ANSI-IEEE STD C37.48-1987

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

H 1 Y 3 1 / l C C C L.3/.

46- I Y U /
(Revision of ANSI/IEEE C37.48-19691

guide for application, operation, and


maintenance of high-voltage fuses,
distribution enclosed single-pole air switches,
fuse disconnecting switches, and accessories

I k c r m h a 2R. 1987 .MII / 7h 7


American National Standard
IEEE Guide for Application, Operation, and
Maintenance of High-Voltage Fuses,
Distribution Enclosed Single-Pole Air Switches,
Fuse Disconnecting Switches, and Accessories

1. Scope and References [4] ANSI C37.46-1981, American National Stan-


dard Specifications for Power Fuses and Fuse
1.1 Scope. This guide applies to high-voltage Disconnecting Switches?
fuses (above 600 V), distribution enclosed single- [5] ANSI C37.47-1981, American National Stan-
pole air switches, fuse disconnecting switches, dard Specfications for Distribution Fuse Discon-
and accessories for ac distribution systems as necting Switches, Fuse Supports, and Current-
follows: Limiting Fuses.
(1) Enclosed, open, and open-link types of dis-
tribution cutouts and fuses [6] ANSI/IEEE C37.40-1981,IEEE Standard Serv-
(2) Distribution current-limiting fuses ice Conditions and Definitions for High-Voltage
( 3 ) Distribution oil cutouts Fuses, Distribution Enclosed Single-Pole Air
(4) Distribution enclosed single-pole air Switches, Fuse Disconnection Switches, and
switches Accessories.3
(5) Power fuses including current-limiting [ 7 ] ANSI/IEEE C37.41-1981, IEEE Standard
types Design Tests for High-Voltage Fuses, Distribution
(6) Outdoor and indoor fuse disconnecting Enclosed Single-Pole Air Switches, Fuse Discon-
switches necting Switches, and Accessories.
(7) Fuse supports, fuse mountings, fuse hooks,
fuse tongs, and fuse links, all of the type used [8] ANSI/IEEE Std 18-1980, IEEE Standard for
exclusively with products listed in (1) through (6) Shunt Power Capacitors.
(8) Removable switch blades for products listed
[9] ASTM E-498-73 (R 1980), Leaks Using the
in (1) through ( 3 ) . Mass Spectrometer Leak Detector or Residual Gas
Analyzer in the Tracer Probe Mode?
1.2 References. This guide shall be used in con-
junction with the following publications:
[ 1 ] ANSI C37.42-1981, American National Stan-
dard Specifications for Distribution Cutouts and
“ANSI publications are available from the American
Fuse Links. National Standards Institute, 1430 Broadway, New York, NY
10018.
[2] ANSI C37.44-1981, American National Stan-
dard Specifications for Distribution Oil Cutouts ‘’ASS1‘IEEE publications are available from IEEE Service
Center, 445 Hoes Lane, PO Box 1331, I’iscataway, NJ 08865-
and Fuse Links. 1331, o r from t h e Sales Department, American National
Standards Institute, 1430 Broadway, New York, NY 10018.
[3] ANSI C37.45-1981, American National Stan-
4ASTM publications a r e available from the American
dard Specifications for Distribution Enclosed Society for Testing and Materials, 1916 Race St, Philadelphia,
Single-Pole Air Switches. PA 19103.

7
ANSI IEEE
C37 48 1987 IKEE GI'IDE FOR APPLICATION. OPERATION, ANI) MAINTENANCE OF HIGH VOLTAGE RISES. DISTRIBIJTION

2. General ANSI/IEEE C37.40-1981 [6],52.1. These condi-


tions spec@ limits in altitude and ambient tem-
The application, operation, and maintenance of perature.
equipment covered by this guide is the responsi-
bility of the user who is expected to take into 3.2 Unusual Service Conditions. Unusual serv-
account h i d h e r own particular requirements. As ice conditions are defined in ANSUIEEE C37.40-
an aid in obtaining satisfactory performance of 1981 [6],paragraph 2.2, which gives examples of
equipment, this guide provides a general guide on such conditions. ANSI/IEEE C37.40-1981 [ 6 ] ,
some of the more important features of the above Table 1 lists altitude correction factors for rated
functions for normal conditions of service; un- voltage, rated continuous current, and ambient
usual conditions may require special measures. temperature for altitudes above 3300 f t (1000 m).
Although fuses are single-phase devices, they
can be applied to single- or three-phase equip- 3.3 Clearances and Spacings. Minimum electri-
ments or lines, or a combination of these. How- cal spacings and clearances for power fuse and
ever, characteristics of the power system should disconnecting switch installations shall be in
be considered when selecting all fuses. accordance with ANSI C37.46-1981 [4],Tables 7,
A fuse when applied in an electric circuit within 8, and 9. The application should recognize the
the limits of its ratings protects the circuit. Its conditions prevalent during proof testing (per
primary function is to isolate faulty equipment ANSI/IEEE C37.41-1981 [7]) and generally con-
from the system. When applied with other equip- form to the test clearances and conditions as a
ment in a coordinated over-current protection minimum, unless the manufacturer recommends
scheme, it may also limit service interruptions to the minimum clearances to be observed.
only a predetermined section of a power system. Vented fuses should be provided with adequate
In many applications it is possible t h a t t h e clearances in the direction or directions in which
equipment connected to the system can be pro- they are vented, and facilities should be provided
tected from excessive damage. In this latter to ensure that operators are not exposed to fuse
application the primary function is to remove the discharges either during replacement or when
faulted equipment from the system, and the working in the area. When this is not possible, the
secondary function is to minimize the damage to circuit should be de-energized.
the connected equipment as much as possible, Clearances for oil cutouts are generally dic-
considering the varying fault or overload circum- tated by type of cable connection and should be in
stances that can occur. accordance with the manufacturer's recommen-
Fuse performance depends upon the integrity dations.
with which it was manufactured, the correctness
of its application, and the attention it receives 3.4 Position on Crossarm. The positioning of
after it is installed. If not properly applied the fuses on a pole or crossarm should be such
and maintained, it might fail to perform when that their operation is facilitated. Fuses that are
required, which might result in considerable far out on a crossarm should open in a plane that
damage to costly equipment or extensive inter- is inclined toward the pole, rather than in a plane
ruptions in service. that is perpendicular to the crossarm.
It cannot be stressed too strongly that prescribed
safety rules and manufacturers' recommenda- 3.5 Noise Level. Vented fuses may produce in-
tions and instructions should be adhered to at all tense short time noise levels during fault inter-
times when operating or maintaining these devi- ruption. The height, location, and exhaust control
ces near energized equipment or conductors. This of vented fuses should be such as to minimize the
is especially true for devices where air insulated noise level at any location normally occupied by
blades, insulating barriers or liners, orfuses are personnel.
remaved or replaced while mating contacts are
energized. 3.6 Factors in Selection of Fuse Voltage Rating.
The selection of the proper voltage rating for
power fuses, distribution cutouts, or distribution
3. Application

3.1 Usual Service Conditions. Usual service "The numbers in brackets correspond to the references
conditions conforming to this guide are defined in listed in 1.2 of this standard.

8
ANSI IEEE
ENCLOSEI) SINGLE I'OI,E: AIR SWITCHES, FIXC DISCONNEC'I'ING SWITCHES, AND ACCESSORIES C37 48- 1987

current-limiting fuses, is based on consideration have a basic insulation level (BIL) coordinated
of the following system parameters: with the line-to-ground insulation of other con-
(1) Maximum system line-to-line or line-to- nected apparatus. A backup device may be re-
ground normal frequency recovery voltage quired to clear such faults, should they occur.
(2) System neutral grounding 3.7.2.2.2 Slant-Voltage-Rated (Multiple-
(3) Single- or three-phase circuits Voltage-Rated) Cutouts.
(1) In single-phase, line-to-neutral circuits, the
3.7 Guide for Selection of Fuse Voltage Ratings cutout should have a maximum voltage rating to
3.7.1 Power Fuses (including current-limiting the left of the slant equal to or exceeding the max-
types). The fuse should have a maximum voltage imum system line-to-ground voltage.
rating equal t o or exceeding the maximum system (2) In three-phase circuits, the cutout should
line-to-line voltage. have a maximum voltage rating to the right of the
NOTE: Most power fuses are used on three-phase applica-
slant equal to or exceeding the maximum system
tions. When used on single-phase line-to-ground circuits, the line-to-line voltage. Some of the criteria for using
fuse should have a maximum voltage rating of a t least 1.15 slant-voltage-ratedcutouts in three-phase circuits
times maximum system line-to-ground voltage or be used so
that fault currents do not exceed 0.87 times t h e fuse rated
as herein set forth are
interrupting current. (a) Three-phase faults not involving ground,
which impose 87% of line-to-line voltage across
3.7.2 Distribution Fuses (Cutouts and Dis- the first cutout to clear, seldom occur. Operation
tribution Current-LimitingTypes) of a backup device may be required to clear such
3.7.2.1 Ungrounded-Neutral Systems or faults, but experience indicates such cases are
Systems Having Grounding Poorer Than Solidly rare.
Grounded Neutral (Multigrounded) Systems. A (b) Phase-to-phase faults not involving
single-voltage-rated distribution fuse should have ground generally cause two cutouts to operate in
a maximum voltage rating equal to or exceeding series to clear the fault. Even with differences in
the maximum system line-to-line voltage. A slant- fuse-link melting time, both cutouts work together
voltage-rated (multiple-voltage-rated) cutout to clear high-current faults. On medium-current
should have a maximum voltage rating to the left faults, the possibility exists of load current con-
of the slant equal to or exceeding the maximum tinuing to flow through one of the cutouts, after
system line-to-line voltage. fault clearing by series operation of the two
3.7.2.2 Solidly Grounded-Neutral (Multi- cutouts. Operation of backup devices may be
grounded) Systems required if the cutout does not clear the continu-
3.7.2.2.1 Single-Voltage-Rated Distribu- ing load current, but experience indicates that
tion Fuses. such cases are extremely rare.
(1) In single-phase, line-to-neutral circuits, the (e) The maximum current to be cleared by
fuse should have a maximum voltage rating equal one cutout operating alone at line-to-line voltage
to or exceeding the maximum system line-to- is limited to approximately the one-cycle melting
ground voltage, and a basic insulation level (BIL) current of the fuse link in the second cutout
coordinated with the line-to-ground insulation of involved. Slant-voltage-rated cutouts will gener-
other connected apparatus. ally clear such relatively low currents at full line-
(2) In three-phase circuits where multiphase to-line recovery voltage.
faults not involving ground can occur, the fuse (d) The basic impulse insulation level (BIL)
should have a maximum voltage rating equal to of a slant-voltage-rated cutout should be coordi-
or exceeding the maximum system line-to-line nated with the line-to-ground insulation of other
voltage. connected apparatus.
(3) In three-phase circuits where multiphase Consideration should also be given to service
faults not involving ground cannot occur or are conditions listed in ANSI/IEEE C37.40-1981 [6],
unlikely (for example, where phase isolation is Section 2, as they apply to dielectric strength.
employed as in underground or cubicle construc- (e) Manufacturer's recommendations should
tion), and the fuse is not required to protect be followed on the suitability of particular slant-
transformers against secondary faults of the types voltage-rated cutouts for three-phase application.
that would impose greater than line-to-ground 3.7.3 All Systems. Expulsion fuse voltage rat-
recovery voltage, the fuse may have a maximum ings may exceed the system voltage by any desired
voltage rating equal to or exceeding the maxi-
mum system line-to-ground voltage, and should "I)cfinition\ and te\t speclficatlon4 undei dmelopnient

9
ANSI IEEE
C37 48 1987 IEEE GI‘IDE FOR APPLICATION, OPERATION, AND MAINTENANCE OF HIGH VOLrAGE K S E S , DISTRIBLTTION

amount. Care should be taken in applying current- transformer protection determined by comparing
limiting fuses with higher voltage ratings than the the appropriate time-current curve for the fuse
system voltage. Current-limiting fuses can pro- selected with the appropriate transformer short-
duce peak arc voltages higher than the fuse volt- time loading curve; both curves need to be prop-
age rating. These overvoltages should not exceed erly adjusted t o reflect differences between
system BIL. The sparkover voltage of source side primary- and secondary-phase currents and
connected surge arresters should be considered. winding currents associated with the specific
The fuse manufacturer’s recommendations should transformer connection involved and the types of
be followed in this regard. possible faults in the secondary circuit.
Provide earliest possible detection and clearing
3.8 Selection of Interrupting Rating. The inter- of internal transformer faults.
rupting rating of the fuse should be equal to or Permit loading the transformer to the maxi-
greater than the maximum fault current available mum loading practice of the user.
on the load side of the fuse. With fuse interrupting Withstand combined transformer magnetizing
ratings in symmetrical amperes, they are directly inrush and load pickup current after short-time
comparable to the calculated fault-current value. (up to 1 min) service interruption, and combined
Fuses will interrupt asymmetrical fault currents transformer magnetizing inrush and load pickup
associated with specified X l R ratios. These ratios current after extended (30 min and longer)
are generally higher than experienced on actual outages.
power systems, so no derating is generally re- Properly coordinate with over-current protec-
quired. For the rare cases where sy’stem X l R is tion devices on the secondary of the transformer.
higher than that specified for fuse testing, de- For small residential transformers (25 kVA and
rating may be necessary. The fuse manufacturer lower), withstand surge discharge through a
should be consulted. grounded primary winding whose magnetic circuit
has become saturated by a long-time lightning-
induced surge.
3.9 Selection of Continuous Current Rating For residential transformers with a fuse located
3.9.1 General. There are no generalizations as ahead of a surge arrester at the transformer,
to the selection of a current rating for a high- withstand the potential surge current that may
voltage fuse since there are radically different be discharged through the arrester.
objectives for using a fuse as an overcurrent pro-
tective device, such as the type and rating of the 3.9.2.2 Fuses for Shunt Capacitor Banks.
equipment being protected, the nature of the Protect the distribution system from major faults
loads imposed by t h e equipment or circuits, at or within the capacitor bank, and coordinate
special operating practices of the user such as with the next upstream overcurrent protective
loading of transformers, special operating require- device up to the maximum fault current available
ments of the user such as ability to withstand cold at the capacitor bank fuse.
load pick-up after extended outages, and coor- Provide earliest possible detection of internal
dination with other series protective devices. faults in individual capacitor units.
This guide, therefore, will present a listing of the Permit loading associated with: larger-than-
most commonly used applications for high-voltage rated capacitance of units, operating voltage in
fuses together with the objectives that are re- excess of nameplate rating, and presence of har-
quired and can be achieved with proper fuse monic currents.
ampere rating and time current characteristic Operate, when one unit in one phase of an
(TCC) selection. ungrounded wye-bank becomes faulted, within a
3.9.2 Primary Distribution System time span that will not damage capacitor units in
3.9.2.1 Fuses for Distribution Transformers the unfaulted phases due to their operating at
-Residential, Industrial, Institutional, and 1.73 times rated voltage for the duration of the
Commercial. Protect the distribution system fault.
from faults at or within the transformer, and Withstand transient currents from the distribu-
coordinate with the next upstream overcurrent tion system and from adjacent banks.
protective device up to the maximum fault cur- Withstand or operate (users choice) on dis-
rent available at the transformer fuse. charge current from the capacitor bank into a
Provide maximum protection to t h e trans- fault on the distribution circuit near the capacitor
former from through faults, with the degree of bank.

10
ANSI / IEEE
ENCLOSED SINGLE-POLE AIR SWITCHES, FIJSE DISCONNECTING SWITCHES, AND ACCESSORIES C37.48- 1987

3.9.2.3 Fuses for Recloser or Circuit- 3.9.3.2.1 Bank Fuses. Protect the substa-
Breaker Bypass. Protect the substation trans- tion bus from faults at the capacitor bank, and
former from feeder faults in the zone from the coordinate with all upstream overcurrent protec-
bypassed device to the next main circuit tion devices up to the maximum fault current
downstream overcurrent protective device, and available at the substation bus.
coordinate with the next upstream overcurrent Permit maximum normal loading associated
protective device up to the maximum through with: larger-than-rated capacitance of units,
fault current available at the bypass fuse. operating voltage in excess of nameplate rating,
Permit loading of the feeder to the maximum and presence of harmonic currents.
loading practice of the user. Withstand energizing transient currents from
Properly coordinate with main circuit down- the source(s) and from other energized capacitor
stream overcurrent protective devices. banks connected to the substation bus.
3.9.2.4 Fuses for Sectionalizing. Protect 3.9.3.2.2 Capacitor Unit Fuses. Provide
conductors from burn-down or extreme heating earliest possible detection of internal faults in
in the zone from the sectionalizing fuse to the individual capacitor units.
next main circuit downstream overcurrent pro- Permit maximum normal loading associated
tective device, and coordinate with the next with: larger-than-rated capacitance of unit, oper-
upstream overcurrent protective device up to the ating voltage in excess of name plate rating, and
maximum fault current available at the sectional- presence of harmonic currents.
izing fuse. Withstand discharge transient current from an
Permit loading of the circuit to the maximum individual capacitor unit into an adjacent faulted
loading practice of the user. unit within the same parallel-capacitor group.
Properly coordinate with main circuit down- Withstand currents 10%greater than maximum
stream overcurrent protective devices. normal loading in the remaining capacitor units
within a group of parallel units, until phase
3.9.3 SubtransmissionSystem imbalance is detected and the capacitor bank
3.9.3.1 Fuses for Distribution Substation de-energized.
Transformer Primary. Protect the substation bus
from faults at or within the transformer, and 3.10 Fuse to Fuse Coordination Procedure. For
coordinate with all upstream overcurrent protec- the fuses on an electric system to operate prop-
tive devices up to the maximum fault current erly and provide the desired system protection,
available on the substation bus. consideration of voltage, continuous current, and
Provide maximum protection to the transformer interrupting ratings is not sufficient to select the
from through faults, with the degree of trans- proper fuse for a particular application. One must
former protection determined by comparing the also ensure that the fuse being selected will oper-
appropriate time current curve for the fuse ate correctly relative to the other fuses being
selected with the appropriate transformer short- used. The procedure by which this is accomplished
time loading curve; both curves need to be is called the fuse to fuse coordination procedure.
properly adjusted to reflect differences between The information required to select fuses that
primary and secondary phase currents and wind- coordinate with one another is usually provided
ing currents associated with the specific trans- in the form of two curves related t o the melting
former connection involved and the types of and clearing characteristics of t h e fuse. The
possible faults in the secondary circuit. minimum melting time-current curve shows the
Provide earliest possible detection and clearing minimum time, expressed in seconds, required to
of internal transformer faults. melt the fusible element(s) for a particular value
Permit loading the transformer to the maxi- of symmetrical sinusoidal current. The total clear-
mum loading practice of the user. ing time-current curve shows the maximum time,
Withstand combined transformer magnetizing expressed in seconds, to complete current inter-
inrush and load pickup current after short-time ruption at a particular value of symmetrical
(up to 1 min) voltage interruption on the sub- current. Both curves take into account variations
station bus. resulting from manufacturing tolerances and
Properly coordinate with overcurrent protec- represent performance under specific conditions
tive devices on the secondary of the transformer. (see ANSI/IEEE C37.41 1981 [7], Section 12).
3.9.3.2 Fuses for Substation Shunt Capaci- On both the minimum melting and total clear-
tor Banks ing time-current curves for current-limiting fuses,

11
ANSI IEkX
C37 48 1987 IEEE GL'IDE FOR APPLICATION. OPERATION, AND MAINTENANCE OF HIGH-VOLTAGE; E'IXES, DISTRIBITION

currents can usually be determined for times as 3.11 Voltage Withstand on Blown Fuses. Typi-
short as 0.01 s. However, as noncurrent-limiting cally, fuse cutouts are designed to incorporate a
fuses do not clear in less than one loop of fault drop-open action following an interrupting oper-
current, the total clearing curves for these fuses ation. This action quickly removes all voltage
show a constant value of time for all currents that stress across the fuse holder. Many applications of
produce melting in less than one loop (that is, nondrop-open fuses, such as the backup current-
approximately 0.8 of a cycle for typical X / R limiting type, utilize a series expulsion fuse or
values). other device coordinated to provide isolation
Characteristic information for current-limiting means and prevent dielectric breakdown of a
fuses for times less than 0.01 s is often provided in contaminated fuse if subjected to long time volt-
terms of 12t (strictly/12dt). Data on the min- age stress. For those applications where long time
imum melting 12t and total clearing Z 2 t can be voltage stress can occur across a blown fuse, and
presented either in tabular form or as curves dielectric breakdown would permit curn
showing 1 2 t as a function of the available fault the fuse manufacturer should be consulted as to
current. As a fuse's melting time decreases, its the adequacy of the product for the proposed
melting 1 2 t approaches a fixed value, which is a application.
function of t h e fusible element material and
geometry. 3.12 Marking of Spare Fuses and Parts. If
Properly coordinating noncurrent-limitingfuses several types and ratings of fuses are used in a
is basically a matter of keeping the minimum given location, spare fuse units should be suitably
melting curve of the upstream fuse above and to marked, coded, or indexed to show the mount-
the right of the total clearing curve of any down- ings, circuits, or equipment with which they are to
stream noncurrent-limiting fuse within the range be used, thus minimizing the possibility of im-
of fault currents available at the downstream proper application.
fuse. To allow for variables such as preloading
and ambient temperature variations there are
two commonly used techniques. One is to allow a
10%safety margin in current for any value of time. 4. Operation
The other utilizes a 25% margin in time for any
value of current. Coordination involving current- 4.1 Operating Speed. Any of the devices that
limiting fuses is dependent upon the type(s) of are used to disconnect or close an energized cir-
current-limiting fuse(s) under consideration. cuit should be operated in a rapid, positive
There are two basic types of current-limiting manner since the success of this function may be
fuses: general purpose and b a ~ k u p When .~ a dependent upon the use of proper procedure and
general purpose fuse is used, the coordination technique as established by the manufacturer.
can be done in a similar fashion as for noncurrent-
limiting fuses. 4.2 Locking or Latching of Fuses, Blades, or
However, for melting and clearing times, less Links in Closed Position. Special care should be
than 0.01 s, minimum melting12t and clearing 12t taken to see that the fuse, blade, or link is securely
data should be compared to be certain that the locked, latched, or held fast in the closed position
desired coordination has been achieved. as recommended by the manufacturer. The fuse
carrier assembly of distribution oil fuse cutouts or
( 1) When a backup current-limitingfuse is used, another other devices applied in sealed enclosures should
protective device must clear all currents below the specified be locked and sealed; therefore, the sealing gaskets
minimum interrupting current of the backup fuse. This is
accomplished by making certain that the crossover of the must be maintained in good condition for satis-
other protecting device's total clearing time-current curve factory operation.
occurs above the minimum interrupting current of the back-
up fuse, but below the maximum interrupting current of the
other protecting device. 4.3 Replacement of Fuses
(2) One method for coordinating backup fuses is referred 4.3.1 Fuses Subject to Partial Melting or
to as matched melt coordination and is used when the other Deterioration. There are fuse constructions that
protecting device is an expulsion fuse. With this method the
expulsion fuse always melts, providing isolation of the backup are subject to partial melting or damage by cur-
fuse after fault interruption. Coordination exists when the rent that is not of sufficient magnitude and time
expulsion fuse's melting 1 2 t is less than or equal to the melting to cause total melting of the fuse. For such fuses it
12t of the backup current-limiting fuse for all currents. To
ensure this condition, refer to manufacturers' recommen- is important that the following precautions be
dations. observed:

12
ANSI, IEEE
ENcI,osEr) SINGLE IWLE AIR SWITCHES, ETSE DISCOKXEC'I'ING SWITCHES, mr) ACCESSORIES C37 48- 1987

(1) In two- or three-phase applications it is de-energizing the circuit, the use of hearing pro-
advisable to replace the fuse units (or fuse links) tectors should be considered.
in all phases when the fuses in one or more 4.3.5 Replacing of Nonvented Fuses of the
phases are found to have blown unless Current-Limiting Type. Current-limiting fuses
(a) The manufacturer's instructions are fol- are inherently fragile because of the multiplicity
lowed for determining t h e suitability of t h e of slender fusible elements surrounded by very
fuse(sj for continued service heavy dielectric material. Careless handling of
(b j There is proof that no damaging current these fuses may result in damage.
occurred in the remaining phase(sj When damage is suspected, the fuse should not
(2 j In applications where these fuses are used be installed.
in series with other fuses or interrupting devices
in the same phase in such a manner that their
melting or clearing curves cross one another, or 4.4 Operation of Energized Fuses
both, it is advisable after an operation to follow 4.4.1 When a fuse or fused equipment not pro-
carefully t h e manufacturer's instructions for vided with a load-break device is used to energize
determining the suitability of the fuses(sj for con- a circuit following fuse replacement, it should not
tinued service. be opened unless the fuse has blown or the circuit
4.3.2 Re-energizationAfter Fuses Have Oper- has been de-energized.
ated. It is advisable to locate and correct the 4.4.2 When a fuse or fused equipment with a
situation that caused the fuse to operate before load-break device is used to energize a circuit
re-energizing. The operator should be aware that following fuse replacement, it should not be
a potential hazard may exist if the circuit is re- reopened immediately. The time delay before
energized with the fault condition still present. reopening will vary considerably, depending upon
4.3.3 Replacing Fuses on Capacitor Installa- the continuous current rating of the fuse, but
tions. Fuses used on capacitors should not be should be adequate to allow the fuse to interrupt
removed or replaced by hand unless due precau- any existing fault current that might exceed the
tions are taken beforehand to discharge and load-break rating of the device. For large-sized
ground the capacitors. fuse links above 100 a, this time delay could be as
Capacitors used in power applications have a long as 10 min.
discharge resistor to reduce the voltage to a speci-
fied value in a specified time after being dis-
connected.
4.5 Open Fuse Holder. Outdoor fuses should
The internal discharge device provided in capac-
not be left hanging in the open position for an
itors should not be considered as a substitute for
extended period of time. If they are left hanging in
the recommended safety practice of manually
the open position they should be inspected to
discharging the residual stored charge before
ensure there is no water damage and that no
working on capacitors. Capacitors can be dam-
warpage has occurred prior to reclosing into the
aged if discharged too soon after de-energization.
circuit.
It is recommended that at least 5 min be allowed
for discharge through the discharge resistor
and then the capacitor terminals be connected
together and grounded. See ANSI/IEEE Std 18- 4.6 Use of Nonexpendable Cap on Expendable
1980 [8] for complete information in regard to Cap Cutouts. Installation of nonexpendable cap
discharging of capacitor units. on an expendable cap cutout results in a reduc-
The entire capacitor bank should be discon- tion of the expendable cap cutout interrupting
nected and grounded while replacing the fuses capability.
unless the fuse link or its mounting, or both, can Refer to manufacturers' instructions as to the
be removed safely and completely from the circuit reduction in rating.
using hot line tools.
4.3.4 Replacing of Vented Fuses. When the
replacing of vented fuses must be done from 4.7 Storing Spare Fuse Units and Replaceable
within the venting area, the circuit should be de- Parts. Spare fuse units and replaceable parts of
energized during t h e replacement procedure. fuse units should be stored in such a manner that
When vented fuses, which are operable from out- they will not be damaged, and so that they will be
side their vented area, must be replaced without readily available when needed.

1:3
ANSI IEEE
C37.48-1987 IEEE GlIIDE FOR APPLICATION, OPERATION, AND MAINTENANCE OF HIGH VOLTAGE FTSES, DISTRIBLTION

5. Maintenance ( 5 ) If applicable to the equipment, the fuse


unit or fuse tube and renewable element should
5.1 Safety Precautions. Examination and main- be examined for corrosion of the fuse element or
tenance of equipment that is connected to an connecting conductors, excessive erosion of the
energized circuit should be done at a safe distance inside of fuse tubes, tracking and dirt on the out-
from any exposed energized parts of equipment side of the fuse tube, and improper assembly that
or conductors, or t h e circuit and equipment may prevent proper operation. Components show-
should be de-energized. In the case of equipment ing significant signs of deterioration should be
on capacitor installations, precautions should be replaced. Fuse tubes made of organic material
taken to discharge the capacitors after de-energi- may be refinished according to manufacturer’s
zation. Alternatively, live line techniques may be specifications.
employed if they are adequate to ensure safety to (6) Current-carrying parts, such as blades or
personnel. fuse links, should be examined for thermal dam-
age resulting from heavy short-circuit currents or
5.2 Inspection of Air Insulated Fused or Switch- overloads. Damaged fuse links and other parts
ing Devices. Equipment within the scope of this significantly deformed should be replaced.
guide usually consists of several parts, some cur- (7) The mechanical operation should be
rent carrying and some noncurrent carrying, all checked per manufacturer’s recommendations.
subject to atmospheric and other environmental
conditions. The equipment is also subject to the
5.2.1 Periodic Inspection of Fuse Links in
normal and abnormal operating conditions of the
Distribution Cutouts. Fuse links in distribution
system in which it is connected. The frequency
cutouts may require periodic replacement since
and completeness of inspection will necessarily be corrosion of the lower terminal of the fuse link
a function of the service reliability required and (generally a flexible cable) at the lower open-end
the conditions at the specific equipment location
of the fuse holder may cause breakage or melting
and must be determined by the user. Some of the
at this point rather than at the current-responsive
items that should be considered are as follows:
element. Link-break cutouts are more susceptible
( 1 ) The equipment should be given a general
to this problem because of the mechanical strain
examination for obvious defects and to ensure
placed upon t h e fuse link by t h e link-break
t h a t bolts, nuts, washers, pins, and terminal
mechanism.
connectors are securely in place and in good
condition.
5.3 Inspection of Distribution Oil Fuse Cutouts.
(2) Insulators and other porcelain or plastic
In addition to items 5.2(1), (2), ( 3 ) , (6), and (7),
parts should be inspected for breaks, cracks,
the following items should be included:
burns, or contamination. Insulators and other
(1) Periodically, a sample of the insulating oil
insulating surfaces should be cleaned of any
should be taken and tested for dielectric break-
excessive contamination, such as salt deposits
down strength. Oil in cutouts that experience
and cement or road dust, to avoid flashover as a
regular load break or fuse interruptinq duty
result of the accumulation of foreign substances
should be tested on a more frequent basis.
on their surfaces. Cracked or broken insulators (2) The fuse carriers of nonvented distribution
and other insulating parts should be replaced. To
oil fuse cutouts generally incorporate insulating
prevent flashover, consideration should be given
materials that may be damaged dielectrically by
to replacing badly burned insulating parts. excessive exposure to moisture or humid atmos-
( 3 ) Current contact surfaces should be exam- phere. The cutout should be kept sealed or the
ined for pitting, burning, alignment, and to ensure components and oil suitably protected from the
that the contacts when closed are held together contaminating exposure.
with adequate pressure. Badly pitted, burned, or ( 3 ) The fuse elements of these cutouts are
distorted contacts should be replaced. Alignment generally not interchangeable and any substitu-
and spring pressure should be adjusted if re- tion for the manufacturer’s fuses may seriously
quired. affect the interrupting characteristics of the
(4) Vent holes on equipment so equipped device.
should be examined t o ensure they a r e not (4) The cutouts should be examined for any
plugged with dirt or other foreign substances, and evidence of oil leakage and the prescribed oil level
cleaned if necessary. must be maintained.

14
ANSIIIEEE
ENCLOSED SINGLE-POLE AIR SWITCHES, FI'SE DISCONNECTING SWITCHES, AND ACCESSORIES C37.48-1987

( 5 ) Moveable bearing gasket surfaces, yoke Because the fuse and its enclosure produce a
compression, and interlocking features should be system with interacting effects, and each compo-
checked for satisfactory operation. nent could be supplied by a different manufac-
turer, it is essential that sufficient data is made
available to permit proper application. Suitability
6. Application and Testing of of a specific application of the fuse in an enclo-
Current-Limiting Fuses in Enclosures sure shall be the responsibility of the supplier of
the fuse enclosure package (FEP).
6.1 General. Many applications require the use
NOTE: For Types (1) a n d (5) the FEP is the fuse itself; for
of current-limiting fuses in enclosures where the Types ( Z ) , (3), and (4), t h e FEP is t h e container a n d fuse
fuse and the associated contacts may be sub- combination.
jected to air temperatures above 40 "C. Other
applications may require the fuse to be immersed 6.2 Tests in Enclosures. The tests specified shall
in a liquid such as transformer oil. Current- be performed with the current-limiting fuse or
limiting fuses intended for such service shall FEP mounted in a manner that will simulate the
comply with the applicable design tests specified service conditions specified by the supplier of the
in this section and in accordance with ANSI/IEEE FEP.
C37.41-1981 [4]and ANSI/IEEE C37.47-1981 [2].
When current-limiting fuses are applied in 6.3 Ambient Temperature. The FEP application
enclosures of any type, the performance charac- shall take into consideration any higher operating
teristics of the total system should be evaluated. temperatures caused by fuse confinement or ele-
The following test sections reflect this basic vated ambient temperatures. The five fuse appli-
requirement for system capability and require cation descriptions in 6.1 also define the ambient
tests of the total system. temperature to which reference is made. The
There are five types of fuse applications covered supplier of the FEP shall speclfy the maximum
by this guide: reference ambient temperature "C allowable,
Type (1). The fuse is mounted in a compart- preferably selected from the 20 series of preferred
ment so that relatively free air circulation exists. numbers (typically 56,63,71,80,90,100, 112,125,
Reference ambient temperature is the enclosure or 140).
air temperature Cfor example, live front pad-
mounted transformers and vaults). 6.4 Time-Current Characteristics (TCC) Shift.
Type (2). The fuse is inside a container that The modification of the the1 lnal environment for
has restricted airflow surrounding the fuse, but the fuse due to an enclosure, and the higher than
relatively free air circulation outside of the con- normal ambient temperatures of the FEP, will
tainer. Reference ambient temperature is that of cause some shift of the fuse TCC. The largest shift
the air outside the container cfw example, fuse occurs at the long time end.
inside a canister in a vault).
NOTE: Use of the general rule of thumb coordinating factor,
Type (3). The fuse is inside a container that that is maximum clearing time of the load side protective
has restricted airflow surrounding the fuse, but device should not exceed 75%of t h e minimum melt time of the
relatively free liquid flow outside of the container. source side device, generally provides sufficient allowance for
TCC shift in the 0.01- 1000 second region.
Reference ambient temperature is that of the
liquid outside the container cfor example, fuse 6.4.1 Derating Factors. Backup-type current-
inside a canister immersed in transformer oil). limiting fuses that are coordinated with other
Type (4). A combination of Types (2) and (3) fuses (or overload sensing devices) intended to
where the container is partially in air and par- operate at low overload currents require no de-
tially in liquid. The reference ambient tempera- rating factors.
ture is that of the liquid outside the container cfw Backup current-limiting fuses t h a t trip an
example, fuse inside a transformer bushing). interrupter switch after the fuse element melts
Type (5). The fuse is directly immersed in may require a derating factor.
liquid, without the need for separate fuse enclo- Application of general-purpose current-limiting
sure, and with relatively free liquid circulating fuses in enclosures, subject to, or producing high
around the fuse. The reference ambient tempera- ambient temperatures will result in a reduction of
ture is that of the liquid surrounding the fuse cfw the current required to produce element melting.
example, oil-immersible fuse in transformer or Because the fuse and enclosure have interacting
switchgear oil). effects that determine the thermal environment

15
ANSI IEEE
C37.48-1987 IEEE GUIDE FOR APPLICATION, OPERATION, AND MAINTENANCE OF HIGH-VOLTAGE FUSES, DISTRIBLTION

of the fuse, the supplier of the FEP shall provide (2) The test current for t h e FEP using a
the long time minimum melting current for each backup-type fuse shall be the rated minimum
fuse size applied as described in 6.1. This current interrupting current of the fuse.
will be determined at the reference ambient 6.5.4 Voltage Withstand. The FEP shall be
temperature of 25 "C f 5 "C. Any derating factor allowed to cool naturally during the voltage with-
so determined will be due to the application of the stand period.
fuse in the container.
A second derating factor may be published by 6.6 Oil-Immersible Fuse. Oil-immersible fuses
the FEP supplier. This factor gives the percentage are designed for partial or total immersion in oil
reduction of the long time minimum melting cur- without the need for a separate fuse enclosure.
rent as related to the reference ambient tempera- These fuses a r e designed for use in various
ture above the standard 25 "C. When no specfic equipments, and the oil temperature to which the
derating factor is provided, the following derating fuse will be subjected will depend on the applica-
factors for the FEP long time minimum melt cur- tion. The specific test sections, therefore, do not
rent may be used as a guide. spec@ a maximum test temperature but utilize
Type (1) 0.4W"C of air temperature above the maximum reference ambient temperature
25 "C specified by the FEP supplier.
Type (2) 0.4%/"C of air temperature above
25 "C 6.7 Tests for Oil Tightness. The FEP test sam-
Type (3) 0.2%/OC of top oil temperature above ple (see 6.7.4) shall be subjected to the following
25 "C tests in the sequence listed (these tests apply to
Type (4) O.l%/"C of top oil temperature above any FEP that is used in an oil environment and
25 "C such as described in 6.1, Types (3), (4),and (5).
Type (5) 0.2%/"C of top oil temperature above 6.7.1 Cycling Test in Air. The FEP shall be
25 "C thermally cycled in air from -30 "C to the maxi-
mum reference ambient temperature as specified
6.5 Interrupting Tests by the FEP supplier. The rate of temperature
6.5.1 Test Practices. Interrupting tests shall change shall be controlled to prevent thermal
be performed in accordance with Test Series 2 shock. Each thermal cycle from one temperature
and 3 of ANSI/IEEE C37.41-1981 141, with the extreme to the other shall be accomplished in not
following exceptions and additions. more t h a n 8 h, with holding periods a t t h e
6.5.2 Reference Ambient Temperature. The temperature extremes of sufficient duration for
tests conducted on FEP Types (2), (3), or (4) in the temperature of the FEP to stabilize at the
accordance with this section shall be performed extreme temperature limits. The test series shall
with the FEP placed both in the reference ambient consist of ten thermal cycles over any convenient
temperature of 25 "C ! I15 "C and at the maximum time period.
reference ambient temperature specified by the 6.7.2 Cycling Test in Oil. The FEP shall be
FEP supplier. FEP Types (1) and (5) shall be thermally cycled in oil with current passed
tested at the maximum reference ambient temper- through the fuse for part of the cycle. The FEP
ature specified by the FEP supplier. Oil-immersible shall be immersed in oil, and the oil temperature
fuses may be tested in either air or oil. shall be raised from room temperature to the
In all cases the test specimen shall be stabilized maximum referenced ambient temperature spec-
at the reference ambient temperature before the fled by the FEP supplier in not more than 6 h. The
test current is applied to the fuse. rate of rise of oil temperature should not exceed
6.5.3 Test Current 0.5 %/min. When the oil temperature reaches the
Series 2: This series is the same as specified in maximum specified, the fuse rated current, or the
ANSI/IEEE C37.41-1981 [7],paragraph 6.1.2.3. maximum permissible continuous current as
Series 3: This series is the same as specified in specified by the FEP supplier shall be maintained
ANSI/IEEE C37.41-1981 [7), paragraph 6.1.2.3 through the fuse for a period of 2 h with the oil
except as follows: temperature held at or above this maximum.
(1) The test current for the FEP using a
NOTE: Current may be used as a supplemental heat source
general-purpose fuse shall cause fuse melting in during the heating cycle.
not less than one hour. For elevated reference
ambient temperature tests, this current shall be At the conclusion of the 2 h current period the
derated according to the FEP derating factors. oil shall be allowed to cool to ambient tempera-

16
ANSIVIEEE
ENCLOSED SINGLE-POLE AIR SWITCHES, FUSE DISCONNECTING SWITCHES, AND ACCESSORIES C37.48-1987

ture (25 "C f 5 "C [cold section of cycle]). The test positive pressure differential and the absence of
series shall consist of ten thermal cycles over any bubbles, while the FEP is submerged in oil (or
convenient time period. suitable equivalent liquid) over a 5 min period.
6.7.3 Alternate Tests. The requirements of Alternate but not necessarily equivalent test
6.7.1 and 6.7.2 may be met by a single test series methods may be one of the following two methods:
made according to 6.7.2 with the following excep- (1) The leak rate shall be measured using a
tions. The test FEP shall be cycled from -30 "C to helium detecting mass spectrometer. The maxi-
the maximum reference ambient temperature mum permissible leak rate, both before and after
specified by the FEP supplier in not more than exposure to the above specified test cycles, shall
8 h, with a holding period at -30 "C of sufficient be 1 times standard cc/s (one atmosphere
duration for the temperature of the fuse or FEP pressure dlfferential).
to stabilize. In addition, at the conclusion of the NOTE: See ASTM E-498-73 (R1980) (91.
2 h maximum temperature period the oil shall be
cooled to -30 "C in not more than 8 h. (2) The test FEP shall be carefully inspected
6.7.4 Test Samples. A total of five FEPs with for oil ingress using ultraviolet light, spectrogra-
the largest current rated fuse in each of the phys- phic analysis, or another equivalent positive oil-
ical fuse sizes manufactured shall be tested. The detecting technique and oil shall not be detected.
FEP shall be mounted or supported in the oil as All five FEP samples shall pass the test criteria.
specified by the FEP supplier. NOTE: The use of ultraviolet light or another technique for
detecting presence of oil inside the fuse will require further
6.7.5 Test Criteria. The criteria to be used in work to permit a quantizing of the test to provide a correlation
determining whether or not a particular FEP with expected long time service when submersed in trans-
former oil. The use of a fluorescent dye in the oil, plus compar-
design passes the test for oil tightness shall be ison with an unexposed fuse, are possible techniques, which
maintenance of a minimum of 14 lbf/in2 (psi) should be considered.

17
ANSIiIEEE
C37.48-1987

Appendix
(This Appendix is not a part of ANSUIEEE C37.48-1987 Guide for Application, Operation, and Maintenance of High-Voltage
Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories, but is included for information
only.)

Appendix A
Fault-Current Calculation

A l . Interrupting Duty current. For those fuses, multiplying factors must


be applied to the calculated fault currents before
To select the proper interrupting rating it is a comparison can be made with the fuse ratings.
necessary to calculate the maximum symmetrical The multiplying factors to be applied depend
fault current on the load side of the fuse and upon the system X l R ratio on the source side of
compare this value with the interrupting capabil- the fuse. Some representative X l R ratios for
ity of the fuse. Most power fuses, distribution application of fuses on systems are given in ANSI/
current-limiting fuses, and distribution cutouts IEEE C37.41-1981 (71, Section 6.
are now rated by the manufacturer,in terms of For specific applications, where the X l R values
symmetrical current. A direct comparison can be are known, multiplying factors can be obtained
made between the calculated values of fault cur- from Fig A l . Normally, the curve labeled rms
rent and the fuse rating. Many power fuses and multiplication factor will be used. Occasionally,
distribution cutouts of earlier manufacture (before the curve labeled peak multiplication factor is of
1970) were rated on the basis of asymmetrical interest during design testing of fuses.

Fig AI
Relation of X / R Ratio to Multiplication Factor
2%

27 I I

1 1.5 2 2.5 3 4 5 6 7 8 9 1 0 15 20 25 30 40 50 60 7 0 8 0 9 0 1 0 0
CIRCUIT X / R RATIO (TAN 6)

19
ANWIEEE
C37.48-1987

A2. Mechanical and Momentary Duty ing for over-excitation of generators, the rms
value of asymmetrical current as calculated for
zero time is approximately 1.8times the symmet-
For many purposes, it is necessary to know the rical fault current. However, as there will always
maximum possible rms current (including ac and be some decay even in the first half cycle, a multi-
dc components) that can flow in a circuit. M o w - plier of 1.55 is acceptable.

20

You might also like