Professional Documents
Culture Documents
Circuit Breakers (< 100kv) Specific System Application Classification According To IEC
Circuit Breakers (< 100kv) Specific System Application Classification According To IEC
according to IEC
A cable system is a system in which the TRV during breaking of terminal fault at 100 % of
shortcircuit breaking current does not exceed the two-parameter envelope derived from
table 1 give in IEC 62271-100. for example circuit-breakers of indoor substations with cable
connection are generally in cable-systems or circuit-breaker in an outdoor substation with
length of cable connected on the supply side of the circuit-breaker is at least 100 m.
A line system is a system in which the TRV during breaking of terminal fault at 100% of
short circuit breaking current is covered by the two-parameter envelope derived from Table
2 of table 2 give in IEC 62271-100.
Systems with overhead lines directly connected to a busbar are typical examples of line-
systems.
Figure shown two circuitbreaker classes different(S1,S2) at full shortcircuit current, the
RRRV in line systems is twice the value for cable systems.
source: https://switchgearcontent.com