Data Panasonic
Data Panasonic
B1-S Series
■ The following symbols are used to indicate the level of danger possibly
occurred when you fail to observe the safety precautions.
△ DANGER
!
Indicates a potentially hazardous situation,
which if not avoided will result in death or
serious injury.
2
Important
△
! DANGER
Do not use in corrosive Do not touch the Do not touch the
atmosphere, flammable rotating part of the terminal for five minutes
gas atmosphere, or near brushless motor while after turning off power.
combustible substance. operating.
The failure could result in The failure could result in The failure could result in
fire. injuries. electric shocks.
Do not climb or stand on Do not give damage to, Do not touch the
the servo equipment. apply excessive force brushless motor
to, place something because it becomes hot.
heavy upon, or pinch
the lead.
The failure could result in The failure could result in The failure could result in
electric shocks, damages, or electric shocks, damages, burns.
malfunction. or malfunction.
The failure could result in The failure could result in The failure could result in
! electric shocks or injuries.
! electric shocks, injuries, fire,
damages or malfunction
! electric shocks, injuries, fire,
damages or malfunction.
3
Safety Precautions
△
! DANGER
△
! CAUTION
Do not turn on or off the Do not place any Do not approach to the
power frequently. obstacle that blocks equipment after recovery
ventilation around the from the instantaneous
brushless motor. stop because they may
restart suddenly.
The failure could result in The failure could result The failure could result in
malfunction. in burns or fire. injuries.
Be sure to turn off power Do not modify, Never start and stop the
when the brushless disassemble, or repair brushless motor by
motor is placed out of the product. magnet contactor, etc.
use for a long time. installed on the main
power line.
The failure could result in The failure could result in
The failure could result in
injuries due to malfunction. fire, electric shock or malfunction.
injuries.
Do not hold the lead or Do not give any strong Do not drive the motor
motor shaft when impact to the motor and shaft externally.
transporting the motor. shaft.
The failure could result in The failure could result in The failure could result in
injuries. malfunction. fire, electric shock or
malfunction.
The failure could result in The failure could result in The failure could result in
! injuries. ! injuries or electric shocks. ! electric shocks, injuries, or
fire.
4
Important
△
! CAUTION
5
Introduction/Name of each part/Precautions
After unpacking
● Make sure that the model is what you have ordered.
● Check whether the product has been damaged or not during transportation.
If any deficiency should be found, contact the dealer store where you bought this product.
6
Installation
How to install
Install the brushless motor properly for preventing failure and accident.
Transport ● Use caution enough in transporting the unit to prevent injury by drop or
fall, and avoid damage to the equipment.
Storage ● Keep the unit indoors in a clean and dry place free from vibration with
little change of temperature.
Location ● Location gives great influence upon the life of brushless motor,
therefore choose a place in conformance with the conditions below:
(1) Indoors where the motor is not subjected to rain water and direct sun beam.
(2) Do not use the motor in corrosive atmosphere such as hydrogen sulfide, sulfurous acid, chlorine,
ammonia, sulfur, gas chloride, gas sulfide, acid, alkali, and salt, in the atmosphere of combustible
gas, or in the vicinity of flammables.
(3) Place not exposed to grinding liquid, oil mist, iron powder, and cutting particle.
(4) Well-ventilated place with little moisture, oil, and entry of water, and place far from heat source such
as a furnace.
(5) Place easy to check and clean
(6) Place free from vibration
(7) Do not use the unit in an enclosed environment. Enclosing may raise the temperature of brushless
motor, and shorten their life.
Environmental condition
Item Condition
*1
-10°C - 40°C (free from freezing)
Ambient Brushless motor
(UL accreditation of 0.75kW product is between -10°C and 30°C.)
temperature
Console A/Digital key pad (sold separately)
-10°C - 50°C (free from freezing)
Ambient humidity 85% RH or below (free from condensation)
Storage temperature -20°C -60°C (free from freezing)*2
IP44
(Excluding output shaft rotation part, lead tip, and terminal box lead portion.)
Protection Brushless motor x This motor conforms to test condition specified in EN standard (EN60529 and
structure EN60034-5). This motor is not applicable to the use which requires long-term
waterproof performance, such as the case where the motor is always washed
with water.
Console A/Digital key pad (sold separately) Equivalent to IP20
Vibration Not greater than 4.9 m/s2 (10 - 60 Hz)
Altitude Not greater than 1000 m
*1 Ambient temperature is measured at a distance of 5cm from the motor.
Others *2 Temperature which is acceptable for a short time, such as during transportation.
7
System configuration and wiring
System configuration/general wiring diagram
Regenerative Magnetic AC
resistor contactor
Noise filter NFB power supply
Wiring
R(L1)
Standard wiring Regenerative
S(L2) P Regenerative resistor (sold
diagram T(L3) resistor separately) can be
AC power supply PB connected.
NFB
Control terminal box
(No-fuse breaker)
Control terminal Rotation Operation
Be sure to ground a block stop
direction
grounding terminal. I1
Console A (sold separately)
Grounding I2
terminal GND Console A can be connected
O1 to the control terminal block.
Rotation speed See "Console A connecting
Do not tighten FIN
screws cable" on page 36 for
+5V 5kΩ connecting.
together.
I3
I4
CN2 I5
External speed setting
Variable resistor
Digital key pad Digital key pad can be connected by digital key
pad connecting cable (sold separately). O2 5KΩB characteristics
(sold separately) 1/4W or above
8
Wiring
Function of terminal
Power terminal box PB Power LED Control
P terminal block
0.75kW P PB
GND
+5V
FIN
O1
O2
I2
I4
I1
I3
I5
L1 L2 L3
Terminal symbol Control terminal box
is indicated on R S T
VR1
terminal block.
R/L1 T/L3
CN2
S/L2
<Power input> (0.75kW for terminal block specification, 0.2kW/0.4kW for lead specification)
■ Recommended tightening torque of power supply terminal box cover fixing screw with terminal block specification is
between 1.0 to 1.4N・m.
Terminal Lead color Terminal Description of function
symbol (0.2kW, 0.4kW) name
R/L1 Red
Power Connect the product to commercial power supply conforming to rated voltage.
S/L2 White supply input As for a model with single-phase power, connect to L1 and L2.
terminal Recommended tightening torque of terminal block: 1.0 - 1.4 N・m
T/L3 Black
P Blue Regenerative Regenerative resistor can be connected between P and PB.
resistor It is a high voltage wire when unused, therefore be sure to insulate individually.
connecting (For lead specification)
PB Brown terminal Recommended tightening torque: 1.0 - 1.4N・m
Terminal for grounding the motor. It is available in two positions inside and outside the
Grounding
Screw terminal
terminal box in terminal block specification. Use either one for grounding.
Recommended tightening torque: 0.6 - 1.0N・m
<Control terminal box> ■ Recommended tightening torque of control terminal box cover fixing screw is
between 0.6 to 1.0N・m.
● Control terminal block
Terminal symbol Terminal name Description of function
*1
I1 Signal input 1 Operation instruction input: Motor runs when "I1" and "GND" are shorted, and stops when they are opened.
9
Wiring/Test run
Input circuit Photo-coupler FIN characteristics
(Typical value)
Preset speed
Internal
power I1, I2, I3,
supply 1.5kΩ (Upper speed limit)
(+5V) I4, I5
GND
Output circuit
O1, O2
Speed potentiometer
(Test run: For console A)
Power
lamp Rotation When RUN/STOP switch is changed to RUN, the motor rotates, and when the motor is returned
direction
selecting to STOP, the motor stops.
switch Rotation direction can be changed by rotation direction choosing switch on the side of console.
When the rotation direction is changed in RUN, the motor is inverted suddenly, and the motor
may trip due to some inertia of load.
Rotation speed can be adjusted by the speed potentiometer.
Turn OFF power when the motor is to be stopped for a long time.
■ When power is turned OFF with RUN/STOP switch on RUN side, and power is turned on
again, the motor may start again, which is dangerous. In turning on power, always make
RUN/STOP switch sure that the switch is on STOP side.
■ Described above is the operating procedure in default setup. If internal parameters have
been changed with the Digital key pad, operation may be different. Return the required
setting (such as parameter 30, 31, and 33) to the shipment setting, or initialize parameters.
(Parameter 54)
However, when a parameter is initialized, note that all parameters return to shipment setting.
10
Checking the load and use condition,
maintenance and inspections
Checking the load and use condition
Check use condition for eternal use of this product. Some use conditions may possibly lead to
heating or damage to the shaft. Fully check use conditions, and use the motor in a permissible range.
Standard life
Standard life is 10, 000 hours for the motor equipped with gear head (MB8G and MB9G).
Standard life refers to a designed life at normal temperature and humidity and uniform load (rated
torque).
Load torque
Set the load torque so that its effective value is below rated torque. When the digital key pad is used,
average torque can be displayed as a load factor. (See the use of digital key pad on page 14.)
● Power-on/off operations should be done by the operators themselves for ensuring safety in checking.
● Do not touch the motor while power on.
● In performing the measuring insulation resistance, remove all connections.
Measuring insulation resistance with connection can cause motor failure.
Maintenance/Inspection item
Inspection item Inspection procedure Condition
Input current Ammeter Must be within rated input current described on nameplate.
Measure the insulation resistance of motor with 500V megger. Measured resistance must be
Insulation
Insulation more than 1MΩ.
resistance
resistance Measurement position:
tester Between power input (R/L1, S/L2, and T/L3) and grounding terminal
Noise level must not be different from the usual level. In addition, abnormal noise
Noise Hearing
such as rumbling noise must not be heard.
Be sure to contact our service division or sales agent for disassembling and repairing.
11
Protective functions/How to clear trip
Protective functions
■ Description of trip can be displayed only when the Digital key pad (option) is connected.
Protection function works even when the Digital key pad is not connected, but it is not displayed.
Display on
Protective item Description Measure Digital key pad
When the internal DC voltage is below specified value,
operation is stopped; when voltage is recovered,
Undervoltage operation is started again. (This is not trip, and no trip
warning (default)
output is made.)
■Trip can be set by parameter 50.
L
Investigate the condition of wiring and circumstances
100V product: Approx DC100V
200V product: Approx DC200V of power supply.
Setting change The motor trips when any important parameter such as This is not abnormal. Reset tripping in order to make
warning "30 Operation instruction selection" is changed. change effective. CAU
External forced trip The motor trips when external forced trip input turns on. Turn off external forced trip input, and trip reset. E-OL
[2] Press the switch and of the Digital key pad simultaneously for one second or more with present trip
state displayed.
[3] Input the trip reset signal.
When F-r or r-F is chosen in " 33 . I1/I2 function selection", enter "I1" and "I2" at the same time: when
F-rST or r-rST is chosen, enter "I2 for trip reset".
Further, when rST is chosen in any of " 34 . I3 function selection " " 35 . I4 function selection " and " 36 . I5
function selection ", enter respective input signal for clearing trip.
Trip reset signal, when continued to be input, is designed to become ineffective in order to prevent inadvertent
restarting. Enter trip signal only when necessary.
Note: As for overcurrent error E - OC , sensor error E - CS , system error Err , and user parameter error E-Upr ,
reset them by turning OFF power as shown in [1] above. No other procedure is effective.
(Caution) In clear trip, be sure to find and remove the trip factor before clear.
12
Troubleshooting
If any trouble should be found, follow the steps below for check and countermeasure.
● If the cause cannot be found, it is recommended to use the Digital key pad and check the detail
of trip. If failure is likely, or when any part is damaged, or when you are in any other trouble,
contact the sales agent of purchase or our company.
Check whether protective function is Check the detail of trip by the Digital key pad.
activated. Remove the cause, and clear trip.
Check whether Analogue speed instruction Raise the analogue speed instruction
is set at 0V. little by little.
Motor does not stop The motor with large inertia does not Stop motor by 0V analogue speed command.
quickly when stop stop quickly because default stop Change stop mode to deceleration stop by Digital
command is input. mode is free-run stop. key pad.
Large vibration or The motor output shaft and load shaft Check the coupling between the motor
noise. are not aligned. output shaft and load shaft.
Rotation speed is
Reduce the fluctuation of load. Increase the
unstable during operation Check whether the load fluctuates greatly.
(actual speed). output capacity.
13
How to use Digital key pad
Name of each part and Installation
● What can be done by Digital key pad
x Monitoring of rotation speed (actual speed) and load factor, etc
(Rotation speed can be displayed being multiplied by the factor set by parameter 47 and 48 .)
x Display detail of trip, and trop history. Trip reset by pressing and .
>>
>>
x Parameter setting, initialization, and copying function at the same time.
x Start and stop of motor by RUN / STOP switch (Setting of parameter " 30 Run command selection" is
required.)
STOP switch
>>
switch
DATA
>>
switch switch
SET
MODE switch
RUN switch
Displays rotation speed (actual speed), commanded speed, trip history, setting of parameter,
5-digit LED
and the like.
This switch enables selection of parameter, and setting and changing of contents.
switch
>>
>>
When the motor is tripped, pressing and at the same time enables clear of trip.
>>
>>
This switch is for instruction of operation. (Only when " 30 Run command selection" is PnL )
RUN switch ■ See " 33 I1/I2 function selection " (2) on page 27 for rotation direction.
■ Operation is stopped by detaching the Digital key pad using RUN switch during operation.
This switch is for instruction of stopping.
STOP switch (Only when " 30 Run command selection " is PnL )
●Description
Displays rotation speed, setting speed, internal DC voltage, load factor, and torque on 5-digit
LED. When power is turned on, this mode is set.
Monitor mode This mode is set when power is turned on.
Control changes to this mode when MODE switch is pressed in parameter number mode,
parameter setting mode.
Displays a parameter number (00 – F0) in flashing.
Parameter
Control changes to this mode when DATA
SET switch is pressed in parameter number mode.
number mode
>>
>>
>>
14
Operating Instruction
Turn on
Monitor mode ●Press MODE switch for changing display.
power.
Rotation ● r/min
○
speed ○
>>
can be directly set by
○
Internal DC
>>
voltage
○ and in monitor mode.
● V
MODE
Flashing
Load factor
○
● %
0
○
MODE Flashing
>>
MODE MODE DATA
SET ○
>>
Torque ● %
○
MODE Flashing
Speed ● r/min
○
setting ○
>>
number 0.30
mode 0
Only Flashing Flashing
" 00 " 00 10
>>
>>
Press Press
>>
>>
DATA DATA
SET SET
Storage Storage
Change (select) a parameter number
>>
by or .
>>
>>
>>
>>
DATA
When SET switch or MODE switch is
pressed in parameter setting mode, data is stored. Change (select) a parameter value by
or .
>>
>>
>>
● When
>>
>>
command selection is PnL , the motor speed also changes following the speed setting if the
motor is running.
(Note) Data is stored only when DATA
SET switch is pressed. Note that data returns to settings when
power is turned OFF.
15
Test run (Digital key pad)
Inspection prior to test run
(Inspection prior to test run)
(1) Make sure that all wiring is correct. (2) Make sure that input power supply conforms to rating.
(Test run)
Test run procedure by the Digital key pad is as follows:
* An example is introduced here where the motor runs CW at 1800r/min with the Digital key pad.
(1) Be sure to first perform the work below for safety.
Separate the motor from machine or equipment, and make sure that the motor alone can be
operated.
(2) Then turn on power and follow the step below for test run.
○ ○
Store by DATA
SET . 30 30
Setting change warning is
issued because setting of CAU
operation instruction has
been changed.
>>
Press and at ○ ●
00
DATA ○ ○
[4] Change of Press SET 0 ○
○
VoL-A ○
○
initial setting 2
>>
Press several
(Change the choice times to choose 00 Flashing 31 Flashing
of speed instruction parameter number 31 .
from analogue
speed instruction Press DATA
SET
○ ○
input to " 00 Speed Press to change
VoL-A ○ PnL ○
>>
○ ○
setting (the 0-th
speed)" to enable parameter value. Flashing Flashing
16
Description of Digital key pad
operation switch LED display
○ ●
>>
[5] Trip reset Press and at CAU 0
>>
○ ○
○ ○
the same time.
00
○ ○
Press DATA
SET 0 ○
○
rS.Fr ○
○
[6] Choosing
rotation Press >> several
times to choose 00 Flashing 33 Flashing
direction* parameter number 33 .
(This operation is not Press DATA
SET
○ ○
required for rotation rS.Fr ○ r-F ○
Press to change
>>
○ ○
forward [CCW].)
parameter value. Flashing Flashing
Store by DATA
SET . 33
30 33
Setting change warning is
issued because setting of 30
operation instruction has CAU
been changed. CAU.
○ ●
>>
>>
[8] Speed 0
○
○
[9] Reset to 0 ○
○ x Data is still stored if power is cut
monitor Press MODE OFF here.
mode. 00
●
x Display of rotation speed changes
[10] Operation 1800 ○ little by little toward 1800 r/min
○
instruction Press RUN x Display of rotation direction *
r (r indicates that the motor is
rotating CW.)
●
[11] Stop 0 ○
○ x Display of rotation speed changes
Press STOP little by little toward 0 r/min.
instruction
00
[12] Power OFF
17
How to copy parameter
1. Reading a parameter value from Motor to the Digital key pad
■Once parameters are read into the console, their details are stored in the Digital key pad.
Description of Digital key pad
operation Switch LED display
●
[1] Turn on 0 ○
○
power.
00
Parameter ● ○
DATA
[2] Call 57 Press SET value ○
○
n0 ○
○
Parameter
Hold down to>>
Copy. choose parameter 00 57
Flashing Flashing
number 57 .
DATA
[3] P.LOAd Press SET
○ ○
Choose reading n0 ○
○
P. LOAd ○
○
a parameter into
>>
2. Copy a parameter value saved in the Digital key pad onto the brushless inverter.
[1] P.PrOG
Press twice.
DATA
○ ○
P. PrOG
SET
Choose writing n0 ○
○
○
○
a parameter to Press
>>
[2] Write a ○
parameter to
DATA
Press SET for 1 P. PrOG ○
○
Flashing Æ Slow flashing
(once per second)
the brushless second while holding
inverter.
down STOP . 57
○
[3] Wait about 10 P. E n d ○
○
seconds.
18
Description of Digital key pad
operation Switch LED display
○
[4] Completion of CAU ○
○
writing a
parameter from
the Digital key
pad to the motor
[5] Return to ●
0
>>
>>
○
Press and at
monitor mode. ○
[4] Initializing of ●
data of Digital 0 ○
○
key pad Press STOP
completed 00
■ Do not turn OFF power or disconnect the cable of Digital key pad during operation such as "Reading a
parameter from the motor to the Digital key pad", "Copying a parameter value stored in the Digital key pad
to the brushless inverter", and "Initializing the data of Digital key pad".
19
Parameters
Overview of parameter
Brushless motor of this series is provided with various parameters for adjusting and controlling its
characteristics and function. Purpose and function of respective parameter are described. Understand them well
enough and adjust the unit at your optimum operation condition.
20
Parameter
Parameter setting
No. Name of parameter
Setting range Minimum unit Default Check*1
O.-r S. – r
Rotation speed
(Actual speed) Command speed
46
Monitor mode
O.-L Torque dC - V Internal DC voltage O.-r
selection
AV.-L Load factor (average torque)
Numerator of display 1 ‒ " 48 Denominator of display 1 time
47 magnification factor magnification factor" x 10 1
Denominator of display 1 time
48 magnification factor 1 - 1000 1
nO No operation
4A Trip history clear
YES Clear trip history
nO
4b Trip history 1 -
4C Trip history 2 -
4d Trip history 3 - -
4E Trip history 4 -
4F Trip history 5 -
Under voltage nO No trip
50 nO C
trip selection YES Trip
51 Retrial selection nO ,1-4 nO C
52 Retrial start time 1 - 120 sec 1 sec 5
Parameter nO No operation
54 initializing YES Initialize to default
nO
nO No copying of parameter
*1 When parameter marked with C in the check column is changed and stored, the unit is tripped for safety. It is not allowed
to change them while the motor is running.
*3 Only "I1" and "I2" are effective for operation instruction. (They correspond to RUN/STOP switch on console A.)
*4 Corresponds to incorporated potentiometer for setting speed (VR1), speed potentiometer of console A, or analogue speed
direction.
*5 Torque is not controlled directly, and no precision is obtained. Especially in setting below 30%, torque is not generated
and the motor does not start. Be cautious.
*6 Setting in shipment depends on rated rotation speed.
1800r/min specification: 24, 3600r/min specification: 12 (It is impossible to set 24 for 3600r/min specification.)
21
LED display
LED display
Figures displayed on the 7 segment display of the digital key pad are shown below:
LED display
Example) Description in the text Display on Digital key pad
22
Detail of parameter
Parameter
No. Name of parameter Description
Desired running speed can be set. This is effective when " 31 Speed command selection" is
Internal speed
00 PnL (PANEL).
(0-th speed)
Upper limit is limited by " 3b Upper speed limit".
1st speed Speed in multi-speed running can be set. It is effective when “ 32 Operation mode selection"
01 to
is set to 2-speed operation mode.
7th speed
Straight line acceleration/deceleration and curve (S-shape) acceleration and deceleration can
be chosen individually for acceleration and deceleration.
LIn LINEAR S−1 “S”SHAPE-1 S−2 “S”SHAPE-2
回転速度
回転速度
回転速度
Acceleration mode
14
Rotation speed
Rotation speed
Rotation speed
selection
Deceleration mode
15 selection
Free-run
Zero-speed control
Deceleration running
When " 16 Stop mode selection" is set to dEC (DECEL) deceleration stop, servo
Free-run
17 waiting time
lock time(Zero-speed control)after deceleration can be adjusted.
(Free-run state is set after that.)
Enables setting of proportional gain of velocity amplifier. It need not be changed normally.
Velocity loop When this value is made greater, gain is increased, which improves responsiveness of the
1A proportional gain motor. When this value is made too large, operation is vibratory.
Setting range: 0 – 10000, Setting resolution: 1
Enables setting of integration gain of velocity amplifier. It need not be changed normally.
Velocity loop When this value is made greater, gain is increased, which improves rigidity of the motor
1b (strength of servo lock). When this value is made too large, overshooting becomes greater,
integration gain and the motor is vibratory.
Setting range: 0 – 10000, Setting resolution: 1
23
Parameter
No. Name of parameter Description
Run Command can be chosen from the following:
PnL (PANEL) : command the motor to stop with RUN STOP switch of Digital
key pad. The motor cannot be operated by signal input "I1" and "I2".
Run command
30 selection
Signal input is effective only in setting rotation direction, etc.
See " 33 I1/I2 function selection".
TEr (TERMINAL) : Only the input terminal "I1" and "I2" are effective.
(Corresponds to RUN/STOP, rotation direction selection switch of Console-A.)
You can choose whether to use " 00 Internal speed (0-th speed)" or analog input terminal
"FIN" for speed command.
Speed command (PANEL) " 00 Internal speed (0-th speed)"
31 selection
PnL
VoL-A (VOL-A) Analog input terminal "FIN" (voltage instruction DC 0-5V)
(Corresponds to speed potentiometer of Console-A.)
Parameter for choosing operation mode
Free-run stop
1st speed
1 External forced trip
operation mode
The 2nd acceleration/deceleration time
Trip reset
2 2nd speed operation mode Speed setting
8 8th speed operation mode Speed setting Speed setting Speed setting
24
Parameter
No. Name of parameter Description
(1) For setting "I1" or "I2" function
F-r (FORWARD-REVERSE)
State of I1 and I2
Action
I1 I2
Stop
OFF OFF
Deceleration stop when " 16 Stop mode selection" is dEC
ON OFF CW run
OFF ON CCW run
Free-run stop
ON ON
Trip reset (which must be retained 0.2 sec or longer)*
ON ON CW run
ON - CCW run
- ON Trip reset (which must be retained 0.2 sec or longer) *
ON - CW run
- ON Trip reset (which must be retained 0.2 sec or longer)*
*Effective only when trip occurs.
25
Detail of parameter
Parameter
No. Name of parameter Description
(2) When " 30 Run command selection" is PnL (PANEL), the motor can
be commanded with RUN STOP switch of Digital key pad.
Rotation direction in this case can be set by parameter and "I1" "I2" state.
"I1" "I2" are off when only digital key pad is connected.
F-r (FORWARD-REVERSE)
State of I1 and I2
Action
I1 I2
- OFF CCW rotation selection
OFF ON CW rotation selection
Free-run stop irrespective of RUN switch
ON ON
Trip reset (which must be retained 0.2 sec or longer)*
r-F (REVERSE-FORWARD)
State of I1 and I2
Action
I1 I2
- OFF CW rotation selection
OFF ON CCW rotation selection
Free-run stop irrespective of RUN switch
ON ON
I1/I2 function Trip reset (which must be retained 0.2 sec or longer)*
33 selection
(continued) rS.Fr (RUN・STOP – FORWARD・REVERSE)
State of I1 and I2
Action
I1 I2
- OFF CCW rotation selection
- ON CW rotation selection
State of I1 and I2
Action
I1 I2
- ON Trip reset (which must be retained 0.2 sec or longer)*
26
Parameter
No. Name of parameter Description
Speed instruction value
When " 31 Speed command selection" is Upper limit speed
Output terminal " 01 " and " 02 " can also be selected as follows.
Polarity of " 40 O1 function selection" and " 41 O2 function selection" can be inverted by "
42 O1 output polarity selection" and " 43 O2 Output polarity selection".
TrIP (TRIP) : Trip signal (Trip: ON)
STbL (STABLE) : Arriving signal (When reached to a command value
O1 function ON) Æ See " 44 Speed matching range".
rUn (RUN) : Run/Stop signal (When running: ON)
40 selection
FrEE (FREE) : Free-run signal (During free run: ON)
41 O2 function
F (FORWARD) : CCW run signal (During CCW run: ON)
selection
r (REVERSE) : CW run signal (During CW run: ON)
Ck - L (CHECK−L) : Overload detection
Output when load exceeds 100%
(Load exceeds 100%:ON)
POUT (PULSE-OUT) : Speed pulse signal
Æ See " 45 Output pulse count selection".
O1 output polarity This is a function for inverting the polarity of signal output between output terminal " O1 "
42 selection " O2" and "GND".
O2 output polarity nOr (NORMAL) : Transistor "ON" when activated
43 selection rEV (REVERSE) : Transistor "OFF" when activated
When " 40 O1 function selection " and " 41 O2 function selection" are chosen to
STbL (STABLE) Arriving signal, "Speed matching range" for output arriving
signal can be adjusted.
Speed matching x When difference between actual rotation speed and speed setting is smaller than
44 range "Speed matching range", arriving signal is output.
x Even if the speed is reached, when speed matching range is set too small,
arriving signal may turn on and off due to speed fluctuation.
x Arriving signal is not output when CCW/CW changes.
When " 40 O1 function selection " and " 41 O2 function selection " are set to
POUT (PULSE-OUT), pulse count is set to be output to " 01" and " 02" while the motor
makes one turn. (To be selected from 1, 2, 3, 4, 6, 8, 12, and 24)
(Ex) When rotation number is 3000
Output pulse count * 24 is allowed for setting only for 1800r/min specification. r/min, in the case where " 45 Output
45 selection T
pulse selection" is 24,
500 ± 100µs
It is impossible to set 24 for a motor with 60
rated rotation speed 3600r/min. T= = 1.39ms
1800×24
Frequency f =1/T= 720Hz
You can choose description to be displayed on 5-digit LED when turning on power.
O.-r (OUTPUT-REVOLUTION) : Rotation speed
O.-L (OUTPUT-LOAD) : Torque
AV.-L (AVERAGE-LOAD) : Load factor (average torque)
Monitor mode
46 selection S.-r (SETTING-REVOLUTION) : Speed command
dC-V (DC-VOLTAGE) : Internal DC voltage
(Voltage of smoothing capacitor of power supply)
In speed display mode, the value multiplied by " 47 Numerator of display multiplying factor" / " 48
Denominator of display multiplying factor" is displayed.
27
Detail of parameter
Parameter
No. Name of parameter Description
You can set the multiplying factor of a value displayed on 5-digit LED.
Numerator of display
47 Value of 47 ÷ 48 is a display multiplying factor. Set a value in the range where calculated
magnification factor
display magnifying factor is 10 – 1/1000.
・ Capable of displaying the speed of line, etc.
Denominator of
When the display magnifying factor is changed, the parameter relating to speed
(below) is displayed by a value multiplied by display multiplying factor.
48 display magnification
factor “ 00 Internal speed (0-th speed)” “ 01 1st speed” - “ 07 7th speed” “ 3A Lower speed
limit” “ 3b Upper speed limit ” “ 44 Speed matching range”
Trip history 1 – 5 can be cleared.
<Clearing procedure>
4A Trip history clearing Cut off power with YES (YES) selection, and turn on power again after display
has disappeared, then ----- is displayed, and trip history is cleared.
When power is turned on again, normal operation is started.
4b Trip history 1
4C Trip history 2 Trip history for 5 times in the past is stored. Trip history 1 is the latest history.
4d Trip history 3 See "Protective function" for displayed description.
4E Trip history 4 When no history is available, ----- is displayed.
4F Trip history 5
When nO (NO) is selection, the motor is not tripped at insufficient voltage. If
voltage should fall and undervoltage status is found while the motor is running, the motor
stops after running free, while if operation instruction is input after recovery of power, the
Undervoltage trip motor is restarted automatically. (■Be cautious.)
50 selection When YES (YES) is selection, the motor is tripped at undervoltage, and trip
signal is output. When normal power is off, trip is not stored in trip history. Trip is stored
only when power has stopped instantaneously. (Trip is stored in trip history only when
voltage once becomes short and then is recovered normal)
Automatic reset in trip (trip retrial) can be set here. Trip can be is automatically reset to
allow operation to continue.
Use this function only on such equipment that has no problem of safety even if the motor
is automatically restarted.
■ Retrial is impossible if trip is by Overcurrent error E - OC , Sensor error
E - CS , System error Err , User parameter error , E - UPr
or System parameter error E-SPr .
51 Retrial selection
When nO (NO) is selection, retrial is not effective.
When 1 – 4 is selection, retrial is made for the set number of times.
When 2 hours has elapsed with no trip, the number of retrying times is initialized to 0.
Set the interval between retrials by 52 Retrial start time.
When trip occurs in excess of preset number of trials, the brushless inverter outputs trip
signal and stops.
■ During retrial, trip signal is not output (It is stored in trip history)
You can set waiting time until retrial operation is performed after tripping is found.
52 Retrial start time
You can set 1 to 120 seconds.
28
Example of running pattern
● Example of running pattern by use of 2nd acceleration/deceleration time
When you choose " 16 Stop mode selection" at dEC : Deceleration stop
Choose " 32 Operation mode selection" at 1 : 1st Speed operation mode,
Choose " 33 I1/I2 function selection" at rS.Fr : (RUNSTOP, FORWARD – REVERSE), and
Choose " 34 I3 function selection" at U - d : 2nd acceleration and deceleration time
CCW
CW
Forward/Reverse
Switch (I2)
2nd acceleration/
deceleration time
(I3)
●Example of operation pattern in 2nd speed operation mode
When you choose " 32 Operation mode selection" at 2 : 2nd speed operation
mode, "I3" is choosing of Speed Setting, and works as follows:
I3 Setting to be chosen
OFF Internal speed(0-th Speed)
ON 1st Speed
0-th Speed
CCW
CW
Speed 0 control
Run/Stop Switch
(I1)
Forward/Reverse
Switch (I2)
2nd acceleration/
deceleration time
(I3)
29
Conformance to EC directive and UL standard
EC Directives
The EC directives apply to all such electronic products as those having specific functions and directly sold to
general consumers in EU countries. These products are required to meet the EU unified standards and to be
furnished with CE marking.
Our brushless motor meet the EC Directives for Low Voltage Equipment so that the machine or equipment
comprising our AC servo can meet relevant EC Directives.
EMC Directives
Our brushless motor can meet EMC Directives and related standards. However, to meet these requirements,
the systems must be limited with respect to configuration and other aspects, e.g. the installation and some
special wiring conditions must be met. This means that in some cases machines and equipment comprising
our servo systems may not satisfy the requirements for wiring and grounding conditions specified by the
EMC Directives. Therefore, conformance to the EMC Directives (especially the requirements for emission
noise and noise terminal voltage) should be examined based on the final products that include our system.
Applicable standard
Be sure to connect a specified no-fuse breaker certified by IEC standard and UL, or a fuse certified by
Fuse
UL between power supply and noise filter. Observance of this condition allows conformance with
breaker UL508C (file No. E164620) and UL1004 (file No.E166557).
Noise When installing one noise filter at the power supply for more than one brushless motor used, contact the
filter manufacturer of noise filter.
Install a surge absorber on the primary side of noise filter. However, in performing the voltage
surge
resistance test of machine and equipment, be sure to remove the surge absorber; otherwise,
absorber
the surge absorber may be ruptured.
Be sure to connect the connecting terminal of brushless motor with the protective earth (PE) for
Grounding
preventing electric shock. Do not tighten protective earths together but connect them individually.
30
Wiring of peripheral equipment
Power supply
Surge absorber
Protective earth (PE) Brushless motor
Noise filter
Surge absorber
1 2 3
1 2 3
31
Specifications
● Specifications
● Common specifications
Item Specifications
Speed control range Rated rotation speed/100 - Rated rotation speed (Speed ratio 1:100)
Speed With load ±1% or below (at 0 – Rated torque, Rated rotation speed)
fluctuation With voltage ±1 % or below (at supply voltage ±10%, rated rotation speed)
factor With temperature ±1% or below (Motor: At -10 – 40°C, Brushless inverter: At -10 – 50°C, rated rotation speed)
Acceleration/Deceleration time 0.5 sec (time for changing 1000r/min)*
Stopping procedure Free-run stop*
Speed setting Analogue voltage (0-5V), incorporated potentiometer, or console A or Digital key pad (digital)
32
● Speed – Torque characteristics (Torque in short-time run area is a typical value.)
MBMA021A□B
Torque MBMA023A□B
1.59N・m
Short-time MBMA023B□B
operation region Torque
1.06N・m
0.80N・m
Continuous Short-time operation region
0.53N・m
operation region
Continuous operation region
1800r/min 3600r/min
Rotation speed Rotation speed
Torque
MBMA043A□B
3.18N・m
Short-time
operation region
2.12N・m
Torque MBMA043B□B
1.59N・m
Short-time
Continuous operation region
operation region 1.06N・m
Continuous
operation region
1800r/min 3600r/min
Rotation speed Rotation speed
Torque MBMA083A□B
5.97N・m
Short-time
operation region
3.98N・m
Torque MBMA083B□B
2.98N・m
Short-time
Continuous
operation region
operation region
1.99N・m
Continuous
operation region
1800r/min 3600r/min
Rotation speed Rotation speed
33
● Dimensional Outline Drawing (in mm)
MBMA023□BB
Grounding terminal
Grounding terminal
MBMA083□BB
Control terminal box
Power supply terminal box
Grounding terminal
34
Power supply lead (three; red, white, and black)
MBMA023□LB Power lead
100V specification, two, red and white
MBMA021ALB
90 +030 mm long from the lead
Regenerative resistance lead
(two; blue and brown)
Control terminal box
200V specification, three, red, white, and black
φ4.3 hole
φ4.3 hole
φ13 hole
φ13 hole
Power supply
terminal box
Grounding terminal
φ23 hole
Control
terminal box
φ13 hole
MBMA083□LB
35
Options
● Digital key pad ● Mounting hole
Options
● Console A ● Digital key pad 65
(sold separately) (sold separately) 55
DV0P3500 DV0P3510 14 Φ30 hole
28
65
8 65
55 20
20 55
60
70
28
70
60
70
60
2-M3 or
Φ3.7 hole
2-Φ3.5 2-Φ3.5 Mounting hole drilling drawing for
Console A and Digital key pad
● Regenerative resistor 65
(sold separately) 57
Power
Powersupply
supplyvoltage
voltage Model
Model name
name Specifications
Specifications
AC100V
AC100V DV0P37902
DV0P37902 40W/50Ω
40W/50Ω 300
60
52
AC200V
AC200V DV0P37901
DV0P37901 40W/200Ω
40W/200Ω
2-φ4.3
10
I1 Brown 1
Connected to control Connected to Console A I2 Red 2
terminal box (loose wire) GND Orange 3
O1 -
FIN Yellow 4
+5V Green 5
L
I3 -
■ Connect the Console A connection I4 -
cable with control terminal box as I5 -
shown on the right. O2 -
● Digital key pad connection cable <Digital key pad side connector>(Mollex)
Connected to CN2 of Housing : 39-01-2105
(sold separately) (5557-10R-210)
control terminal box Terminal: 39-00-0046
Model
Model name
name Length
Length (L)
(L) 1 (5556T2)
or 39-00-0047
DV0P35810
DV0P35810 1m
1m 6 (5556T2L)
DV0P35830 3m L
DV0P35830 3m
DV0P35850
DV0P35850 5m
5m Terminal number of CN2 1 2 3 4 5 6
Terminal name - +5V SOT SIN GND SCK
Connector pin number on Digital key pad side - 5 9 8 3 7
36
Warranty
Warranty period
● Warranty period of this product is 1 year from purchasing, or 1.5 years from our manufacturing month.
Detail of warranty
● If any trouble should be found within warranty period under normal use condition in conformance with
this instruction manual, it will be repaired free of charge.
Repair will be chargeable in the following cases even if within warranty period:
(1) When trouble is caused by wrong use, and inappropriate repair or modification.
(2) When trouble is caused by dropping after purchase, or damage in transportation.
(3) When trouble is caused by use out of specification range of the product.
(4) When trouble is caused by fire, earthquake, lightning stroke, damage by wind and flood, damage by
salt, abnormal voltage and any other natural disaster.
(5) When trouble is caused by entry of water, oil, metal strip, and any other foreign substance.
● Warranty covers only the body of delivered product, and damage induced by trouble of delivered
products will be excluded from compensation.
Caution in use
● If you are planning to use this product under special environment, such as atomic power control,
aerospace equipment, traffic organization, medical equipment, various safety systems, and
equipment which requires cleanliness, please contact us.
● When this product is operated without the shaft electrically grounded, such as in driving
the fan, bearing noise may become higher due to the occurence of electrocorrosion
depending on the motor used or setting emvironment, so confirm and verify the condition
on the customer side in such a case.
● Although we make efforts as far as possible for ensuring the quality of this product, it may operate
out of setting due to external noise and static electricity more than expected, or accidental trouble of
power supply, wiring, and components, use caution for ensuring safety in your failsafe design and
operable range in moving place.
37
MEMO
MEMO
After-sale service (repair)
Repair
x Ask the seller where the product was purchased for details of repair work.
When the product is installed in a machine or device, consult first the manufacturer of the machine or device.
Web site
Place of purchase
TEL ( ) -
Motor Company, Matsushita Electric Industrial Co., Ltd.
7-1-1, Morofuku, Daito, Osaka 574-0044, Japan
+81-72-871-1212
IMC90
S0804-0