Product Specification
37171D
IKD 1
Digital I/O Expansion Board
APPLICATIONS DESCRIPTION
SPECIFICATIONS
Power supply ......................................... 12/24 Vdc (6 to 36 Vdc) CAN interface ................................................................ isolated
Intrinsic consumption ....................................................max. 3 W Insulation voltage (continuously) .................................... 100 Vac
Ambient temperature ................................................-40 to 85 °C Insulation test voltage (≤ 5 s) ...................................... 1,000 Vac
Ambient humidity ..................................... 95 %, non-condensing Version .......................................................................... CAN bus
DIMENSIONS
51 mm
168 mm
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
128 mm
Configuration port
10
12
13
14
15
16
17
18
11
1
2
3
4
5
6
7
8
9
WIRING DIAGRAM
NC
Relay 7
NO
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
NC CAN-H
Relay 6 CAN-L
NC CAN-H
Relay 5 CAN-L
NO
N/C
NC Digital input 8 8
NC Digital input 5 5
NC Digital input 2 2
0 V DC
NC
Relay 1 0 V DC
NO
12/24 V DC
1
Subject to technical modifications. 2002-11-07 | IKD 1 Wiring Diagram ikd1ww-4502-ap.skf
Released
TYPICAL APPLICATIONS
CONTACT
The digital inputs are read by the IKD 1 and transferred via the
North & Central America CAN bus to the control unit (incl. alarm class). Each alarm
Tel.: +1 (208) 278 3370 input may have a delay as well as the control logic (NO/NC)
configured individually during set up. The status of the alarm
South America
input is monitored in the control device and will show the
Tel.: +55 19 3708 4800
alarm text in its display. The alarm class assigned in the
Europe control device evaluates the alarm input and reacts
Tel.: +49 711 78954 510 accordingly.
V~
Middle East & Africa The control device’s relay manager controls the IKD 1 relays.
Tel.: +971 2 678 4424 I~
The control logic for each IKD 1 relay can be programmed
Russia individually in the control device. Logical commands can be
Tel.: +49 711 78954 515 configured using internal events as well as the status of the
digital inputs coming from the IKD 1.
China
Tel.: +86 512 8818 5515 If a discrete input on the IKD 1 is enabled, the control device
displays a text message and the control functions of the alarm
Load
India V~ class are executed (refer to all manuals relating to the control
Tel.: +91 124 4399 500 device). The control device must operate the IKD 1 relays.
ASEAN & Oceania e.g.
easYgen-3200
Tel.: +49 711 78954 510
V~
SALES SUPPORT
industrial.sales PG@woodward.com I~
TECHNICAL SUPPORT
industrial.support@woodward.com
www.woodward.com G V/Q
/n/Vbatt/..
Start/Stop
Subject to alterations, errors excepted. n/f/P
CAN bus