Demand factor calculations for different loads using Egyptian Standard

Load Type Multi story buildings Private Small hotels or Offices, shops and
residential public public buildings
apartments or except for
similar workshops and
factories
Illumination 50% total load 66% total load 75% total load 90% total load
Sockets 100% for highest load 100% for 100% for highest 100% for highest
in circuit + 40% for highest load in load in circuit + load in circuit + 40%
total load for the rest circuit + 40% for 40% for total load for total load for the
of the circuits total load for for the rest of the rest of the circuits
the rest of the circuits+ 75%
circuits
Fixed appliances 100% of rated load of 100% of all 100% of rated load 100% of rated load
except for motors , largest equipment loads rated up of largest of largest
heaters and + 50% for rated load to 10 amperes equipment equipment + 75% of
cooking for the 1st equipment + 50% of all + 80% for rated total connected load
following the largest loads rated load for the 1st of other equipment
nd
one + 33% for the 2 more than 10 equipment
equipment following amperes following the
the largest load + largest one + 60%
20% of total of total connected
connected load of load of other
other equipment equipment
Fixed cooking 100% of rated load of 100% of all 100% of rated load 100% of rated load
equipment largest equipment loads rated up of largest of largest
+ 50% for rated load to 10 amperes equipment equipment
for the 1st equipment + 30% of all + 80% for rated + 80% for rated load
following the largest loads rated load for the 1st for the 1st
one + 33% for the 2nd more than 10 equipment equipment following
equipment following amperes + 5 following the the largest one +
the largest load + amperes if largest one + 60% 60% of total
20% of total device requires of total connected connected load of
connected load of an extra outlet load of other other equipment
other equipment equipment
Motors except for 100% of rated load of 100% of rated 100% of rated load 100% of rated load
motors used in largest equipment + load of largest of largest of largest
elevators which 50% of total equipment + equipment + 50% equipment + 80%
requires special connected load of 50% of total of total connected for rated load for
needs other equipment connected load load of other the 1st equipment
of other equipment following the largest
equipment one + 60% of total
connected load of
other equipment
Electric heaters 100% of rated load of largest equipment + 100% for rated Determined by
(non-continuous load for the 1st equipment following the largest one + 25% of designers depending
operation) total connected load of other equipment on operation
conditions
Electric heaters 100% of total connected load in all cases
(continuous
operation)