ACCURA
2700 / 2750
Smart Motor Management System
Provides a Total Management System for the Entire MCC Unit
Revision 1.30[English]
2021/06/09
Accura 2700/2750_Smart Motor Management System
Overview
Effectively Meets the Needs of Managing Power Consumption of Motors and
Improves Space Efficiency in MCCs
Motors are used for various purposes; pump, ventilator, compressor, etc. The motor is one
of the largest energy-consuming equipment, and its energy consumption accounts for about
75% of industrial energy consumption and about 55% of the total energy consumption. The
importance of efficient energy management for motors has increased, but most existing
motor protection devices do not have voltage and power measurement function. Although
motor protection devices with the voltage and power measurement function have been
supplied recently, their field application is limited due to increasing product prices, additional
space required with the voltage input and increased efforts needed for wiring work. Accura
2700/2750, the Smart Motor Management System shares the voltage data sampled from
the incoming unit of the Motor Control Center (MCC) unit with Accura 2750P[C] in real time
by communicating with the individual motor-unit protection[control] module. Therefore, it
is possible to measure the power of each motor without the need for increased space and
wiring work for the motor unit. This helps to effectively meet the requirements for power
consumption management of the motor and to improve the space efficiency of the MCC.
It is difficult to conduct accurate diagnosis of ground current and effectively prevent accidents
caused by ground current due to the very low accuracy of existing current leakage detectors
used for ground current detection. Motor-Unit Protection[Control] Module Accura 2750P[C]
has a built-in ZCT for accurate measurement of ground current along with a CT for current
measurement. The built-in ZCT is designed to enable accurate measurement of current up
to 20A, providing the ground fault protection function and helping to prevent ground fault
accidents by analyzing the trends of leakage current. In addition, Accura 2750P[C] provides the
residual current value calculated by summing up the values measured by the built-in three-
phase CTs for when a large ground current above 20A flows. Thus, it makes it possible to
prevent a ground fault regardless of the magnitude of ground current. When using external CTs
with Accura 2750P[C]-5A model, the measurement accuracy of ground current(measured by the
ZCT) and residual ground current (the value obtained by summing up three phase CT output) is
not guaranteed in 3 CT connection(3 external CTs) due to the error of the external CT, and the
ground current and residual ground current are not measured even if a ground fault occurs in 2
CT connection (using 2 external CTs).
02/03
When configuring the motor-unit of the MCC, it is necessary to decide whether to apply a
module integrating the protection and control functions, or apply the protection module
separately and configure separate units with the control function. The Smart Motor
Management System provides Accura 2750P, the motor-unit protection module which
performs only the protection function and Accura 2750PC, the motor-unit protection &
control module which performs both the protection and control functions. The system also
provides Accura 2750D and Accura 2750DC as the display of the motor-unit. Thus, you can
Protection Module Protection&Control Module select the module that suits your needs according to the MCC configuration.
For the MCC’s space efficiency and accurate measurement, we have designed and produced
motor-unit protection[control] modules with various current ratings. Motor-unit protection
modules are classified into 5A, 30A, and 100A models according to the magnitude of the
rated current, and the 5A model with an external CT is applied on the unit with the rated
current over 100A. Motor-unit protection& control modules are classified into 5A, 30A,
100A, 160A, 250A, and 400A models according to the magnitude of the rated current, and
the 5A model with an external CT is applied on the unit with the rated current over 400A.
The 5A and 30A models are designed to minimize volume, considering their low rated current.
In order to measure the inverter's output power in a motor-unit driven by the inverter,
the output voltage and current values of the inverter are required. In addition to Accura
2750PC motor-unit protection control module, Accura 2750INV/VOL module which can
measure the inverter output voltage is used to provide the inverter's output voltage,
current, power and energy. Accura 2750INV/VOL module supports a separate RS-485
communication port to communicate with inverters that support RS-485 communication.
Accura 2750INV module also provides additional digital I/O channels to enable a hardwired
interface for the inverter.
Convenient Maintenance
As motors should be run and managed at all times in the industrial field, it is vital to easily
maintain the motor protection device in that it determines the power supply of motors.
Accura 2700/2750 feature various functions and the structure design that improves the
convenience of maintenance. The features that allow for safe and fast maintenance include
the function to modify control logic, the firmware update function through communication,
the Unit-Socket used for communication continuity of other motor units when modules are
withdrawn from the motor-unit for the 2nd and 3rd times, the separated structure of the
control power and the DIO part of Accura 2750P[C](models below 100A).
In case that maintaining the operational continuity of the motor is very important, the motor-
unit is configured to shut off the power supply when both motor protection modules detect
a fault condition. Two HMI modules are needed to set up and monitor each motor protection
module. However, in the Smart Motor Management System, two motor-unit protection
modules can be connected to one HMI module, thereby increasing space efficiency and
reducing costs. In addition, by connecting with two integrated modules, Accura 2700D
supports redundancy(Active/Standby) of the integrated modules which are installed in the
incoming-unit and are responsible for communication and control of the entire MCC module.
Accura 2700/2750_Smart Motor Management System
Excellent Field Analysis through Integrated HMI Module with Color Touch TFT
LCD
It is essential to effectively check the operational status of the individual motor and the
MCC and to analyze accidents quickly in the field. The Smart Motor Management System
offers Accura 2700D, the integrated HMI module with 8.5" Wide Type Color Touch TFT LCD
installed in front of the MCC's incoming-unit. With its touch function and exceptional user
interface, Accura 2700D enables real-time analysis of operating conditions, settings, and
events of all motors in the MCC, maximizing the MCC's operational efficiency.
Connection between the MCC and the LOP via Communication for Effective Controls and
Reduced Installation Costs
The existing LOPs and the MCC's motor-unit protection control devices are connected
by multiple analog signal lines. Installation costs are high and preventive maintenance is
difficult due to the connection of many analog signal lines between the MCC and the LOP in
proportion to the number of motor-units.
In the Smart Motor Management System, the LOP control module(Accura 2750LC[I]) is
connected to the integrated incoming-unit module(Accura 2700M) via the LOP control
gateway(Accura 2750LCG). The control command(RUN / STOP) through the front button on
Accura 2750LC[I] is transmitted to Accura 2700M via communication, and Accura 2700M
Accura 2750LC[I] Accura 2750LCG transmits the control command to the corresponding motor-unit protection control module
(Accura 2750PC) via communication. On the contrary, Accura 2750PC monitors the motor's
operational status and transmits the data to Accura 2700M via communication, and Accura
2750LC[I] displays the operation status data received from Accura 2700M. The connection of
the MCC and the LOP through communication greatly reduces the line installation cost, and
also helps users to prevent uncontrolled situations at a critical moment through immediate
error detection and notification when an error occurs in the communication line.
The integrated incoming-unit module has two external Ethernet communication ports,
an internal communication port for connection with the motor-unit protection & control
module, and two serial communication ports for connection with the LOP control
gateway. The LOP control gateway has four communication ports for connection with
the LOP control module. Since two communication ports are provided respectively, all
communication networks can be configured in a ring so that communication issues can be
solved through two-way communication even when a communication line is disconnected
or broken. In particular, the LOP control gateway can configure two ring networks with four
communication ports, effectively connecting LOP control modules that can be scattered
over long distances. Thus, communication redundancy increases communication reliability
in the field.
04/05
Supports Device Redundancy for the Field that Requires High Reliability
Provides Setup Manager for All Device Settings and Commissioning through
Communication
Individually setting up and inspecting all devices installed in the MCC on site is a demanding
and time-consuming task. The Smart Motor Management System provides Setup Manager, a
program that allows easy setup and commissioning of all connected modules using a computer.
Setup Manager also provides information on fault, alarm, and caution events along with the
setup, instrumentation, and control functions for detailed analysis of accidents occurring during
the operation of motors.
The basic control logic is programmed in the motor-unit protection module, and Accura
Logic Editor is provided for users to change the control logic according to on-site operational
conditions. The control logic editor has editing, debugging, and simulation functions so that
errors in the control logic can be easily changed, saved and restored.
Through Accura Logic Editor, users can create the control logic according to requirements for
the MCC unit and download it to Accura 2700M for proper controls.The control logic operating
in the motor-unit protection & control module is limited to the control of the corresponding
motor-unit only, but the control logic operating in the integrated incoming-unit module enables
interconnected controls between multiple motors in the MCC. In addition, Accura 2700M
module enables interconnected controls between motors in other MCC units by communicating
with other Accura 2700M modules.
Accura 2700/2750_Smart Motor Management System
Ac Ac
cu cu
ra ra
27 27
50L 50L
CG C[I
]
Ac
Hub cu
ing ra
27
tch 00
Swi Ac M
cu
ra
27
00
D
Ac
cu
ra
27
5 0D
[C/
CI]
T Un
R NE it-
So
HE MC ck
et
ET CP
ane
Ac
cu
l ra
27
50P
[C
]
Ac
cu
ra
37
00
AC
B Pan
e Ac
l cu
ra
37
00
MC
CP
ane
l
AC
B Pan
Ac
cu el
ra Ac
37 cu
00 ra
37
00
Tra
nsf
orm
er
Hig
hV
olt AC
age B
Pan Pan
el e l
O N E
io nZ
r i b ut
Dis t
06/07
Steel Plant
Ac
Semiconductor Plant
cu
ra
27
50L
C
Ac Chemical Plant
cu
ra
27
50L
C
Ac
cu
ra
27
50L
C
MC
CP
ane
l
O N E
MC
CP
ane
l
MCCZ
ONE
Accura 2700/2750_Smart Motor Management System
Product Information
The Smart Motor Management System is the system that manages the entire MCC[Motor Control Center] unit. It
consists of Accura 2700M installed inside the incoming unit, Accura 2700D mounted at the front of the incoming
unit, Accura 2750P[C] mounted inside the individual motor unit, Accura 2750INV/VOL mounted inside the
individual inverter unit, Accura 2750D[C/CI] mounted at the front of the individual motor unit, Accura 2750LC[I]
LOP Control Module mounted at the LOP(Local Operating Panel), and Accura 2750LCG(LOP Control Gateway)
which performs the communication relay function between Accura 2750LC[I] and Accura 2700M. Accura 2700M
and each Accura 2750P[C] module are connected via communication using the RJ45 connector and Ethernet
cable. The Unit-Socket is provided additionally to help users effectively connect cables without T-branch
connection.
Accura 2700M is connected with Accura 2750LCG via communication and Accura 2750LCG is connected with
Accura 2750LC[I] mounted at the LOP via communication. If users execute the RUN/STOP command of the motor
by pressing the front button of Accura 2750LC[I], the command data are transmitted to Accura 2750PC through
Accura LCG and Accura 2700M, and then Accura 2750PC controls the motor of the corresponding motor unit.
The operation status data on the motor are transmitted to the corresponding Accura 2750LC[I] through Accura
2750PC, Accura 2700M and Accura 2750LCG in sequence. The motor control button LED on the front of Accura
2750LC[I] displays the operation status of the motor.
Accura 2700D and Accura 2750D[C/CI] are HMI modules connected with Accura 2700M and Accura 2750P[C]
modules respectively.One Accura 2700M module can manage up to 40 Accura 2750P[C] and Accura 2750LC[I]
modules respectively, through communication. It is connected with the host system through Ethernet or RS-485
communication.
For a motor-unit driven by the inverter, it measures the power using the voltage
data received from Accura 2750INV/VOL of the unit through communication
For a motor-unit driven by the inverter, it measures power using the voltage
data received from Accura 2750INV/VOL of the unit through communication.
Performs accurate ground current measurement with the built-in ZCT1
5A Rated current 5A(External CT connection is required for the motor unit
with the rated current over 400A 1 )
30A Rated current 30A
100A Rated current 100A
160A Rated current 160A
250A Rated current 250A
400A Rated current 400A
TM-PC 160A The terminal block can be installed to the load side or both sides of the motor-
Terminal Block 250A unit protection & control module without large-diameter power cables.
(for Motor-Unit Protection & Control Module) 400A Only provided with models with the rated current 160A, 250A, 400A.
Accura 2750INV Measures the output voltage of the inverter and sends the voltage data to
Inverter-Unit Voltage Accura 2750PC module.
Measurement & Control Module
Provides a hardwired interface with additional DI/DO channels.
Provides an easy-to-use communication interface via RS-485 communication
Accura 2750VOL Measures the output voltage of the inverter and sends the voltage data to
Inverter-Unit Voltage Accura 2750PC module.
Measurement Module
Provides an easy-to-use communication interface via RS-485 communication
Accura 2750D 2.7" Graphic FSTN LCD, Motor setup, status monitoring
Motor-Unit Protection HMI Module Redundancy : it can be connected with two Accura 2750P modules
Accura 2750DC 2.7" Graphic FSTN LCD, Motor setup, status monitoring, and controls
Motor-Unit Protection & Redundancy: two Accura 2750PC and Accura 2750P modules can be connected
Control HMI Module
DC-AO Supports 4-20mA analog output
DC-RS485 Supports the RS-485 communication port
Accura 2750DCI 2.7" Graphic FSTN LCD
Inverter-Unit Protection& Redundancy : Accura 2750PC and Accura 2750P can be connected
Control HMI Module
Motor setup, state monitoring, and controls in the Inverter-unit
DPCable 2.5M For connection with the display 2.5m Cat.5e FTP(F/UTP) cable2
Display Cable 3.0M For connection with the display 3.0m Cat.5e FTP(F/UTP) cable
3.5M For connection with the display 3.5m Cat.5e FTP(F/UTP) cable
Accura 2750LCG Communication relay between Accura 2700M and Accura 2750LC[I]
LOP Control Gateway
Communication with Accura 2700M: 2 ports
(Redundancy: It enables communication with two Accura 2700M modules)
1. When using external CTs with Accura 2750P[C]-5A model, the measurement accuracy of ground current and residual ground current is not guaranteed in 3 CT connection(3 external CTs)
due to the error of the external CT, and ground current and residual ground current are not measured in 2 CT connection(2 external CTs).
2. It is provided with the product. FTP[F/UTP]: Foiled Shield Twisted Pair.
Accura 2700/2750_Smart Motor Management System
Display
Users can select HOME, SETUP, and EVENT modes with the buttons at the bottom of the LCD screen.
HOME Mode
Motor Control Summary Confirm Motor Control Command Detailed Motor Measurement Screen Event Summary
10/11
SETUP Mode
Top Screen[Chain View] Top Screen[MCC Draw View] Password Input Window Meter Setup of Incoming-Unit
Meter Setup of Motor-Unit Protection Setup of Motor-Unit Control Setup of Motor-Unit DIO Setup of Motor-Unit
EVENT Mode
Top Screen[Chain View] Top Screen[MCC Draw View] Event Log of Motor-Unit
1. Accura 2750P module only supports overload protection and Accura 2750PC module supports five starter modes.
Operation Control
Description
Function
Emergency Start Starts the motor quickly even in start inhibit state
Limit on the Number Inhibits the start of the motor when the number of starts within
of Starts the specified time window reaches the allowed start number
Control Command Monitors the operation state of the motor according to the motor
Error Check control command
Auto Restart Restarts the motor automatically after instantaneous power outage
Remote Reset Automatic fault reset for sites where it is difficult to manually reset the fault status
12/13
Accura 2700M
Accuracy Item Accuracy Measurement Condition Minimum Measured Value
Voltage Line-to-neutral IEC 61557-12 Class 0.5 65 – 300V 5V(secondary voltage)
Line-to-line IEC 61557-12 Class 0.5 110 – 520V 9V(secondary voltage)
Current IEC 61557-12 Class 0.2 50mA – 10A 20mA(secondary current)
Power Active IEC 61557-12 Class 0.5 -
Reactive IEC 61557-12 Class 1 -
Apparent IEC 61557-12 Class 0.5 -
Energy Active IEC 62053-22 Class 0.5S -
Reactive IEC 62053-24 Class 1S -
Apparent IEC 61557-12 Class 0.5 -
Demand Power IEC 61557-12 Class 0.5 -
Current IEC 61557-12 Class 0.2 -
Frequency IEC 61557-12 Class 0.02 (±10mHz) 42 - 69 Hz
Power factor IEC 61557-12 Class 0.5 -
Dip(Sag)/Swell ±0.5% Full Scale IEC 61000-4-30, 1-cycle RMS (refreshed every cycle)
Harmonics Voltage ±0.5% Full Scale Supports measurement of harmonics up to
Current ±0.5% Full Scale the 50th order
Vector Voltage ±0.5% Full Scale -
diagram Current ±0.5% Full Scale
Unbalance Voltage ±0.5% Negative/Zero-sequence unbalance[IEC 61000-4-30]
[%] Current ±0.5% Unbalance [NEMA-MG1]
THD [%] Voltage ±0.5% @Fund. voltage(L-N): 300V, up to the 50th harmonic
Current ±0.5% @Fund. current: 5A,up to the 50th harmonic
TDD [%] Current ±0.5% @Fund. current: 5A,up to the 50th harmonic
Accura 2750P[C]
Item Model Accuracy Measurement Condition Min/Max Measured Value
Current IEC 61557-12 Class 0.5 0.02 * Ib – Ib1 0.01 * Ib / 8 * Ib
5A 2 0.1A – 5A 0.05A / 40A
30A 0.6A – 30A 0.30A / 240A
100A 2.0A – 100A 1.00A / 800A
160A3 3.2A – 160A 1.60A / 1280A
250A3 5.0A – 250A 2.50A / 2000A
400A3 8.0A – 400A 4.00A / 3200A
Ground Ground(ZCT) ±1% Reading ± 0.01% Ib Up to 20A 5mA
current Residual(CT) ±1% Reading 20A – Ib -
Power Active IEC 61557-12 Class 0.5 -
Reactive IEC 61557-12 Class 1 -
Apparent IEC 61557-12 Class 0.5 -
Energy Active IEC 62053-21 Class 0.5 -
Reactive IEC 62053-24 Class 1 -
Apparent IEC 61557-12 Class 0.5 -
Demand Voltage IEC 61557-12 Class 0.5 -
Current IEC 61557-12 Class 0.5 -
Power factor IEC 61557-12 Class 0.5 -
Current vector diagram ±0.5% Full Scale
Current unbalance[%] ±0.5% Negative/Zero-sequence unbalance[IEC 61000-4-30]
Unbalance [NEMA-MG1]
Current THD [%] ±0.5% @Fund. current: 5A,up to the 31st harmonic
Current TDD [%] ±0.5% @Fund. current: 5A,up to the 31st harmonic
Accura 2750INV/VOL
Item Accuracy Measurement Condition Minimum Measured Value
Voltage Line-to-neutral IEC 61557-12 Class 0.5 65 – 300V 5V
Line-to-line IEC 61557-12 Class 0.5 110 – 520V 9V
Frequency ±30 mHz 5 - 180 Hz
Unbalance Voltage ±0.5% Negative/Zero-sequence unbalance [IEC 61000-4-30],
[%] Unbalance [NEMA-MG1]
1. IEC 61557-12
Accura 2700/2750_Smart Motor Management System
Power Quality
Item Standard Measurement Condition Accuracy
Voltage Dip(Sag)/Swell IEC61000-4-30 1-cycle RMS ±0.5% Full scale
(Refreshed every cycle)
Accura 2700M Voltage/current THD[%]1 - Up to the 50th harmonic 3 ±0.5%
Accura 2750P[C] Current THD [%] - Up to the 31st harmonic 3 ±0.5%
3
Accura 2750P[C] Current TDD [%] - Up to the 31st harmonic ±0.5%
Vector diagram - - ±0.5% Full scale
Voltage/current unbalance [%] IEC61000-4-30 - ±0.5%
NEMA MG1 - ±0.5%
IL
L
2. TDD[Total Demand Distortion], Current TDD: where, ILcan be set to the rated current(default) or peak demand current.
I-
3. Harmonics above the 22nd order are measured after being attenuated.
Digital Input/Output
Accura 2750P and Accura 2750PC have different numbers of digital input and output channels. Accura 2750P is applied when only
measurement and protection functions are required. When motor RUN and STOP control functions are required, Accura 2750PC is applied.
Communication
Model Communication Number of Port(Port Name) Description
Accura 2700M External Ethernet 2(ETHERNET1, ETHERNET2) Modbus TCP protocol
communication 100Base-TX(100 Mbps/Full Duplex)
with the host system Ethernet switching
RS-485 1(Ta, Tb) Modbus RTU protocol
Communication with HMI module 1(DISPLAY A2700D) Dedicated communication with Accura 2700D
Communication with 2(UNIT1, UNIT2) Dedicated communication with Accura 2750P[C], ring
Protection & Control module connection, support for communication redundancy
Communication with LOP 2(A2750LCG-1, A2750LCG-2) Dedicated communication with Accura 2750LCG
control module support for device redundancy
Accura 2750P[C] Connection with Unit-Socket 1(UNIT-SOCKET) Dedicated communication with Accura 2700M
Communication with
1(DISPLAY) Dedicated communication with Accura 2750D[C]
Accura 2750D[C]
Accura 2750LCG Communication with
2(A2700M-1, A2700M-2) Accura 2700M device redundancy
Accura 2700M
Communication with 4(LC/LM-1, LC/LM-2, Ring connection
Accura 2750LC[I] LC/LM-3, LC/LM-4) (Communication redundancy)
Accura 2750LC[I] Communication with 2(LC/LM-A, LC/LM-B) Ring connection
Accura 2750LCG (Communication redundancy)
Unit-Socket Connection with 3(RJ45A, A2750, RJ45B) Connects cables between Accura 2700M and motor
Accura 2750P[C] units
Bridge-Socket Communication network sharing 3(CH_A, COM, CH_B) Support for device redundancy
14/15
Installation
The following installation diagram shows different types of modules installed and connected at the incoming
unit, motor unit and LOP in the MCC. Accura 2700D and Accura 2750D[C/CI] are installed at the front of the
unit, and Accura 2700M and Accura 2750P[C] are installed inside the unit. Accura 2750P[C] modules are
connected with Accura 2700M via communication using the Unit-Socket. Accura 2750LC[I] is installed at the
front of the LOP and Accura 2750LCG is installed inside the individual LOP unit. Accura 2750LCG performs
the communication relay function between Accura 2700M and Accura 2750LC[I]. Refer to the user guide for
details on the voltage/current and DI/DO wiring methods of Accura 2700M and Accura 2750P[C].
Installation Example
A2700M-1
Accura 2750LCG
④
LC/LM- 1
LC/LM- 2
⑥ Ring configuration
Accura 2750LC[I] (Communication redundancy)
DISPLAY
UNIT 1 LC/LM-A
UNIT 2 LC/LM-B
UNIT-SOCKET
② DISPLAY RJ45A
A2750
RJ45B
Accura 2750PC
UNIT-SOCKET
Accura 2700D Accura 2750DC
⑤
① Ring configuration LO
(Communication redundancy) PP
ane
l
*FTP,
MC
CP
ane
l
② Connection from Accura 2700M to Accura 2700D Ethernet cable Cat.5e FTP(F/UTP) Maximum 3.5m -
③ Connection between Unit-Sockets Ethernet cable Cat 5e FTP, STP, SFTP Average 3m -
④ Connection from Accura 2700M to Accura 2750LCG Ethernet cable Cat 5e FTP, STP, SFTP Maximum 300m per port -
⑤ Connection from Accura 2750P[C] to Accura 2750D[C] Ethernet cable Cat 5e FTP(F/UTP) Maximum 3.5m -
⑥ Ring connection b/n Accura 2750LC[I] and Accura 2750LCG Ethernet cable Cat 5e FTP, STP, SFTP Maximum 800m per group Up to 20 Accura 2750LC[I] modules in ring connection
Accura 2700/2750_Smart Motor Management System
Device Redundancy
On sites that necessitate high reliability, Active-Standby redundancy is required in the event of an error in an
active module so that the other standby module can continue to perform the function of the device. The Smart
Motor Management system supports the active-standby device redundancy of Accura 2700M.
Installation Example
Host System
Switching Hub
Switching Hub
Accura 2700M
(Active)
Bridge-Socket
Accura 2700D
Accura 2700M Accura 2750D[C]
(Standby) Unit-Socket
Accura 2750P[C]
MC
C P
ane
l
16/17
On sites that necessitate high reliability, Active-Standby redundancy is required in the event of an error in an
active module so that the other standby module can continue to perform the function of the device. The Smart
Motor Management System supports the Active-Standby device redundancy of the LOP Control Gateway
Accura 2750LCG.
Installation Example
Accura 2750LCG
(Active)
Accura 2750LC[I]
Accura 2700M
(Active)
Bridge-Socket
Accura 2700M
(Standby) Accura 2750LCG
(Standby)
MC
C P
ane
l
LO
P P
ane
l
If the continuity of the motor operation is required, the motor-unit can be configured to shut off the power
when both Accura 2750P[C] motor protection modules detect faults. One Accura 2750D[C] HMI module
supports redundancy by connecting with two Accura 2750P[C] modules. Device redundancy of Accura
2750P[C] is not the active-standby redundancy but the redundancy of the protection function.
Installation Example
Accura 2700M
Unit-Socket
Accura 2750P[C]
Accura 2750D[C]
Accura 2750P
Accura 2700/2750_Smart Motor Management System
Panel Mounting
Panel Mounting of Accura 2700M
Accura 2700M is mounted inside the MCC's incoming-unit. You can mount the module on the panel with
screws or mount the module on a Din rail. When using screws, the module can be mounted either in the left-
to-right or the top-to-bottom direction.
4 fixing wings are used to mount the module on the panel in the left-to-right direction, and 2 fixing wings are
used to mount the module on the panel in the top-to-bottom direction. Before mounting, decide the direction
to fix the module to the panel and insert the fixing wings into the screw holes of Accura 2700M.
95.0mm
[3.74"]
Ø4.0mm
Self TAP SCREW
Ø4.0mm
Self TAP SCREW
175.0mm
100.0mm [6.89"]
[3.94"]
NOTE
When using the DIN rail, the module can be installed only
on the top hat rail. When Accura 2700M is installed with
the DIN rail vertically placed, it may slide downward, thus
1 use a DIN rail stopper to prevent it.
2
1
NOTE
When turning the fixing wheel, it can be easily fixed
with the human hand. If an extra tool is used to apply
excessive force while turning the fixing wheel, it can
damage the TFT LCD screen of Accura 2700D.
CREW 130.0mm
[5.12"]
Ø8.0mm Hole
[0.31"]
70.0mm
[2.75"]
Ø105.0mm
[Ø4.13"]
4 fixing wings are used to mount the module on the panel. Before mounting, decide the direction to fix the
module to the panel and insert the fixing wings into the screw holes of Accura 2750P[C].
105.0mm 40.0mm
[4.13"] [1.57"]
Ø4.0mm
Ø4.0mm Self TAP SCREW
Self TAP SCREW
60.0mm
[2.36"] 110.0mm
[4.33"]
60.0mm
[2.36"]
120.0mm
[4.72"]
Ø4.0mm
Self TAP SCREW
Ø4.0mm
Self TAP SCREW
110.0mm
60.0mm [4.33"]
[2.36"]
50.0mm
[1.97"]
115.0mm
[4.53"]
Ø4.0mm
Self TAP SCREW
Ø4.0mm
Self TAP SCREW
60.0mm
[2.36"] 110.0mm
[4.33"]
60.0mm
[2.36"]
130.0mm
[5.12"]
Ø4.0mm
Self TAP SCREW
Ø4.0mm
Self TAP SCREW
110.0mm
[4.33"]
W 60.0mm
[2.36"]
100.0mm 130.0mm
[3.94"] [5.12"]
Ø4.0mm Ø4.0mm
Self TAP SCREW Self TAP SCREW
90.0mm
[3.54"] 90.0mm
[3.54"]
120.0mm
[4.72"]
100.0mm
[3.94"]
90.0mm
[3.54"]
120.0mm
[4.72"]
Panel Cutouts of Accura 2750PC-160A/250A: When using terminal block[TM-PC-160A/250A] in both directions
17.2mm
[0.68"]
90.0mm
[3.54"]
15.0mm
[0.59"]
100.0mm
[3.94"]
120.0mm
[4.72"]
Panel Cutouts of Accura 2750PC-160A/250A: When using terminal block[TM-PC-160A/250A] only on load side
it is directly connected with MCCB using terminal block and bus bar.
22/23
150.0mm
[5.91"]
130.0mm
[5.12"]
90.0mm
[3.54"] 130.0mm
[5.12"]
Panel Cutouts of Accura 2750PC-400A: When using terminal block[TM-PC-400A] in both directions
17.2mm
[0.68"]
90.0mm
[3.54"]
20.0mm
[0.79"]
130.0mm
[5.12"]
150.0mm
[5.91"]
Panel Cutouts of Accura 2750PC-400A: When using terminal block[TM-PC-400A] only on load side
it is directly connected with MCCB using terminal block and bus bar.
Accura 2700/2750_Smart Motor Management System
60.0mm
[2.36"]
Ø4.0mm
Self TAP SCREW Ø4.0mm
Self TAP SCREW
110.0mm 105.0mm
[4.33"] [4.13"]
NOTE
78.0mm
[3.07"]
Ø6.0mm Hole
[0.24"]
1
45.0mm
[1.77"]
Ø66.0mm
[Ø2.59"]
95.0mm
[3.74"]
Ø4.0mm
Self TAP SCREW
Panel Cutouts of Accura 2750LCG Panel Mounting of Accura 2750LCG: Mounting on the DIN Rail
Accura 2700/2750_Smart Motor Management System
Ø105.0mm
[4.13"]
Ø8.0mm
[Ø0.31"]
50.0mm
[1.97"]
1
Ø4.0mm
Self TAP SCREW
2 2
Device Features
Accura 2700M Integrated Incoming-Unit Module
Mounted at the MCC incoming-unit, Accura 2700M performs the main function of the Smart Motor
Management System. It measures the power consumed at the entire MCC by sensing the voltage/current of
the incoming line and the power of the individual motor-unit by sending the sampled voltage data to all Accura
2750P[C] modules connected with the internal communication cable.
Through the cable, it delivers/receives measurement and motor control commands and operating status data
to/from multiple Accura 2750P[C] modules at the MCC. It also sends/receives those data to/from multiple
Accura 2750LC[I] modules at the LOP(Local Operating Panel) through Accura 2750LCG. By sending this data
to Accura 2700D, the Incoming-Unit Integrated HMI Module, it allows users to check the operation state
of all motors in front of the MCC panel. It is connected to the host system through Ethernet and RS-485
communication.
Function
Connection with Accura 2750P[C]
Transmits voltage data of the incoming line to multiple Accura 2750P[C] modules.
Collects the measurement and operational data of each motor-unit from multiple Accura 2750P[C] modules.
Internal dedicated protocol 2 ports with the same functions(UNIT1, UNIT2)
Two ports: ring connection Communication redundancy
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP, STP, SFTP
Number of connected Accura 2750P[C] modules Maximum 40(ring connection)
Communication cable length Between Unit-Sockets Average 3m
Total ring network length Maximum 120m
Between Unit-Socket and Accura 2750P[C] Average 3m
Power Measurement of MCC Incoming Line
Measures and analyzes the characteristics of the power consumed at the entire MCC by sensing voltage/current of the incoming line
Measurement Parameter
Voltage Line-to-neutral voltage(each phase/average, maximum), Line-to-line voltage(each line-to-line/average, maximum)
Fundamental voltage(each phase/average)
Harmonics(each phase, up to the 50th order), THD(each phase, maximum)
Vector diagram(Phasor diagram)
Symmetrical components(positive-, negative-, zero-sequence, maximum), Unbalance(IEC, NEMA, maximum)
Dip(Sag), Swell
Frequency Instantaneous, maximum, minimum
Current RMS(each phase/average, maximum), Fundamental(each phase/average)
Harmonics(each phase, up to the 50th order), THD(each phase, maximum), TDD(each phase, maximum)
Vector diagram(Phasor diagram)
Symmetrical components(positive, negative, zero, maximum), Unbalance(IEC, NEMA, maximum)
Demand current(each phase, average), Peak demand current(each phase, average)
Crest Factor(each phase, maximum), K-factor(each phase, maximum)
Power Active, Reactive, Apparent(each phase/ total, maximum)
Demand active power(each phase/total), Peak demand active power(each phase/total)
Power factor Each phase, total
Active energy Total value of three phases(Received, Delivered, Sum, Net)
Reactive energy Total value of three phases(Positive, Negative, Sum, Net)
Apparent energy Total value of three phases
External Communication with Host System
Ethernet 100Base-TX(100Mbps/Full Duplex) Modbus TCP protocol 2 ports with the same functions
communication Accura 2700M device redundancy (ETHERNET1, ETHERNET2)
Two ports: Ethernet switching, RSTP Communication redundancy via ring connection
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP, STP, SFTP
Communication cable wiring method Star, Daisy-chain, Ring
Accura 2700/2750_Smart Motor Management System
Function
RS-485 1200 – 115200 bps1, Modbus RTU protocol 1 port(Ta, Tb)
communication
Connector type Screw-type terminal(pluggable)
Communication cable UL2919 RS-485 1P[2P] 24AWG
Connection with Accura 2700D
Communication with 100Base-TX(100Mbps/Full Duplex) 1 port(DISPLAY A2700D)
the HMI module Internal dedicated protocol
Accura 2700D is mounted at the front of the MCC incoming-unit and is connected to Accura 2700M with the
Ethernet cable. Through communication, it provides information of Accura 2700M as well as measurement,
control and operational status data on multiple Accura 2750P[C] and Accura 2750LC[I] modules collected by
Accura 2700M on the TFT Color LCD screen on the front. All functions of Accura 2700M, Accura 2750P[C]
and Accura 2750LC[I] can be set up on the TFT Color LCD screen which has the touch function. Accura 2700D
supports redundancy of Accura 2700M modules by connecting with two Accura 2700M modules at the same
time using its two built-in communication ports.
Function
Connection to Accura 2700M
Displays the information of Accura 2700M, multiple Accura 2750P[C] and Accura 2750LC[I] modules collected by
Accura 2700M through communication on the TFT Color LCD screen.
Performs setup for the functions of Accura 2700M, multiple Accura 2750P[C] and Accura 2750LC[I] modules connected to
Accura 2700M through communication
Installed at the individual motor unit in the MCC, Accura 2750P mainly protects the motor by measuring the current
supplied to the motor. It also measures the various power characteristics of the individual motor-unit based on
the current signal data measured by the built-in CT and the voltage signal data received from Accura 2700M via
communication. For a motor-unit driven by an inverter, it measures the various power characteristics of the individual
motor unit by receiving the sampled output voltage data of the inverter processed with the Low Pass Filter(LPF) from
Accura 2750INV/VOL module via communication. Accura 2750PC provides the motor control function along with the
measurement and protection function of Accura 2750P.
Function
Connection with Accura 2700M through Unit-Socket
Receives the voltage data of the incoming line from Accura 2700M.
Transmits the measurement and operating status data of the corresponding motor-unit to Accura 2700M.
Internal dedicated protocol 1 port(UNIT-SOCKET)
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP, STP, SFTP
Communication cable length Maximum 3m
Power Measurement of Motor-Unit Branch Line
Measures and analyzes various power characteristics based on the voltage data received from Accura 2700M and the current
data of the motor-unit branch line.
Measures and analyzes the various power characteristics of the motor-unit branch line based on the inverter output
voltage data received from Accura 2750INV/VOL module.
Measurement Parameter
Current RMS(each phase/average, maximum per phase/average), Fundamental(each phase/average)
Harmonics(each phase, 1st – 31st order), THD(each phase, maximum), TDD(each phase, maximum)
Vector diagram(Phasor diagram)
Symmetrical components(positive-, negative-, zero-sequence, maximum), Unbalance(IEC, NEMA, maximum)
Maximum starting current (each phase/average), Maximum running current(each phase/average)
Demand(each phase/average), Peak demand(each phase/average)
Crest Factor(each phase, maximum), K-factor(each phase, maximum)
Ground current 1 Ground(RMS value measured by the built-in ZCT)(instantaneous, maximum)
Residual ground(RMS value measured by summing up three phase current)(instantaneous, maximum)
Power Active, Reactive, Apparent(each phase/total, maximum)
Demand, Peak demand(each phase/total)
Power factor Each phase, total
Active energy Total value of three phases(Received, Delivered, Sum, Net)
Reactive energy Total value of three phases(Positive, Negative, Sum, Net)
Apparent energy Total value of three phases
Motor Protection Function
Measures current and analyzes current data for protection of the individual motor powered by the motor-unit.
Protection Item
Thermal protection THR(49)
Overcurrent protection Overcurrent(50TD), JAM(50LR-TD), Long start relay(48), Instantaneous Overcurrent(50)
Current unbalance protection Unbalance(46), Phase out current relay(46), Phase sequence relay(46)
Undercurrent protection Undercurrent(37)
Ground current protection1 Built-in ZCT(64), Sum of 3-phase current(50G-TD)
Magnetic contactor Magnetic contactor supervision
Motor Control Function(Supported only in Accura 2750PC)
Starts and stops the single/three-phase motor and monitors the operation status
Motor control functions are available by default. However, you can use "Accura Logic" to meet your specific needs.
Starter Mode
Overload relay Only performs the protection function with Accura 2750P
Direct starter Starts/stops the motor in one direction
Reversing starter Starts/stops the motor in both forward and reverse directions
2-speed starter Changes the polarity of the motor for speed control
2-step starter Changes the wiring method while starting the motor to reduce its starting current
Connection to Motor-unit HMI Module Accura 2750D[C] 2
Internal protocol 1 port(DISPLAY)
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP(F/UTP)
Communication cable length Maximum 3.5m
Temperature Measurement
Number of the temperature
measurement sensor on 1
Accura 2750P[C]
Accura 2700/2750_Smart Motor Management System
1. When using external CTs with Accura 2750P[C]-5A model, the measurement accuracy of ground current and residual ground current is not ensured due to the error of the
external CT in 3 CT connection(using 3 external CTs), and the ground current and residual ground current are not measured in 2 CT connection(using 2 external CTs).
2. For an inverter unit, it communicates with Accura 2750DCI module via Accura 2750INV/VOL module.
Terminal Block
As the rated current of the motor gets higher, a larger-diameter power cable should be used. You can install
Accura 2750PC-160A/250A/400A models with high current ratings, using the terminal block (separately
provided) or the through-hole busbar.
Function
Easy Installation of Accura 2750PC-160A/250A, Accura 2750PC-400A
It is possible to install the terminal block on the load side or both sides without the need for a large-diameter power cable
to directly penetrate the module.
Saves space when the MCCB of the motor-unit and the through-hole busbar are connected directly.
Model Description
TM-PC-160A Terminal block for Accura 2750PC-160A
TM-PC-250A Terminal block for Accura 2750PC-250A
TM-PC-400A Terminal block for Accura 2750PC-400A
The output voltage signal of the inverter is required to measure the inverter's output power in the motor-unit driven
by the inverter. Accura 2750INV/VOL module processes the inverter output voltage with the Low Pass Filter(LPF) to
generate voltage data and transmits it to Accura 2750PC module via communication. It also supports a separate RS-485
communication port to communicate with the inverter supporting RS-485 communication. By providing additional digital
I/O channels, Accura 2750INV module allows for an easy-to-use, hardwired interface in connection with the inverter.
Function
Output Voltage Measurement of the Inverter-unit
Provides voltage data by processing the inverter output voltage with the Low Pass Filter(LPF)
Frequency measurement range 5 – 180 Hz
Cut-off frequency of LPF 188 Hz
Connection with Accura 2750P[C]
Transmits the voltage data of the inverter-unit to Accura 2750P[C] via internal communication
Internal dedicated protocol 1 port(A2750PC)
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP(F/UTP)
Communication cable length Maximum 3.5m
Connection with Motor-Unit HMI Module Accura 2750DCI
Internal dedicated protocol 1 port (DISPLAY A2750DCI)
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP(F/UTP)
Communication cable length Maximum 3.5m
Connection with Inverter (RS-485 communication)
Receives inverter status data and controls the inverter via RS-485 communication
Modbus RTU protocol 1 port (Ta, Tb, SG)
Connector type Screw-type terminal(pluggable)
Communication cable UL2919 RS-485 1P[2P] 24AWG
Digital Input/Output
Digital input Accura 2750INV 5 channels(external power input)
Digital output Accura 2750INV Form-A 9 channels
Accura 2750VOL Form-C 1 channel
Control Power Supply
Rated voltage(Us) 110 – 240V AC 50/60Hz, 110 – 300V DC
Operating voltage range 0.8 x Us – 1.1 x Us
30/31
Function
Connection with Accura 2750P[C]1
Collects information of Accura 2750P[C] and Accura 2750LC[I] through internal dedicated communication and provides various
information for users through the LCD screen on the front side.
Configures all functions of Accura 2750P[C] and some functions of Accura 2750LC[I].
Internal dedicated protocol 2 ports with the same functions(DISPLAY1, DISPLAY2)
2 ports used to connect 2 Accura 2750P[C] modules Supports redundancy of the protection function
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP(F/UTP)
Communication cable length Maximum 3.5m
Power supplied from Accura 2750P[C] through the communication cable
Display Specifications
2.7" Graphic 80x128 Dots[40.0 x 58.0mm] FSTN LCD
Front Buttons
4 muti-function buttons Left[<]/ESC, Up[^]/SETUP, Down[v]/
for changing directions(short-press)/performing special functions(long-press) EVENT, Right[>]/ENTER
1 Test/Reset button TEST/RESET
3 motor Run/Stop buttons RUN1, RUN2, STOP Accura 2750DC[I] only
1 Local/Remote button LOCAL/REMOTE Accura 2750DC[I] only
1 INVERTER/BYPASS button INVERTER/BYPASS Accura 2750DCI only
1 AUTO/MANUAL button AUTO/MANUAL Accura 2750DCI only
Control Power Supply
Power supply Supplied from Accura 2750P[C]
1. Accura 2750DCI module communicates with Accura 2750PC module through Accura 2750INV/VOL module.
Accura 2700/2750_Smart Motor Management System
Accura 2750LCG performs two-way data transmission between Accura 2700M and Accura 2750LC[I]. Accura
2750LCG supports two ports to communicate with two Accura 2700M modules for redundancy.
Accura 2750LCG supports two networks(2 ports per group) for communication with Accura 2750LC[I]. It
supports communication redundancy via ring connection of Accura 2750LC[I] using 2 ports in a single group.
Up to 20 Accura 2750LC[I] modules can be connected in a single ring connection, and up to 40 modules can
be connected in two ring connections. Accura 2750LCG supplies 24V DC control power to Accura 2750LC[I]
through the communication cable. Due to the limit on the power supply of Accura 2750LCG, when the number
of Accura 2750LC[I] modules exceeds 10 per network group, one Accura 2750LC POW module should be
additionally connected to the rear of Accura 2750LC[I] to operate up to 20 modules per group.
Function
Connection with Accura 2700M
Internal dedicated protocol 2 ports with the same functions(A2700M-1, A2700M-2)
2 ports used to connect 2 Accura 2700M modules Accura 2700M device redundancy
Connector type RJ45 connector
Communication cable Ethernet cable Cat 5e FTP, STP, SFTP
Communication cable length Maximum 300m for each port
Connection with Accura 2750LC[I]
Internal dedicated protocol 4 ports with the same functions
(LC/LM-1,LC/LM-2,LC/LM-3,LC/LM-4)
In the existing LOPs, once the RUN/STOP command is executed by pressing the push button, it is sent
to Accura 2750PC through the signal cable connected with the contact point of the push button and the
digital input of the corresponding Accura 2750PC. However, when pressing the RUN/STOP button on Accura
2750LC[I], the control command is sent to Accura 2700M through Accura 2750LCG. Accura 2700M performs
the RUN/STOP command by sending the command to Accura 2750PC of the corresponding motor-unit
through communication. This communication method is beneficial since a single communication cable replaces
multiple signal cables connecting the MCC to the LOP at the existing system. It allows users to easily identify
the disconnection and short-circuit state of the cable.
Accura 2750LCG supports communication redundancy through ring connection using 2 communication ports
on Accura 2750LC[I].
Function
Connection with Accura 2750LCG
Accura 2750LCG performs the gateway function between Accura 2700M and Accura 2750LC[I].
The command of the corresponding motor-unit at the LOP is transmitted to Accura 2750PC through Accura 2750LCG and Accura 2700M.
Current, power, and operational status data on the corresponding motor-unit are transmitted from Accura 2750PC to
Accura 2750LC[I] through Accura 2700M and Accura 2750LCG.
Additional power supply Accura 2750LC POW module: 24V DC(Can supply power to 10 Accura 2750LC[I] modules)
through LC power module
Accura 2700/2750_Smart Motor Management System
Unit-Socket
One Accura 2700M module and multiple Accura 2750P[C] modules are connected through communication.
The Category 5e FTP, STP, or SFTP Ethernet cable is used for high reliability and convenience. Accura 2700M
should be connected with Accura 2750P[C] modules of individual motor units with the Daisy-chain method.
However, the Unit-Socket is provided for convenience in installing communication cables and withdrawing
motor units. A single Ethernet cable is also used to connect the Unit-Socket and Accura 2750P[C]. It makes it
easy to disconnect the communication line when withdrawing motor units.
Function
Easy Connection of Internal Communication Cables
As Accura 2750P[C] modules are connected through the Unit-Socket with communication cables, it is easy to disconnect the cables when
withdrawing a motor unit with Accura 2750P[C]. Even if the cable is disconnected, it does not affect communication of other motor units.
Removes T-stub connections through the input/output structure of the communication cable
Communication Port
Number of ports 3 ports(RJ45A, A2750, RJ45B)
(The RJ45A and RJ45B ports have the same functions)
Bridge-Socket
Through the Bridge-Socket, two Accura 2700M modules share the communication network of Accura
2750P[C]. It allows for the redundant wiring of Accura 2700M modules. Two Accura 2750LCG modules also
share the communication network of Accura 2750LC[I] through the Bridge-Socket, allowing for the redundant
wiring of Accura 2750LCG.
Function
Redundancy
As two Accura 2700M modules share Accura 2750P[C]’s network, it allows for redundancy of Accura 2700M modules.
As two Accura 2750LCG modules share Accura 2750LC[I]’s network, it allows for redundancy of Accura 2750LCG modules.
Communication Port
Number of ports 3 ports(CH_A, COM, CH_B)
(The CH_A and CH_B ports have the same functions)
Specifications
General Specifications
Certification and Standard
UL UL61010-1, UL60947-4-1
CE EN61326-1, EN55011
KC KN22, KN24
Environmental Condition
Shock
All modules 15 g/11 ms IEC 60068-2-27
Heat-resistance
All product cases V0 UL94
960°C IEC 60695-2-11
Membrane V2 UL94
Accura 2750D[C/CI] LCD Window
650°C IEC 60695-2-11
EMC Immunity IEC 60947-5-1 ROOTECH IEC 60947-1
Electrostatic discharge 8kV/air 12kV/air IEC 61000-4-2
4kV/contact 12kV/contact
Radiated radio-frequency 10V/m 10V/m IEC 61000-4-3
electromagnetic field
Connection with Accura 2750LCG Internal dedicated protocol 2 ports with the same functions
(A2750LCG-1, A2750LCG-2)
2 ports used to connect 2 Accura 2750LCG modules Support for Accura 2750LCG device redundancy
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP, STP, SFTP 3
Communication cable length Maximum 300m per port
Management Function
Management of Accura 2750P[C] Maximum number of connected modules in ring connection: 40 units
Management Performs the server function of the MCC for the host system's requests
function
Automatic Unit ID assignment, automatic recognition of the withdrawal
and insertion of the motor-unit
Management Transmits the current, power and operational status data of the motor-unit
function
Transmits the control commands of the motor-unit
Event Monitoring Voltage dip/swell
Item
1. The built-in Ethernet switch allows Ethernet connection between Accura 2700M modules without a separate external switch.
2. RSTP[Rapid Spanning Tree Protocol], IEEE 802.1D-2004.
3. FTP: Foiled Shield Twisted Pair, STP: Braided Shield Twisted Pair, SFTP: Braided Foiled Shield Twisted Pair. Cable length: less than 100 m.
4. Up to 16 modules can be connected per bus at 115200 bps.
5. It is provided with the product. FTP(F/UTP): Foiled Shield Twisted Pair
6. It can be selected among 2.5m / 3.0m / 3.5m when ordering the product.
38/39
LCD
Current Input
Connector type Through-hole type
Sampling 64 samples/ cycle
Through- Maximum
Rated Motor FLC
Item Model full measurement
current setup range
diameter current
Accura 2750P[C]-5A Ø12mm 5A 0.5 - 5A 40A
Accura 2750P[C]-30A Ø12mm 30A 3.0 - 30A 240A
Accura 2750P[C]-100A Ø19mm 100A 10.0 - 100A 800A
Accura 2750PC-160A Ø25mm 160A 16.0 - 160A 1280A
Accura 2750PC-250A Ø25mm 250A 25.0 - 250A 2000A
Accura 2750PC-400A Ø30mm 400A 40.0 - 400A 3200A
Digital Input
Number of channels Accura 2750P 1 channel(external power supply)
Accura 2750PC 10 channels(external power supply)
Connector type Screw-type terminal(pluggable)
Wire specifications 0.21 – 3.5 mm2 (24 – 12AWG)
Insulation method Insulated between groups, uninsulated within a group
Group 1: channel 1-5 (1DI1 – 1DI5) 1DIG common
Group 2: channel 6-10 (2DI6 – 2DI10) 2DIG common
Input Impedance 220 kΩ
Input type Connection of external power supply
Input maximum voltage AC/DC 240V
Low voltage range AC 0 – 70V, DC 0 – 70V
High voltage range AC 85 – 240V, DC 85 – 240V
Minimum pulse width 50 msec
Digital output
Number of channels/output form Accura 2750P 3 channels(Form-A 2 channels, Form-C 1 channel)
Accura 2750PC 4 channels(Form-A 3 channels, Form-C 1 channel)
Connector type Screw-type terminal(pluggable)
Wire specifications 1.5 – 3.5 mm2(16 – 12AWG)
Insulation AC 2,000V/1min.
Output rating Form-A: 5A/250Vac, 5A/30Vdc(DO1 – DO3)
Form-C: 3A/250Vac, 3A/30Vdc(DO4)
LCD
LCD features 1.2"(24.5 x 21.0mm) Customized Mono LCD, LED backlight
Connection with Module
Motor protection[control] module Internal dedicated protocol 1port(UNIT-SOCKET)
RS-485 communication:
Connector type RJ45 connector
Unit-Socket
Communication cable Ethernet cable Cat.5e FTP, STP, SFTP 1
Communication cable length Average 3m
HMI RS-485 communication: Internal dedicated protocol 1 port(DISPLAY)
Accura 2750D[C]
Connector type RJ45 connector
Communication cable Ethernet cable Cat.5e FTP(F/UTP) 2
Communication cable length Maximum 3.5m 3
4
Temperature Measurement
Temperature measurement range -20 to 100°C
Accuracy ±2% Full scale (full scale: 100°C)
40/41
1. FTP: Foiled Shield Twisted Pair, STP: Braided Shield Twisted Pair, SFTP: Braided Foiled Shield Twisted Pair
2. It is provided with the product. FTP(F/UTP): Foiled Shield Twisted Pair
3. It can be selected 2.5m / 3.0m / 3.5m when ordering the product.
4. Connect the control power supply to the DI input and set it to "Control Power Monitoring" in the corresponding DI input setting.
5. Events are divided into Fault, Alarm, Caution, and General events according to their importance. Fault, Alarm, and Caution events support
the notification function.
Accura 2700/2750_Smart Motor Management System
LED
Front LED POWER Green Turned on when control power operates normally
DEVICE Green Blinks when the device operates normally
(can be set to be turned on)
2 ports used to connect 2 Accura 2750P[C] modules Supports redundancy of the protection function
Connector type RJ45 connector
Communication cable Ethernet cable Cat 5e FTP(F/UTP) 3
Communication cable length Maximum 3.5m 4
Power supplied from Accura 2750P[C]
1. Accura 2750DCI module provides two separate INVERTER/BYPASS LEDs, as well as separate LEDs that indicate the MCCB Trip status.
2. It is available only in Accura 2750DCI module, and two separate INVERTER/BYPASS LEDs indicate the MCCB Trip status.
3. It is provided with the product. FTP(F/UTP): Foiled Shield Twisted Pair
4. It can be selected among 2.5m / 3.0m / 3.5m when ordering the product.
44/45
2 ports used to connect 2 Accura 2700M modules Accura 2700M device redundancy
Connector type RJ45 connector
Communication cable Ethernet cable Cat 5e FTP, STP, SFTP2
Communication cable length Maximum 300m for each port
Communication with Internal dedicated protocol 4 ports with the same functions
Accura 2750LC[I] (LC/LM-1,LC/LM-2,LC/LM-3,LC/LM-4)
1. Ring connection should be made between two ports in the same group, and ring connections across two groups are not supported.
2. FTP: Foiled Shield Twisted Pair, STP: Braided Shield Twisted Pair, SFTP: Braided Foiled Shield Twisted Pair
3. If the number of Accura 2750LC[I] modules per group exceeds 10, an Accura 2750LC POW module should be additionally connected.
Accura 2700/2750_Smart Motor Management System
Inverter operation mode LED INV Green Turned On when inverter mode is selected as motor-unit operation
(Accura 2750LCI only) mode
Temperature Measurement
Temperature measurement range 0 to 100°C
Accuracy ±2% Full Scale (Full Scale: 100°C)
LC POW Module Optional module which can be additionally connected to the rear of Accura 2750LC[I]
Port name L+, N-, G(Earth Ground)
Connector type Screw-type terminal(pluggable)
Wire specifications 2.1 – 3.5 mm2 (14 – 12 AWG)
Rated voltage(Us) 110 – 240V AC 50/60Hz, 110 – 300V DC
Operating voltage range 0.8 x Us – 1.1 x Us
Rated output voltage/power 24V DC / 20W
Rated insulation voltage(Ui) 300V (at pollution degree 2)
Rated impulse voltage(Uimp) 4kV
Inrush current Peak 22A, duration less than 1.5 msec(AC 220V)
Peak 11A, duration less than 300 usec(DC 110V)
External input fuse capacity 2A, 500V
Accepted instantaneous
Typ. 50ms
power outage time
1. If the number of Accura 2750LC[I] modules exceeds 10, an Accura 2750LC POW module should be additionally connected.
2. When the safety lock key status is changed from Locked to Unlocked, if the safety lock status of other modules is Locked,
the red LED (LOCK) is turned on and the green LED (UNLOCK) blinks to indicate that it is in the Locked state.
3. It is possible to start the motor only when the locked status of other modules is released.
4. FTP: Foiled Shield Twisted Pair, STP: Braided Shield Twisted Pair, SFTP: Braided Foiled Shield Twisted Pair
Unit-Socket
Function
Connection of communication The Unit-Socket is used to connect Accura 2750P[C] modules, enabling easy separation of cables
cables per unit when the unit with Accura 2750P[C] module is withdrawn. This does not affect communication of other units.
Removes T-stub connections through the input and output structure of communication cables
Communication
Port Number of ports 3 ports(RJ45A, A2750, RJ45B)
(The RJ45A and RJ45B ports have the same functions)
Connector type RJ45 connector
RJ45A, RJ45B Port Used to connect with Accura 2700M or an adjacent Unit-socket
Supports communication redundancy through ring connection
Communication cable length Average 3m
between Unit-Sockets
Total communication cable length Max.120m (40 modules in ring connection with the Unit-Socket)
Accura 2750 Port Used to connect with Accura 2750P[C]
Communication cable length Average 3m
Bridge-Socket
Function
Support for redundancy 2 Accura 2700M modules share the communication network of Accura 2750P[C] for redundancy
2 Accura 2750LCG modules share the communication network of 2750LC[I] for redundancy
Communication
Port Number of ports 3 ports(CH_A, COM, CH_B) (CH_A/CH_B ports have the same functions )
Connector type RJ45 connector
Accura 2750P[C] Network Sharing
CH_A, CH_B Port Used to connect Accura 2700M modules
Communication cable length Maximum 3m
COM Port Used to connect with the Unit-Socket
Communication cable length Maximum 10m
Accura 2750LC[I] Network Sharing
CH_A, CH_B Port Used to connect Accura 2750LCG modules
Communication cable length Maximum 3m
COM Port Used to connect with Accura 2750LC[I] module
Total communication cable length Maximum 800m per group(20 Accura 2750LC[I] modules in ring connection)
Accura 2700/2750_Smart Motor Management System
Ordering Information
Model Product Name
Accura 2700M Integrated Incoming-Unit Module
1
Accura 2700D Incoming-Unit Integrated HMI Module
1. You should select the length of the HMI display cable when ordering the HMI module.
1. You should select the length of the HMI display cable when ordering the HMI module.
Products
Integrated Incoming-Unit Module Integrated Incoming-Unit HMI Module
Motor-Unit Protection[Control] HMI Module Inverter-Unit Protection & Control HMI Module
Accura 2750D Accura 2750DC Accura 2750DC-AO Accura 2750DC-RS485 Accura 2750DCI
LOP Control Gateway LOP Control Module/LC POW Module Unit-Socket Bridge-Socket
Accura 2750LCG Accura 2750LC Accura 2750LCI Accura 2750LC POW Unit-Socket Bridge-Socket
Accura 2700/2750_Smart Motor Management System
Dimensions
Accura 2700M
75.0mm
[2.95"]
157.0mm
[6.18"]
94.0mm
[3.70"]
Accura 2700D
Ø102.0mm
239.8mm [4.02"]
[9.44"]
184.7mm
[7.27"]
18.2mm
[0.72"]
Front Rear
22.6mm
[0.89"]
50/51
59.4mm
48.2mm [2.34"]
22.2mm
[1.90"] [0.87"]
17.6mm
[0.69"] 113.2mm
95.2mm 33.7mm
30.0mm [3.75"] [1.33"] [4.46"]
[1.18"] 85.2mm 103.2mm
[3.35"] 14.8mm [4.06"]
10.5mm
[0.41"] 10.5mm [0.58"]
14.8mm
[0.41"] [0.58"]
Ø12 Ø19
91.0mm
[3.58"] 91.0mm
[3.58"]
90.0mm
[3.54"] 105.0mm
[4.13"]
48.2mm
[1.90"]
17.6mm 59.4mm
[0.69"] [2.34"] 22.2mm
105.2mm [0.87"]
30.0mm [4.14"]
[1.18"] 95.2mm
[3.75"] 33.7mm 123.2mm
10.5mm [4.85"]
[0.41"] [1.33"]
10.5mm 113.2mm
[0.41"] 14.8mm [4.46"]
[0.58"]
14.8mm
Ø12 [0.58"]
Ø19
91.0mm
[3.58"]
91.0mm
[3.58"]
90.0mm
[3.54"]
105.0mm
[4.13"]
Accura 2700/2750_Smart Motor Management System
28.2mm 126.4mm
40.2mm [1.11"] [4.98"]
[1.58"] 35.0mm
[1.38"]
Ø25 35.0mm
[1.38"]
28.2mm
[1.11"]
73.0mm
[2.87"]
80.2mm
[3.16"]
38.2mm
[1.50"]
133.0mm
[5.24"]
135.2mm
[5.32"]
30.0mm
[1.18"]
26.2mm 126.4mm
40.2mm [1.03"] [4.98"]
[1.58"] 37.0mm
[1.46"]
Ø25 37.0mm
[1.46"]
26.2mm
[1.03"]
73.0mm
[2.87"]
80.2mm
[3.16"]
38.2mm
[1.50"]
133.0mm
[5.24"]
135.2mm
[5.32"]
30.0mm
[1.18"]
52/53
32.5mm 158.0mm
44.5mm [1.28"] [6.22"]
[1.75"]
46.5mm
[1.83"]
Ø30 46.5mm
[1.83"]
32.5mm
[1.28"]
73.0mm
[2.87"]
mm
6"] 99.2mm
[3.90"]
41.4mm
[1.63"]
164.0mm
[6.46"]
144.0mm
[5.67"]
35.0mm
[1.38"]
84.8mm
[3.34"]
46.8mm
[1.84"]
91.0mm
91.0mm [3.58"]
[3.58"]
mm
6"]
90.0mm
105.0mm [3.54"]
[4.13"]
Accura 2700/2750_Smart Motor Management System
Accura 2750D
Ø64.0mm
[2.52"]
94.0mm
[3.70"]
80.0mm
[3.15"]
17.6mm
[0.69"]
Accura 2750DC
Ø64.0mm
115.5mm [2.52"]
[4.55"]
80.2mm
[3.16"]
17.6mm
[0.69"]
13.3mm
Front [0.52"] Rear
Accura 2750DCI
Ø64.0mm
[2.52"]
98.7mm
[3.89"]
115.8mm
[4.56"]
17.2mm
[0.68"]
13.7mm
Front [0.54"] Rear
54/55
28.0mm
28.0mm [1.10"]
[1.10"]
88.0mm
[3.46"]
Accura 2750LC[I]
86.2mm
[3.39"]
130.0mm
[5.12"]
19.9mm
[0.78"]
37.1mm
[1.46"]
156.6mm
[6.17"]
Front Rear
91.0mm
[3.58"]
86.2mm
[3.39"]
38.0mm
[1.50"]
Rootech provides comprehensive energy
management solutions that ensure high-
accuracy measurements and perfectly meet
customer needs.
Rootech, Inc.
102-611 Digital Empire2,
88, Sinwon-ro, Yeongtong-gu, Suwon-si, Gyeonggi-do, Korea
Tel. +82 31 695 7350 Fax. +82 31 695 7399