance range, S pumps, range 70


Performance range

H
[m]
S Pumps
80
Range 70
70 60 Hz
60

50
S2.90.200
40

30
S2.100.200 S2
.12
25 2. 2
50

20
S3.
120
.30
0
15

S2.105.250 S2.145.300

10 S3.115.500

TM04 2263 4818


0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900
Q [l/s]

0 400 800 1200 1600 2000 2400 2800 Q [m³/h]

List of pump curves


3 x 380/660 V 3 x 460 V
Curve chart on Curve chart on
Pump type Pressure range Pump type Pressure range
page page
S3.115.500.800.8.70L S3.115.500.800.8.70L
Low 40 Low 42
S3.115.500.1400.6.70L S3.115.500.1400.6.70L
S2.100.200.1000/1200.4.70M S2.100.200.1000/1200.4.70M
44 46
S2.145.300.1100.6.70M S2.145.300.1100.6.70M
Medium Medium
S3.120.300.800.8.70M S3.120.300.800.8.70M
48 50
S3.120.300.1400.6.70M S3.120.300.1400.6.70M

S2.90.200.1000/1200.2.70H 52 S2.90.200.1000/1200.2.70H 54
High High
S2.105.250.800.8.70H S2.105.250.800.8.70H
56 58
S2.122.250.1100/1400.6.70H S2.122.250.1100/1400.6.70H

6
S pumps, range 70
3

3. Identification

Identification
Type key 1
The power output (P2) indicated in the type key, which is used to
indicate the motor size, can deviate from the actual power output.
Please note that the pump type described in this Please refer to the nameplate or the chapter Performance curves
and technical data for the exact power output.
booklet is not necessarily available in all variants. 2 PTC sensors are connected directly to IO 113 or other PTC relay.
Example S1.100.100.55.4.50M.S.205.G.N.D.511.Z
Code Explanation Designation Pump nameplate
Grundfos sewage and wastewater
S
pump
Pump type 1
Multi-channel impeller pump installed
ST
in a column pipe 2 23
1 Single-channel impeller
2 Two-channel impeller 3 12
Impeller type
3 Three-channel impeller 4 13
V SuperVortex impeller 14
100 Maximum solid size [mm] Pump passage 5
15
Nominal diameter of pump outlet port 6
Pump outlet, S-type 16
100 [mm]
Nominal diameter of column pipe [mm] Pump outlet, ST-type 7 17
P2 = Code number from type
55 Power output [kW] 1 8 18
designation / 10

TM06 0370 5313


2 2-pole motor 19
9
4 4-pole motor 20
6 6-pole motor 10
Number of poles 21
8 8-pole motor
11 22
10 10-pole motor
12 12-pole motor Fig. 2 Pump nameplate
50 Range 50
54 Range 54
Pos. Description
58 Range 58
Pump range 1 Type designation
62 Range 62
66 Range 66 2 Product number
70 Range 70 3 Serial number
S Super-high 4 Maximum head
H High 5 Maximum installation depth
M Medium 6 Number of phases
Pressure version
L Low 7 Voltage, delta connection
E Extra-low
8 Voltage, star connection
F Super-low
9 Rated power input, P1
Submersible installation without
S 10 Cos φ, 1/1 load
cooling jacket
Submersible installation with cooling 11 Production code, year and week
C Installation type
jacket 12 Generation code
D Dry installation, vertical 13 Maximum ambient temperature
H Dry installation, horizontal
14 Maximum flow rate
Impeller diameter
205 Impeller diameter [mm] 15 Enclosure class
(mean)
Cast iron impeller, pump housing and 16 Frequency
G
stator housing 17 Rated speed
Stainless steel impeller, DIN W.-Nr. Material code for 18 Current, delta connection
Q
1.4408 impeller, pump
19 Current, star connection
Stainless steel impeller and pump housing and stator
S housing 20 Rated power output, P2
housing, DIN W.-Nr. 1.4408
Stainless steel impeller, pump housing 21 Insulation class
R
and stator housing, DIN W.-Nr. 1.4408 22 Net weight
N Non-explosion-proof pump 23 Place of production
Pump version
Ex Pump with explosion-proof motor
B Pump with built-in SM 113 2
C Not in use
Sensor version
S pump without built-in SM 113
D
module.
5 50 Hz
Frequency [Hz]
6 60 Hz
3 x 400 / 690 V, Y/D (50 Hz only)
11
3 x 460 V, Y/D (60 Hz only) Voltage code and
13 3 x 415 V, Y/D (50 Hz only) connection
15 3 x 380 / 660 V, Y/D (60 Hz only)
GPA Pumps only for Australia
Customisation
Z Custom-built products

7
3 S pumps, range 70

Ex approval plates Cable entry approval plate


Identification

TM06 7260 1217


II2G
Baseefa17ATEX0013U
DK-8850 Bjerringbro, Denmark DK-8850 Bjerringbro, Denmark
0344

Made in H-8000 Székesfehérvár, Hungary

Made in H-8000 Székesfehérvár, Hungary


IECEx BAS 17.0007U
II2G 0344 II2G 0344 Ex db IIB Gb Tamb =-5°C–+80°C
ID no DK-8850
Ex b c IIB T3 Ex b c IIB T4
Baseefa 09ATEX0020X Baseefa 09ATEX0020X Fig. 4 Cable entry approval plate

TM06 7560 4617 - TM06 7561 4617


Ex db IIB T3 Gb Ex db IIB T4 Gb
IECEx BAS09.0006X IECEx BAS09.0006X The approval plate gives the following details:
Type Type Pos. Description

yyww/no yyww/no CE CE-mark


Warnings: Warnings: 1180 Number of quality assurance notified body
Do not open when energized. Do not open when energized or when
explosive gas atmosphere is present.
Cable temperature may exceed 70ºC.
Cable temperature may exceed 70°C. EU ex-symbol
Cable gland size and installation:see
Cable gland size and installation:see
installation and operating instructions.
Tamb=-5°C–+40°C
installation and operation manual. II Equipment group (II = non-mining)
Tamb=-5°C–+40°C
98488084 98488082 2 Equipment category (high protection)
G Type of explosive atmosphere
Fig. 3 Approval plates of Ex pumps, range 70
Ex Explosion-proof motor according to European standard

The approval plates give the following details: b Control of ignition sources
d Flameproof
Pos. Description IIB Gas group (Ethylene)
Tamb Ambient temperature
EU Ex symbol
Gb Equipment protection level, zone 1
II Equipment group (II = non-mining)
Baseefa Certificate number
2 Equipment category (high protection)
IECEx Certificate number
G Type of explosive atmosphere (G = Gas)
ID no Inlet identification number (e.g. 36-1)
CE CE mark
0344 Number of quality assurance notified body
Ex Explosion-proof motor according to European standard
b Control of ignition sources
c Constructional safety
db Flameproof enclosure
IIB Gas group (Ethylene)
T3 Maximum surface temperature of the motor is 200 °C
T4 Maximum surface temperature of the motor is 135 °C.
Gb Equipment protection level, zone 1
Baseefa Certificate number
IECEx Certificate number

8
S pumps, range 70
4

4. Selection of product

Selection of product
Ordering the product Accessories
When ordering the product you need to take the Depending on the installation type, you may need to
following four aspects into consideration: order accessories. See Accessories, page 60 for
selection of the correct accessories.
1. pump
Note: Ordered accessories are not fitted from factory.
2. custom-built variation (option)
3. accessories Controller
4. controller.
Grundfos Dedicated Controls (DC) is available.
Pump
Use Product range, page 10 and Type key, page 7 to
identify the pump that best fulfils your needs. The list
below is a detailed description of the product you get if
you order the following pump:
Pump Product no
S2.90.200.1000.4.70H.S.340.G.N.D.611 95113053
• Pump as specified in the type key
• 10 m cable
• Paint: black, NCS 9000N/RAL 9005, gloss 30,
thickness 150 µm
• Three thermal switches (Klixon) or three thermal
sensors (PTC) in stator windings
• One moisture switch below the motor top cover (two
moisture switches in explosion-proof versions; one

TM06 6501 1515


below the motor top cover and one in the stator
housing in the bottom of the motor)
• Test according to ISO 9906:2012, grade 3B.
See Performance curves and technical data, page 40
Fig. 5 Grundfos Dedicated Controls
for selection of a standard pump.
Note: Product-specific data for the pump can also be Grundfos Dedicated Controls is a control system
found in Grundfos Product Center using the product designed for installation in either commercial buildings
number 95113053. or network pumping stations with one to six pumps.
As standard, the system is supplied with application-
Custom-built variants optimised software and can be configured to meet your
The S pumps can be customised to meet individual specific pumping needs.
requirements. Many pump features and options are For more information about Grundfos Dedicated
available for customisation, e.g. explosion-proof controls, see Level controllers, page 28.
versions, various cable lengths or special materials.
Variants can be seen in List of variants, page 14. For
requirements or designs not included in the list,
contact Grundfos.

9
5 S pumps, range 70

5. Product range
Product range

Standard pumps - cast iron, 3 x 380/660 V


Accessories

Cable length To be ordered separately


Pump type Pump Horizontal base
[m]
stand 1 Vertical base plate
Auto-coupling
system 2
S2.90.200.1000.4.70H.S.340.G.N.D... 10 96800719 - - 96641489
S2.90.200.1000.4.70H.C.340.G.N.D... 10 96800720 - - 96641489
S2.90.200.1000.4.70H.D.340.G.N.D... 10 96800732 - 96308240 -
S2.90.200.1000.4.70H.H.340.G.N.D... 10 96800733 96308212 - -
S2.90.200.1200.4.70H.S.361.G.N.D... 10 96800744 - - 96641489
S2.90.200.1200.4.70H.C.361.G.N.D... 10 96800745 - - 96641489
S2.90.200.1200.4.70H.D.361.G.N.D... 10 96800747 - 96308240 -
S2.90.200.1200.4.70H.H.361.G.N.D... 10 96800748 96308212 - -
S2.100.200.1000.4.70M.S.332.G.N.D... 10 96800779 - - 96641489
S2.100.200.1000.4.70M.C.332.G.N.D... 10 96800780 - - 96641489
S2.100.200.1000.4.70M.D.332.G.N.D... 10 96800782 - 96308240 -
S2.100.200.1000.4.70M.H.332.G.N.D... 10 96800783 96308212 - -
S2.100.200.1200.4.70M.S.355.G.N.D... 10 96800784 - - 96641489
S2.100.200.1200.4.70M.C.355.G.N.D... 10 96800785 - - 96641489
S2.100.200.1200.4.70M.D.355.G.N.D... 10 96800787 - 96308240 -
S2.100.200.1200.4.70M.H.355.G.N.D... 10 96800788 96308212 - -
S2.105.250.800.8.70H.S.523.G.N.D... 10 99442981 - - 96782483
S2.105.250.800.8.70H.C.523.G.N.D... 10 99442982 - - 96782483
S2.105.250.800.8.70H.D.523.G.N.D... 10 99442983 - 96308241 -
S2.105.250.800.8.70H.H.523.G.N.D... 10 99442984 96308192 - -
S2.122.250.1100.6.70H.S.443.G.N.D... 10 96800734 - - 96782483
S2.122.250.1100.6.70H.C.443.G.N.D... 10 96800735 - - 96782483
S2.122.250.1100.6.70H.D.443.G.N.D... 10 96800736 - 96308241 -
S2.122.250.1100.6.70H.H.443.G.N.D... 10 96800738 96308192 - -
S2.122.250.1400.6.70H.S.465.G.N.D... 10 96800749 - - -
S2.122.250.1400.6.70H.C.465.G.N.D... 10 96800750 - - 96782483
S2.122.250.1400.6.70H.D.465.G.N.D... 10 96800751 - 96308241 -
S2.122.250.1400.6.70H.H.465.G.N.D... 10 96800753 96308192 - -
S3.115.500.800.8.70L.S.402.G.N.D... 10 96800769 - - 96782485
S3.115.500.800.8.70L.C.402.G.N.D... 10 96800770 - - 96782485
S3.115.500.800.8.70L.D.402.G.N.D... 10 96800771 - 96308244 -
S3.115.500.800.8.70L.H.402.G.N.D... 10 96800773 96308192 - -
S3.115.500.1400.6.70L.S.371.G.N.D... 10 96800759 - - 96782485
S3.115.500.1400.6.70L.C.371.G.N.D... 10 96800760 - - 96782485
S3.115.500.1400.6.70L.D.371.G.N.D... 10 96800761 - 96308244 -
S3.115.500.1400.6.70L.H.371.G.N.D... 10 96800763 96308192 - -
S3.120.300.800.8.70M.S.442.G.N.D... 10 96800774 - - 96782484
S3.120.300.800.8.70M.C.442.G.N.D... 10 96800775 - - 96782484
S3.120.300.800.8.70M.D.442.G.N.D... 10 96800776 - 96308241 -
S3.120.300.800.8.70M.H.442.G.N.D... 10 96800778 96308192 - -
S3.120.300.1400.6.70M.S.407.G.N.D... 10 96800764 - - 96782484
S3.120.300.1400.6.70M.C.407.G.N.D... 10 96800765 - - 96782484
S3.120.300.1400.6.70M.D.407.G.N.D... 10 96800766 - 96308241 -
S3.120.300.1400.6.70M.H.407.G.N.D... 10 96800768 96308192 - -
S2.145.300.1100.6.70M.S.420.G.N.D... 10 96800739 - - 96782484
S2.145.300.1100.6.70M.C.420.G.N.D... 10 96800740 - - 96782484
S2.145.300.1100.6.70M.D.420.G.N.D... 10 96800741 - 96308241 -
S2.145.300.1100.6.70M.H.420.G.N.D... 10 96800743 96308255 - -
1
Pumps of installation type H include the standard horizontal stand. Pumps with material code G or Q include a painted-steel stand. If another
horizontal stand is required, order a pump of installation type D together with the required stand.
2
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw mounted on the flange.

10
S pumps, range 70
5
Cast iron, 3 x 460 V

Product range
Accessories

Cable length To be ordered separately


Pump type Pump Horizontal base
[m]
stand 1 Vertical base plate
Auto-coupling
system 2
S2.90.200.1000.4.70H.S.340.G.N.D... 10 95113053 - - 96641489
S2.90.200.1000.4.70H.C.340.G.N.D... 10 95113054 - - 96641489
S2.90.200.1000.4.70H.D.340.G.N.D... 10 96800721 - 96308240 -
S2.90.200.1000.4.70H.H.340.G.N.D... 10 95113055 96308212 - -
S2.90.200.1200.4.70H.S.361.G.N.D... 10 95113062 - - 96641489
S2.90.200.1200.4.70H.C.361.G.N.D... 10 95113063 - - 96641489
S2.90.200.1200.4.70H.D.361.G.N.D... 10 96800746 - 96308240 -
S2.90.200.1200.4.70H.H.361.G.N.D... 10 95113064 96308212 - -
S2.100.200.1000.4.70M.S.332.G.N.D... 10 95113083 - - 96641489
S2.100.200.1000.4.70M.C.332.G.N.D... 10 95113084 - - 96641489
S2.100.200.1000.4.70M.D.332.G.N.D... 10 96800781 - 96308240 -
S2.100.200.1000.4.70M.H.332.G.N.D... 10 95113085 96308212 - -
S2.100.200.1200.4.70M.S.355.G.N.D... 10 95113086 - - 96641489
S2.100.200.1200.4.70M.C.355.G.N.D... 10 95113087 - - 96641489
S2.100.200.1200.4.70M.D.355.G.N.D... 10 96800786 - 96308240 -
S2.100.200.1200.4.70M.H.355.G.N.D... 10 95113088 96308212 - -
S2.105.250.800.8.70H.S.523.G.N.D... 10 99442977 - - 96782483
S2.105.250.800.8.70H.C.523.G.N.D... 10 99442978 - - 96782483
S2.105.250.800.8.70H.D.523.G.N.D... 10 99442979 - 96308241 -
S2.105.250.800.8.70H.H.523.G.N.D... 10 99442980 96308192 - -
S2.122.250.1100.6.70H.S.443.G.N.D... 10 95113056 - - 96782483
S2.122.250.1100.6.70H.C.443.G.N.D... 10 95113057 - - 96782483
S2.122.250.1100.6.70H.D.443.G.N.D... 10 95113058 - 96308241 -
S2.122.250.1100.6.70H.H.443.G.N.D... 10 96800737 96308192 - -
S2.122.250.1400.6.70H.S.465.G.N.D... 10 95113065 - - 96782483
S2.122.250.1400.6.70H.C.465.G.N.D... 10 95113066 - - 96782483
S2.122.250.1400.6.70H.D.465.G.N.D... 10 95113067 - 96308241 -
S2.122.250.1400.6.70H.H.465.G.N.D... 10 96800752 96308192 - -
S3.115.500.800.8.70L.S.402.G.N.D... 10 95113077 - - 96782485
S3.115.500.800.8.70L.C.402.G.N.D... 10 95113078 - - 96782485
S3.115.500.800.8.70L.D.402.G.N.D... 10 95113079 - 96308244 -
S3.115.500.800.8.70L.H.402.G.N.D... 10 96800772 96308192 - -
S3.115.500.1400.6.70L.S.371.G.N.D... 10 95113071 - - 96782485
S3.115.500.1400.6.70L.C.371.G.N.D... 10 95113072 - - 96782485
S3.115.500.1400.6.70L.D.371.G.N.D... 10 95113073 - 96308244 -
S3.115.500.1400.6.70L.H.371.G.N.D... 10 96800762 96308192 - -
S3.120.300.800.8.70M.S.442.G.N.D... 10 95113080 - - 96782484
S3.120.300.800.8.70M.C.442.G.N.D... 10 95113081 - - 96782484
S3.120.300.800.8.70M.D.442.G.N.D... 10 95113082 - 96308241 -
S3.120.300.800.8.70M.H.442.G.N.D... 10 96800777 96308192 - -
S3.120.300.1400.6.70M.S.407.G.N.D... 10 95113074 - - 96782484
S3.120.300.1400.6.70M.C.407.G.N.D... 10 95113075 - - 96782484
S3.120.300.1400.6.70M.D.407.G.N.D... 10 95113076 - 96308241 -
S3.120.300.1400.6.70M.H.407.G.N.D... 10 96800767 96308192 - -
S2.145.300.1100.6.70M.S.420.G.N.D... 10 95113059 - - 96782484
S2.145.300.1100.6.70M.C.420.G.N.D... 10 95113060 - - 96782484
S2.145.300.1100.6.70M.D.420.G.N.D... 10 95113061 - 96308241 -
S2.145.300.1100.6.70M.H.420.G.N.D... 10 96800742 96308255 - -
1
Pumps of installation type H include the standard horizontal stand. Pumps with material code G or Q include a painted-steel stand. If another
horizontal stand is required, order a pump of installation type D together with the required stand.
2
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw mounted on the flange.

11
5 S pumps, range 70

Explosion-proof pumps
Product range

Cast iron, 3 x 380/660 V


Accessories

Cable length To be ordered separately


Pump type Pump Horizontal base
[m]
stand 1 Vertical base plate
Auto-coupling
system 2
S2.90.200.1000.4.70H.C.340.G.EX.D... 10 96800989 - - 96641489
S2.90.200.1000.4.70H.D.340.G.EX.D... 10 96800991 - 96308240 -
S2.90.200.1000.4.70H.H.340.G.EX.D... 10 96801002 96308212 - -
S2.90.200.1000.4.70H.S.340.G.EX.D... 10 96800988 - - 96641489
S2.90.200.1200.4.70H.C.361.G.EX.D... 10 96801019 - - 96641489
S2.90.200.1200.4.70H.D.361.G.EX.D... 10 96801021 - 96308240 -
S2.90.200.1200.4.70H.H.361.G.EX.D... 10 96801022 96308212 - -
S2.90.200.1200.4.70H.S.361.G.EX.D... 10 96801018 - - 96641489
S2.100.200.1000.4.70M.C.332.G.EX.D... 10 96801004 - - 96641489
S2.100.200.1000.4.70M.D.332.G.EX.D... 10 96801006 - 96308240 -
S2.100.200.1000.4.70M.H.332.G.EX.D... 10 96801007 96308212 - -
S2.100.200.1000.4.70M.S.332.G.EX.D... 10 96801003 - - 96641489
S2.100.200.1200.4.70M.C.355.G.EX.D... 10 96801024 - - 96641489
S2.100.200.1200.4.70M.D.355.G.EX.D... 10 96801026 - 96308240 -
S2.100.200.1200.4.70M.H.355.G.EX.D... 10 96801027 96308212 - -
S2.100.200.1200.4.70M.S.355.G.EX.D... 10 96801023 - - 96641489
S2.105.250.800.8.70H.S.523.G.EX.D... 10 99442989 - - 96782483
S2.105.250.800.8.70H.C.523.G.EX.D... 10 99442990 - - 96782483
S2.105.250.800.8.70H.D.523.G.EX.D... 10 99442991 - 96308241 -
S2.105.250.800.8.70H.H.523.G.EX.D... 10 99442993 96308192 - -
S2.122.250.1100.6.70H.C.443.G.EX.D... 10 96801009 - - 96782483
S2.122.250.1100.6.70H.D.443.G.EX.D... 10 96801010 - 96308241 -
S2.122.250.1100.6.70H.H.443.G.EX.D... 10 96801012 96308192 - -
S2.122.250.1100.6.70H.S.443.G.EX.D... 10 96801008 - - 96782483
S2.122.250.1400.6.70H.C.465.G.EX.D... 10 97549520 - - 96782483
S2.122.250.1400.6.70H.D.465.G.EX.D... 10 97549542 - 96308241 -
S2.122.250.1400.6.70H.H.465.G.EX.D... 10 97549544 96308192 - -
S2.122.250.1400.6.70H.S.465.G.EX.D... 10 97549518 - - 96782483
S2.145.300.1100.6.70M.C.420.G.EX.D... 10 96801014 - - 96782484
S2.145.300.1100.6.70M.D.420.G.EX.D... 10 96801015 - 96308241 -
S2.145.300.1100.6.70M.H.420.G.EX.D... 10 96801017 96308255 - -
S2.145.300.1100.6.70M.S.420.G.EX.D... 10 96801013 - - 96782484
S3.115.500.1400.6.70L.C.371.G.EX.D... 10 97549548 - - 96782485
S3.115.500.1400.6.70L.D.371.G.EX.D... 10 97549550 - 96308244 -
S3.115.500.1400.6.70L.H.371.G.EX.D... 10 97549552 96308192 - -
S3.115.500.1400.6.70L.S.371.G.EX.D... 10 97549546 - - 96782485
S3.115.500.800.8.70L.C.402.G.EX.D... 10 96801034 - - 96782485
S3.115.500.800.8.70L.D.402.G.EX.D... 10 96801035 - 96308244 -
S3.115.500.800.8.70L.H.402.G.EX.D... 10 96801037 96308192 - -
S3.115.500.800.8.70L.S.402.G.EX.D... 10 96801033 - - 96782485
S3.120.300.1400.6.70M.C.407.G.EX.D... 10 97549556 - - 96782484
S3.120.300.1400.6.70M.D.407.G.EX.D... 10 97549558 - 96308241 -
S3.120.300.1400.6.70M.H.407.G.EX.D... 10 97549560 96308192 - -
S3.120.300.1400.6.70M.S.407.G.EX.D... 10 97549554 - - 96782484
S3.120.300.800.8.70M.C.442.G.EX.D... 10 96801039 - - 96782484
S3.120.300.800.8.70M.D.442.G.EX.D... 10 96801040 - 96308241 -
S3.120.300.800.8.70M.H.442.G.EX.D... 10 96801042 96308192 - -
S3.120.300.800.8.70M.S.442.G.EX.D... 10 96801038 - - 96782484
1
Pumps of installation type H include the standard horizontal stand. Pumps with material code G or Q include a painted-steel stand. If another
horizontal stand is required, order a pump of installation type D together with the required stand.
2
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw mounted on the flange.

12
S pumps, range 70
5
Cast iron, 3 x 460 V

Product range
Accessories

Cable length To be ordered separately


Pump type Pump Horizontal base
[m]
stand 1 Vertical base plate
Auto-coupling
system 2
S2.90.200.1000.4.70H.C.340.G.EX.D... 10 95113092 - - 96641489
S2.90.200.1000.4.70H.D.340.G.EX.D... 10 96800990 - 96308240 -
S2.90.200.1000.4.70H.H.340.G.EX.D... 10 95113093 96308212 - -
S2.90.200.1000.4.70H.S.340.G.EX.D... 10 95113091 - - 96641489
S2.90.200.1200.4.70H.C.361.G.EX.D... 10 95113104 - - 96641489
S2.90.200.1200.4.70H.D.361.G.EX.D... 10 96801020 - 96308240 -
S2.90.200.1200.4.70H.H.361.G.EX.D... 10 95113105 96308212 - -
S2.90.200.1200.4.70H.S.361.G.EX.D... 10 95113103 - - 96641489
S2.100.200.1000.4.70M.C.332.G.EX.D... 10 95113095 - - 96641489
S2.100.200.1000.4.70M.D.332.G.EX.D... 10 96801005 - 96308240 -
S2.100.200.1000.4.70M.H.332.G.EX.D... 10 95113096 96308212 - -
S2.100.200.1000.4.70M.S.332.G.EX.D... 10 95113094 - - 96641489
S2.100.200.1200.4.70M.C.355.G.EX.D... 10 95113107 - - 96641489
S2.100.200.1200.4.70M.D.355.G.EX.D... 10 96801025 - 96308240 -
S2.100.200.1200.4.70M.H.355.G.EX.D... 10 95113108 96308212 - -
S2.100.200.1200.4.70M.S.355.G.EX.D... 10 95113106 - - 96641489
S2.105.250.800.8.70H.S.523.G.EX.D... 10 99442985 - - 96782483
S2.105.250.800.8.70H.C.523.G.EX.D... 10 99442986 - - 96782483
S2.105.250.800.8.70H.D.523.G.EX.D... 10 99442987 - 96308241 -
S2.105.250.800.8.70H.H.523.G.EX.D... 10 99442988 96308192 -
S2.122.250.1100.6.70H.C.443.G.EX.D... 10 95113098 - - 96782483
S2.122.250.1100.6.70H.D.443.G.EX.D... 10 95113099 - 96308241 -
S2.122.250.1100.6.70H.H.443.G.EX.D... 10 96801011 96308192 - -
S2.122.250.1100.6.70H.S.443.G.EX.D... 10 95113097 - - 96782483
S2.122.250.1400.6.70H.C.465.G.EX.D... 10 97549519 - - 96782483
S2.122.250.1400.6.70H.D.465.G.EX.D... 10 97549541 - 96308241 -
S2.122.250.1400.6.70H.H.465.G.EX.D... 10 97549543 96308192 - -
S2.122.250.1400.6.70H.S.465.G.EX.D... 10 97549517 - - 96782483
S2.145.300.1100.6.70M.C.420.G.EX.D... 10 95113101 - - 96782484
S2.145.300.1100.6.70M.D.420.G.EX.D... 10 95113102 - 96308241 -
S2.145.300.1100.6.70M.H.420.G.EX.D... 10 96801016 96308255 - -
S2.145.300.1100.6.70M.S.420.G.EX.D... 10 95113100 - - 96782484
S3.115.500.1400.6.70L.C.371.G.EX.D... 10 97549547 - - 96782485
S3.115.500.1400.6.70L.D.371.G.EX.D... 10 97549549 - 96308244 -
S3.115.500.1400.6.70L.H.371.G.EX.D... 10 97549551 96308192 - -
S3.115.500.1400.6.70L.S.371.G.EX.D... 10 97549545 - - 96782485
S3.115.500.800.8.70L.C.402.G.EX.D... 10 95113113 - - 96782485
S3.115.500.800.8.70L.D.402.G.EX.D... 10 95113114 - 96308244 -
S3.115.500.800.8.70L.H.402.G.EX.D... 10 96801036 96308192 - -
S3.115.500.800.8.70L.S.402.G.EX.D... 10 95113112 - - 96782485
S3.120.300.1400.6.70M.C.407.G.EX.D... 10 97549555 - - 96782484
S3.120.300.1400.6.70M.D.407.G.EX.D... 10 97549557 - 96308241 -
S3.120.300.1400.6.70M.H.407.G.EX.D... 10 97549559 96308192 - -
S3.120.300.1400.6.70M.S.407.G.EX.D... 10 97549553 - - 96782484
S3.120.300.800.8.70M.C.442.G.EX.D... 10 95113116 - - 96782484
S3.120.300.800.8.70M.D.442.G.EX.D... 10 95113117 - 96308241 -
S3.120.300.800.8.70M.H.442.G.EX.D... 10 96801041 96308192 - -
S3.120.300.800.8.70M.S.442.G.EX.D... 10 95113115 - - 96782484
1
Pumps of installation type H include the standard horizontal stand. Pumps with material code G or Q include a painted-steel stand. If another
horizontal stand is required, order a pump of installation type D together with the required stand.
2
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw mounted on the flange.

13
6 S pumps, range 70

6. Variants
Variants

List of variants
Motor
15 m
25 m
Various cable lengths
30 m
50 m
10 m
15 m
EMC power cables Screened power cables for variable-speed drives 25 m
30 m
50 m
Special motor Insulation class H
Special oil Non-toxic Shell Ondina X420 1

Motor protection
Pt100 on lower bearing + Pt100 on upper bearing + Pt100
Sensor set 2
on windings
Pt100 on lower bearing + Pt100 on upper bearing + Pt100
Sensor set 3
on windings + PVS3 vibration sensor
External water-in-oil sensor WIO

Coating
300 µm (painted twice)
Special paint thickness
450 µm (painted three times)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Impeller (external surface)
Belzona 1321 coating (brush painted, blue)
Impeller (internal surface) Chesterton ARC 855 ceramic coating (grey)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Pump housing (internal) Belzona 1321 coating (brush painted, blue)
Chesterton ARC 855 ceramic coating (grey)
Epoxy coating (NCS 900N/RAL 9005 gloss 30, black)
Inlet cover Belzona 1321 coating (brush painted, blue)
Chesterton ARC 855 ceramic coating (grey)
Zinc anodes (outside of inlet cover / pump housing) 3 pcs.

Materials
Stainless steel lifting bracket AISI 316
Stainless steel shaft AISI 329
Impeller Duplex stainless steel ASTM A890 Grade 3A

Tests
Test at specified duty on standard impeller curve
Trimmed impeller for specified duty test
Additional test of entire QH curve (including report) 5-10 points on the pump performance curve
ISO 9906:2012 grade 1E
tolerances
ISO 9906:2012 grade 1B/1U
Different test standard Efficiency guaranteed by Grundfos
tolerances
ISO 9906:2012 grade 2B/2U
tolerances
Vibration test (including report) According to Grundfos factory quality standard
Performance test on dry test stand Contact Grundfos
NPSHr test Contact Grundfos
String test Contact Grundfos
Witness test Contact Grundfos

Miscellaneous
Special packaging Contact Grundfos
Special nameplate Contact Grundfos
Old UK-guide shoe Contact Grundfos / order guide shoe installation kit
Other variants Contact Grundfos
1
For pumps with WIO sensor Shell Ondina is not an option.

14
S pumps, range 70
7

7. Construction

Construction
Sectional drawing, motors

TM06 3962 1315

Fig. 6 Non-explosion-proof motor without cooling jacket (installation type S)

15
7 S pumps, range 70
Construction

TM06 3964 1315

Fig. 7 Non-explosion-proof motor with cooling jacket (installation types C, D and H)

16
S pumps, range 70
7

Construction
TM06 3963 1315

Fig. 8 Explosion-proof motor without cooling jacket (installation type S)

17
7 S pumps, range 70
Construction

TM06 3965 1315

Fig. 9 Explosion-proof motor with cooling jacket (installation types C, D and H)

18
S pumps, range 70
7
Pump

Construction
TM04 2589 2708

Fig. 10 Basic pump, installation types S and C

19
7 S pumps, range 70
Construction

TM04 2707 2808

Fig. 11 Basic pump, installation types D and H

20
S pumps, range 70
7

Construction
TM04 2708 4116

Fig. 12 Installation type S and C pump on auto coupling

21
7 S pumps, range 70
Construction

TM04 2585 2708


Fig. 13 Installation type D, dry, vertical pump on base plate - version 1

TM04 2588 2708

Fig. 14 Installation type D, dry, vertical pump on base plate - version 2

22
S pumps, range 70
7

Construction
494
495

37
7a 301 26 26c
76

0.7 0.2

62
66
9a
67
67b
62a

12c 12

35a

TM04 2590 0817


35

487 37b 1 50 49 39a 12a 39


Fig. 15 Installation type H, dry, horizontal installation on base stand - version 1

495
494
50
37b
7a 39a
76 301 26
12a
39
12
35 0.7 0.2

62a
9a
67b
35a
67
12c

62 49
TM04 2591 0817

487
Fig. 16 Installation type H, dry, horizontal installation on base stand - version 2

23
7 S pumps, range 70
Construction

494/495

12 39 12a 39a 50 37b 26 301 76/ 7a

0.7 0.2
35

35a
67
12c 67b
66
62a
9a
62

49

TM07 0974 0918


487

Fig. 17 Installation type H, dry, horizontal installation on base stand -version 3

24
S pumps, range 70
7
Components and material specification

Construction
Motor
DIN W.Nr./ DIN W.Nr./
AISI/ AISI/
Pos. Component Material EN Pos. Component Material EN
ASTM ASTM
standard standard

7a Rivet Stainless steel 1.4436 316 250b Rubber seal


25 Pressure test plug Stainless steel 1.4436 316 250 Cable clamp PA or cast iron
25a Screw Stainless steel 1.4436 316 252 Cable ATON
26a Screw Stainless steel 1.4436 316 269 Angle ring Steel
37a O-ring NBR rubber 270 Lock nut Steel
48 Stator package 271 Lock washer Steel
55 Stator housing Cast iron 1 EN-JL 1040 A48 30 520 Moisture switch3
58 Seal housing Cast iron 520a Screw Stainless steel 1.4436 316
59 Bearing bracket cover Cast iron 522 Holder
59a Locking ring Aluminium 522c Spring washer
59b Pin Steel 1
Available in stainless steel (custom-built option).
Lower bearing bracket 2
60 Cast iron Ex versions have cast iron cable entry.
cover
3
61c Upper bearing bracket Cast iron Ex versions have two moisture switches.
72 O-ring NBR rubber
72a O-ring NBR rubber Pump
76a Approval plate Stainless steel
77 Seal housing cover Cast iron DIN W.Nr./
AISI/
Pos. Component Material EN
100 O-ring NBR rubber ASTM
standard
SiC/SiC or
105 Primary shaft seal 1 Intermediate ring Cast iron
SiC/carbon
SiC/SiC or 7a Rivet
105b Secondary shaft seal
SiC/carbon 9a Key (for keyway) Stainless steel 1.4436 316
107 O-ring NBR rubber 12 Flange Cast iron
109 O-ring Viton rubber 12a Inlet cover Cast iron
150 Stator housing complete 12c Adjusting screw Stainless steel 1.4436 316
150c Cooling jacket Galvanized steel 26 Screw Stainless steel 1.4436 316
153 Ball bearing Stainless steel 26c Screw Stainless steel 1.4436 316
153a Spring Steel 35 Screw Stainless steel
154 Ball bearing Stainless steel 35a Screw Stainless steel
155 Lower bearing bracket Cast iron 1 37 O-ring NBR rubber
157 O-ring NBR rubber 37b O-ring NBR rubber
157b O-ring NBR rubber 39 O-ring NBR rubber
Steel, brass or 39a O-ring NBR rubber
162 Roller bearing
steel cage
49 Impeller Cast iron1 EN-JL 1050
164a Motor top cover Cast iron
50 Volute casing Cast iron1 EN-JL 1050
168 Cable entry PA or cast iron 2
62 O-ring NBR rubber
High tensile
172 Shaft with rotor 1.7225 62a O-ring NBR rubber
steel
Cast iron or
173 Screw Stainless steel 1.4436 316 66 Cap
stainless steel
173b Earth terminal
67 Impeller screw Stainless steel 1.4436 316
173e Screw Stainless steel 1.4436 316
67b O-ring NBR rubber
173f Spring washer Stainless steel 1.4436 316
76 Nameplate
173g Earth connector
301 Motor housing
176a Terminal block
487 Base stand, horizontal Steel
176b Screw Stainless steel 1.4436 316
487a Base plate
176c Terminal block
494 Plug Stainless steel 1.4436 316
176d Terminal block
495 O-ring NBR rubber
177a Protection sleeve Rubber or plastic
762 Stand
178 Screw Stainless steel 1.4436 316
180 Cable clamp PA or cast iron 1 Available in stainless steel (custom-built option).
180a Screw Stainless steel 1.4436 316
181 Cable ATON Accessories
181a Screw Stainless steel 1.4436 316
182a Screw Stainless steel 1.4436 316 Pos. Component Material
182b Screw Stainless steel 1.4436 316
487 Base stand, horizontal1 Cast iron or steel
184 Screw Stainless steel 1.4436 316
701 Auto-coupling base unit Cast iron2
186 Screw Stainless steel 1.4436 316
702 Guide rail bracket Cast iron2
190 Lifting handle Steel
703 Guide claw 3 Cast iron2
190a Screw Stainless steel
762 Base plate, vertical Cast iron or steel
190b Screw Stainless steel
190c Lifting bracket Galvanized steel 1 Pumps of installation type H include the standard horizontal stand.
193 Plug Stainless steel 1.4436 316 Pumps with material code G or Q include a painted-steel stand. If
194 O-ring NBR rubber another horizontal stand is required, order a pump of installation
type D together with the required stand.
197 Washer Stainless steel 1.4436 316
2
198 Rubber seal
Available in stainless steel (custom-built option).
3 Guide claws for DN 250 outlets or bigger are factory fitted.
248 Screw Stainless steel 1.4436 316
248a Screw Stainless steel 1.4436 316
250a Cable entry PA or cast iron

25
8 S pumps, range 70

8. Product description
Product description

Features Shaft seal


The pumps have a primary and a secondary shaft seal.
SmartTrim
The material combination of the primary shaft seal of
On conventional pumps, maintaining factory-set all pump types is silicon carbide/silicon carbide. For
impeller clearance is a time-consuming and costly the secondary shaft seal, the material combination is
task. The pumps need to be disconnected from the silicon carbide/carbon.
pipes and to be totally dismantled, and new parts need
The shaft seals are placed in the oil chamber of the
to be mounted in order to maintain full pumping
pump. The oil chamber provides reliable sealing
efficiency. Not so with Grundfos SmartTrim!
between the pumped liquid and the motor.
All Grundfos heavy-duty channel-impeller pumps,
The shaft seals have no springs or other parts in direct
whether for submerged or dry installation, are
contact with the pumped liquid. This prevents rags and
equipped with the unique SmartTrim impeller
fibres from getting caught. The shaft seals are
clearance adjustment system. This enables you to
bidirectional, meaning that they can operate in either
easily restore factory-set impeller clearance and
direction, thus allowing for opposite rotation caused by
maintain peak pumping efficiency. All you need to do is
back-flow of liquid through the pump.
to tighten the adjustment screws on the exterior of the
impeller housing. This can be done on site, quickly and Motor
easily, without dismantling the pump and without using The motor is a watertight, totally encapsulated motor.
special tools. • Insulation class F (155 °C).
Efficiency drop in % • Temperature rise class F (105 K).
• Enclosure class IP68.
Factory-set impeller clearance
0 For motor protection and sensors, see Sensors, page
3 A 27.
6 Cables
9 The pumps have H07RN-F AT power cables as
12 standard or screened ATON EMC VSCCB power
TM04 2391 2508

cables on request.
15 B
The pumps have H07RN-F 450/750 V control cables
Years as standard or screened ATON VSCB 450/750 V
1 2 3 4 5 control cables on request.
A: With Grundfos SmartTrim impeller clearance The cables are 10 m long as standard. Other cable
adjustment system lengths are available on request. See List of variants,
B: Without impeller clearance adjustment system page 14.
SmartSeal The number and dimension of cables depend on the
motor size.
For the pumps with DN 250 outlet or larger, the
Grundfos SmartSeal auto-coupling sealing mounted on Motor power
Voltage
Cable size
[kW] [power + control]
the pump outlet flange provides a completely leak-
proof connection between the pump and the base unit 2 x 4 x 25 mm2 +
3 x 460 V 7 x 1.5 mm2
of the auto-coupling system. This optimises the 80
3 x 380/660 V 2 x 4 x 25 mm2 +
efficiency of the entire pumping system and keeps 10 x 1.5 mm2
operating costs at a minimum. 2 x 4 x 25 mm2 +
3 x 460 V
7 x 1.5 mm2
Bearings 95
2 x 4 x 35 mm2 +
3 x 380/660 V
The bearings are greased for life. 7 x 1.5 mm2
Main bearings: Double-row angular contact ball 2 x 4 x 35 mm2 +
3 x 460 V
7 x 1.5 mm2
bearing. Single or pair mounted angular contact ball 110
2 x 4 x 50 mm2 +
bearings for axial forces and cylindrical roller bearing 3 x 380/660 V
7 x 1.5 mm2
for radial forces. 2 x 4 x 50 mm2 +
3 x 460 V
Support bearings: Single-row deep-groove ball 7 x 1.5 mm2
120
bearing. 2 x 4 x 70 mm2 +
3 x 380/660 V
7 x 1.5 mm2
3 x 460 V 2 x 4 x 70 mm2 +
140
3 x 380/660 V 7 x 1.5 mm2

26
S pumps, range 70
8
Power cable Testing

Product description
All pumps are tested before leaving the factory. The
Outer cable
Cable type Weight Bending radius factory test report is based on ISO 9906:2012, grade
diameter
[mm2] [kg/m] [cm]
[mm] 3B. Test reports can be ordered directly with the pump
4 x 25 28.9 -31.4 1.88 19 or can be ordered separately based on the pump serial
4 x 35 32.5 - 34.7 2.43 22 number.
4 x 50 37.7 - 40.4 3.24 25
Other tests or third party inspection certificates are
4 x 70 42.7 - 45.4 4.30 28
available on request. See List of variants, page 14.
Control cable

Cable type
Outer cable
Weight Bending radius
Operating conditions
diameter
[mm2] [kg/m] [cm]
[mm] Pumps without cooling jacket in submerged
7 x 1.5 14.4 - 16.4 0.35 10 installation:
Cable entry • Continuous operation when pump is fully
submerged to the top of the motor.
Watertight PA or cast iron cable entry with soft shape
and sealing rings to prevent damage of the cable or • Intermittent operation with maximum 20 starts per
leaks. hour when the pump is submerged to the middle of
the motor and with short periods of operation down
Sensors to the top of the pump housing.
As standard the pump is equipped with these switches Warning: A motor protection device must be used
or sensors: to cut off power supply in case of overheating.
• Three thermal switches (Klixon) or three thermal Note: Explosion proof pumps without cooling jacket
sensors in the stator housing. must always be fully submerged.
• One moisture switch under the motor top cover. Pumps with cooling jacket in submerged and dry
Customised sensor options installation:
1. WIO (water-in-oil) sensor • Continuous and intermittent operation with
The WIO sensor measures the water content in the maximum 20 starts per hour with water level down
oil and converts the value into an analog current to the top of the pump housing.
signal. The two sensor conductors are for power
supply as well as for carrying the signal to the Pumped liquids
measuring device or controller. The sensor pH value: 4-10
measures the water content from 0 to 20 %. It also Liquid temperature: 0-40 °C
sends a signal if the water content is outside the When pumping liquids with a density and/or a
normal range (warning), or if there is air in the oil kinematic viscosity higher than that of water, use
chamber (alarm). The sensor is fitted in a stainless motors with correspondingly higher outputs.
steel tube for mechanical protection.
The sensor is either built-in with the motor (Ex) or Sound pressure
installed as an accessory. If the sensor is installed The sound pressure level of the pump is lower than the
externally, it is fitted in a plastic hose for mechanical limiting values stated in EC Council directive 2006/42/
protection. The WIO sensor is connected to EC relating to machinery (the EC Machinery Directive).
Grundfos IO 113.
2. PVS3 (pump vibration sensor)
The vibration sensor monitors the vibration level of
the pump by using measurements of three axes and
combining them into a single measurement
outputted in an analog current signal. The sensor
acts only as a general indicator of changes in the
vibration levels. PVS3 is to be connected to
Grundfos IO 113 and SM 113. A substantial
increase in vibration will trigger a warning or an
alarm.
An increase in vibrations can be caused by a
clogged impeller, worn bearings, closed force main
valves, etc. indicating that service inspection should
be carried out quickly in order to protect the pump
or the pipe system from being damaged.
3. Bearing temperature sensor
Pt100 bearing temperature sensor installed within
the motor housing. Sensors to be connect using SM
113 and IO 113.

27
8 S pumps, range 70

Motor range Level controllers


Product description

Grundfos offers dedicated pump controllers for


Motor power [kW] Number of poles
monitoring liquid levels in the wastewater collecting
80 8
tanks to ensure correct operation and protection of the
95 4
110 6
pumps.
120 4 Grundfos pump controllers are ideally suited to
140 6 Grundfos S pumps, and include:
• Grundfos Dedicated Controls (DC)
Explosion-proof pumps • Grundfos LC controllers
Use explosion-proof pumps in potentially explosive Grundfos DC Controllers
environments.
Note: All installations must be approved by the local
authorities.
Relevant standards/regulations
• EN ISO 80079-36
• EN ISO 80079-37
• EN 60079-0
• EN 60079-1
• IEC 60079-0
• IEC 60079-1
Explosion protection classification (IECEx & ATEX)
• Group II, Category 2, Gas or vapor environment
• Ex db eb h mb IIB T3 or T4 Gb (Tamb = -5 °C to

Gr-1016086
+40 °C)
Operation with frequency converter
Only temperature class T3. Fig. 18 Grundfos Dedicated Controls control cabinet

Notified body Grundfos Dedicated Controls (DC) is a control system


SGS Baseefa designed for installation in municipal wastewater
transportation, commercial buildings or network
pumping stations with up to six wastewater pumps and
an optional mixer or a flush valve.
Advanced control and data communication are also
possible with the Grundfos Dedicated Controls system.
The control cabinets are delivered with a built-in main
switch and thermal magnetic circuit breaker.
Features and benefits:
• Advanced Flow Calculation
• Automatic energy optimisation
• Easy installation and configuration
• Configuration wizard
• Electrical overview
• Advanced data communication
• Advanced alarm and warning priority
• Supports several languages
• Daily emptying
• Mixer control or flush valve
• User-defined functions
• Anti-blocking
• Start level variation
• Advanced pump alternation with pump groups
• SMS scheduling
• Communication to SCADA, BMS, GRM or cell
phone.
Dedicated Controls is ordered either with or without a
built-in communication interface module (CIM).

28
S pumps, range 70
8
The communication module enables the possibility for IO 113

Product description
fieldbus protocol (e.g. PROFIBUS DP, Modbus RTU
The IO 113 module is a protection module for Grundfos
and PROFINET IO/Modbus TCP) and the
wastewater pumps.
communication line.
IO 113 has inputs for digital and analog pump sensors
For further information about Grundfos Dedicated
and can stop the pump if a sensor indicates a pump
Controls, please see Grundfos Product Center:
fault.
• Grundfos Dedicated Controls, brochure http://
IO 113 can be connected to the Grundfos Dedicated
net.grundfos.com/qr/i/96925597
Controls system and allows advanced monitoring
• Grundfos iSolutions, brochure http:// functions:
net.grundfos.com/qr/i/99249771
• motor temperature
• Grundfos Controls Guide, product guide http://
• moisture in motor
net.grundfos.com/qr/i/97954965
• water in oil
Additional features, CUE or VFD • insulation resistance.
The CUE/VFD (optional), which is either a Grundfos
variable frequency drive or a general variable SM 113
frequency drive, offers better pump protection and a The SM 113 module is used for collection and transfer
more steady flow through the pipe system. of sensor data in pumps and includes a large number
In addition, Grundfos CUE,VFD offers these features of sensors.
and benefits: SM 113 can be placed either inside the pump (allowing
• Anti-blocking fewer sensor conductors out of the pump) or in the
• Automatic energy optimisation control cabinet next to the pump installation.
• Specific-energy test SM 113 works together with IO 113 through a power-
• Output frequency line communication using the Grundfos GENIbus
• Monitoring of: protocol.
– voltage* SM 113 can collect data from:
– current* • 3 current sensors, 4-20 mA
– phase sequence* • 3 Pt100 thermal sensors or 3 Pt1000 thermal
sensors
– power*
• 1 PTC thermal sensor
– energy*
• 1 digital input.
– torque*
• Reverse start** MP 204
• Run flushing The MP 204 cabinet can be used as a stand-alone
• Stop flushing motor protector. MP 204 may also be incorporated in a
• PID control. Grundfos Dedicated Controls system in which it
* These functions are only available with a Grundfos functions as a motor protector. The pump is protected
CUE. secondarily by measuring the temperature with a
** We do not recommend reversing at full speed at Pt100 sensor and a PTC sensor or thermal switch.
any time. When reduced reverse operation settings
are set, make sure constant torque is enabled in
Variable Frequency Drive (VFD) (i.e. Grundfos
CUE, Siemens Simatic, ABB, Schneider Electric
etc.) to have maximum torque available when
reversing.
Grundfos LC controllers
The LC 231 pump controller is designed for level
control, monitoring and protection of Grundfos
pumping stations featuring one pump or two pumps,
starting direct-on-line. The LC 231 controller is
integrated in a polymer cabinet.
The LC 241 is a modular pump controller that has a
metal or polymer cabinet and can be customised
according to your needs.
It is designed for level control, monitoring and
protection of Grundfos pumping stations featuring one
pump or two pumps, starting direct-on-line with 0-23 A,
star-delta with 0-59 A or soft starter with 0-72 A.

29
8 S pumps, range 70
Product description

Grundfos CUE, < 250 kW, or another


frequency converter.

Control cabinet

Dedicated Controls or PLC

IO 113 SM 113
T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE

D1 D2 D3 D4 D5 D6 D7 D8 A Y B

Reset

ON DIP

1 2 3 4 5 6 7 8 9 10

P1 P2 P3 P4 P5 I1 I2 I3 1 2 3 4 5 6 7 8 9 1011 1213 14

Level sensor

SM 113, optional
1 2 3 4 5 6 7 8 9 1011 1213 14

PVS3 sensor, optional

Wiring diagram Pt100 sensor, PTC Moisture switch


optional
T2
Thermistor
T1
+t +t +t
Thermal switches WIO sensor, optional
1 1 1
Moisture switches
2 2 2

3 3 3
Pt100 in lower bearing
4 4 4
9 1
8 2 5 5 5
7 3 Pt100 in stator
6 6 6
6 4 +t
5
Pt100 in upper bearing
7 7 7
+t
TM06 8753 1117

8 Oil indicator
8 8
4 to 20 mA
9 9 9

Fig. 19 Pump with frequency converter operation

30
S pumps, range 70
8

Product description
MP 204
MP 204

Control cabinet

Dedicated Controls or PLC

IO 113 SM 113
T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 PE

D1 D2 D3 D4 D5 D6 D7 D8 A Y B

Reset

ON DIP

1 2 3 4 5 6 7 8 9 10

P1 P2 P3 P4 P5 I1 I2 I3 1 2 3 4 5 6 7 8 9 1011 1213 14

Level sensor

SM 113, optional
1 2 3 4 5 6 7 8 9 1011 1213 14

PVS3 sensor, optional

Wiring diagram PTC Moisture switch


Pt100 sensor,
optional
T2
Thermistor
T1
+t +t +t
Thermal switches
WIO sensor, optional
1 1 1
Moisture switches
2 2 2

3 3 3
Pt100 in lower bearing
4 4 4
9 1
8 2 5 5 5
7 3 Pt100 in stator
6 6 6
6 4 +t
5
Pt100 in upper bearing
7 7 7
+t
TM06 8754 1117

8 Oil indicator
8 8
4 to 20 mA
9 9 9

Fig. 20 Pump with MP 204 motor protector

31
8 S pumps, range 70

Wiring diagrams
Product description

Thermal switch Moisture switch and thermal


protectors

In Ex pumps 2 moisture switches

Motor
Read clockwise
from GND

Pt100 in lower bearing

Pt100 in stator

Thermistor

Supply cable conductors

176c
520d

176a

Stator conductors
TM04 3729 5008

Optional equipment

Fig. 21 Wiring diagrams, pumps with one power cable

Pos. Description
1 Female push-on connector
2 Wire pin
3 Butt splice
4 Ring connector
176a Terminal block (power cable connections)
176c Terminal block (sensor connections)
520d Moisture sensor

32
S pumps, range 70
8

Product description
Thermal switch Moisture switch and thermal protectors
Read clockwise
from GND
In Ex pumps 2 moisture switches Motor

Pt100 in lower bearing

Pt100 in stator

Thermistor

Supply cable conductors

176c

520d

176a

Stator conductors
TM04 3274 4008

Optional equipment

Fig. 22 Wiring diagrams, pumps with two power cables

Pos. Description
1 Female push-on connector
2 Wire pin
3 Butt splice
4 Ring connector
176a Terminal block (power cable connections)
176c Terminal block (sensor connections)
520d Moisture sensor

33
9 S pumps, range 70

9. Curve charts and technical data


Curve charts and technical data

The following many pages are divided into sections.


On pages 34-39 you will find a brief explanation of how to read the curve charts, the curve conditions, etc.

How to read the curve charts


Total pump head Pump type
H = Htotal Max. efficiency m ark
70: Range 70
M: Pressure range (Medium pressure)
S: Insulation type

p H
[kPa] [m]
600
S 2.
100
70M.S
60 .2 0
0 .1
.4 .
200 60 Hz
S2. ISO 9906:2012 3B
100
500 50
.200
.10
QH curve for the individual
00.4
. pump
400 40
S2.1
NPSH
45.30
0.110
0.6.
[m]
300 30 15

S2.145.300.1100.6.
200 20 S2.100.200.1200.4. 10

100 10
S2.100.200.1000.4.
5
NPSH curve for all variants
shown. When sizing the
pumps, add a safety margin
0 0 0 of at least 0.5 m.
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Q [m³/h]
P2
[kW]
120
S2.100.200.1200.4.
S2.145.300.1100.6.
100

80 S2.100.200.1000.4.

TM04 2089 1914


The power curves indicate
60 the pump shaft power [P2]
for the pump shown
40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

Note: The pumps are tested according to ISO 9906:2012 grade 3B tolerance. Testing equipment and measuring
instruments are designed and calibrated according to the standards mentioned. The pumps are approved according to
tolerances for entire curves, specified in grade 3B.

34
S pumps, range 70
9
Curve conditions These tolerance grades can be used in the contract

Curve charts and technical data


between the pump manufacturer and the customer, or
The guidelines below apply to the curves shown in the they can be used as part of a default tolerance factor
performance charts on pages 40-58. for cases in which no specific tolerance grade has
• Tolerances according to ISO 9906:2012, grade 3B. been agreed between the manufacturer and the
• The curves show pump performance with different customer.
impeller diameters at rated speed. The performance acceptance grades are explained in
• The curves apply to the pumping of airless water at Specifying acceptance grades, pages 38 and 39,
a temperature of 20 °C and a kinematic viscosity of showing the performance grades related to an ordinary
1 mm2/s (1 cSt). pump curve.
• NPSH: The curves show average values measured
under the same conditions as the performance The guarantee point
curves. According to ISO 9906:2012 the acceptance-grade
When sizing the pump, add a safety margin of at tolerance applies to one guarantee point.
least 0.5 m. A guarantee point is defined by a guaranteed flow rate
• In case of densities other than 1000 kg/m3, the and a guaranteed head.
outlet pressure is proportional to the density. In addition, either minimum total efficiency or
• When pumping liquids with a density higher than maximum total input power may be guaranteed at the
1000 kg/m3, motors with correspondingly higher specified conditions.
outputs must be used. This means that the standard sets guidelines for a duty
Calculation of total head point guaranteed for the following:
The total pump head consists of the height difference – Q and H, or
between the measuring points + the differential head + – Q, H and total efficiency (Eta-total), or
the dynamic head. – Q, H and total consumed power (P1).
The guarantee point is defined by a minimum of five
H total = H geo + Hstat + Hdyn measured test points.
Example of a duty point test living up to ISO 9906:2012
requirements
Hgeo: Height difference between measuring points.
Hstat: Differential head between the inlet and the H [m]
outlet side of the pump. 20
Hdyn: Calculated values based on the velocity of the 18
pumped liquid on the inlet and the outlet side of 16
the pump.
14
12
Pump performance testing 10

S pump testers are all capable of performing hydraulic 8

performance tests according to ISO 9906:2012 6

requirements. 4

TM07 0448 5117


ISO 9906:2012 sets standards for "rotodynamic 2

pumps, Hydraulic performance acceptance tests, 0


0 20 40 60 80 100 120 140 160
Grades 1, 2 and 3". Q [m3/h]

Performance acceptance grades Fig. 23 Five measured test points are used to verify one
guarantee point
Six-pump-performance-test acceptance grades, 3B,
2B, 2U, 1B, 1E and 1U are defined in ISO 9906:2012.
Mandatory Optional
Acceptance measurements measurements
grade
Q H P1 Eta-tot
3B ±9% ±7% +9% -7%
2B ±8% ±5% +8%
-5%
2U + 16 % + 10 % + 16 %
1B ±5% ±3% +4% -3%
1E ±5% ±3% +4%
≥ 0%
1U + 10 % +6% + 10 %

Q: Flow
H: Head
P1: Total consumed power
Eta-tot: Total efficiency

35
9 S pumps, range 70

Evaluation of performance What Grundfos is able to guarantee for the different


Curve charts and technical data

acceptance grades will be evaluated on a case-by-


The test must show that the measured pump curve
case basis. Contact your local sales company on this.
touches or passes through a tolerance surrounding the
guarantee point, as defined by the selected Grundfos makes duty-point verification according to
acceptance grade. ISO 9906:2012 for one guarantee point at full speed,
50 or 60 Hz. The customer must tell Grundfos which
Guarantee-point evaluation must be made at the rated
duty point to verify.
speed, which for S pumps means 50 Hz or 60 Hz.
The requested duty point is verified by five measured
Head points.
Grade 1U duty-point verification
The following example illustrates performance testing
according to Grade 1U.
Pass Flow rate and head are mandatory, and efficiency or
H-
guaranteed power consumption, P1, is optional.
Fail
Tolerances for a Grade 1U test are as follows:
Pass
– Flow rate: 10 %

TM07 1544 1818


Pass Fail – Head: 6 %
– Efficiency: 0 %, only equal to or better than the
guaranteed value
Q-guaranteed Flow – P1: 10 %
Fig. 24 Pump curves that either pass or fail to cross the 1. Q, H and Eta-tot are tested and verified
tolerance cross of the guarantee point
H [m]
20
Performance-test types for end- 18
suction pumps 16
14
Two types of performance tests are available for S
12
pumps:
10
• duty-point-verification test 8
• curve test. 6
Tests carried out on S pumps 4

TM07 1542 1618


2
– Tests are saved for at least five years and can be
traced using the pump’s unique serial number. 0
0 200 400 600 800 1000 1200
– It is not possible to change acceptance grade on 3
Q [m /h]
an already tested and supplied pump; if required,
a re-test of the pump is needed. Fig. 25 Measured values for flow rate and head
– Witness testing can be arranged.
Eta-tot % [m]
Duty-point-verification test, Grades 3B, 2B, 2U, 1B,
1E and 1U 80

This test method offers the possibility to perform a 70

duty-point verification of the following: 60

– Q and H, or 50

– Q, H and total efficiency (Eta-tot), or 40

– Q, H and total consumed power (P1). 30


20
Mandatory Optional
TM07 1543 1618

Acceptance measurements measurements 10


grade
Q H P1 Eta-tot 0
0 200 400 600 800 1000 1200
3B Standard On request
Q [m3/h]
2B
On request On request
2U
Fig. 26 Measured values for total efficiency
1B
1E On request On request 2. Q, H and P1 tested and verified
1U

36
S pumps, range 70
9
In fig. 29, tolerance crosses according to Grade 3B

Curve charts and technical data


H [m]
have been distributed across the complete
20
performance range of a pump. We generate the upper
18
and lower limit of the performance curve by drawing
16
two curves at the outlines of these crosses.
14
When the pump is tested, and the measured point is
12
located within the range between upper and lower
10
limit, it meets the ISO 9906:2012 Grade 3B tolerances.
8 This way of qualifying the pump performance is stricter
6 than a duty-point-verification test for Grade 3B.
4

TM07 1542 1618


2 How does Grundfos perform curve
0
0 200 400 600 800 1000 1200
testing for S pumps
Q [m3/h] Grundfos applies two types of curve tests:
• a reference curve test
Fig. 27 Measured values for flow rate and head
• a performance curve test.

P1 [kW] Reference curve test, Grade 3B


20 A reference curve test is made when no curve test
18 report is specified with the order. Three or four test
16 points are measured depending on production site,
14 and no curve test report is supplied with the pump.
12 Measurements are made to maintain and observe
10 continuous quality and to ensure that the supplied
8 pump is within test grade tolerances. Test grade
6 tolerances are set as for Grade 3B but without
4 certification.
TM07 1545 1618

2 Example of a reference curve test


0
0 200 400 600 800 1000 1200
H P1
Q [m3/h] [m] [kW]
75 150
70 140
Fig. 28 Measured values for consumed power
65 130
60 120
Note that other points than the guarantee point can be 55 110
measured and displayed in a curve-test report 50 100
according to Grade 3B tolerances. 45 90
40 80

Curve test, Grade 3B 35


30
70
60
This test method is developed by Grundfos and is 25 50
20 40
based on ISO 9906:2012 performance acceptance

TM07 1674 1918


15 30
grade 3B tolerances: Q = ± 9 %, H = ± 7 %. 10 20
5 10
H [m] 0 0
0 100 200 300 Q [l/s]

Fig. 30 Measured values for tested pump







/RZHUOLPLW
TM07 1515 1618

 8SSHUOLPLW

6WDQGDUGFXUYH

     
Q [m3/h]

Fig. 29 Q-H curve with tolerance crosses on complete


performance range

37
9 S pumps, range 70

If the customer requires more points on the curve to be


Curve charts and technical data

H P1
[m] [kW] checked, individual measurements must be made,
75 150
70 140
which is not part of the performance curve test.
65 130
Static high pressure test
60 120
55 110 All produced pumps undergo a static high pressure
50 100
test of 1.5 x PN (nominal pressure of the pump).
45 90
40 80
35
30
70
60
Specifying acceptance grades
25 50
The graphs in the table on page 39 show the

TM07 1693 2018


20 40
15 30
tolerances as stated in the standard, related to an
10 20 ordinary pump curve. The graphs also show which
5 10 pump performance to expect if the customer, having
0
0 100 200 300 Q [l/s]
0
the same pump to start with, orders a pump with the
same guarantee point for different tolerances (B, E or
Fig. 31 The values in fig. 30 calculated to reference speed
U) within the acceptance grades.
for comparison to a reference performance curve
In some cases, it will not be possible to fulfil the same
If a pump performance report is requested at a later guarantee point for a unilateral tolerance as it will for a
stage, only reference test data are available. bilateral tolerance. This is indicated by the lower curve
for "E" and "U" grades.
Performance curve test, grade 3B
If the requested guarantee point is the same for a
A performance curve test is carried out when a curve Grade U pump as for a Grade B pump, the
test report is specified with the order. consequence of the production tolerances could be
The pump is tested at pre-specified flow rates, and test that a larger pump is required to obtain the requested
grade tolerances are set as for Grade 3B but without duty point.
certification.
What Grundfos is able to guarantee for the different
Example of an S pump curve test acceptance grades will be evaluated on a case-by-
case basis. Contact your local sales company on this.
H P1
[m]
75
[kW]
150 Acceptance grades and tolerances
70 140
65 130
Acceptance grade B
60 120 This acceptance grade refers to grades with a bilateral
55 110
50 100
tolerance on flow rate and head and with a tolerance
45 90 on efficiency.
40 80
35 70
Acceptance grade E
30 60 This acceptance grade refers to a grade with a
25 50
20 40
bilateral tolerance on flow rate and head, but without
tolerance on efficiency.
TM07 1674 1918

15 30
10 20
5 10
Acceptance grade U
0 0 This acceptance grade refers to a grade with a
0 100 200 300 Q [l/s] unilateral tolerance on flow rate and head. For the 2U
Fig. 32 Measured values for tested pump grade, there is a tolerance on efficiency. For the 1U
grade, there is no tolerance on efficiency.
H P1
Note that if the acceptance grade changes from Grade
[m] [kW] 1B to 1U, the customer does not necessarily get a
75 150
70 140
better pump with a higher efficiency. More likely, he
65 130 gets a pump where the performance is always to the
60 120 positive side of the guarantee point.
55 110
50 100
45 90
40 80
35 70
30 60
25 50
TM07 1693 2018

20 40
15 30
10 20
5 10
0 0
0 100 200 300 Q [l/s]

Fig. 33 The values in fig. 32 calculated to a reference


speed for comparison to a reference performance

38
S pumps, range 70
9

Curve charts and technical data


Acceptance grade
B E U
H
H: ±7%

Q: ±9%

Grade 3

Ș Ș: í7%

H H
H: ±5% H: +10%

Q: ±8% Q: +16%

Q Q
Grade 2

Ș Ș: í5% Ș Ș: í5%

Q Q

H H H
H: ±3% H: ±3% H: +6%

Q: ±5% Q: ±5% Q: +10%

Q Q Q

Grade 1

Ș: í3% Ș: •0% Ș: •0%


Ș Ș Ș

Q Q Q

Certificates Witness test


Certificates have to be confirmed for every order and When the pumps are being tested or are tested with a
are available on request as follows: certification, it is possible for the customer to witness
• certificate of compliance with the order the testing procedure according to ISO 9906:2012.
(EN 10204-2.1) The witness test is not a certificate and will not result in
• pump test sheet. a written statement from Grundfos. The witness itself is
the only guarantee that everything is carried out as
prescribed in the testing procedure.
If the customer wants to witness the test, place this
request on the order.

39
10
Performance curves and technical data

10. Performance curves and technical data


Low pressure - 3 x 380/660 V
S3.115.500.800.8 and S3.115.500.1400.6

p H
[kPa] [m]
240
70L.S
24
S3.115.500.1400.6.
60 Hz
ISO 9906:2012 3B
200 20

160 16
S3.115.500.800.8. NPSH
[m]
120 12 12
S3.115.500.1400.6.

80 8 8
S3.115.500.800.8.

40 4 4

0 0 0
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Q [m³/h]
P2
[kW]
140 S3.115.500.1400.6.

120

100

80 S3.115.500.800.8.

TM04 2087 1914


60

40
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

40
10

Performance curves and technical data


p H
[kPa] [m]
240
70L.C/D/H
24
S3.115.500.1400.6. 60 Hz
ISO 9906:2012 3B
200 20

160 16
S3.115.500.800.8. NPSH
[m]
120 12 12
S3.115.500.1400.6.

80 8 8
S3.115.500.800.8.

40 4 4

0 0 0
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Q [m³/h]
P2
[kW]
140 S3.115.500.1400.6.

120

100

80 S3.115.500.800.8.

TM04 2088 1914


60

40
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]
Motor data

I N1 Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S3.115.500.800.8.70L.S.402... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.C.402... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.D.402... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.H.402... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.1400.6.70L.S.371... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.115.500.1400.6.70L.C.371... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.115.500.1400.6.70L.D.371... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.115.500.1400.6.70L.H.371... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930

1 Low/high voltage (380/660 V).


Note: Enclosure class: IP68

Pump data

Impeller Maximum solids Pump housing Maximum


Moment of inertia*
Pump type diameter size pressure installation depth

[mm] [mm] PN [m] [kgm 2]


S3.115.500.800.8.70L.S/C/D/H.402... 402 1,7680
115 10 20
S3.115.500.1400.6.70L.S/C/D/H.371... 371 1,4270

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

41
10
Performance curves and technical data

Low pressure - 3 x 460 V


S3.115.500.800.8 and S3.115.500.1400.6

p H
[kPa] [m]
240
70L.S
24
S3.115.500.1400.6.
60 Hz
ISO 9906:2012 3B
200 20

160 16
S3.115.500.800.8. NPSH
[m]
120 12 12
S3.115.500.1400.6.

80 8 8
S3.115.500.800.8.

40 4 4

0 0 0
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Q [m³/h]
P2
[kW]
140 S3.115.500.1400.6.

120

100

80 S3.115.500.800.8.

TM04 2087 1914


60

40
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

42
10

Performance curves and technical data


p H
[kPa] [m]
240
70L.C/D/H
24
S3.115.500.1400.6. 60 Hz
ISO 9906:2012 3B
200 20

160 16
S3.115.500.800.8. NPSH
[m]
120 12 12
S3.115.500.1400.6.

80 8 8
S3.115.500.800.8.

40 4 4

0 0 0
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Q [m³/h]
P2
[kW]
140 S3.115.500.1400.6.

120

100

80 S3.115.500.800.8.

TM04 2088 1914


60

40
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Q [l/s]

Motor data

IN Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S3.115.500.800.8.70L.S.402... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.C.402... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.D.402... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.800.8.70L.H.402... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.115.500.1400.6.70L.S.371... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.115.500.1400.6.70L.C.371... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.115.500.1400.6.70L.D.371... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.115.500.1400.6.70L.H.371... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930

Note: Enclosure class: IP68

Pump data

Impeller Maximum solids Pump housing Maximum installation


Moment of inertia*
Pump type diameter size pressure depth

[mm] [mm] PN [m] [kgm2]


S3.115.500.800.8.70L.S/C/D/H.402... 402 1,7680
115 10 20
S3.115.500.1400.6.70L.S/C/D/H.371... 371 1,4270

* Applies to material code G (see Type key). For other material codes, please contact Grundfos.

43
10
Performance curves and technical data

Medium pressure - 3 x 380/660 V


S2.100.200.1000.4, S2.145.300.1100.6 and S2.100.200.1200.4

p H
[kPa] [m]
600
S 2.
100
70M.S
60 .2 0
0 .1
200
.4 .
60 Hz
S2. ISO 9906:2012 3B
100
500 .200
50 .10
00.4
.

400 40
S2.1
NPSH
45.30
0.110
0.6.
[m]
300 30 15

S2.145.300.1100.6.
200 20 S2.100.200.1200.4. 10

S2.100.200.1000.4.
100 10 5

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Q [m³/h]
P2
[kW]
120
S2.100.200.1200.4.
S2.145.300.1100.6.
100

80 S2.100.200.1000.4.

60

TM04 2089 1914


40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

44
10

Performance curves and technical data


p H
[kPa] [m]
600
S2.
100
70M.C/D/H
60 .20
0 .1
200 60 Hz
.4.
S2. ISO 9906:2012 3B
100
500 .200
50 .10
00.4
.

400 40
S2.1 NPSH
45.3
00.1
100.6 [m]
300 30 . 15

S2.100.200.1200.4. S2.145.300.1100.6.
200 20 10

S2.100.200.1000.4.
100 10 5

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Q [m³/h]
P2
[kW]
120
S2.100.200.1200.4.
S2.145.300.1100.6.
100

S2.100.200.1000.4.
80

TM04 2090 1914


60

40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

Motor data

IN1 Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm 2] Mmax [Nm]
S2.100.200.1000.4.70M.S.332... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.C.332... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.D.332... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.H.332... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1200.4.70M.S.355... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.86 1.1000 1935
S2.100.200.1200.4.70M.C.355... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.86 1.1000 1935
S2.100.200.1200.4.70M.D.355... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.86 1.1000 1935
S2.100.200.1200.4.70M.H.355... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.86 1.1000 1935
S2.145.300.1100.6.70M.S.420... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.81 0.81 2.1000 2223
S2.145.300.1100.6.70M.C.420... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.81 0.81 2.1000 2223
S2.145.300.1100.6.70M.D.420... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.81 0.81 2.1000 2223
S2.145.300.1100.6.70M.H.420... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.81 0.81 2.1000 2223

1
Low/high voltage (380/660 V).
Note: Enclosure class: IP68

Pump data

Impeller Maximum solids Pump housing Maximum installation Moment of


Pump type diameter size pressure depth inertia *

[mm] [mm] PN [m] [kgm2]


S2.100.200.1000.4.70M.S/C/D/H.332... 332 0,5580
100
S2.100.200.1200.4.70M.S/C/D/H.355... 355 10 20 0,6687
S2.145.300.1100.6.70M.S/C/D/H.420... 420 145 1,2037

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

45
10
Performance curves and technical data

Medium pressure - 3 x 460 V


S2.100.200.1000.4, S2.145.300.1100.6 and S2.100.200.1200.4

p H
[kPa] [m]
600
S 2.
100
70M.S
60 .2 0
0 .1
200
.4 .
60 Hz
S2. ISO 9906:2012 3B
100
500 .200
50 .10
00.4
.

400 40
S2.1
NPSH
45.30
0.110
0.6.
[m]
300 30 15

S2.145.300.1100.6.
200 20 S2.100.200.1200.4. 10

S2.100.200.1000.4.
100 10 5

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Q [m³/h]
P2
[kW]
120
S2.100.200.1200.4.
S2.145.300.1100.6.
100

80 S2.100.200.1000.4.

60

TM04 2089 1914


40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

46
10

Performance curves and technical data


p H
[kPa] [m]
600
S2.
100
70M.C/D/H
60 .20
0 .1
200 60 Hz
.4.
S2. ISO 9906:2012 3B
100
500 .200
50 .10
00.4
.

400 40
S2.1 NPSH
45.3
00.1
100.6 [m]
300 30 . 15

S2.100.200.1200.4. S2.145.300.1100.6.
200 20 10

S2.100.200.1000.4.
100 10 5

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Q [m³/h]
P2
[kW]
120
S2.100.200.1200.4.
S2.145.300.1100.6.
100

S2.100.200.1000.4.
80

60

TM04 2090 1914


40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 Q [l/s]

Motor data

IN Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S2.100.200.1000.4.70M.S.332... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.C.332... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.D.332... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1000.4.70M.H.332... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.100.200.1200.4.70M.S.355... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.100.200.1200.4.70M.C.355... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.100.200.1200.4.70M.D.355... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.100.200.1200.4.70M.H.355... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.145.300.1100.6.70M.S.420... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.83 2.1000 2223
S2.145.300.1100.6.70M.C.420... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.83 2.1000 2223
S2.145.300.1100.6.70M.D.420... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.83 2.1000 2223
S2.145.300.1100.6.70M.H.420... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.83 2.1000 2223

Note: Enclosure class: IP68

Pump data

Impeller Maximum solids Pump housing Maximum


Moment of inertia*
Pump type diameter size pressure installation depth

[mm] [mm] PN [m] [kgm2]


S2.100.200.1000.4.70M.S/C/D/H.332... 332 0,5580
100
S2.100.200.1200.4.70M.S/C/D/H.355... 355 10 20 0,6687
S2.145.300.1100.6.70M.S/C/D/H.420... 420 145 1,2037

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

47
10
Performance curves and technical data

Medium pressure - 3 x 380/660 V


S3.120.300.800.8 and S3.120.300.1400.6

p H
[kPa] [m]
32 70M.S
S3.120.300.1400.6.
60 Hz
280 28 ISO 9906:2012 3B

240 24 S3.120.300.800.8.

200 20

160 16 NPSH
[m]
120 12 15

80 8 S3.120.300.1400.6. 10

40 4 5
S3.120.300.800.8.

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 Q [m³/h]
P2
[kW]
140
S3.120.300.1400.6.
120

100

80
S3.120.300.800.8.
60

TM04 2091 1914


40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Q [l/s]

48
10

Performance curves and technical data


p H
[kPa] [m] S3
18
.1 1
0 .5
00
70L.C/D/H
.6 5
0 .8 50 Hz
160 16 .(4
64
) ISO 9906:2012 3B
140 S3
14 .11
0 . 50
0.8
00
120 .6.(
12 37
0)

100 10

80 8 NPSH
[m]
60 6 10

40 4 8
S3.110.500.800.6.(370)
20 2 6
S3.110.500.650.8.(464)

0 0 4
0 100 200 300 400 500 600 700 800 900 Q [l/s]

0 500 1000 1500 2000 2500 3000 Q [m³/h]


P2
[kW]

80 S3.110.500.800.6.(370)

S3.110.500.650.8.(464)
60

40

TM04 0688 1914


20
0 100 200 300 400 500 600 700 800 900 Q [l/s]

Motor data

IN1 Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm 2] [Nm]
S3.120.300.800.8.70M.S.442... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.C.442... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.D.442... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.H.442... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.1400.6.70M.S.407... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.120.300.1400.6.70M.C.407... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.120.300.1400.6.70M.D.407... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S3.120.300.1400.6.70M.H.407... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930

1
Low/high voltage (380/660 V).
Note: Enclosure class: IP68

Pump data

Impeller Pump housing Maximum Moment of


Maximum solids size
Pump type diameter pressure installation depth inertia*

[mm] [mm] PN [m] [kgm2]


S3.120.300.800.8.70M.S/C/D/H.442... 442 120 10 20 1,4653
S3.120.300.1400.6.70M.S/C/D/H.407... 407 120 10 20 1,1747

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

49
10
Performance curves and technical data

Medium pressure - 3 x 460 V


S3.120.300.800.8 and S3.120.300.1400.6

p H
[kPa] [m]
32 70M.S
S3.120.300.1400.6.
60 Hz
280 28 ISO 9906:2012 3B

240 24 S3.120.300.800.8.

200 20

160 16 NPSH
[m]
120 12 15

80 8 S3.120.300.1400.6. 10

40 4 5
S3.120.300.800.8.

0 0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 Q [m³/h]
P2
[kW]
140
S3.120.300.1400.6.
120

100

80
S3.120.300.800.8.

TM04 2091 1914


60

40
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Q [l/s]

50
10

Performance curves and technical data


p H
[kPa] [m] S3
18
.1 1
0 .5
00
70L.C/D/H
.6 5
0 .8 50 Hz
160 16 .(4
64
) ISO 9906:2012 3B
140 S3
14 .11
0 . 50
0.8
00
120 .6.(
12 37
0)

100 10

80 8 NPSH
[m]
60 6 10

40 4 8
S3.110.500.800.6.(370)
20 2 6
S3.110.500.650.8.(464)

0 0 4
0 100 200 300 400 500 600 700 800 900 Q [l/s]

0 500 1000 1500 2000 2500 3000 Q [m³/h]


P2
[kW]

80 S3.110.500.800.6.(370)

S3.110.500.650.8.(464)
60

40

TM04 0688 1714


20
0 100 200 300 400 500 600 700 800 900 Q [l/s]

Motor data

IN Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] Mmax [Nm]
S3.120.300.800.8.70M.S.442... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.C.442... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.D.442... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.800.8.70M.H.442... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S3.120.300.1400.6.70M.S.407... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.120.300.1400.6.70M.C.407... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.120.300.1400.6.70M.D.407... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S3.120.300.1400.6.70M.H.407... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930

Note: Enclosure class: IP68

Pump data

Pump housing Maximum Moment of


Impeller diameter Maximum solids size
Pump type pressure installation depth inertia*

[mm] [mm] PN [m] [kgm2]


S3.120.300.800.8.70M.S/C/D/H.442... 442 1,4653
120 10 20
S3.120.300.1400.6.70M.S/C/D/H.407... 407 1,1747

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

51
10
Performance curves and technical data

High pressure - 3 x 380/660 V


S2.90.200.1000.4 and S2.90.200.1200.2

p H
[kPa] [m]
90 70H.S
800 S2.90.200.1200.4.
60 Hz
80
ISO 9906:2012 3B
700 70 S2.90.200.1000.4.

600 60

500 50

400 40 NPSH
[m]
300 30 12
S2.90.200.1200.4.
200 20 8
S2.90.200.1000.4.
100 10 4

0 0 0
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

0 100 200 300 400 500 600 700Q [m³/h]


P2
[kW]
120 S2.90.200.1200.4.

100 S2.90.200.1000.4.

80

60

TM04 2083 1914


40

20
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

52
10

Performance curves and technical data


p H
[kPa] [m]
90 70H.C/D/H
800 S2.90.200.1200.4.
60 Hz
80
ISO 9906:2012 3B
700 70 S2.90.200.1000.4.

600 60

500 50

400 40 NPSH
[m]
300 30 12
S2.90.200.1200.4.
200 20 8
S2.90.200.1000.4.
100 10 4

0 0 0
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

0 100 200 300 400 500 600 700Q [m³/h]


P2
[kW]
120 S2.90.200.1200.4.

100
S2.90.200.1000.4.

80

60

TM04 2084 1914


40

20
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

Motor data

I N1 Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S2.90.200.1000.4.70H.S.340... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.C.340... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.D.340... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.H.340... 103 95 4 1778 Y/D 179/103 1337 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1200.4.70H.S.361... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.88 1.1000 1935
S2.90.200.1200.4.70H.C.361... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.88 1.1000 1935
S2.90.200.1200.4.70H.D.361... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.88 1.1000 1935
S2.90.200.1200.4.70H.H.361... 129 120 4 1777 Y/D 231/133 1671 94 94 92 0.77 0.85 0.88 1.1000 1935

1
Low/high voltage (380/660 V).
Note: Enclosure class: IP68

Pump data

Pump housing Maximum Moment of


Impeller diameter Maximum solids size
Pump type pressure installation depth inertia*

[mm] [mm] PN [m] [kgm2]


S2.90.200.1000.4.70H.S/C/D/H.340... 340 0,5610
90 10 20
S2.90.200.1200.4.70H.S/C/D/H.361... 361 0,6010

*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

53
10
Performance curves and technical data

High pressure - 3 x 460 V


S2.90.200.1000.4 and S2.90.200.1000.4

p H
[kPa] [m]
90 70H.S
800 S2.90.200.1200.4.
60 Hz
80
ISO 9906:2012 3B
700 70 S2.90.200.1000.4.

600 60

500 50

400 40 NPSH
[m]
300 30 12
S2.90.200.1200.4.
200 20 8
S2.90.200.1000.4.
100 10 4

0 0 0
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

0 100 200 300 400 500 600 700Q [m³/h]


P2
[kW]
120 S2.90.200.1200.4.

100 S2.90.200.1000.4.

80

60

TM04 2083 1914


40

20
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

54
10

Performance curves and technical data


p H
[kPa] [m]
90 70H.C/D/H
800 S2.90.200.1200.4.
60 Hz
80
ISO 9906:2012 3B
700 70 S2.90.200.1000.4.

600 60

500 50

400 40 NPSH
[m]
300 30 12
S2.90.200.1200.4.
200 20 8
S2.90.200.1000.4.
100 10 4

0 0 0
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

0 100 200 300 400 500 600 700Q [m³/h]


P2
[kW]
120 S2.90.200.1200.4.

100
S2.90.200.1000.4.

80

60

TM04 2084 1914


40

20
0 20 40 60 80 100 120 140 160 180 200 Q [l/s]

Motor data

IN Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S2.90.200.1000.4.70H.S.340... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.C.340... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.H.340... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1000.4.70H.D.340... 103 95 4 1778 Y/D 148 1105 94 94 92 0.80 0.86 0.88 0.8500 1479
S2.90.200.1200.4.70H.S.361... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.90.200.1200.4.70H.C.361... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.90.200.1200.4.70H.H.361... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935
S2.90.200.1200.4.70H.D.361... 129 120 4 1777 Y/D 193 1380 94 94 92 0.77 0.84 0.85 1.1000 1935

Note: Enclosure class: IP68

Pump data

Pump housing Maximum Moment of


Impeller diameter Maximum solids size
Pump type pressure installation depth inertia*

[mm] [mm] PN [m] [kgm2]


S2.90.200.1000.4.70H.S/C/D/H.340... 340 0,5610
90 10 20
S2.90.200.1200.4.70H.S/C/D/H.361... 361 0,6010

* Applies to material code G (see Type key). For other material codes, please contact Grundfos.

55
10
Performance curves and technical data

High pressure - 3 x 380/660 V


S2.105.250.800.8, S2.122.250.1100.6 and S2.122.250.1400.6

p H
[kPa] [m]
50 70H.S
S2.12
450 2.250
45 .1400
.6. 60 Hz
S2.1 ISO 9906:2012 3B
400 22.2
40 50.1
S2.1 100
05.2 .6.
350 35 50.8
00.8
.
300 30

250 25

200 20
NPSH
[m]
150 15 12

100 10 8

50 5 S2.122.250.1100.6. 4
S2.122.250.1400.6.
0 0 0
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 Q [m³/h]


P2
[kW]
140
S2.122.250.1400.6.
120
S2.122.250.1100.6.
100

80 S2.105.250.800.8.

60

TM04 2085 4818


40
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

56
10

Performance curves and technical data


p H
[kPa] [m]
50 70H.C/D/H
S2.12
2.250
450 45 .1400 60 Hz
.6 .
S2.1 ISO 9906:2012 3B
400 22.2
40 50.1
100
S2.1 . 6.
350 05.2
35 50.8
00.8
.
300 30

250 25

200 20
NPSH
[m]
150 15 12

100 10 8
S2.122.250.1400.6.
50 5 S2.122.250.1100.6. 4

0 0 0
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 Q [m³/h]


P2
[kW]
140
S2.122.250.1400.6.
120
S2.122.250.1100.6.
100

80 S2.105.250.800.8.

TM04 2086 4818


60

40
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]
Motor data
I N1 Istart η motor [%] Cos φ Moment Breakdown
P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S2.105.250.800.8.70H.S.523... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.C.523... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.D.523... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.H.523... 86 80 8 882 Y/D 156/90 1042 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.122.250.1100.6.70H.S.443... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.80 0.81 2.1000 2223
S2.122.250.1100.6.70H.C.443... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.80 0.81 2.1000 2223
S2.122.250.1100.6.70H.D.443... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.80 0.81 2.1000 2223
S2.122.250.1100.6.70H.H.443... 118 110 6 1181 Y/D 230/132 1543 89 90 90 0.73 0.80 0.81 2.1000 2223
S2.122.250.1400.6.70H.S.465... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S2.122.250.1400.6.70H.C.465... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S2.122.250.1400.6.70H.D.465... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
S2.122.250.1400.6.70H.H.465... 152 140 6 1186 Y/D 276/159 2395 92 92 92 0.67 0.78 0.84 2.8000 2930
1
Low/high voltage (380/660 V).
Note: Enclosure class: IP68

Pump data
Impeller Maximum solids Pump housing Maximum
Moment of inertia*
Pump type diameter size pressure installation depth

[mm] [mm] PN [m] [kgm2]


S2.105.250.800.8.70H.S/C/D/H.523... 523 105 2,5300
S2.122.250.1100.6.70H.S/C/D/H.443... 443 10 20 1,5447
122
S2.122.250.1400.6.70H.S/C/D/H.465... 465 1,7727
*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

57
10
Performance curves and technical data

High pressure - 3 x 460 V


S2.105.250.800.8, S2.122.250.1100.6 and S2.122.250.1400.6

p H
[kPa] [m]
50 70H.S
S2.12
450 2.250
45 .1400
.6. 60 Hz
S2.1 ISO 9906:2012 3B
400 22.2
40 50.1
S2.1 100
05.2 .6.
350 35 50.8
00.8
.
300 30

250 25

200 20
NPSH
[m]
150 15 12

100 10 8

50 5 S2.122.250.1100.6. 4
S2.122.250.1400.6.
0 0 0
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 Q [m³/h]


P2
[kW]
140
S2.122.250.1400.6.
120
S2.122.250.1100.6.
100

80 S2.105.250.800.8.

60

TM04 2085 4818


40
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

58
10

Performance curves and technical data


p H
[kPa] [m]
50 70H.C/D/H
S2.12
2.250
450 45 .1400 60 Hz
.6 .
S2.1 ISO 9906:2012 3B
400 22.2
40 50.1
100
S2.1 . 6.
350 05.2
35 50.8
00.8
.
300 30

250 25

200 20
NPSH
[m]
150 15 12

100 10 8
S2.122.250.1400.6.
50 5 S2.122.250.1100.6. 4

0 0 0
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]

0 200 400 600 800 1000 1200 1400 1600 Q [m³/h]


P2
[kW]
140
S2.122.250.1400.6.
120
S2.122.250.1100.6.
100

80 S2.105.250.800.8.

TM04 2086 4818


60

40
0 50 100 150 200 250 300 350 400 450 500 Q [l/s]
Motor data

IN Istart ηmotor [%] Cos φ Moment Breakdown


P1 P2 No. of Starting
Pump type RPM of inertia torque Mmax
[kW] [kW] poles method [A] [A] 1/2 3/4 1/1 1/2 3/4 1/1 [kgm2] [Nm]
S2.105.250.800.8.70H.S.523... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.C.523... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.D.523... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.105.250.800.8.70H.H.523... 86 80 8 882 Y/D 129 861 93 94 93 0.77 0.83 0.84 2.1000 2170
S2.122.250.1100.6.70H.S.443... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.85 2.1000 2223
S2.122.250.1100.6.70H.C.443... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.85 2.1000 2223
S2.122.250.1100.6.70H.D.443... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.85 2.1000 2223
S2.122.250.1100.6.70H.H.443... 118 110 6 1181 Y/D 185 1275 89 90 90 0.73 0.81 0.85 2.1000 2223
S2.122.250.1400.6.70H.S.465... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S2.122.250.1400.6.70H.C.465... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S2.122.250.1400.6.70H.D.465... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930
S2.122.250.1400.6.70H.H.465... 152 140 6 1186 Y/D 246 1978 89 90 91 0.62 0.72 0.78 2.8000 2930

Note: Enclosure class: IP68

Pump data
Maximum solids Pump housing Maximum
Impeller diameter Moment of inertia*
Pump type size pressure installation depth

[mm] [mm] PN [m] [kgm2]


S2.105.250.800.8.70H.S/C/D/H.523... 523 105 2,5300
S2.122.250.1100.6.70H.S/C/D/H.443... 443 10 20 1,5447
122
S2.122.250.1400.6.70H.S/C/D/H.465... 465 1,7727
*
Applies to material code G (see Type key). For other material codes, please contact Grundfos.

59
11 S pumps, range 70

11. Accessories
Accessories

Accessories (for installation)


Pump type Installation accessories
Range 50-70 S and C DN 80-DN 200 without a guide claw (guide claw included in auto-coupling kit)
Range 50-70 S and C DN 250-DN 600 with a guide claw mounted on the pump
Range 50-70 D Pump without installation accessories (accessories as separate kit)
Range 50-70 H Base stand for horizontal, dry installation supplied together with the pump.
Pumps with material code G or Q include a painted-steel stand. If another horizontal stand is required, order a pump of
installation type D together with the required stand.

Weight Product
Pictures Description Size PN
[kg] number

DN 200 250 96641489


Cast iron, epoxy-coated auto-coupling system complete

Outlet flange
with: DN 250 225 96782483
• guide claw 1
10
• base unit
• upper guide rail bracket DN 300 275 96782484
GR8126

• gaskets and bolts.


DN 500 705 96782485
1
Installation type S and C pumps with outlet flange size DN 250 and higher are supplied with a guide claw
mounted on the flange.

Intermediate guide rail bracket For guide rails longer than 6 m DN 200-600 8 96255842

Standard pipes.
Guide rails
Not supplied by Grundfos

Grundfos flange/Flygt flange

DN 200/DN 200 - 3" 25 97908872


Adapter for Flygt auto-coupling with:
TM06 5164 3915

• flange seal DN 250/DN 250 - 3" 33 97908887


• bolts. 10
DN 300/DN 300 - 3" 120 97908892

DN 300/DN 300 - 4" 120 97908893

DN 250 90 96308240
TM04 3693 4908 TM03 2015 3505

Steel, epoxy-coated.
Base plate for vertical, dry installation with:
DN 300 87 96308241
• gaskets
Inlet flange

• bolts.
DN 500 167 96308245

Cast iron, epoxy-coated.


Base plate for vertical, dry installation with:
DN 400/DN 500 195 96308244
• gaskets
• bolts.

Base stand for horizontal, dry installation products:


• S2.100.200.1000/1200.4.70M.H
• S2.122.250.1100/1400.6.70H.H
TM04 4158 0909

• S2.105.250.800.8.70H.H
Version 1 140 96308192
• S3.115.500.1400.6.70L.H
• S3.115.500.800.8.70L.H
• S3.120.300.1400.6.70M.H
• S3.120.300.800.8.70M.H

Base stand for horizontal, dry installation product:


TM04 4160 0909

• Version 2 140 96308212


• S2.90.200.1000/1200.4.70H.H
TM04 4159 0909

Base stand for horizontal, dry installation product:


Version 3 125 96308255
• S2.145.300.1100.6.70M.H

60
S pumps, range 70
11

Accessories
Weight Product
Pictures Description Size PN
[kg] number

TM06 4971 3415


Special base stand for horizontal, dry installation with Contact
customized height. Grundfos.

Bend
Pipe/pump inlet
Cast iron, epoxy-coated

L = 350 mm DN 250 64 99035998


L

L = 400 mm DN 300 81 99035999


TM04 4033 0509

10
L = 500 mm DN 400 148 99036000
L
L = 500 mm DN 500 351 99036001

Reducing bend
Pipe/pump inlet
Cast iron, epoxy-coated

L = 400 mm DN 300/DN 250 76 99036011


L

L = 450 mm DN 350/DN 250 93 99036012

L = 500 mm DN 400/DN 250 118 99036013


TM04 4034 0509

10
L = 500 mm DN 400/DN 300 128 99036014

L L = 600 mm DN 500/DN 400 306 99036015

L = 700 mm DN 600/DN 500 411 99031225

61
11 S pumps, range 70

Other accessories
Accessories

Product
Pictures Description Size
number

4m 98425788
Galvanised lifting chain with lifting link and safety hook. 6m 98425789
Certified.
Maximum lifting capacity 3200 kg. 8m 98425790

10 m 98425791

4m 98425805
TM02 6126 5102
Stainless steel lifting chain with lifting link and safety hook. 6m 98425806
Certified.
Maximum lifting capacity 3200 kg. 8m 98425807

10 m 98425808

Contact
TM06 4974 3415

Cable support bracket (case by case)


Grundfos

AMD.08.16.1730 mixer, 3 x 460 V, 60 Hz 99056115

AMD.08.16.1690 mixer, 3 x 380 V, 60 Hz 99083810

Bracket for wall mounting 2" thread


TM06 5110 3815

Bracket for floor mounting 2" thread

Bracket for suspended mounting 2" thread

Tube for suspended mounting, length 3 m 2" thread

10 m cable 96003332
Float switch
TM02 8862 0904 TM01 6982 3999

20 m cable 96003695

10 m cable 96003421
Float switch for use in potentially explosive environments.
20 m cable 96003536

Bracket for two float switches 96003338

Float switches with bracket

2 switches, 1 pump without alarm 62500013

3 switches, 1 pump with alarm 62500014


10 m cable
3 switches, 2 pumps with alarm 62500014

3 switches, 2 pumps with alarm 62500015

Float switches with bracket for use in potentially explosive environments

2 switches, 1 pump without alarm 62500016


TM02 8860 0904 TM02 0670 5000

3 switches, 1 pump with alarm 62500017


10 m cable
3 switches, 2 pumps with alarm 62500017

3 switches, 2 pumps with alarm 62500018

For 38 mm mounting
Bracket for level electrodes 91713196
pipe

62
S pumps, range 70
12

12. Dimensions

Dimensions
Recommendation for pump foundations
Note: This applies only to pumps above 15 kW. • The foundation must be 15 cm wider than the base
All rotating equipment generates vibrations as a mass, plate for pumps up to 350 kW and 25 cm wider for
such as an impeller or rotor, is turning at high speeds. larger pumps.
Proper installation and anchorage of Grundfos pumps • The concrete used in the foundation must have a
and installation accessories is critical to limit vibrations minimum tensile strength of 250 N/cm 2. Epoxy grout
and achieve reliable, trouble-free installation. It is must always be used to secure the pump base plate
important to note that all mechanically connected to the foundation.
pipes, fittings and supports to the pump are part of a
single system. Pull-out strengths for anchor bolts
The rotating mass of the entire pump, together with the Submerged installation on auto-coupling (type S and
forces from the motor and hydraulics, will generate C):
disturbances related to the speed of the motor.
Unbalance and impeller vane pass in hydraulics are Auto-coupling base Pull-out resistance
Anchor bolts
unit [kN]
the two most important frequencies affecting vibration.
DN 100 5
When these frequencies coincide with the natural 4 x M16
DN 125/DN 150 1 8
frequency of the entire mechanical system, the DN 200 16
vibration level will increase substantially. DN 250 4 x M24 30
Pumps from Grundfos are designed and produced DN 300 40
according to the highest quality standards. The method DN 500 40
6 x M30
DN 600 40
and grade of balancing is specified by the
manufacturer in order to achieve acceptable vibration 1 Pump outlet DN 125 and base plate outlet DN 150.
levels. Although the pump itself can withstand rather Dry installation (type H and D):
high vibration levels under operating conditions without
considerable lifetime reduction, the pipes and Dry installation Anchor bolts
Pull-out resistance
[kN]
supportive structure might suffer and crack if vibration
levels are too high. Furthermore, noticeable noise DN 100 3 x M20 18
DN 150 18
levels might be generated. 6 x M20
DN 200 18
The likelihood of high vibration levels occurring is DN 250 25
increased in variable-speed applications where the DN 300 25
6 x M24
pump is operated over a range of speeds rather than DN 500/DN 4001 25
at a single constant speed. Most variable-speed drives DN 500 25
provide the possibility to exclude certain frequency 1
Base plate inlet DN 500 and pump inlet DN 400.
ranges to avoid operating areas with high vibrations.
To ensure acceptable vibration levels in the field, all
parts of the system must be sufficiently stiff and firmly
anchored to minimise vibrations:
• The foundation and concrete must be of adequate
strength to support the weight of the pump including
accessories, the weight of the liquid passing
through the pump and the forces generated by the
pump.
• As a rule of thumb, the mass of the concrete
foundation must be a minimum of three to five times
the mass of the supported equipment and must
have sufficient rigidity to withstand the axial,
transverse and torsional loadings generated by the
equipment.

63
12 S pumps, range 70

Basic pump
Dimensions

Installation types S and C

MOT_H

DT2 MOT Hfix


D02 x D2N

DN2

H DC02

HYDR_H
E

Installation types D and H

DC10

D01 x D1N

MOT_H

A
TM04 2412 2018 - TM07 1653 2018

DT2 MOT Hfix

D02 x D2N
DN2

DC02
E DN1
HYDR_H
C

Fig. 34 Basic pumps

64
S pumps, range 70
12
Note: Dimensions D01, D1N, DC10 and DN1 are equal to zero for installation types C and S because of the inlet type.

Dimensions
HYDR MOT MOT
Pump type A C D D01 D02 D1N D2N DC02 DC10 DN1 DN2 DT2 E F H
H H Hfix
S2.90.200.1000.4.70H.C 1625 770 285 - 24 - 8 295 - - DN 200 26 500 570 203 305 1320 20
S2.90.200.1000.4.70H.D 1638 770 285 M20 24 12 8 295 350 DN 250 DN 200 26 500 570 226 318 1320 20
S2.90.200.1000.4.70H.H 1638 770 285 M20 24 12 8 295 350 DN 250 DN 200 26 500 570 226 318 1320 20
S2.90.200.1000.4.70H.S 1625 770 285 - 24 - 8 295 - - DN 200 26 500 570 203 305 1320 20
S2.90.200.1200.4.70H.C 1625 970 285 - 24 - 8 295 - - DN 200 26 700 570 203 305 1320 20
S2.90.200.1200.4.70H.D 1638 770 285 M20 24 12 8 295 350 DN 250 DN 200 26 500 570 226 318 1320 20
S2.90.200.1200.4.70H.H 1638 770 285 M20 24 12 8 295 350 DN 250 DN 200 26 500 570 226 318 1320 20
S2.90.200.1200.4.70H.S 1625 970 285 - 24 - 8 295 - - DN 200 26 700 570 203 305 1320 20
S2.100.200.1000.4.70M.C 1638 809 400 - 24 - 8 295 - - DN 200 26 460 720 215 318 1320 20
S2.100.200.1000.4.70M.D 1638 809 400 M20 24 12 8 295 350 DN 250 DN 200 26 460 720 215 318 1320 20
S2.100.200.1000.4.70M.H 1638 809 400 M20 24 12 8 295 350 DN 250 DN 200 26 460 720 215 318 1320 20
S2.100.200.1000.4.70M.S 1638 809 400 - 24 - 8 295 - - DN 200 26 460 720 215 318 1320 20
S2.100.200.1200.4.70M.S 1638 809 400 - 24 - 8 295 - - DN 200 26 460 720 215 318 1320 20
S2.100.200.1200.4.70M.D 1638 809 400 M20 24 12 8 295 350 DN 250 DN 200 26 460 720 215 318 1320 20
S2.100.200.1200.4.70M.H 1638 809 400 M20 24 12 8 295 350 DN 250 DN 200 26 460 720 215 318 1320 20
S2.100.200.1200.4.70M.S 1638 809 400 - 24 - 8 295 - - DN 200 26 460 720 215 318 1320 20
S2.105.200.800.8.70H.C 1719 1193 478 - 24 - 12 350 - - DN 250 30 750 891 235 369 1350 20
S2.105.200.800.8.70H.D 1773 1193 478 M20 24 12 12 250 400 DN 300 DN 250 30 750 891 289 423 1350 20
S2.105.200.800.8.70H.H 1773 1193 478 M20 24 12 12 250 400 DN 300 DN 250 30 750 891 289 423 1350 20
S2.105.200.800.8.70H.S 1719 1193 478 - 24 - 12 350 - - DN 250 30 750 891 235 369 1350 20
S2.122.250.1100.6.70H.C 1689 1193 478 - 24 - 12 350 - - DN 250 30 450 891 235 369 1320 20
S2.122.250.1100.6.70H.D 1743 1193 478 M20 24 12 12 250 400 DN 300 DN 250 30 450 891 289 423 1320 20
S2.122.250.1100.6.70H.H 1743 1193 478 M20 24 12 12 250 400 DN 300 DN 250 30 450 891 289 423 1320 20
S2.122.250.1100.6.70H.S 1689 1193 478 - 24 - 12 350 - - DN 250 30 450 891 235 369 1320 20
S2.122.250.1400.6.70H.C 1844 1193 478 - 24 - 12 350 - - DN 250 30 750 891 235 369 1475 20
S2.122.250.1400.6.70H.D 1898 1193 478 M20 24 12 12 350 400 DN 300 DN 250 30 750 891 289 423 1475 20
S2.122.250.1400.6.70H.H 1898 1193 478 M20 24 12 12 350 400 DN 300 DN 250 30 750 891 289 423 1475 20
S2.122.250.1400.6.70H.S 1844 1193 478 - 24 - 12 350 - - DN 250 30 750 891 235 369 1475 20
S2.145.300.1100.6.70M.C 1915 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1320 20
S2.145.300.1100.6.70M.D 1743 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 278 1320 20
S2.145.300.1100.6.70M.H 1743 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 278 1320 20
S2.145.300.1100.6.70M.S 1915 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1320 20
S3.115.500.800.8.70L.C 1830 1743 719 - 27 - 20 620 - - DN 500 37 1200 1269 380 510 1320 20
S3.115.500.800.8.70L.D 1783 1743 719 M24 27 16 20 620 515 DN 400 DN 500 37 1200 1269 333 463 1320 20
S3.115.500.800.8.70L.H 1783 1743 719 M24 27 16 20 620 515 DN 400 DN 500 37 1200 1269 333 463 1320 20
S3.115.500.800.8.70L.S 1830 1743 719 - 27 - 20 620 - - DN 500 37 1200 1269 380 510 1320 20
S3.115.500.1400.6.70L.C 1985 1843 719 - 27 - 20 620 - - DN 500 37 1200 1269 380 510 1475 20
S3.115.500.1400.6.70L.D 1938 1843 719 M24 27 16 20 620 515 DN 400 DN 500 37 1200 1269 333 463 1475 20
S3.115.500.1400.6.70L.H 1938 1843 719 M24 27 16 20 620 515 DN 400 DN 500 37 1200 1269 333 463 1475 20
S3.115.500.1400.6.70L.S 1985 1843 719 - 27 - 20 620 - - DN 500 37 1200 1269 380 510 1475 20
S3.120.300.800.8.70M.C 1915 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1320 20
S3.120.300.800.8.70M.D 1743 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 423 1320 20
S3.120.300.800.8.70M.H 1743 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 423 1320 20
S3.120.300.800.8.70M.S 1915 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1320 20
S3.120.300.1400.6.70M.C 2070 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1475 20
S3.120.300.1400.6.70M.D 1898 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 423 1475 20
S3.120.300.1400.6.70M.H 1898 1139 522 M20 24 12 12 400 400 DN 300 DN 300 33 700 907 278 423 1475 20
S3.120.300.1400.6.70M.S 2070 1139 522 - 24 - 12 400 - - DN 300 33 700 907 450 595 1475 20

65
12 S pumps, range 70

Installation on auto-coupling system


Dimensions

Upper guide rail bracket dimensions

TM06 9915 3617

Fig. 35 Installation dimensions for upper guide rail bracket

Auto-coupling X
Product number Size [mm]

96641489 DN 200
96782483 DN 250
150
96782484 DN 300
96782485 DN 500

Auto-coupling dimensions

G C

A H I J

TM06 6497 1516

E D K

Fig. 36 Dimension for cast iron base unit

Dimensions [mm]
Product number Size
A B C D E F G H I J K
96641489 DN 200 485 710 365 535 89 86 175 500 430 430 710
96255838 DN 250 545 753 375 565 89 86 175 540 470 470 745
96782484 DN 300 650 860 450 670 80 95 175 620 550 550 845
96782485 DN 500 890 1148 564 735/150 1 127 99 226 720 660 660 1120

1
Six bolt installation: distance between the front bolt hole and the middle bolt hole / distance between the middle bolt hole and the back bolt hole.

66
S pumps, range 70
12
Pump installation dimensions

Dimensions
ZDN1 C
Z01

c1
ZD

Z2 Z3
F

Z4

Z6
Z7
Z8
Z9

Z10
Z17G
Z17S Installation S
Ex pump
ZL1

Z15 ZL2
ZDT1
Installation S
Std. pump Z1
Installation C Z23 Z11
S3OPR

Z12B

TM06 8504 2518


Z13 Z12A

ZM Z14

Fig. 37 Installation on auto-coupling system - version 1 (base unit with 4 anchor bolts)

Note: Z12A is the minimum recommended distance from pit bottom to bottom of pump inlet side.
Note: Z11 is the total height of pump installed on Grundfos accessory in the pit.
Note: The pump in this figure might not equal Z12A + Z1.

67
12 S pumps, range 70
Dimensions

Pump type C F Z01 Z1 Z2 Z3 Z4 Z6 Z7 Z8 Z9 Z10 Z11 Z12A Z12B


S2.90.200.1000.4.70H.S/C 770 570 8 x 23 1625 430 200 535 1531 1162 892 170 88 1768 143 196
S2.90.200.1200.4.70H.S/C 970 570 8 x 23 1625 430 200 535 1731 1362 1092 170 88 1768 143 196
S2.100.200.1000.4.70M.S/C 809 720 8 x 23 1638 430 200 535 1570 1201 852 170 88 1769 131 196
S2.100.200.1200.4.70M.S/C 809 720 8 x 23 1638 430 200 535 1570 1201 852 170 88 1769 131 196
S2.105.250.800.8.70H.S/C 1193 891 12 x 23 1689 471 200 565 1992 1585 1142 170 88 1878 189 224
S2.122.250.1100.6.70H.S/C 1193 891 12 x 23 1689 471 200 565 1992 1585 1142 170 88 1878 189 224
S2.122.250.1400.6.70H.S/C 1193 891 12 x 23 1844 471 200 565 1992 1585 1142 170 88 2033 189 224
S2.145.300.1100.6.70M.S/C 1139 907 12 x 23 1915 551 200 670 2040 1531 1092 170 88 2121 206 256
S3.120.300.800.8.70M.S/C 1139 907 12 x 23 1915 551 200 670 2040 1531 1092 170 88 2121 206 256
S3.120.300.1400.6.70M.S/C 1139 907 12 x 23 2070 551 200 670 2040 1531 1092 170 88 2276 206 256

Z17 Z23 S3OPR


Pump type Z13 Z14 Z15 Z16 ZDC1 ZDN1 ZDT1 ZL1 ZL2 ZM
G S Std. Ex. Std. Ex.
S2.90.200.1000.4.70H.C 150 86 365 485 3 3 422 422 295 DN 200 31 761 222 4 x M24 415 415
S2.90.200.1000.4.70H.S 150 86 365 485 3 3 780 1329 295 DN 200 31 761 222 4 x M24 773 1322
S2.90.200.1200.4.70H.C 150 86 365 485 3 3 422 422 295 DN 200 31 761 222 4 x M24 415 415
S2.90.200.1200.4.70H.S 150 86 365 485 3 3 780 1329 295 DN 200 31 761 222 4 x M24 773 1322
S2.100.200.1000.4.70M.C 150 86 365 485 3 3 435 435 295 DN 200 31 761 222 4 x M24 416 416
S2.100.200.1000.4.70M.S 150 86 365 485 3 3 793 1342 295 DN 200 31 761 222 4 x M24 774 1323
S2.100.200.1200.4.70M.C 150 86 365 485 3 3 435 435 295 DN 200 31 761 222 4 x M24 416 416
S2.100.200.1200.4.70M.S 150 86 365 485 3 3 793 1342 295 DN 200 31 761 222 4 x M24 774 1323
S2.105.250.800.8.70H.C 200 86 375 545 3 3 486 486 350 DN 250 32 799 222 4 x M24 475 475
S2.105.250.800.8.70H.S 200 86 375 545 3 3 844 1393 350 DN 250 32 799 222 4 x M24 833 1382
S2.122.250.1100.6.70H.C 200 86 375 545 3 3 486 486 350 DN 250 32 799 222 4 x M24 475 475
S2.122.250.1100.6.70H.S 200 86 375 545 3 3 844 1393 350 DN 250 32 799 222 4 x M24 833 1382
S2.122.250.1400.6.70H.C 200 86 375 545 3 3 486 486 350 DN 250 32 799 222 4 x M24 475 475
S2.122.250.1400.6.70H.S 200 86 375 545 3 3 921 1548 350 DN 250 32 799 222 4 x M24 910 1537
S2.145.300.1100.6.70M.C 400 95 450 650 3 3 712 712 400 DN 300 32 901 222 4 x M24 518 518
S2.145.300.1100.6.70M.S 400 95 450 650 3 3 1070 1619 400 DN 300 32 901 222 4 x M24 876 1425
S3.120.300.800.8.70M.C 400 95 450 650 3 3 712 712 400 DN 300 32 901 222 4 x M24 518 518
S3.120.300.800.8.70M.S 400 95 450 650 3 3 1070 1619 400 DN 300 32 901 222 4 x M24 876 1020
S3.120.300.1400.6.70M.C 400 95 450 650 3 3 712 712 400 DN 300 32 901 222 4 x M24 518 518
S3.120.300.1400.6.70M.S 400 95 450 650 3 3 1147 1774 400 DN 300 32 901 222 4 x M24 953 1097

68
S pumps, range 70
12

Dimensions
C

ZDN1
Z01

Z3 F

Z2

ZDC1 Z4

Z6
Z7
Z8
Z9

Z10
Z17G
Installation S
Z17S
ZL1 Ex pump

Z15 ZL2
ZDT1 Installation S
Std. pump
Z1
Installation C Z11
S3OPR Z23

Z16

Z12B

TM04 2418 2018


Z13 Z12A

ZM Z5 Z14

Fig. 38 Installation on auto-coupling system - version 2 (base unit with 6 anchor bolts)

Note: Z12A is the minimum recommended distance from pit bottom to bottom of pump inlet side.
Note: Z11 is the total height of pump installed on Grundfos accessory in the pit.
Note: The pump in this figure might not equal Z12A + Z1.

Pump type C F Z01 Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12A Z12B


S3.115.500.800.8.70L.S/C 1843 1269 20 x 27 1830 657 200 885 150 3028 2297 1654 170 88 2030 250 380
S3.115.500.1400.6.70L.S/C 1843 1269 20 x 27 1985 657 200 885 150 3028 2297 1654 170 88 2185 250 380

Z17 Z23 S3OPR


Pump type Z13 Z14 Z15 Z16 ZDC1 ZDN1 ZDT1 ZL1 ZL2 ZM
G S Std. Ex. Std. Ex.
S3.115.500.800.8.70L.C 250 98 565 890 3 3 627 627 620 DN 500 42 1185 284 6 x M30 627 627
S3.115.500.800.8.70L.S 250 98 565 890 3 3 985 1534 620 DN 500 42 1185 284 6 x M30 985 1534
S3.115.500.1400.6.70L.C 250 98 565 890 3 3 627 627 620 DN 500 42 1185 284 6 x M30 627 627
S3.115.500.1400.6.70L.S 250 98 565 890 3 3 1062 1689 620 DN 500 42 1185 284 6 x M30 1062 1382

69
12 S pumps, range 70

Dry, vertical installation on concrete foundation


Dimensions

X1

X02

DN2
XDC2
X16
XM1
X2

X3

X6

X7

X8
X12 X04
X03

X11

X9

X11 C

E
TM04 2424 2018

X10

XDC3

Fig. 39 Dry, vertical installation on concrete foundation

70
S pumps, range 70
12

Dimensions
Pump type C E ∅ X02 ∅ X03 ∅ X04 X1 X2 X3 X6 X7 X8
S2.90.200.1000.4.70H.D 770 500 24 23 28 1638 249 20 700 500 900
S2.90.200.1200.4.70H.D 770 500 24 23 28 1638 249 20 700 500 900
S2.100.200.1000.4.70M.D 809 460 24 23 28 1638 238 20 700 500 900
S2.100.200.1200.4.70M.D 809 460 24 23 28 1638 238 20 700 500 900
S2.105.250.800.8.70H.D 1193 750 24 23 28 1743 312 20 800 600 900
S2.122.250.1100.6.70H.D 1193 750 24 23 28 1743 312 20 800 600 900
S2.122.250.1400.6.70H.D 1193 750 24 23 28 1898 312 20 800 600 900
S2.145.300.1100.6.70M.D 1139 700 24 23 28 1743 301 20 800 600 900
S3.115.500.800.8.70L.D 1843 1200 27 27 28 1783 496 160 1450 850 1180
S3.115.500.1400.6.70L.D 1843 1200 27 27 28 1938 496 160 1450 850 1180
S3.120.300.800.8.70M.D 1139 700 24 23 28 1743 301 20 800 600 900
S3.120.300.1400.6.70M.D 1139 700 24 23 28 1898 301 20 800 600 900

Pump type X9 X10 X11 X12 X16 DT2 XDC2 XDC3 DN2 XM1
S2.90.200.1000.4.70H.D 700 DN 250 300 800 2358 28 295 350 DN 200 6 x M24
S2.90.200.1200.4.70H.D 700 DN 250 300 800 2358 28 295 350 DN 200 6 x M24
S2.100.200.1000.4.70M.D 700 DN 250 300 800 2358 28 250 350 DN 200 6 x M24
S2.100.200.1200.4.70M.D 700 DN 250 300 800 2358 28 295 350 DN 200 6 x M24
S2.105.250.800.8.70H.D 700 DN 300 300 800 2563 28 350 400 DN 250 6 x M24
S2.122.250.1100.6.70H.D 700 DN 300 300 800 2563 28 350 400 DN 250 6 x M24
S2.122.250.1400.6.70H.D 700 DN 300 300 800 2718 28 350 400 DN 250 6 x M24
S2.145.300.1100.6.70M.D 700 DN 300 300 800 2563 28 400 400 DN 300 6 x M24
S3.115.500.800.8.70L.D 700 DN 400 300 1100 3393 34 620 620 DN 500 6 x M24
S3.115.500.1400.6.70L.D 700 DN 400 300 1100 3548 34 620 620 DN 500 6 x M24
S3.120.300.800.8.70M.D 700 DN 300 300 800 2563 28 400 400 DN 300 6 x M24
S3.120.300.1400.6.70M.D 700 DN 300 300 800 2718 28 400 400 DN 300 6 x M24

71
12 S pumps, range 70

Dry, horizontal installation on base stand


Dimensions

DN2

Ø DC2

D2N
D2NxxØD02
D02

Q2 DT2

QDN1

Ø QDC1
QZ2
QZ3
Q3
D1N xD1N
Q01x Q01

Q4

QZ4
Q9 Q10
Q1

Q5 Q6 Q7

Q8
F

D
TM04 2415 2018

ØQ03
Ø Q03

Fig. 40 Dry, horizontal installation on base stand

72
S pumps, range 70
12

Dimensions
Pump type D F Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10
S2.90.200.1000.4.70H.H 285 570 1638 226 1300 800 395 600 600 700 288 1357
S2.90.200.1200.4.70H.H 285 570 1638 226 1300 800 395 600 600 700 288 1357
S2.100.200.1000.4.70M.H 400 720 1638 215 1260 800 395 600 600 700 288 1357
S2.100.200.1200.4.70M.H 400 720 1638 215 1260 800 395 600 600 700 288 1357
S2.105.250.800.8.70H.H 478 891 1743 289 1550 800 500 600 600 700 393 1357
S2.122.250.1100.6.70H.H 478 891 1743 289 1550 800 500 600 600 700 393 1357
S2.122.250.1400.6.70H.H 478 891 1898 289 1550 800 500 600 600 700 393 1357
S2.145.300.1100.6.70M.H 522 907 1743 278 1500 800 500 600 600 700 393 1357
S3.115.500.800.8.70L.H 719 1269 1783 333 2000 800 540 600 600 700 433 1357
S3.115.500.1400.6.70L.H 719 1269 1938 333 2000 800 540 600 600 700 433 1357
S3.120.300.800.8.70M.H 522 907 1743 278 1500 800 500 600 600 700 393 1357
S3.120.300.1400.6.70M.H 522 907 1898 278 1500 800 500 600 600 700 393 1357

Pump type ∅ QDC1 QDN1 D1N Q01 DN2 D2N D02 DC02 DT2 ∅ Q03 QZ2 QZ3 QZ4
S2.90.200.1000.4.70H.H 350 DN 250 12 M20 DN 200 8 24 295 26 28 338 -50 107
S2.90.200.1200.4.70H.H 350 DN 250 12 M20 DN 200 8 24 295 26 28 338 -50 107
S2.100.200.1000.4.70M.H 350 DN 250 12 M20 DN 200 8 24 295 26 28 338 -50 107
S2.100.200.1200.4.70M.H 350 DN 250 12 M20 DN 200 8 24 295 26 28 338 -50 107
S2.105.250.800.8.70H.H 400 DN 300 12 M20 DN 250 12 24 350 30 28 443 -50 107
S2.122.250.1100.6.70H.H 400 DN 300 12 M20 DN 250 12 24 250 30 28 443 -50 107
S2.122.250.1400.6.70H.H 400 DN 300 12 M20 DN 250 12 24 350 30 28 443 -50 107
S2.145.300.1100.6.70M.H 400 DN 300 12 M20 DN 300 12 24 400 33 28 443 -50 107
S3.115.500.800.8.70L.H 515 DN 400 16 M24 DN 500 20 27 620 37 28 483 -50 107
S3.115.500.1400.6.70L.H 515 DN 400 16 M24 DN 500 20 27 620 37 28 483 -50 107
S3.120.300.800.8.70M.H 400 DN 300 12 M20 DN 300 12 24 400 33 28 443 -50 107
S3.120.300.1400.6.70M.H 400 DN 300 12 M20 DN 300 12 24 400 33 28 443 -50 107

73
13 S pumps, range 70

13. Weights
Weights

Weights include 10 m cable.


Weight1
Pump type
[kg]
S2.90.200.1000.4.70H.S.340... 1050
S2.90.200.1000.4.70H.C.340... 1160
S2.90.200.1000.4.70H.D.340... 1260/1160
S2.90.200.1000.4.70H.H.340... 1260/1300
S2.90.200.1200.4.70H.S.361... 1050/1100
S2.90.200.1200.4.70H.C.361... 1160/1150
S2.90.200.1200.4.70H.D.361... 1260/1250
S2.90.200.1200.4.70H.H.361... 1260/1400
S2.100.200.1000.4.70M.S.332... 1100/1050
S2.100.200.1000.4.70M.C.332... 1210
S2.100.200.1000.4.70M.D.332... 1320
S2.100.200.1000.4.70M.H.332... 1320
S2.100.200.1200.4.70M.S.355... 1050
S2.100.200.1200.4.70M.C.355... 1160
S2.100.200.1200.4.70M.D.355... 1260/1160
S2.100.200.1200.4.70M.H.355... 1260
S2.105.250.800.8.70H.S.523... 1307
S2.105.250.800.8.70H.C.523... 1447
S2.105.250.800.8.70H.D.523... 1414
S2.105.250.800.8.70H.H.523... 1601
S2.122.250.1100.6.70H.S.443... 1150
S2.122.250.1100.6.70H.C.443... 1270
S2.122.250.1100.6.70H.D.443... 1380/1270
S2.122.250.1100.6.70H.H.443... 1380
S2.122.250.1400.6.70H.S.465... 1270
S2.122.250.1400.6.70H.C.465... 1400
S2.122.250.1400.6.70H.D.465... 1520/1400
S2.122.250.1400.6.70H.H.465... 1520
S2.145.300.1100.6.70M.S.420... 1300
S2.145.300.1100.6.70M.C.420... 1430
S2.145.300.1100.6.70M.D.420... 1560/1430
S2.145.300.1100.6.70M.H.420... 1560
S3.115.500.800.8.70L.S.402... 1500/1750
S3.115.500.800.8.70L.C.402... 1650/1800
S3.115.500.800.8.70L.D.402... 1590/1800
S3.115.500.800.8.70L.H.402... 1500/1920
S3.115.500.1400.6.70L.S.371... 1620/1950
S3.115.500.1400.6.70L.C.371... 1780/2100
S3.115.500.1400.6.70L.D.371... 1830/2000
S3.115.500.1400.6.70L.H.371... 1620/2140
S3.120.300.800.8.70M.S.442... 1300
S3.120.300.800.8.70M.C.442... 1430
S3.120.300.800.8.70M.D.442... 1560/1350
S3.120.300.800.8.70M.H.442... 1560/1490
S3.120.300.1400.6.70M.S.407... 1420
S3.120.300.1400.6.70M.C.407... 1560
S3.120.300.1400.6.70M.D.407... 1700/1560
S3.120.300.1400.6.70M.H.407... 1700

1 Material variants: G/Q.

74
S pumps, range 70
14

14. Flange forces

Flange forces
The flange forces and moments are according to EN
Horizontal installations
ISO 5199.
Z Forces can be found for both horizontal and vertical
installations in table B.3 in EN ISO 5199, by selecting
the correct flange dimension. Forces cannot be used
Y directly for end-suction wastewater pumps without
using a coefficient which can be found in table B.5 in
EN ISO 5199 by selecting the correct pump family.
Z For Grundfos wastewater pumps the pump families
Y and coefficients are as stated below.
Horizontally installed pumps
Pump family A4 = Coefficient 0.35

X
Vertically installed pumps
Pump family 10A = Coefficient 0.30

Vertical installations

X
Base unit

Z
TM06 4901 3115 - TM06 4903 3115 - TM06 4902 3115

Fig. 41 Characteristics of pumps

75
15 S pumps, range 70

15. Grundfos Product Center


Grundfos Product Center

Online search and sizing tool to help you make the right choice.
http://product-selection.grundfos.com

All the information you need in one place


Performance curves, technical specifications, pictures, dimensional
drawings, motor curves, wiring diagrams, spare parts, service kits,
3D drawings, documents, system parts. The Product Center displays
any recent and saved items - including complete projects - right on
the main page.
Downloads
On the product pages, you can download installation and operating

TM07 2384
instructions, data booklets, service instructions, etc. in PDF format.

2 3 4 5

TM07 2383

Pos. Description
1 This drop-down menu enables you to set the search function to "Products" or "Literature".
2 SIZING enables you to size a pump based on entered data and selection choices.
3 CATALOGUE gives you access to the Grundfos product catalogue.
REPLACEMENT enables you to find a replacement product.
Search results will include information on
4 the lowest purchase price
the lowest energy consumption
the lowest total life cycle cost.
5 LIQUIDS enables you to find pumps designed for aggressive, flammable or other special liquids.

76
77
78
79
ECM: 1307628

GRUNDFOS A/S
96846146 01.2021

www.grundfos.com
Telephone: +45 87 50 14 00
DK-8850 Bjerringbro . Denmark