DATE: 8-Nov-2023
Page No.: 1
Cladding Class A is adopted since wind actions will be checked on all units of glazings and their intermediate fixings.
The maximum horizontal dimension of building does not exceed 50m.
Height above local ground floor level = 9.7 m
Ground Roughness, S2 = 0.995 CAT 1
Topographical Factor , S1 = 1 (Building is an inland building with no valley)
Statistical Factor , S3 = 1
Reductio Force
Fn = CfnqKja
Member Length, l Width, ja Ratio, l/ja n factor, coeficient,
cfn (KN/m)
K
RHS 75x25 1881 25 75 0.93 2.1 0.17
RHS 75x25 1881 75 25 0.83 2.1 0.47
Design Wind pressure on Member at Wind 0 Deg = Fn x q = 0.63 KN/m2 (Perpendicular to smaller face)
2
Design Wind pressure on Member at Wind 0 Deg = Fn x q = 1.68 KN/m (Perpendicular to larger face)
PROJECT: MARADIVA RESIDENCE - APPARTMENT
DATE: 29-Aug-2023
Page No.: 2
ELEVATION 1
T1
M1
T1
T2
T1
PROJECT: MARADIVA RESIDENCE - APPARTMENT
DATE: 29-Aug-2023
Page No.: 3
DEFLECTION CHECK
Max. Deflection, dact = (uTly4)/(185EIxx) 0.5 mm
Allowable Deflection, dall = span/175 10.7 mm
Therefore, Deflection OK
MOMENT CHECK
Max. Moment , Mact =1.2x wl2 /8 = 0.01 KNm
Moment Capacity , Mo = (Po x Z )/1.2 0.21 KNm
Therefore, Moment OK
CHECK CONNECTION
RHS is connected to horizontal with 4.8mm Rivet pop
Page No.: 4
DEFLECTION CHECK
Max. Deflection, dact = (uTly4)/(185EIxx) 4.4 mm
Allowable Deflection, dall = span/175 10.7 mm
Therefore, Deflection OK
MOMENT CHECK
Max. Moment , Mact =1.2x 5 wl/8 = 0.18 KNm
Moment Capacity , Mo = (Po x Z )/1.2 0.21 KNm
Therefore, Moment OK
CHECK CONNECTION
RHS is connected to horizontal with 4.8mm Rivet pop
Page No.: 5
CHECK MEMBER T2
Reaction at ends from M1, R1 = 3wL/8 = 0.011 KN
Page No.: 6
ELEVATION 2
T3
T1
PROJECT: MARADIVA RESIDENCE - APPARTMENT
DATE: 29-Aug-2023
Page No.: 7
ELEVATION 2
CHECK MEMBER M2
LOADING ARRANGEMENT
Nodal load = 0.011 KN