Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/371201429

Frequency Spectrum Analysis of Partial Discharge Activities in WBG-based AC


Machine Drives

Conference Paper · March 2023


DOI: 10.1109/APEC43580.2023.10131363

CITATION READS

1 45

3 authors, including:

Kangbeen Lee Woongkul Lee


Michigan State University Michigan State University
20 PUBLICATIONS 70 CITATIONS 76 PUBLICATIONS 1,087 CITATIONS

SEE PROFILE SEE PROFILE

All content following this page was uploaded by Kangbeen Lee on 02 June 2023.

The user has requested enhancement of the downloaded file.


Frequency Spectrum Analysis of Partial Discharge
Activities in WBG-based AC Machine Drives
Kangbeen Lee Mohamad Saleh Sanjari Nia Woongkul Lee
Electrical and Computer Engineering Advanced Systems Innovation Electrical and Computer Engineering
Michigan State University Electric Drives Michigan State University
East Lansing, USA BorgWarner Inc. East Lansing, USA
leekangb@msu.edu Auburn Hills, USA leewoong@msu.edu
ssanjari@borgwarner.com

Abstract—High voltage and fast switching speed of wide


bandgap (WBG)-based AC machine drives can aggravate the
insulation stress and cause more frequent partial discharge
(PD) activities leading to premature failures of the dielectric
materials. A particular PD type occurring between the drive
system and the ground (e.g., winding to a core and/or winding
to a housing) shares an identical leakage current conduction
path to that of the conducted common-mode electromagnetic
interference (CM EMI) affecting the CM EMI noise level as
well. To fully understand and prevent the PD activities in the
WBG-based AC machine drives, it is critical to measure and
analyze a full frequency spectrum of the PD activities, which
are often concurrently measured with CM EMI noise. In the
conventional PD measurement systems, the full frequency
spectrum of the PD cannot be captured due to an additional
high-pass filter (HPF) with a cutoff frequency generally higher
than 50 MHz. This HPF is commonly used to segregate the PD
signal from the switching and EMI-induced noises, but the PD Fig. 1. Repetitive voltage signals from AC machine drives and
activities produce electromagnetic noises with a wide frequency high voltage overshoot and ringing at the machine terminal [9].
spectrum, including less than 20 MHz. In this paper, the full
spectra of PD activities during the switching transition of the located in the insulation material for starting an electron
WBG-based AC machine drive are measured with two avalanche.
different methods without any additional HPF. The measured
Since the applied voltage at the insulation is proportional
signals are analyzed in the time and frequency domain to
identify major signatures of PD activities in WBG-based AC
to the dc-link voltage, PD activities can more frequently
machine drives. occur with the low-voltage insulation system. It was reported
that a pulse width of voltage output provided by the high-
Keywords—AC machine drive, frequency spectra, high slew frequency electric drive affects the magnitude and rate of PD
rate, insulation degradation, partial discharge, wide bandgap in [3]-[5]. Moreover, it is also validated that the magnitude of
device PD can increase as a slew rate of the power switching device
increases [6]-[7]. Since the connecting cable between the
I. INTRODUCTION electric drive and the electric machine increase ringing and
overshoot at the machine terminal due to reflected wave, it
With more electrification and emission-free was proved that the PDIV tends to decrease as the cable
transportation trends, propulsion systems in aircraft and length increases [8]. It was also experimentally validated that
electric vehicles are rapidly changing from fossil fuel-based turn-to-ground PD activities in AC machine drives affect
engines to electric AC machine drive systems. Due to the common-mode electromagnetic interference (CM EMI) noise
ever-increasing demand for high efficiency and high-power [9].
density AC machine drives, the voltage and switching
frequency are expected to increase as they are the most The PD measurement and analysis have become more
effective ways of boosting efficiency while reducing system challenging under repetitive voltage pulses with a high slew
mass by reducing the system joule losses and the size of rate as the PD and switching transition occur simultaneously
passive components [1]-[2]. Although high-voltage and high- [10]. Several different methods using ultra-high-frequency
frequency drives have several advantages, they are becoming (UHF) antenna, coupling capacitors, and radio-frequency
more vulnerable to partial discharge (PD). current transformer (RFCT) have been developed to detect
PD activities and predict the lifetime of stator winding [11]-
Partial discharge (PD) is defined as a localized electrical [14]. However, those methods require a high-pass filter,
discharge that only partially bridges the insulation between commonly used to separate the PD signal from the switching
conductors and can or cannot occur adjacent to a conductor (i.e., overshoot and ringing) and EMI noises [5]-[6], [15].
from IEC 60270 standard. From the definition, the PDs can Although these filters can segregate the PD signals from the
occur in electric machines in the forms of internal, surface, EMI noises, they also filter out a substantial portion of the
and corona discharges at the inside of the slot, the surface of PD signatures in the frequency range under cut-off frequency.
the insulation, and end-windings, respectively. The PDs Therefore, a new measurement method without any filter is
generally occurs when the electric field overrides the required to fully capture and analyze the full frequency
inception field, and the initial free electron exists in a cavity spectra of the PDs in AC machine drives. Furthermore, the
TABLE. 1. Characteristics of twisted winding pair samples for
the PD and EMI estimation.
Type Sample 1 Sample 2
Two fully One fully enameled
Description
enameled wires wire and one bare wire
Wire gauge 34 34
Insulation
Polyamide-imide Polyamide-imide
Material
Estimated
> 600 V < 500 V
PDIV

Fig. 2. Partial discharge measurement setup for the time and while the other was made with higher PDIV. Since the
frequency domain data acquisition and analysis. applied voltage to the machine winding is proportional to the
dc-link voltage, the PDIV generated by the power supply is
frequency domain analysis with the measured full frequency set to be less than 600 V. The PDIVs can be dependent on
spectra is required to understand the features of PD in AC the structures (i.e., round, and rectangular) of the magnet
machine drives. wire. From Dakin’s equations, PDIVs of rectangular and
To bridge this knowledge gap, this paper round magnet wire can be calculated using
comprehensively analyzes the PD phenomena of the WBG- V = √2 × 163 × (2×t/εr)0.46, (2)
based AC machine drives and provides non-filtered raw data
with time and frequency domain analysis of the measured PD V = √2 × 163 × (t/εr)0.46, (3)
signals. The experiment results can clearly show the
influence of PD activities at the machine terminal and drive
where V is partial discharge inception voltage, t is the
output voltage. Moreover, the full frequency spectra of PD
thickness of the insulation film, and εr is the relative
during the switching transition (i.e., turn-on and -off) of the
WBG-based AC machine drive are measured with two permittivity of the insulation film [16]-[17].
different methods (i.e., conducted and radiated) without any
additional HPF. The measured signals from RFCT and For both twisted pair samples, the 34 AWG round magnet
coaxial cable are analyzed in the time and frequency domain wires are used, which have 11 μm of the thickness of the
to identify major signatures of PD activities in WBG-based insulation film. The first sample is made by twisting two
AC machine drives. The full frequency spectra of the PDs fully enameled wires, and the PD activities do not occur at
with the different slew rate are also included in the analysis. less than 600 V of the dc-link voltage. On the other hand, the
other sample is made with one fully enameled wire and one
This paper is organized as the following. Section II will bare magnet wire to deliberately reduce the PDIV, and the
describe the details of the PD measurement setup with WBG- PD activities occur under 500 V of the dc-link voltage. The
based AC machine drives. The full frequency spectra of the specifications of the samples are summarized in Table. 1.
PDs will be presented in both time and frequency domain in
Section III. Finally, the conclusion will be drawn in Section B. Partial Discharge Measurement Setup
Ⅳ.
A partial discharge measurement setup is built to capture
PD signals from the twisted pair samples. To measure both
II. PARTIAL DISCHARGE EXPERIMENTAL SETUP the high-frequency capacitive discharge current of PD and
the CM EMI noise without any filter in the high-frequency
A. Twisted Pair Sample range, the experimental setup is designed with a 1.7 kV SiC-
The standardized twisted pair sample (i.e., two insulated based half-bridge inverter with a high-voltage power supply,
wires are twisted together) is commonly used for the PD measurement equipment (i.e., voltage probe, coaxial cable,
study of a random-wound winding systems since the twisted RFCT, and oscilloscope), and the twisted pair samples, as
pair represents the worst-case scenario of the PD events with shown in Fig. 2. One terminal of the twisted pair samples is
the highest electric field between two conductors. The connected to the inverter, and the other terminal is directly
electric field between two wires is proportional to the voltage connected to the ground to form a capacitive leakage current
difference and inverse proportional to the distance between path for both CM EMI and PD. Two voltage probes are
the wires, connected to the terminal of the twisted pair samples and the
output of the drive to investigate the influence of PD
Ecrit < V / d, (1) activities on the voltage waveforms. A regular coaxial cable
with roughly 1 cm of the center conductor exposed is
where V is the voltage difference between two wires and d is installed near the twisted pair samples to measure high-
the distance between the two wire pairs. When the electric frequency radiated emission from EMI and PD events.
field exceeds the critical electric field of the insulation
system, PD occurs. For measuring the conducted emission, a radio-frequency
current transformer (RFCT) is used to detect both PD signals
and CM EMI noise. The RFCT (CLCE-438) is compatible
Two twisted pair samples are needed for comparative
for CISPR, Mil-Std 461, and DO-160 standards since the
analysis between the samples with and without PD activities.
measurement bandwidth range from 9 kHz to 400 MHz. The
One of the samples was made more susceptible to PD
oscilloscope has a bandwidth of 600 MHz with up to 10 GHz
activities at low partial discharge inception voltage (PDIV),
sampling frequency. The experiments are repeatedly
(a) Fig. 4. Measured voltage at the terminal with high slew rate in
WBG-based AC machine drives.

The experimental setup includes the sample 2, 340 V of


dc-link voltage, and 28 V/ns of slew rate to measure the
ringing voltage at the sample terminal. As expected, the
voltage ringing is generated for over 0.015 ms duration at the
terminal of the sample, as shown in Fig. 3 (a). This leads to
several voltage drops at the terminal when PDs occur in the
insulation. The stiff voltage drops indicate the occurrences of
several PD activities in one turn-on transition. The PD
signals are also captured at the RFCT and coaxial cable to
(b) confirm that the abrupt voltage drops come from the PDs.
The magnitude of the ground current, including CM EMI,
increases at the PD events, as shown in Fig. 3 (b). The
measured data from the coaxial cable also shows that the
increased voltage magnitude is synchronized with the PD
events, as shown in Fig. 3 (c). These measured data indicate
that PDs can occur more than one time during one switching
cycle when there is a high terminal voltage overshoot and
ringing. This is due to the fact that the terminal voltage may
exceed the PDIV several times for the duration of the voltage
ringing.
While changing the gate resistances of SiC MOSFETs
(c) from 2 Ω to 47 Ω with the same experimental setup with
Fig. 3. Measured PD signals in time domain (a) at the terminal sample 1, the voltage overshoots at the terminal are measured
of the twisted pair, (b) from the RFCT, and (c) from the coaxial to verify that a high slew rate system makes the insulation
cable. system more vulnerable to PD when the dc-link voltage is
400 V. The voltage overshoot increases with the increased
conducted with both samples under the identical condition, slew rate, as shown in Fig. 4. As high as 20% voltage
while various control variables (e.g., cable length between overshoot was observed with the slew rate of 28 V/ns, which
the drive and the sample, and slew rate) are changed to is measured with the 2 Ω gate resistance. This indicates that
investigate and extract the critical features of PD in AC the electric drive with a high slew rate can lead to more
machine drives. Since four channels from each measurement frequency PD activities due to the increased peak voltage
equipment (i.e., two voltage probes, RFCT, and coaxial applied to the insulation.
cable) are provided, both the time and frequency domain data
of four data set will be presented for more detailed
comparative analysis. IV. FULL FREQUENCY SPECTRA OF PARTIAL DISCHARGE IN
AC MACHINE DRIVES
III. PARTIAL DISCHARGE PHENOMENA IN AC MACHINE A. Time Domain Analysis
DRIVES WITH HIGH SLEW RATE
The two twisted pair samples introduced in Table I are
Since high-frequency and high switching speed electric used to comprehensively compare measured voltage and
drives can generate high voltage ringing and overshoot at the current waveforms with and without PDs in the time domain.
machine terminal, a detailed time domain data analysis is The experimental setup can measure four different
needed to investigate the PD phenomena of WBG-based AC waveforms, which include the half-bridge inverter output
machine drives with a high slew rate. This section voltage, terminal voltage, ground current with RFCT, and
investigates the impact of the various slew rate on PD radiated EM noise with coaxial cable.
phenomena in the time domain.
(a)
Terminal Voltage w/o PD Terminal Voltage with PD PD
of Twisted Pair of Twisted Pair

(b)
Measured signal w/o PD
from RFCT Measured signal with PD
from RFCT
PD

(c)
Measured signal w/o PD PD
from coaxial cable
Measured signal with PD
from coaxial cable

(d)
Fig. 5. Measured PD signals in time domain (a) half-bridge inverter output voltage, (b) terminal voltage of twisted pair, (c) RFCT, and
(d) coaxial cable comparison between without PD vs. with PD.

First of all, there is no significant impact of PD on the difference is observed as expected. On the other hand, since
half-bridge inverter output voltage, as shown in Fig. 5 (a). PDs cause the stiff voltage drops at the terminal, the peak
The inverter output voltages are almost identical to each voltage magnitude at 4 MHz is 25 V lower, and the
other regardless of the PD event. However, the PDs generate frequency band of the terminal voltage with the PDs is wider
a stiff voltage drop of more than 600 V from the peak voltage than that without PDs, as shown in Fig. 6 (b). As the stiff
at the terminal of Sample 2, as shown in Fig. 5 (b). This stiff voltage drops are introduced by the PD events, the frequency
voltage drop is associated with the abrupt discharge of spectra of the terminal voltage tend to extend towards the
electrons through the ground current path when the PD higher frequency range. Furthermore, PDs change the
occurs. The measured peak ground current with PD from the frequency spectra of the measured voltage from RFCT, as the
RFCT (i.e., voltage signal converted from the measured voltage magnitude at 11 MHz is 10 times higher compared to
current) is approximately 2 V higher than without PDs, as that without PDs, as shown in Fig. 6 (c). Lastly, the measured
shown in Fig. 5 (c). The coaxial cable also captured the PDs voltage magnitude from coaxial cable in all frequency band
through the radiated EMI noise, producing roughly 300 mV (< 50 MHz) changes with PDs, especially at 4 and 8 MHz.
higher peak voltage than that without PDs, as shown in Fig. 5 These results indicate that PDs produce a wide frequency
(d). These results show that PDs can generate stiff voltage band conducted emission below the 20 MHz range. Since the
fluctuations at the machine terminal and affect CM EMI filters, commonly used to segregate the PD signal from the
noise since the PD conduction path is identical to the switching and EMI noises, have a 50 MHz cut-off frequency
conducted CM EMI path. for conducted emission, it is confirmed that full spectra of
PDs can only be captured without these additional filters.
B. Frequency Domain Analysis
Frequency analysis from the measured time domain C. Full Frequency Spectra depending on a Slew Rate
signals without any additional filter is conducted to find the The ground current, including PD signals, with the high
full frequency spectra of PDs. Fig. 6 (a) show that the (28V/ns) and low slew rate (7 V/ns) are measured to verify
measured voltage magnitude at half-bridge inverter output which frequency band of the PD signal is changed depending
voltages with and without PDs where no significant on the slew rate. The magnitude of the ground current with
Drive output voltage Terminal Voltage of Twisted Pair
W/O PD W/O PD
With PD With PD

(a) (b)
Measured signal from RFCT Measured signal from coaxial cable
W/O PD W/O PD
With PD With PD

(c) (d)
Fig. 6. Measured PD signals in frequency domain (a) at half-bridge inverter output, (b) at the terminal of twisted pair, (c) by RFCT, (d)
by coaxial cable comparison between without PD vs. with PD.
Mesured signal with PD from RFCT
which can affect the CM EMI noise generation as well.
High slew rate (24 V/ns)
However, there is no significant impact of PD on the drive
Low slew rate(7 V/ns)
side output voltage. The frequency domain analysis presented
the full frequency spectra of PDs, including below the 20
MHz range, without any additional HPF. It verified that the
measured voltage with PDs from RFCT was more than 10
times higher at 11 MHz than that without PD events. Since
these filters generally have a 50 MHz cut-off frequency for
conducted emission, which are commonly used to segregate
the PD signals from the switching induced and EMI noise, it
was confirmed that full spectra of PDs can only be captured
without these filters.
Fig. 7. Measured PD signals in frequency domain by RFCT
comparison between high slew rate (24 V/ns) vs. low slew rate
(7 V/ns). REFERENCE

the high slew rate is 50 mV larger at the peak than that with [1] L. Chang, W. Lee, T. M. Jahns, and K. Rahman, “Investigation and
the low slew rate, as shown in Fig. 7. In addition, a 30 mV prediction of high-frequency iron loss in lamination steels driven by
increased magnitude of the ground current is observed in a voltage-source inverters using wide-bandgap switches,” IEEE Trans.
Ind. Appl., vol. 57, no.4, pp. 3607-3618, Jul.-Aug. 2021.
frequency band ranging from 4 to 6 MHz. It indicates that the
[2] A. K. Morya, M. C. Gardner, B. Anvari, L. Liu, A. G. Yepes, J.
magnitude of PD increases as the slew rate increases, and the Doval-Gandoy, and H. A. Toliyat, “Wide bandgap devices in AC
measured voltage magnitude with PDs from RFCT changes electric drives: Opportunities and challenges,” IEEE Trans. Transport.
in a frequency band (4 – 12 MHz) as the slew rate changes. Electrific., vol. 5, no. 1, pp. 3-20, March 2019.
[3] D. D’Amato, J. Loncarski, V. G. Monopoli, F. Cupertino, L. P. D.
Noia, and A. D. Pizzo, “A impact of PWM voltage waveforms in
V. CONCLUSION high-speed drives: A survey on high-frequency motor models and
In this paper, critical signatures of PD activities in WBG- partial discharge phenomenon,” Energies, 15(4), 1406, 2002.
based AC machine drives were investigated by both time and [4] M. Diab, W. Zhou, C. Emersic, X. Yuan, and I. Cotton, "Impact of
frequency domain analysis. An experimental setup without PWM voltage waveforms on magnet wire insulation partial discharge
in SiC-based motor drives," IEEE Access, vol. 9, pp. 156599-156612,
any additional filter was proposed to compare conducted and 2021.
radiated emission between two twisted pair samples with and [5] P. Wang, H. Xu, J. Wang, W. Wang, and A. Cavallini, "Effect of
without PD events. The RFCT measured the conducted repetitive impulsive voltage duty cycle on partial discharge features
ground current, including PD signals and the coaxial cable is and insulation endurance of enameled wires for inverter-fed low
used to capture the radiated EM noise, including PD signals. voltage machines," IEEE Trans. Dielect. and Elect. Insul., vol. 24, no.
The time domain analysis verified that the AC machine 4, pp. 2123-2131, 2017.
drives with a high slew rate are more vulnerable to PD due to [6] B. Hu, Z. Wei, H. You, R. Na, R. Liu, H. Xiong, P. Fu, J. Zhang, and
J. Wang, "A partial discharge study of medium-voltage motor winding
the increased peak voltage and oscillation with the increased insulation under two-level voltage pulses with high dv/dt," IEEE Open
switching speed. Furthermore, PD activities generate a stiff Journal of Power Electronics, vol. 2, pp. 225-235, 2021
voltage drops at the machine terminal from the PD activities,
[7] P. Wang, A. Cavallini, G. C. Montanari, and G. Wu, "Effect of rise
time on PD pulse features under repetitive square wave voltages,"
IEEE Trans. Dielect. and Elect. Insul., vol. 20, no. 1, pp. 245-254,
Feb. 2013.
[8] K. Choksi, Y. Wu, M. U. Hassan, and F. Luo, "Evaluation of factors
impacting reflected wave phenomenon in WBG based motor
drives," 2022 International Power Electronics Conference (IPEC-
Himeji 2022- ECCE Asia), 2022, pp. 736-740.
[9] K. Lee, M. Fereydoonian, M. Benson, and W. Lee, “Partial discharge
and electromagnetic interference under repetitive voltage signals with
high slew rate in AC machine drives,” IEEE/AIAA Transp. Electrific.
Conf. and Elect. Aircr. Technol. Symp. (ITEC+EATS), 2022, pp. 917-
922.
[10] S. Grubic, J. M. Aller, B. Lu, and T. G. Habetler, "A Survey on testing
and monitoring methods for stator insulation systems of low-voltage
induction machines focusing on turn insulation problems," IEEE
Trans. Ind. Electron., vol. 55, no. 12, pp. 4127-4136, Dec. 2008.
[11] M. D. Judd and I. B. B. Hunter, “Partial discharge monitoring of
power transformers using uhf sensors. part i: sensors and signal
interpretation,” IEEE Elect. Insul. Mag., vol. 21, no. 2, pp. 5–14,
March 2005.
[12] H. Okubo, N. Hayakawa, and G. C. Montanari, “Technical
development on partial discharge measurement and electrical
insulation techniques for low voltage machines driven by voltage
inverters,” IEEE Trans. Dielect. and Elect. Insul., vol. 14, no. 6, pp.
1516–1530, December 2007.
[13] B. T. Phung, S. Shao, M. F. Rahman, M. Chu, and C. Vickers, "Partial
discharge measurements in PWM inverter-driven low-voltage
motors," 2009 Australasian Universities Power Engineering Conf.,
2009, pp. 1-6.
[14] N. Hayakawa, H. Inano, and H. Okubo, “Partial discharge inception
characteristics by different measuring methods in magnet wire under
surge voltage application,” 2007 Annual Report – Conf. Elect. Insul.
and Dielect. Phenomena, Oct 2007, pp. 128–131.
[15] H. Lee, H. Kim, J. Jeong, K. Lee, S. B. Lee, and G. C. Stone,
"Inverter-embedded partial discharge testing for reliability
enhancement of stator winding insulation in low voltage
machines," IEEE Trans. Ind. Appl., vol. 58, no. 2, pp. 2088-2096,
March-April 2022.
[16] S. Ota, M. Yamauchi, A. Mizoguchi, K. Yoshida, and Y. Tamura,
“Rectangular magnet wire for electric and hybrid electric inverter-
drive motors.,” SEI technical review, no. 88, Apr. 2019.
[17] S. Ota, M. Yamauchi, A. Mizoguchi, K. Yoshida, and Y. Tamura,
“Magnet wire with enhanced tolerance for high frequency voltage,”
SEI technical review, no. 84, Apr. 2017.

View publication stats

You might also like