Professional Documents
Culture Documents
RPC Cool Springs 1
RPC Cool Springs 1
01-006-1820-LW-2
PNSDW Limit
Parameter Unit Method Result Remarks
Non Purified Purified
Color CU 2120 B 10 CU <10 PASSED
pH ― 4500-H+ B 6.5 – 8.5 5.0 – 7.0 7.5 PASSED
Turbidity NTU 2130 B 5 NTU 0.39 PASSED
Total Dissolved Solids mg/L 2540 C 600 mg/L 10 mg/L 386 PASSED
Chlorine Residual (Free Chlorine) mg/L 4500 G 0.3 – 1.5 mg/L 0.486 PASSED
Nitrate mg/L 4500-NO3- B 50.00 mg/L 0.371 PASSED
Arsenic mg/L 3113 B 0.01 mg/L <0.01 PASSED
Cadmium mg/L 3113 B 0.003 mg/L <0.003 PASSED
Lead mg/L 3113 B 0.01 mg/L <0.01 PASSED
References:
• Standard Methods for the Examination of Water and Wastewater, 23rd edition (American Public Health Association,
American Water Works Association, Water Environment Federation)
• Philippine National Standards for Drinking Water – 2017
The MOST Credible Water Testing Laboratory in North and Central Luzon