OUT-OF-STEP ELEMENT TESTING

RELAY SETTINGS AND OTHER PARAMETERS ENTERED BY THE USER

Quantity
General Settings
Z1MAG
Z1ANG
Z1MP
Z2MP
Z2PD

OOS Blinder Settings


X1T7
X1T6
R1R7
R1R6
X1B7
X1B6
R1L7
R1L6

OOS Element Settings


OSBD
EOOST
OSTD
50ABCP
50QUBP
UBD
50Q1P
67Q1D
UBOSBF

Other Parameters
INNOM
NFREQ
VTEST
SET V-TEST TO 115 V when this message appears
OUT-OF-STEP ELEMENT TESTING

RELAY SETTINGS AND OTHER PARAMETERS ENTERED BY THE USER

Description Value
General Settings
Positive Sequence Line Impedance Magnitude (ohms-sec) 7.8
Positive Sequence Line Impedance Angle (degrees) 84
Mho Phase Distance Element Zone 1 Reach (ohms-sec) 6.24
Mho Phase Distance Element Zone 2 Reach (ohms-sec) 9.38
Phase Distance Element Zone 2 Time Delay (cyc) 20

OOS Blinder Settings


Zone 7 Reactance - Top (ohms-sec) 23
Zone 6 Reactance - Top (ohms-sec) 21
Zone 7 Resistance - Right (ohms-sec) 23
Zone 6 Resistance - Right (ohms-sec) 21
Zone 7 Reactance - Bottom (ohms-sec) -23
Zone 6 Reactance - Bottom (ohms-sec) -21
Zone 7 Resistance - Left (ohms-sec) -23
Zone 6 Resistance - Left (ohms-sec) -21

OOS Element Settings


Out-of-Step Block Time Delay (cyc) 2
Enable Out-of-Step Tripping N
Out-of-Step Trip Delay (cyc) 0.5
Positive Sequence Current Supervision (A) 1
Negative Sequence Current Supervision (A) 1
Negative Sequence Current Unblock Delay (cyc) 0.5
Negative Sequence Overcurrent Level 1 Pickup (A) 1
Negative Sequence Overcurrent Level 1 Time Delay (cyc) 0.5
Out-of-Step Angle Blocking Rate 4

Other Parameters
Nominal Current Rating of the Current Inputs 5
Nominal System Frequency (Hz) 60
Test Voltage Selection (V-sec) 67
SET V-TEST TO 115 V when this message appears
OOS Element Tests OOS Blinder Tests

Test 1 Resistance Blinder


OOS Blocking Test

Test 2 Reactance Blinder


OOS Unblocking - Test
Balanced Fault

Test 3
OOS Unblocking -
Unbalanced Fault

Test 4
OOS Tripping TOWI

Test 5
OOS Tripping TOWO
RESISTA
The settings for this application either have a high R blinder value or a low
Point 1 Point 2
Load Zone 7 - Right Blinder
Magnitude Angle Magnitude Angle

VA 67.00 0.00 67.00 0.00


VB 67.00 -120.00 67.00 -120.00
VC 67.00 120.00 67.00 120.00

IA 2.38 0.00 2.90 0.00


IB 2.38 -120.00 2.90 -120.00
IC 2.38 120.00 2.90 120.00

Impedance 28.13 0.00 23.13 0.00

30

20

10
X (ohms - sec)

Point 5
Point 6 Point 4 Point 2 Point 1
Point 3
0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-30

R (ohms - sec)
RESISTANCE BLINDER TEST
igh R blinder value or a low Z1ANG. For such conditions, this spreadsheet will not work. Please use other testing methods.
Point 3 Point 4 Point 5
Zone 6 - Right Blinder Intermediate Point Zone 6 - Left Blinder
Magnitude Angle Magnitude Angle Magnitude

67.00 0.00 67.00 0.00 67.00


67.00 -120.00 67.00 -120.00 67.00
67.00 120.00 67.00 120.00 67.00

3.17 0.00 4.23 -180.00 3.17


3.17 -120.00 4.23 -300.00 3.17
3.17 120.00 4.23 -60.00 3.17

21.12 0.00 15.84 180.00 21.12

RR6
RR7
RL6
RL7
XT6
Point 2 Point 1 XT7
int 3
XB6
XB7
20 30 40
ZLine
Mho Zone1
Mho Zone2
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6

e other testing methods. Back
Point 5 Point 6 to
Zone 6 - Left Blinder Zone 7 - Left Blinder Main
Angle Magnitude Angle Menu

0.00 67.00 0.00


-120.00 67.00 -120.00
120.00 67.00 120.00

-180.00 2.90 -180.00


-300.00 2.90 -300.00
-60.00 2.90 -60.00

180.00 23.13 180.00


REACTA
The settings for this application either have a high R blinder value or a low
Point 1 Point 2
Load Zone 7 - Top Blinder
Magnitude Angle Magnitude Angle

VA 67.00 0.00 67.00 0.00


VB 67.00 -120.00 67.00 -120.00
VC 67.00 120.00 67.00 120.00

IA 2.38 -90.00 2.90 -90.00


IB 2.38 -210.00 2.90 -210.00
IC 2.38 30.00 2.90 30.00

Impedance 28.13 90.00 23.13 90.00

40

30
Point 1

Point 2
Point 3
20
X (ohms - sec)

10

0
-30 -20 -10 0 10 20

-10

Point 4

-20
Point 5
Point 6

-30

R (ohms - sec)
-30

R (ohms - sec)
REACTANCE BLINDER TEST
igh R blinder value or a low Z1ANG. For such conditions, this spreadsheet will not work. Please use other testing methods.
Point 3 Point 4 Point 5
Zone 6 - Top Blinder Intermediate Point Zone 6 - Bottom Blinder
Magnitude Angle Magnitude Angle Magnitude

67.00 0.00 67.00 0.00 67.00


67.00 -120.00 67.00 -120.00 67.00
67.00 120.00 67.00 120.00 67.00

3.17 -90.00 4.23 90.00 3.17


3.17 -210.00 4.23 -30.00 3.17
3.17 30.00 4.23 210.00 3.17

21.12 90.00 15.84 -90.00 21.12

RR6
RR7
RL6
RL7
XT6
XT7
XB6
XB7
ZLine
Mho Zone1
20 30 Mho Zone2
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6

e other testing methods. Back
Point 5 Point 6 to
Zone 6 - Bottom Blinder Zone 7 - Bottom Blinder Main
Angle Magnitude Angle Menu

0.00 67.00 0.00


-120.00 67.00 -120.00
120.00 67.00 120.00

90.00 2.90 90.00


-30.00 2.90 -30.00
210.00 2.90 210.00

-90.00 23.13 -90.00


TEST 1 - OUT-OF-STEP BLOCKI
The settings for this application either have a high R blinder value or a low Z1ANG. For such conditions, this s
State 1 State 2
Load Between Zone 6 & 7 Right Blinders
Magnitude Angle Magnitude

VA 67.00 0.00 67.00


VB 67.00 -120.00 67.00
VC 67.00 120.00 67.00

IA 1.94 -10.00 2.93


IB 1.94 -130.00 2.93
IC 1.94 110.00 2.93

Impedance 34.50 10.00 22.86

State Time (cyc) 60.00 3.50

30

20

10
X (ohms - sec)

State 3 State 2

0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-30

R (ohms - sec)
- OUT-OF-STEP BLOCKING ←
or a low Z1ANG. For such conditions, this spreadsheet will not work. Please use other testing methods. Back
State 2 State 3 State 4 to
een Zone 6 & 7 Right Blinders Inside Zone 1 Load Main
Angle Magnitude Angle Magnitude Angle Menu

0.00 67.00 0.00 67.00 0.00


-120.00 67.00 -120.00 67.00 -120.00
120.00 67.00 120.00 67.00 120.00

-9.77 17.18 -84.00 1.94 -15.00


-129.77 17.18 -204.00 1.94 -135.00
110.23 17.18 36.00 1.94 105.00

9.77 3.90 84.00 34.50 15.00

3.50 22.00 60.00

RR6
State 4 RR7
State 1 RL6
RL7
State 2
XT6
XT7
XB6
10 20 30 40
XB7
ZLine
Mho Zone1
Mho Zone2
State 1
State 2
State 3
State 4

- sec)
- sec)

Back
to
Main
Menu

Change Voltage
TEST 2 - OUT-OF-STEP UNBLOCKING
The settings for this application either have a high R blinder value or a low Z1ANG. For such conditions, this spread
use other testing methods.
State 1 State 2
Load Between Zone 6 & 7 Right Blinders
Magnitude Angle Magnitude

VA 67.00 0.00 67.00


VB 67.00 -120.00 67.00
VC 67.00 120.00 67.00

IA 1.94 -10.00 2.93


IB 1.94 -130.00 2.93
IC 1.94 110.00 2.93

Impedance 34.50 10.00 22.86

State Time (cyc) 60.00 3.50

30

20

10
X (ohms - sec)

State 3 State 2

0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-20

-30

R (ohms - sec)
TEP UNBLOCKING ←
Back
w Z1ANG. For such conditions, this spreadsheet will not work. Please
ng methods. to
State 2 State 3 Main
een Zone 6 & 7 Right Blinders Inside Zone 1 Menu
Angle Magnitude Angle

0.00 67.00 0.00


-120.00 67.00 -120.00
120.00 67.00 120.00 Change Voltage

-9.77 17.18 -84.00


-129.77 17.18 -204.00
110.23 17.18 36.00

9.77 3.90 84.00

3.50 125.00

RR6
RR7
State 1 RL6
State 2 RL7
XT6
XT7
10 20 30 40 XB6
XB7
ZLine
Mho Zone1
Mho Zone2
State 1
State 2
State 3

- sec)
- sec)
TEST 3 - OUT-OF-STEP UNBLOCKING - UNBALANCED F
The settings for this application either have a high R blinder value or a low Z1ANG. For such conditions, this spread
use other testing methods.
State 1 State 2
Load Between Zone 6 & 7 Right Blinders
Magnitude Angle Magnitude

VA 67.00 0.00 67.00


VB 67.00 -120.00 67.00
VC 67.00 120.00 67.00

IA 1.94 -10.00 2.93


IB 1.94 -130.00 2.93
IC 1.94 110.00 2.93

Impedance 34.50 10.00 22.86

State Time (cyc) 60.00 3.50

30

20

10
X (ohms - sec)

State 3 State 2

0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-30

R (ohms - sec)
CKING - UNBALANCED FAULT ←
w Z1ANG. For such conditions, this spreadsheet will not work. Please
Back
ng methods. to
State 2 State 3 Main
een Zone 6 & 7 Right Blinders Inside Zone 1 Menu
Angle Magnitude Angle

0.00 67.00 0.00


-120.00 35.00 -150.00
120.00 35.00 150.00 Change Voltage

-9.77 0.00 0.00


-129.77 4.49 -174.00
110.23 4.49 6.00

9.77 3.90 84.00

3.50 22.50

RR6
RR7
State 1 RL6
State 2 RL7
XT6
XT7
10 20 30 40 XB6
XB7
ZLine
Mho Zone1
Mho Zone2
State 1
State 2
State 3

- sec)
- sec)
TEST 4 - OUT-OF-STEP TRIPPING - TOWI
The settings for this application either have a high R blinder value or a low Z1ANG. For such conditions, this spread
use other testing methods.
State 1 State 2
Load Between Zone 6 & 7 Right Blinders
Magnitude Angle Magnitude

VA 67.00 0.00 67.00


VB 67.00 -120.00 67.00
VC 67.00 120.00 67.00

IA 1.94 -10.00 2.93


IB 1.94 -130.00 2.93
IC 1.94 110.00 2.93

Impedance 34.50 10.00 22.86

State Time (cyc) 60.00 1.60

30

20

10
X (ohms - sec)

State 3 State 2

0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-30

R (ohms - sec)
P TRIPPING - TOWI ←
w Z1ANG. For such conditions, this spreadsheet will not work. Please
Back
ng methods. to
State 2 State 3 Main
een Zone 6 & 7 Right Blinders Inside Zone 1 Menu
Angle Magnitude Angle

0.00 67.00 0.00


-120.00 67.00 -120.00
120.00 67.00 120.00 Change Voltage

-9.77 17.18 -84.00


-129.77 17.18 -204.00
110.23 17.18 36.00

9.77 3.90 84.00

1.60 4.00

RR6
RR7
State 1 RL6
State 2 RL7
XT6
XT7
10 20 30 40 XB6
XB7
ZLine
Mho Zone1
Mho Zone2
State 1
State 2
State 3

- sec)
- sec)
TEST 5 - OUT-OF-STEP TRIPPING -
The settings for this application either have a high R blinder value or a low Z1ANG. For such conditions, this s
State 1 State 2
Load Between Zone 6 & 7 Right Blinders
Magnitude Angle Magnitude

VA 67.00 0.00 67.00


VB 67.00 -120.00 67.00
VC 67.00 120.00 67.00

IA 1.94 -10.00 2.93


IB 1.94 -130.00 2.93
IC 1.94 110.00 2.93

Impedance 34.50 10.00 22.86

State Time (cyc) 60.00 1.60

30

20

10
X (ohms - sec)

State 4 State 3 State 2

0
-30 -20 -10 0 10 20 30

-10

-20

-30

R (ohms - sec)
-30

R (ohms - sec)
UT-OF-STEP TRIPPING - TOWO ←
or a low Z1ANG. For such conditions, this spreadsheet will not work. Please use other testing methods. Back
State 2 State 3 State 4 to
een Zone 6 & 7 Right Blinders Inside Zone 1 Between Zone 6 & 7 Left Blinders Main
Angle Magnitude Angle Magnitude Angle Menu

0.00 67.00 0.00 67.00 0.00


-120.00 67.00 -120.00 67.00 -120.00
120.00 67.00 120.00 67.00 120.00

-9.77 17.18 -84.00 3.04 -169.87


-129.77 17.18 -204.00 3.04 -289.87
110.23 17.18 36.00 3.04 -49.87

9.77 3.90 84.00 22.06 169.87

1.60 2.00 2.00

RR6
RR7
State 1 RL6
RL7
State 2
XT6
XT7
XB6
10 20 30 40
XB7
ZLine
Mho Zone1
Mho Zone2
State 1
State 2
State 3
State 4

- sec)
- sec)

Back
to
Main
Menu

Change Voltage

You might also like