Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

ANSUIEEE C37.

63-1984
(Reaffirmed 1974)
(Revision of ANSI
C37.63-1969)

.
A n American National Standard

IEEE Standard Requirements for Overhead,


Pad-Mounted, Dry-Vault, and Submersible
Automatic Line Sectionalizers for AC Systems

Sponsor
Switchgear Committee of the
IEEE Power Engineering Society

Secretariat
Institute of Electrical and Electronics Engineers, Inc
National Electrical Manufacturers Association

Approved May 29,1980


IEEE Standards Board

Approved September 30,1983


American National Standards Institute

0 Copyright 1984 by

The Institute of Electrical and Electroni s Engin-ers, Inc


345 East 47th Street, New York, NY 10017, USA

N o part of this publication may be reproduced in any form,


in an electronic retrieval system or otherwise,
without the prior written permission of the publisher.
IEEE Standards documents are developed within the Technical Com-
mittees of the IEEE Societies and the Standards Coordinating Commit-
tees of the IEEE Standards Board. Members of the committees serve
voluntarily and without compensation. They are not necessarily mem-
bers of the Institute. The standards developed within IEEE represent
a consensus of the broad expertise on the subject within the Institute
as well as those activities outside of IEEE which have expressed an in-
terest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways t o pro-
duce, test, measure, purchase, market, or provide other goods and ser-
vices related to the scope of the IEEE Standard. Furthermore, the view-
point expressed at the time a standard is approved and issued is subject
t o change brought about through developments in the state of the art
and comments received from users of the standard. Every IEEE Stan-
dard is subjected t o review a t least once every five years for revision
or reaffirmation. When a document is more than five years old, and has
not been reaffirmed, it is reasonable t o conclude that its contents,
although still of some value, do not wholly reflect the present state of
the art. Users are cautioned t o check t o determine that they have the
latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE. Sug-
gestions for changes in documents should be in the form of a proposed
change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean-
ing of portions of standards as they relate t o specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since
IEEE Standards represent a consensus of all concerned interests, it is
important to ensure that any interpretation has also received the con-
currence of a balance of interests. For this reason IEEE and the mem-
bers of its technical committees are not able t o provide an instant re-
sponse to interpretation requests except in those cases where the matter
has previously received formal consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, N Y 10017
USA
Foreword

(This Foreword is not a part of ANSI/IEEE C37.63-1984,IEEE Standard Requirements for Overhead,Pad-Mounted,
Dry-Vault, and Submersible Automatic Line Sectionalizers for AC Systems.)
This standard is a revised and updated version of ANSI C37.63-1969 (R 1974),which incorporates
significant improvements that reflect the present state of the art in sectionalizers. These improve-
ments include changes and additions in the following areas :
(1)Expansion of the standard to include pad-mounted and submersible sectionalizers;
(2) Inclusion of information for sectionalizers utilizing vacuum interrupters;
(3) New and expanded information related to interrupting tests, particularly for (a) cable charging
currents, (b) transformer magnetizing currents, and (c) load currents;
(4) The addition of surge withstand capability requirements for sectionalizer control elements;
(5) Expanded production test requirements.
Also included is the recognition of the need for partial discharge tests for some type of section-
alizers. While the procedure and related requirements have not yet been finalized (see 6.7), effort is
presently underway to develop this information, and it will be published after it has been completed
and has gone through the full approval process.
The preparation of ANSI C37.63-1984 was the cooperative work of the IEEE Switchgear Com-
mittee (Reclosers and Sectionalizer Subcommittee), the NEMA Switchgear Section (SG 13-Auto-
matic Circuit Reclosers Technical Committee), and the C37 Subcommittee on Automatic Circuit
Reclosers and Line Sectionalizers.
Upon recommendation of this latter subcommittee, the proposed American National Standard
was voted on by Standards Committee C37 on Power Switchgear and was subsequently approved as
an American National Standard.
The Standards Committee on Power Switchgear, C37, which reviewed and approved this standard,
had the following personnel at the time of approval :
C . L.Wagner, Chairman John D.Hopkins, Secretary
J. E. Beehler, Executive Vice-chairman of High-Voltage Switchgear Standards
W.E. Laubach, Executive Vice-chairman of Low-Voltage Switchgear Standards
S. H.Telander, Executive Vice-Chairman of IEC Activities
Organization Represented Name of Representative
Association of American Railroads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Association of Iron and Stee! Engineers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. M. Tillman
Electric Light and Power Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. E. Beehler
R. L. Capra
D. 0. Craghead
H. G. Frus
K. D. Hendrix
R. L. Lindsey ( A l t )
J. P. Markey
Institute of Electrical and Electronics Engineers ............................. H. W. Mikulecky
M. J. Beachy
G. Hanks
C. A. Mathews
R. A. McMaster
E. W. Schmunk
C. A. Schwalbe
G. W.Walsh
C.E. Zanzie
National Electrical Manufacturers Association .............................. C.A. Wilson
R. W.Dunham
T. L. Fromm
Tennessee Valley Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R. C.St. Clair
Testing Laboratory Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L. Frier
E . J. Huber
R. W.Seelbach ( A l t )
US Department of the Army Corps of Engineers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . John S.Robertson
US Department of the Interior, Bureau of Reclamation . . . . . . . . . . . . . . . . . . . . . . . . Edward M. Tomsic
us Department of Defense, Defense Communications Agency . . . . . . . . . . . . . . . . . . . .
US Department of the Navy, Naval Construction Batallion Center . . . . . . . . . . . . . . . . . R. L. Clark
Western Area Power Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G. D. Birney
At the time this standard was approved, the Reclosers and Sectionalizers Subcommittee of the
IEEE Switchgear Committee had the following membership :
P. C. Lyons, Chairman
M. J. Beachy G. Genest C. A. Popeck
G . W. Dolloff P. F. Johnson J. C. W. Ransom
R. Donnelly L. V. McCall D. R. Shapleigh
R. A. Few A. F. Parks R. Singer
G. B Fritz B. F. Wirtz

The NEMA Technical Committee on Automatic Circuit Reclosers, which prepared Tables 2 through
8 and approved this standard, had the following membership at the time of approval:
Robert A. Few, Chairman
D Akers R. L. Gasnier C. A. Popeck
R. E. Bennett David G. Kumbera Clarence L. Welter

The C37 Subcommittee on Automatic Circuit Reclosers and Line Sectionalizers, which approved
this standard, had the following membership a t the time of approval:
B. H. Schultz, Chairman
R. H. Arndt R. A. Few L. V. McCall
M. 3. Beachy P. F. Johnson R. H. Miller
R. Bergstrom D. G. Kumbera R. W. Nelson
H. L. Caldwell K. Lloyd N. L. Paulson
R. L. Capra P. C. Lyons 6. W. Schneider
G. W. Dolloff J. P. Markey B. F. Wirtz

When the IEEE Standards Board approved this standard on May 29, 1980, it had the following
membership:
Irvin N. Howell, Jr, Chairman Irving Kolodny, Vice Chairman
Ivan G . Easton, Secretary
G . Y. R Allen H. Mark Grove Donald T. Michael*
C. N Berglund Loering M Johnson F. Rosa
Edward Chelotti Joseph L Koepfinger B.A. Rowley
Edward J. Cohen W R. Kruesi Robert L. Simpson
Warren H Cook Neil T. Larsen W. E. Vannah
Len S. Corey Leon Levy Virginius N. Vaughan, Jr
R 0.Duncan J. E. May Art Wall
Jay Forster Robert E. Weiler
*Member emeritus
Contents

SECTION PAGE

1. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 . References ................................................................ 9
3. Serviceconditions .......................................................... 9
3.1 Usual Service Conditions ................................................. 9
3.2 Unusual Service Conditions ............................................... 9
3.2.1 Abnormal Ambient Temperatures ..................................... 9
3.2.2 Altitudes Above 3300 ft (1000 m) .................................... 9
3.2.3 Other Conditions That May Affect Design and Applications . . . . . . . . . . . . . . . . . 10
4 . Definitions ................................................................ 10
5. Rating ................................................................... 10
5.1 Rating Information .................................................... 10
5.2 Rated Maximum Voltage ................................................ 11
5.3 RatedFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.4 Rated Continuous Current ............................................... 11
5.4.1 Conditions of Continuous Current Rating .............................. 11
5.4.2 Limits of Observable Temperature Rise ............................... 11
5.4.2.1 Classification of Insulating Materials ........................... 11
5.5 Rated Minimum Actuating Current ........................................ 13
5.6 Rated Symmetrical Interrupting (Load Break) Current (Manual Operation Only) . . . . . 13
5.7 Rated Making Current .................................................. 13
5.8 Rated Momentary Current ............................................... 13
5.9 Rated 1s Current ...................................................... 13
5.10 Rated 1 0 s Current ..................................................... 13
5.11 Rated Impulse Withstand Voltage ......................................... 13
5.12 Overload Rating ....................................................... 13
5.13 Rated Control Voltage and Ranges ........................................ 14
5.14 Rated Cable Charging Interrupting Current (where applicable) ................... 1 4
6 . DesignTests ............................................................... 14
6.1 General ............................................................. 14
6.1.1 Condition of Device to be Tested ................................... 14
6.1.2 Mounting of Device .............................................. 14
6.1.3 Grounding Device ............................................... 14
6.1.4 Frequency ..................................................... 15
6.1.5 Control Voltage ................................................ 15
6.2 Insulation (Dielectric Tests) .............................................. 15
6.2.1 Withstand Test Voltages .......................................... 15
6.2.2 Electrical Connections ................................... ....... 15
6.2.3 Points of Application of Test Voltage ................................ 15
6.2.4 Temperature ................................................... 16
6.2.5 Dielectric Test Procedures and Voltage Measurements ................... 16
6.3 InterruptingTests ..................................................... 16
6.3.1 Load Break Interrupting Tests ..................................... 16
6.3.1.1 Test Conditions ......................................... 16
6.3.1.2 Test Procedure ......................................... 16
6.3.2 Cable Charging Current Interrupting Test ............................. 16
6.3.2.1 Test Conditions ......................................... 16
6.3.2.2 Test Procedure ......................................... 16
6.3.2.3 Performance. .......................................... 18
SECTION PAGE

6.3.3 Transformer Magnetizing Current Interruption Test ..................... 18


6.3.3.1 Test Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.3 5.2 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.3.3.3 Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.4 Standard Operating Duty Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.4.1 Operating Duty Tests for Load Interrupting Sectionalizers . . . . . . . . . . . . . . . . 19
6.4.2 Operating Duty Tests for Nonload Intempting Sectionalizers . . . . . . . . . . . . . 19
6.4.3 Operating performance ........................................... 19
6.4.4 Condition After Standard Operating Duty Tests ........................ 19
6.4.5 Interpretation of Standard Operating Duty Tests ....................... 19
6.5 Making and Momentary Current Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.6 Minimum Actuating Current Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.6.1 Test Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.6.2 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.7 Partial Discharge Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8 Radio Influence Voltage (RIV) Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.1 Test Voltages and Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.2 Test Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.2.1 Proximity of Other Apparatus ............................. 20
6.8.2.2 Oil-Filled Sectionalizers . . . . . . . . . . . . . . . . . . . . . . 1.. . . . . . . . . . . 20
6.8.2.3 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.2.4 Ambient Radio Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.2.5 Atmospheric Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.3 Test Equipment and Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.3.1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.8.3.2 Tests on Multipole Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.8.3.3 Tests on Assembled Apparatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.8.3.4 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.9 ShorbTime Current Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.9.1 Determination of 1 s and 1 0 s Currents ............................... 21
6.9.2 Condition After Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.10 Surge Current Test-Series Coil Sectionalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.10.1 Test Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.10.2 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.10.3 Condition After Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.11 TemperatureRiseTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.11.1 Test Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.11.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.11.3 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.1 1.3.1 Method of Temperature Determination ...................... 22
6.11.3.2 Value of Ambient Temperature During Test . . . . . . . . . . . . . . . . . . . 22
6.11.3.3 Determination of the Ambient Temperature . . . . . . . . . . . . . . . . . . . 22
6.11.3.3.1 Placing of Thermocouples ....................... 22
6.11.3.3.2 Use o f o i l c u p ................................ 22
6.12 Mechanical Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.12.1 Mechanical Duty Test ............................................ 23
6.12.2 Cold Temperature Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13 Control Elements Surge Withstand Capability Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13.1 Oscillatory Surge Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13.1.1 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13.2 Simulated Surge Arrester Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13.2.1 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.13.3 Condition of Control During and After Test . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
SECTION PAGE

7 . ProductionTests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1 Counting and Overcurrent Trip Calibration . . . . . . . . . . . . . . . .: . . . . . . . . . . . . . . . . . . 24
7.2 Control, Secondary Wiring, and Accessory Devices Check Tests . . . . . . . . . . . . . . . . . . . 24
7.3 Dielectric Withstand Test-1 min Dry Low Frequency ........................... 24
7.4 Mechanical Operation Tests . . . . . . . . . . . . . . . . . . . .--........................... 24
7.5 LeakTest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8. Construction Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 Tank Construction .....................................................
. ........ 25
25
8.2 Grounding Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.3 Insulating Medium Quantity Indicators (Submersible Sectionalizers). . . . . . . . . . . . . . . 25
8.4 Oil Sampling Provisions (Submersible Sectionalizers) ........................... 25
8.5 Manual Operating Provision .............................................. 25
8.5.1 Submersible or Dry-Vault Sectionalizer ............................... 25
8.5.2 Pad-Mounted Sectionalizers ........................................ 25
8.6 Position Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.7 Nameplate Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.8 Stored Energy Mechanism Charge Indicator .................................. 26
8.9 Safety Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.10 Separate Mounting of Control Apparatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.11 Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.12 Conductor Terminal Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.13 Vacuum Interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
FIGURES

Fig 1 Load Break Interrupting Test Circuits (a) Three-phase Circuit


(b) Single-phase Test Circuit .............................................. 17
Fig 2 Cable Charging Current Interrupting Test Circuit .............................. 17
Fig 3 Magnetizing Current Test Circuits (a) Test Circuit-Wye Connected
(b) Test Circuit-Delta Connected .......................................... 18
Fig 4 Surge Withstand Test Circuits-Control (a) Control Element with
Sectionalizer (b) Control Element with Transformer .......................... 23
TABLES

Table 1 Altitude Conection ................................................... 10


Table 2 Rated Maximum Voltage. Rated Impulse Withstand Voltage. Rated
Continuous Current. Rated Symmetrical Interrupting Current. and
Performance Characteristics of Automatic Line Sectionalizers . . . . . . . . . . . . . . . . . . 10
Table 3 Rated Continuous Current. Rated Minimum Actuating Current. Rated
Asymmetrical Making Current. Rated Momentary Current. Rated 1s
Current. and Rated 10 s Current of Automatic Line Sectionalizers . . . . . . . . . . . . . . . 1 2
. Table 4 Rated Control Voltages and Ranges for Sectionalizers ........................ 14
Table 5 Cable Charging Interrupting Current Ratings ................................ 14
Table 6 Test Voltages and Limits of Conducted Radio Influence Voltage ................ 20
Table 7 Size of Bare Copper Leads .............................................. 22
Table 8 Size of Aluminum Cable Leads .......................................... 22
A n American National Standard

IEEE Standard Requirements for Overhead,


Pad-Mounted, Dry-Vault,and Submersible
Automatic Line Sectionalizers for AC Systems

1. Scope for operation at their standard rating provided


This standard applies to all overhead, pad- that:
mounted, dry-vault, and submersible single- (1)The temperature of the cooling air (ambi-
or multi-pole alternating current automatic ent temperature) is not above 40 "C or below
line sectionalizers for rated maximum voltages -30 OC.
above 1000 V. (2)The altitude does not exceed 3300 f t
In order to simplify this standard where pos- (1000 m).
sible, the term sectionalizer has been substi- (3)For submersible units, the water head
tuted for automatic line sectionalizer. does not exceed 10 f t (3 m) above the base of
the enclosure during occasional submersion.
2. References Exposure to chemical or electrochemical reac-
[l]ANSI C37.85-1972 (R1978), American tions may be encountered in a subgrade envi-
National Standard Safety Requirements for X- ronmen t.
Radiation Limits for AC High-Voltage Power
Vacuum Interrupters Used in Power Switch-
gear.' 3.2 Unusual Service Conditions.
[ 21 ANSI/IEEE C37.09-1979,IEEE Standard 3.2.1 Abnormal Ambient Temperatures. Sec-
Test Procedure for AC High-Voltage Circuit tionalizers may be applied at higher or lower
Breakers Rated on a Symmetrical Current Basis. ambient temperatures than specified, but per-
[3]ANSI/IEEE C37.100-1981,IEEE Standard formance may be affected and special consid-
Definitions for Power Switchgear. eration shall be given to these applications.
[4]ANSI/IEEE Std 4-1978, IEEE Standard 3.2.2 Altitudes Above 3300 f t (1000m). Sec-
Techniques for High-Voltage Testing. tionalizers may be applied at altitudes higher
[ 51 ANSI/IEEE Std 386-1977,IEEE Standard than 3300 f t (1000 m). However, the basic
for Separable Insulated Connectors for Power impulse insulation level, rated maximum volt-
Distribution Systems Above 600 V. age, and rated continuous current shall be
[6]NEMA 107-1964 (R1981), Methods of multiplied individually by the correction fac-
Measurement of Radio Influence Voltage tors in Table 1,columns (3) and (4), to obtain
(RIV) of High-Voltage Apparatus.2 values at which the application may be made.
(The rated interrupting current, related required
3. Service Conditions capabilities, and rated interrupting time are not
3.1 Usual Service Conditions. Sectionalizers affected by altitude.)
conforming to this standard shall be suitable Sectionalizers designed for standard tempera-
ture rise may be used at normal current rating
'ANSI publications are available from the Salts without exceeding standard temperature limits
Department of American National Standards Institute, provided that the ambient temperature does
1430 Broadway, New York, NY 10018.
not exceed the ambient allowed in 2.1 multi-
*NEMA publications are available from the National
Electrical Manufacturers Association, 2101 L Street, plied by the factor shown in Table 1, column
NW, Washington, DC 20037. (5).

9
ANSI/IEEE
C31.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

Table 1 fumes or vapors, excessive or abrasive dust,


AI ti t u de Correct ion explosive mixtures of dust or gases, salt air,
extreme humidity
Correction Factor ( 5 ) For submersible sectionalizers: exposure
To Be Applied To t o tidal water, highly acidic water, water con-
Altitude
Voltage Current Ambient taining abnormal amounts of dissolved road
Feet Meters Rating Rating Temperature salt or fertilizer, continuous submersion, and
Col (1) Col ( 2 ) Col (3) Col (4) Col ( 5 ) stray direct currents.
3300 1000 1.00 1 .oo 1 .oo
4000 1200 0.98 0.99 0.99 4. Definitions
5000 1500 0.95 0.99 0.98
10000 3000 0.80 0.96 0.92 For definitions, refer t o ANSI/IEEE C37 .loo-
16000 4900 0.63 0.93 0.85
1981 [3].3
NOTE: Correction factors in Columns 4 and 5 shall not
be applied simultaneously.
5. Rating
3.2.3 Other Conditions That May Affect 5.1 Rating Information. The rating shall include
Design and Applications. Where other unusual the following:
conditions exist they should be brought to the (1)Rated maximum voltage
attention of those responsible for the manufac- (2) Rated frequency
ture of the equipment. Examples of such con- (3) Rated continuous current
ditions are: (4)Rated minimum actuating current
(1)Abnormal vibrations, shocks or tilting (5) Rated symmetrical interrupting (load
(2) Unusual transportation or storage con- break) current (where designed for this opera-
ditions tion)
( 3 ) Unusual operating duty, frequency of (6) Rated asymmetrical making current
operation, inadequate maintenance, special in- (where designed for this operation)
sulation requirements
( 4 ) For overhead, pad-mounted, and dry- J T h e numbers in brackets correspond to those of
vault sectionaliz er s : exposure t o damaging the references listed in Section 2.

Table 2
Rated Maximum Voltage, Rated Impulse Withstand Voltage, Rated Continuous Current,
Rated Symmetrical Interrupting Current, and Performance Characteristics
of Automatic Line Sectionalizers
-
Low -Frequency 60 Hz Current
Identification Insulation Level Ratings (amperes)t
Rated Withstand Tests*
Nominal Rated Impulse (kV rms) dc Symmetrical
Voltage Maximum Withstand 15 min Interrupting
Line Class Voltage Voltage 1 min 10 s Withstand (Load Break)
No (kV rms) (kV rms) (kV crest) Dry Wet (kV) Continuous (rms)
Col (1) Col ( 2 ) Col ( 3 ) Col ( 4 ) Col ( 5 ) Col ( 6 ) Col (7) Col (8) Col ( 9 )
Single-phase Sectionalizers
1 14.4 15.0 95 35 30 53 200 440
2 14.4 15.0 125 42 36 53 200 200
3 14.4 15.0 125 42 36 53 200 440
4 24.9 27.0 125 t 60 50 78 200 -
Three-phase Sectionalizers
5 14.4 15.5 110 50 45 53 200 440
6 14.4 15.5 110 50 45 53 400 880
1 14.4 15.5 110 50 45 53 600 1320
8 34.5 38.0 150 70 60 103 400 880

*These are performance characteristics specified as test requirements in this standard.


*On the basis of maximum continuous-current rating only. See Table 3 for complete data on current ratings for all
continuous-curren t ratings.

10
ANSUIEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

(7) Rated momentary current, asymmetrical Contacts,


Conducting Joints, Limit of
(8) Rated 1s current or Bushing Observable
(9) Rated 10 s current Terminals Hottest Spot Total
(10) Rated impulse withstand voltage When Clean Temperature Rise Temperature
(11) Rated control voltage (where applicable) And Bright ("C) ("C)
(12) Rated cable charging interrupting current Series coils with
over 220 class
(where designed for this application) insulation, or
bare N o Limit No Limit
5.2 Rated Maximum VoItage. The rated maxi-
Sectionalizer Con-
mum voltage of sectionalizers shall be the values tacts, Conducting
shown in Table 2, column (3). Joints and Other
Parts f l \
5.3 Rated Frequency. The rated frequency of Silver to Silver in
sectionalizers shall be 60 Hz. Air 65 105
Silver to Silver in
5.4 Rated Continuous Current. The rated con- -
Air Vacuum
Interrupter
tinuous currents of sectionalizers shall be the Studs/Clamps 85 125
values shown in Table 3, column (1). Silver t o Silver in
5.4.1 Conditions of Continuous Current Rat- 0il 50 90
Copper to Copper in
inp- Air 50 90
Sectionalizers are used under the usual
(I) Copper to Copper in
service conditions defined in 3.1. Oil 30 IO
Copper to Aluminum
(2) Current ratings shall be based on the in Air 50 90
total temperature limits of the materials used Copper t o Aluminum
for such parts. A temperature rise reference is in Oil 30 IO
(1)Contacts or other parts in other than oil or air may
given to permit testing at reduced ambien:. be operated a t other temperatures providing it can be
(3) Sectionalizers without enclosures shall shown by experience or tests that accelerated deterior-
have ratings based on a 40 O C ambient temper- ation will not occur.
ature. Sectionalizers installed in enclosures shall Oil 1 in (2.5 cm)
have their ratings based on the ventilation of Below Surface
(TODOil) 45 85
such enclosures and a 40 OC ambient tempera-
ture outside the enclosure. Terminal
Connections*
5.4.2 Limits of Observable Temperature Rise.
Silver t o Silver 65 105
At rated current, the observabIe hottest-spot Copper to Copper 50 90
temperature rise above ambient, and the maxi- Copper t o Aluminum 50 90
mum temperature of each of the various parts, *If connections are made t o cables, recognition must
be given to possible thermal limitations of cable and
shall not exceed the following temperatures: appropriate measures taken.

5.4.2.1 Classification of Insulating Mate-


Contacts,
Conducting Joints, Limit of rials. For the purpose of establishing tempera-
or Bushing 0bservable ture limits, insulating materials shall be classified
Terminals Hottest Spot Total as follows:
When Clean Temperature Rise Temperature
And Bright ("C) ("C) (1)Class 90 Insulation: Materials or combina-
Coils and Their tions of materials such as cotton, silk, and
Terminals paper without impregnation. Other materials or
Class 90 combinations of materials may be included in
Insulation 50 90
Class 105 this class if, by experience or accepted tests,
Insulation 65 105 they can be shown to be capable of operation
Class 130 at 90 O C .
Insulation 90 130
Class 155 (2) Class 105 Insulation: Materials or com-
Insulation 115 155 binations of materials such as cotton, silk, and
Class 180 paper when suitable impregnated or coated or
Insulation 140 180
Class 220 when immersed in a dielectric liquid such as
Insulation 180 220 oil. Other. materials or combinations of mate-

11
ANSUIEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

I I I I I I I I

I I I I I I I I

*,
e
E L

>oooooooo
b
>oooooooo
g m- f ~ ~ 0 l n 0 0 0 0 Ie -
.r

Hi *+e4m**m
Y
d
d
CI
C
e
a >oooooooo
L: >oooooooo
>*ooooooo
*hl*(Df-mmwb,

'01
0' E
rn

000000000
*(
0 0D
0o0m
0 o0o0
o0o0
ol
*+e4m**cr

000000000
000000000
(D*oomo1blnmm~
HN*W(D(DcDWW

12
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

rials may be included in this class if, by expen- themselves or in simple combinations. Experience or
test data, used in classifying insulating materials, are
ence or accepted tests, they can be shown t o be distinct from the experience or test data derived for the
capable of operation at 105 'C. use of materials in complete insulation systems. The
(3)Class 130 Insulation: Materials or com- thermal endurance of complete systems may be deter-
binations of materials such as mica, glass fiber, mined by test procedures specified by the responsible
technical committees. A material that is classified as
asbestos, etc, with suitable bonding substances. suitable for a given temperature in the preceding may
Other materials or combinations of materials, be found suitable for a different temperature, either
not necessarily inorganic, may be included in higher or lower, by an insulation system test procedure.
For example, it has been found that some materials
this class if, by experience or accepted tests, suitable for operation a t one temperature in air may be
they can be shown to be capable of Operation suitable for a higher temperature when used in a sys-
at 130 OC. tem operated in an enert gas atmosphere.
( 4 ) I t is important t o recognize that the other charac-
(4)Class 155 Insulation: Materials or com- teristics in addition to thermal endurance, such as
binations of materials such as mica, glass fiber, mechanical strength and moisture resistance, are
asbestos, etc, with suitable bonding substances. required in varying degrees in different applications
for the successful use of insulating materials.
Other materials or combinations of materials,
not necessarily inorganic, may be included in 5.5 Rated Minimum Actuating Current. The
this class if, by experience or accepted tests, rated minimum actuating current of sectionali-
they can be shown to be capable of operation zers shall be the values shown in Table 3,
at 155 OC. column (2).
(5)Class 180 Insulation: Materials or com- NOTE: The minimum actuating current is 1.6 times
binations of materials such as silicone elastomer, the continuous current rating.
mica, glass fiber, asbestos, etc, with suitable
bonding substances such as appropriate silicone 5.6 Rated Symmetrical Interrupting (Load
resins. Other materials or combinations of Break) Current (ManualOperation Only). The
materials may be included in this class if, by rated symmetrical interrupting (load break)
experience or accepted tests, they can be current of sectionalizers designed for this oper-
shown t o be capable of operation at 180 O C . ation shall be the values shown in Table 2,
(6)Class 220 Insulation: Materials or com- column (9).
binations of materials that by experience or 5.7 Rated Making Current. The rated making
accepted tests can be shown t o be capable of current of sectionalizers shall be the values
operation at 220 OC. shown in Table 3, columns (3),( 6 ) ,and (9).
(7) Over Class 220 Insulation: Insulation that
consists entirely of mica, porcelain, glass, 5.8 Rated Momentary Current. The rated
momentary current of sectionalizers shall be
quartz, and similar inorganic materials. Other
materials or combinations of materials may be the values shown in Table 3, columns (3),(6),
included in this class if, by experience or ac- and (9).
cepted tests, they can be shown to be capable 5.9 Rated 1 s Current. The rated 1 s current
of operation at temperatures over 220 OC. of sectionalizers shall be the values shown in
Table 3, columns (4), (7), and (10).
NOTES: (1)Insulation is considered to be impregnated
when a suitable substance provides a bond between 5.10 Rated 10 s Current. The rated 10 s cur-
components of the structure and also a degree of filling rent of sectionalizers shall be the values shown
or surface coverage sufficient to give adequate perform-
ance under the extremes of temperature, surface con- in Table 3,columns (5),( 8 ) ,and (11).
tamination (moisture, dirt, etc), and mechanical stress
expected in service. The impregnant must not flow or 5.11 Rated Impulse Withstand Voltage. The
deteriorate enough at operating temperature so as to rated impulse withstand voltage of sectionalizers
seriously affect performance in service.
(2) The electrical and mechanical properties of the shall be as given in Table 2, column (4), and
insulation must not be impaired by the prolonged ap- shall be negative or positive, depending upon
plication of the limiting insulation temperature per- which gives the lower insulation strength. The
mitted for the insulation class. The word impaired is
here used in the sense of causing any change that could voltage wave shall reach its crest value in 1.2 ps
disqualify the insulating material from continuously and decay to one-half of its crest value in 50 ps.
performing its intended function, whether it is creep-
age spacing, mechanical support, or dielectric barrier 5.12 Overload Rating. Sectionalizers have no
action.
(3) In the preceding definitions, the words accepted standard overload rating.
tests are intended to refer t o recognized test procedures NOTE: Sectionalizers are rated at the maximum rms
established for the thermal evaluation of materials by current they can carry continuously, and since they are

v
13
ANSI/IEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT.

designed to actuate and trip a t a current 1.6 times as here due to abnormal conditions such as abrupt changes
great, they may carry an overload for which they are in line loading. Such applications require specific
not self-protecting. Information as t o operation in this study, and the manufacturer should be consulted. Also,
region should be obtained from the manufacturer. applications of sectionalizers containing solid-state
control exposed continuously to control voltages ap-
5.13 Rated Control Voltage and Ranges. When proaching the upper limits of ranges specified herein
require specific attention and the manufacturer should
measured at the control power terminals of the be consulted before application is made.
operating mechanisms with the maximum oper- (6)Sectionalizers having self-contained dc control
ating current flowing, nominal voltages and sources shall operate over the range of 85% to 115% of
nominal voltage, and Table 4 shall not apply.
their permissible ranges for the control power
supply of sectionalizers shall be as shown in
5.14 Rated Cable Charging Interrupting Current
Table 4.
(where applicable). The cable charging inter-
rupting current ratings €or sectionalizers having
Table 4 this capability are as given in Table 5.
Rated Control Voltages and
Ranges for Sectionalizers
Table 5
Direct Current (1,4,5 ) Cable Charging Interrupting Current Ratings
Closing and
Nominal Auxiliary Tripping Cable Charging Current
Voltage Functions Functions Rated (rms Amperes)
Maximum
24 (2) - 14 - 28 (6) Line Voltage Pad Mounted and
48 (2) 38 - 56
100 - 140
-
28 56 (6)
70 - 140
(kV) Overhead Submersible
125
250 200 - 280 140 - 280 15.5 2 10
27.0 5 25
Alternating Current (3,4,5) 38.0 5 40

Nominal
Voltage Closing, Tripping, and
(60 Hz) Auxiliary Functions
6. Design Tests
Single Phase

120 104 - 127 (3)


240 208 - 254 (3) Sectionalizers shall be capable of meeting the
480 416 - 508 (3) design tests described in 6.2 through 6.13,
Polyphase
inclusive. Once made, the design tests need not
be repeated unless the design is changed so as
208Y/120 180Y/104 - 22OYl127 to modify the performance characteristics of
240 208 - 254 the sectionalizer.
480 416 - 508
480Yf277 416Yl240 - 508Yl292
6.1 General.
NOTES: (1) I t is recommended that the coils of clos- 6.1.1 Condition of Device to be Tested. The
ing, auxiliary, and tripping devices that are directly sectionalizer shall be new and in good condition,
connected continually to one dc potential should be
connected to the negative control bus so as to mini- and tests shall be applied before the device is
mize electrolytic deterioration. put into commercial use.
(2)Twenty-four-volt or forty-eight-volt tripping, 6.1.2 Mounting of Device. The sectionalizer
closing, and auxiliary functions are recommended only
when t h e device is located near the battery or where shall be mounted in a manner closely approxi-
special effort is made to ensure the adequacy of mating the normal service conditions for which
conductors between battery and control terminals. it is designed. If the sectionalizer normally
Twenty-four volts as the primary closing source is n o t
recommended. I t is suitable for operation of the requires control apparatus, the control appara-
auxiliary functions such as relays and contactors. tus shall be connected during the tests. The
(3)Include heater circuits. mounting bracket shall be attached to the sec-
(4)Relays, motors, or other auxiliary equipment
which functions as a part of the control for a device tionalizer during impulse tests.
shall be subject to the voltage limits imposed by this 6.1.3 Grounding of Device. All groundable
standard, whether mounted a t the device or a t a re- parts of the sectionalizer, and control apparatus
m o b location.
(5)Sectionalizers in some applications may be ex- where used, shall be grounded by a lead attached
posed to control voltages exceeding those specified to the grounding terminal and other ground-

14
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

able parts in a manner not to decrease the with- 1.414 times the rated low-frequency withstand
stand voltage. dry and wet test values given in Table 2,
6.1.4 Frequency. The frequency of the supply columns (5) and (6), with test durations of 60 s
voltage shall be 60 Hz 25%. A sine wave of for the dry test and 10 s for the wet test. Wet
acceptable commercial standards shall be tests shall be made in accordance with ANSI/
applied. IEEE Std 4-1978[ 41 . If bushing coordination
6.1.5 Control Voltage. The sectionalizer shall gaps are used, they shall be retained in place
perform satisfactorily over the full range of during tests and shall withstand these test
control voltages specified in 5.13. voltages. Wet tests shall not apply to section-
alizers utilizing submersible cables and termina-
6.2 Insulation (Dielectric Tests). Sectionalizers tions.
shall be capable of withstanding, without (3) On sectionalizers using submersible
damage to the sectionalizer and associated cable connectors a dc withstand test shall be
control apparatus, if any, the following test used in addition t o the low frequency with-
voltages when tested in accordance with 6.1 stand test in (2) above. When used the test
and as follows: voltage applied shall be the value given in
6.2.1 Withstand Test Voltages. Table 2, column (7).
(1)Impulse withstand test voltage shall be
a 1.2 X 50 ps voltage impulse, with a crest 6.2.2 Electrical Connections.
value as given in Table 2, column (4). At least (1)On overhead sectionalizers electrical
three positive and three negative impulses shall connections shall be made by means of bare
be applied to the test device. If flashover wire, inserted in each terminal. These bare
occurs on only one test during any group of wires shall project in such a manner as not to
three consecutive tests, three more tests shall decrease the withstand value. Any necessary
be made. If the sectionalizer successfully with- bends may be made at the terminals. The test
stands all three of the second group of tests, lead connections shall be made to the wires
the flashover in the first group shall be consid- projecting from the terminals.
ered a random flashover and the sectionalizer (2)On pad-mounted, submersible, and dry-
shall be considered as having successfully passed vault sectionalizers connections shall be made
the test. If an additional flashover occurs the through a cable termination similar to that for
sectionalizer shall be considered to have failed. which the sectionalizer was designed. If termi-
The following tolerances shall apply during nations capable of meeting the specified dielec-
these tests, unless otherwise specified. tric voltage are not available, other terminations
(a) Design Tests. Sectionalizers shall pass a (bushing or connectors, or both) may be substi-
full wave 1.2 X 50 ps voltage impulse with a tuted for the purpose of performing these tests.
virtual front time based on the rated full-wave 6.2.3 Points of Application of Test Voltage.
impulse voltage equal t o or less than 1.2 ps Tests 1, 2, and 3 shall be made on multipole
with a crest voltage equal to or exceeding the sectionalizers. Tests 1 and 2 shall be made on
crest value given in Table 2, column (4), and single-pole sectionalizers.
with a time to the 50% value of the crest Test 1. With the sectionalizer closed, and
voltage equal to or greater than 50 ps. with tanks and groundable parts grounded, the
(b) Conformance Tests. When impulse volt- test voltage shall be applied simultaneously to
age tests are required for conformance tests, all of the terminals on one side of the sectional-
sectionalizers shall be capable of passing a 1.2 izer.
X 50 ps full-wave impulse voltage test series Test 2. With the sectionalizer open, the test
with values as specified by the purchaser in voltage shall be applied simultaneously to the
accordance with the following: a virtual front terminals on one side of the sectionalizer. The
time, based on the rated full-wave impulse other terminals, tanks, and groundable parts
voltage, equal to or greater than 1.2 ps; a crest shall be grounded. Then, reverse connections
voltage not exceeding the rated full-wave and repeat procedure.
impulse withstand voltage: and a time to the Test 3. With the sectionalizer closed, the test
50% value of the crest voltage not exceeding voltage shall be applied to the middle phase of
50 ps. the sectionalizer. The terminals of the other
(2)Low-frequency withstand test voltages phases, all tanks and groundable parts, shall be
shall be applied with a crest value equal to grounded.

15
ANSI/IEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

6.2.4 Temperature. Dielectric tests shall be (3) With either terminal connected to the line
made at the temperature attained under the conductor unless the line and load terminals
conditions of commercial testing. are identified on the device.
6.2.5 Dielectric Test Procedures and Voltage 6.3.1.1 Test Conditions. The power factor
Measurements. The dielectric test procedures of the test circuit shall be equal t o or less than
and methods of voltage measurement shall be 70% lagging. The test circuit shall consist of
in accordance with ANSI/IEEE Std 4-1978 at least 10% series resistance and inductive re-
MI. actance having an X / R ratio of two or more,
with the remaining impedance consisting of
6.3 Interrupting Tests. The following test pro- parallel connected resistance and inductive
cedures shall be followed when testing sec- reactance, as shown in Fig l ( a ) or Fig l ( b ) .
tionalizers t o verify the capability to interrupt 6.3.1.2 Test Procedure. Power shall be
load current, cable charging current, and trans- applied to the sectionalizer in the closed posi-
former magnetizing current. tion. After the closing transient has subsided,
the sectionalizer shall be opened by means of
6.3.1 Load Break Interrupting Tests. If three- the manual operating handle, or by means of
phase tests are made, when testing sectionalizers the shunt-trip coil if the sectionalizer is so
intended for applications on multigrounded equipped.
wye system both the source and load neutrals Representative oscillographic records shall be
shall be grounded for one-fourth of the unit obtained of the device performance on each
operations specified in 6.4.1(3). Otherwise, for different test circuit.
three-phase tests, either the load neutral or the 6.3.2 Cable Charging Current Interrupting
supply shall be grounded, but not both. If Test. Sectionalizers which are rated for opera-
single-phase tests are made, a ground shall be tion on grounded wye cable circuits shall be
placed on the test circuit. When single-phase capable of interrupting the charging current of
testing is used for proof of three-phase per- unloaded lengths of single-phase shielded cable.
formance, the test voltage shall be 87% of the (Not a l l sectionalizers have this capability.) The
corresponding phase-to-phase voltage; opening purpose of this test is t o demonstrate the capa-
and closing speeds shall be maintained at levels bility of interrupting the capacitive switching
comparable t o those obtained during a corres- current rating of the sectionalizer.
ponding three-phase test. Consideration should 6.3.2.1 Test Conditions. The test circuit for
also be given to the possibility of flashover cable charging currents shall be as shown in Fig
between phases during actual three-phase 2. This circuit will simulate an unloaded shielded
operation where ionized gases can communi- cable with the shield grounded.
cate. This condition could be simulated on If it can be shown that there is no phase-to-
single-phase tests with the addition of tempo- phase interaction during three-phase operation,
rary ground screens or barriers. single-phase tests may be used to demonstrate
Sectionalizers, when designed t o break load, three-phase performance. If single-phase tests
shall be capable of nonautomatically (manually) are run, the tests shall be made at the phase-to-
interrupting all currents up to and including neutral voltage corresponding t o the rated maxi-
the rated interrupting currents, as shown in mum voltage, as shown in Table 2, column (3).
Table 2, column (9), when tested as specified Tests on single-phase sectionalizers shall be
in 6.1,6.4.1, and as follows: made at the phase-to-neutral voltage corres-
(1)At a test voltage such that the normal ponding t o the rated maximum voltage, as
frequency recovery voltage is at least shown in Table 2, column (3).
(a) for single-phase sectionalizers, the rated 6.3.2.2 Test Procedure. With the source
maximum voltage; terminal of the sectionalizer energized, the sec-
(b) for three-phase tests on three-phase sec- tionalizer shall be closed. After the closing
tionalizers, the rated maximum voltage; transient has subsided, the sectionalizer shall
(c) for single-phase tests to prove three- be opened by means of the manual operating
phase performance on three-phase sectional- handle, or by means of the shunt trip, if the
izers, 87% of the rated maximum voltage. sectionalizer is so equipped. A t least 20 ran-
(2)A t the minimum control voltage for which domly timed close-open operations shall be
a sectionalizer is designed. performed, if three-phase tests are run, and at

16
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

4 SECTIONALIZER

RP

I XP
I I

MAXIMUM "
r "
-

' 1
' I

NOTE: Neutral connections are to be


--
made as stated in 6 . 3 .

(a) Three-phase Test Circuit

r --
/'

--
L
(b) Single-phaseTest Circuit

Fig 1
Load Break Interrupting Test Circuits

SOURCE "Z" S U F F I C I E N T T O L I M I T F A U L T
CURRENT TO SYMMETRICAL MOMENTARY
R A T I N G O F S E C T I O N A L I Z E R SHOWN IN T A B L E 3 SECTIONALIZER
COLUMNS 3,6,& 9

MAXIMUM
VOLTAGE

-
Fig 2
Cable Charging Current Interrupting Test Circuit

17
ANSI/IEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

least 60 randomly timed close-open operations 6.3.3 Transformer Magnetizing Current Inter-
shall be performed if single-phase tests are run. ruption Test. Sectionalizers shall be capable of
6.3.2.3 Performance. Sectionalizer per- interrupting magnetizing currents equal to 3.591,
formance is acceptable if it successfully inter- (+0.5%) of the continuous current of the sec-
rupts the required capacitive currents. The tionalizer.
maximum transient overvoltage produced dur- 6.3.3.1 Test Conditions. The test circuit
ing the tests shall not exceed 2.5 times the for transformer magnetizing current interrup-
peak line-to-ground voltage, measured from the tion shall be as shown in Fig 3(a) or 3(b).
sectionalizer source and load terminals t o If it can be shown that there is no phase-to-
ground. phase interaction during three-phase operation,

Fig 3
Magnetizing Current Test Circuits
SECTION ALIZER
TANK
\
TRANSFORMER
-51 OR R E A C T O H ,

RATED
MAXIMUM
-1
--
-
-1-
NOTE 1

NOTE 1: Either the neutral of the load or the source -


-
is to be grounded, b u t not both.

(a) Test Circuit-Wye Connected

SECTIONALIZER
TANK -)-?,
OR

(b) Test Circuit-Delta Connected

18
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

single-phase tests may be used to demonstrate (4)Sufficient nonautomatic closing opera-


three-phase performance. If single-phase tests tions, t o obtain one operation with 90% asym-
are run, the tests shall be made at 87% of the metry. This test shall be made atrated maximum
rated maximum voltage, as shown in Table 2, voltage, with a circuit capable of a current
column (3). equal to the rated momentary current. For
Tests on single-phase sectionalizers shall be three-phase sectionalizers this test shall be
made at the rated maximum voltage of the made on a three-phase basis.
sectionalizer . ( 5 ) One nonautomatic opening operation at
6.3.3.2 Test Procedure. With the source rated maximum voltage interrupting the rated
terminal of the sectionalizer energized, the (load break) interrupting current specified in
sectionalizer shall be closed. After the closing 5.6. The power factor of the test circuit shall
transient has subsided, the sectionalizer shall be be as specified in 6.3.1.1.
opened by means of the manual operating 6.4.2 Operating Duty Tests for Nonload In-
handle, or by means of the shunt trip, if the terrupting Sectionalizers. For sectionalizers not
sectionalizer is so equipped. A t least 20 ran- designed t o i n t e m p t load current the standard
domly timed close-open operations shall be operating duty shall consist of:
performed, (1)Automatic operations as specified in
6.3.3.3 Performance. The performance of 6.4.1 (1)and (2)
the sectionalizer is acceptable if it successfully (2)Nonautomatic closing operations as speci-
interrupts the required magnetizing current. fied in 6.4.1 (4)
6.4 Standard Operating Duty Tests, The stan- 6.4.3 Operating Performance. Sectionalizers
dard operating duty shall consist of the follow- shall meet the automatic and nonautomatic
ing tests made without maintenance in the duties specified without emitting flame or oil.
order named on the same sectionalizer of the 6.4.4 Condition After Standard Operating
highest continuous current rating of a design. Duty Tests. A t the end of the standard operat-
These tests shall prove conformance with these ing duty tests the sectionalizer shall be in the
standards for all lower current ratings of this following condition:
design. (1)Mechanical. Substantially in the same
6.4.1 Operating Duty Tests for Load Inter- mechanical condition as at the beginning
rupting Sectionalizers. For sectionalizers de- except that the contacts may show some sign
signed to interrupt load current the standard of arc pitting.
operating duty shall consist o f (2) Electrical. Capable of withstanding rated
(1)Twenty automatic lockout operations at maximum voltage in the open position and of
rated maximum voltage and actuated by a cur- carrying rated continuous current at rated max-
rent whose symmetric value is equal t o the imum voltage but not necessarily without ex-
rated 1 s current. Five operations each at one- ceeding rated temperature rise in the closed
and two-shot lockout and ten at three-shot position.
lockout. 6.4.5 Interpretation of Standard Operating
(2) Eighty automatic lockout operations Duty Tests. After the series of operations
actuated by a current whose symmetric value is equivalent t o the standard operating duty, it is
equal to the rated 1 s current supplied from a not to be inferred that the sectionalizer can
low-voltage source. The shots t o lockout shall again meet its rating without being inspected,
be such as to give 50% three-shot lockout. The and if necessary, repaired.
remaining 50% may be divided between one-
and two-shot lockout. Tests shall show that the 6.5 Making and Momentary Current Tests. The
isolating time from current cessation to sec- test t o prove the capability to meet the rated
+
tionalizer contact parting does not exceed s. making and momentary current as given in 5.7
(3) Fifty nonautomatic operations at rated and 5.8 shall be requirement 6.4.1(4).
maximum voltage making and interrupting the The value of momentary current shall be de-
rated continuous current. A sufficient time termined from the envelope of the current
interval should be used between nonautomatic wave and shall be the rms value, including the
operations to prevent the formation of exces- direct-current component, if present, at the
sive pressures. The power factor of the test major peak of the maximum cycle. The test
circuit shall be as specified in 6.3.1.1. period shall extend for not less than 10 cycles.
U

19
ANSI/IEEE
~37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

Determine the magnitude of current in accord- its terminals undergoing test than three times
ance with ANSI/IEEE C37.09-1979 121. the longest overall dimension of the test piece
with a minimum allowable spacing of 3 f t (1m).
6.6 Minimum Actuating Current Tests. Section- Where space requirements under test condi-
alizers shall meet the rated minimum actuating tions do not permit the above clearances to be
current within the specified limits of +lo% maintained, the test shall be considered as satis-
when tested as specified in 6.1 and as follows. factory if the limits of radio influence voltage
6.6.1 Test Circuit. The sectionalizer shall be obtained axe equal t o or less than those speci-
connected to a low-voltage power source of fied in 6.8.1. In such cases a record should be
alternating current in series with a means for made of the object, structures, etc, and their
increasing the current and of delivering succes- distances from the sectionalizer under test;
sive current impulses to cause operation of the these data are to be keDt for future use.
counting mechanism.
6.8.2.2 Oil-Filled Sectionalizers. The tanks
6.6.2 Test Procedure. The sectionalizer, set of oil-filled sectionalizers shall be filled with
for one shot lockout, shall be subjected t o suf- the prescribed amount of oil.
ficient current impulses to verify that it does
not operate below 90% but does operate at 6.8.2.3 Electrical Connections. Conductors
110% of minimum actuating current. of the largest size intended for use with the
sectionalizer under test shall be connected to
6.7 Partial Discharge Tests. (This section is each terminal. The length of the conductors,
presently being studied by committees and will when used, shall be equal to or greater than
be published when available.) the longest overall dimension of the sectionali-
zer except that the length need not exceed 6 f t
6.8 Radio Influence Voltage (RIV) Tests. When (1.8m). The free end of any such conductor
the primary conductor insulation consists of shall terminate in a sphere having a diameter of
self-restoring dielectric such as porcelain, oil, or twice the diameter of the conductor +lo%or
gas (including air), the RIV test shall be made if shall be shielded in some other suitable manner
the partial discharge test is not made. Section- to eliminate the effect of the end of the con-
alizers shall meet the RIV limits when tested in ductor as a source of radio influence voltage.
accordance with 6.1 and as follows:
6.8.1 Test Voltages and Limits. The test volt- 6.8.2.4 Ambient Radio Noise. Tests may be
made under conditions prevailing at the time
ages and limits of conducted radio influence
voltage when tested at 1000 kHz shall be as . and place of test. However, it is recommended

specified in Table 6. that tests be avoided when the radio influence


voltage of the test equipment (including the
Table 6 influence voltage of irrelevant electrical de-
Test Voltages and Limits of Conducted vices) exceeds 50% of the radio influence volt-
Radio Influence Voltage age of the sectionalizer to be tested.
6.8.2.5 Atmospheric Conditions. Since the
Limit of Radio effects of humidity and air density upon radio
Rated Maximum 60 Hz Test Influence Voltage
Voltage kV Voltage kV Microvolts at 1.0 MHz influence voltage are not definitely known, no
correction factors are recommended for either
15.0 - 15.5 09.4 500 at the present time. However, it is recommended
27.0 16.4 650
38.0 23.0 650 that barometric pressure and dry and wet bulb
NOTE: ( 1 ) In the case of sectionalizers havingvoltage thermometer readings be recorded so that, if
ratings not covered by this table, the test shall be made suitable correction factors should be deter-
at 105% of the line to neutral voltage, based on the mined, they could be applied to previous
rated maximum voltage.
( 2 ) Sectionalizers having two or more voltage ratings measurements.
shall be treated on the basis of the highest voltage rat- 6.8.3 Test Equipment and Procedure. The
ing given on the nameplate. equipment and general method used in making
radio influence voltage tests shall be in accord-
6.8.2 Test Conditions. ance with the recommendations of NEMA
6.8.2.1 Proximity of Other Apparatus. No 107-1964 [ 6 ] .
other grounded or ungrounded object or struc- 6.8.3.1 Procedure. Tests shall be made with
ture (except mounting structure when required) the sectionalizer in the closed and open posi-
shall be nearer any part of the sectionalizer or tions.

20
ANWIEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

When tests are made with the sectionalizer in specified time. Single-phase tests are acceptable
the open position, the radio influence voltage for three-phase sectionalizers.
shall be determined with the pole or group of 6.9.2 Condition After Test. There shall be no
poles not connected to the measuring apparatus visible damage to the device after the tests have
both grounded and ungrounded. been completed. However, the tests may result
6.8.3.2 Tests on Multipole Devices. In the in some visual evidence of the device having
case of multipole sectionalizers, one pole or passed current, such as slight contact markings.
terminal or groups of the same may be tested When this occurs, rating shall be considered
at one time. met when the device will withstand repeated
6.8.3.3 Tests on Assembled Apparatus. In mechanical operations without cumulative
the case of assembled equipment, the test shall damage and is capable of carrying its rated con-
be made without removing any component tinuous current without exceeding the temper-
part, and the test voltage shall be determined ature limits specified for the device being
by the lowest rated voltage of any component tested.
part. The limiting radio influence voltage shall 6.10 Surge Current Test-Series Coil Sectional-
be identical with the highest value fixed for hers. A sectionalizer shall be capable of with-
any of the component parts that determine the standing two current surges of 65 000 A crest
test voltage. having a 5 X 10 ps waveshape.
6.8.3.4 Precautions. The following precau- 6.10.1 Test Conditions. If a coil bypass device
tions shall be observed when making radio in- is required, it shall be mounted in the sectional-
fluence tests: izer in the same manner as furnished for normal
(1)The sectionalizer should be at approxi- service. The leads from the high current impulse
mately the same temperature as the room in generator shall be connected to the terminals
which the tests are made. of the sectionalizer.
(2)The sectionalizer should be dry and clean. 6.10.2 Test Procedure. Two current surges of
(3) The sectionalizer should not have been the specified current value shall be applied.
subjected t o dielectric tests within 2 h prior to Following this test the sectionalizer shall be
the radio influence voltage tests. tested at the minimum actuating current so as
(4)In some cases it may be found that the to cause it t o go through one automatic opera-
radio influence voltage falls off after the 60 Hz tion to lockout.
voltage has been applied for a short time. In 6.10.3 Condition After Test. A t the end of
such cases, it may be desirable t o pre-excite the the test the sectionalizer and the coil bypass
sectionalizer at normal operating voltage for a device shall be in the following condition:
period not exceeding 5 min before proceeding
with the tests. (1)Mechanical. Substantially in the same
mechanical condition as at the beginning ex-
cept for minor arc scars on any gap electrodes
6.9 Short-Time Current Tests. Sectionalizers of the coil bypass device. There shall be no in-
shall carry the rated short-time currents as dication of external flashover of the coil bypass
given in Table 3,columns (4),(5),(7), and (8), device, from the terminals of the coil bypass
for one counting operation only. device t o any other parts of the sectionalizer or
6.9.1 Determination of 1 s and 10 s Currents. of the series coil of the sectionalizer.
The value of current may be determined by (2) Electrical. With the coil bypass connected
measurement of the steady-state current with in its normal operating position, the sectionali-
an ammeter where the circuit characteristics zer shall be capable of withstanding rated maxi-
are such that there is no decay in current value mum voltage in the open position and, in the
after the initial transient. Where the current in closed position, of functioning correctly on
the circuit continues to decay after the initial overcurrent to go through its counting cycle to
transient, measurement shall be made by means lockout at the minimum actuating current.
of an oscillograph. The device shall be consid-
ered to have been properly tested if the inte- 6.11 Temperature Rise Test. The sectionalizer
grated heating equivalent of the 1 s or 10 s shall meet the conditions of continuous current
rating has been obtained. A specific test voltage rating and limits of observable temperature rise
is not required; however, the voltage must be as specified in 5.4.1 and 5.4.2,respectively,
sufficient to maintain the test current for the when tested as specified in 6.1 and as follows:

21
ANSI/IEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

6.11.1 Test Conditions. The device shall be reading, the tests shall be continued. All tem-
mounted in a closed room substantially free perature determinations shall be made as
from air currents other than those generated by follows:
heat from the device being tested. 6.11.3.1 Method of Temperature Determin-
6.11.2 Electrical Connections. The sectionali- ation. This method consists of the determina-
zer shall have a bare conductor connected to tion of the temperature by thermocouples
each terminal having a minimum length of 4 f t applied t o the hottest part of the apparatus.
(1.2 m), specified for the sectionalizer being
tested, as given in Table 7 for sectionalizers 6.11.3.2 Value of Ambient Temperature
with bushings designed for connection to bare During Test.
conductors. The connection shall be made to (1)The ambient temperature shall be taken
the ends of these conductors. as that of surrounding air, which should not be
less than 10 O C nor more than 40 " C .
Table 7 (2) N o correction shall be applied for varia-
Size of Bare Copper Leads tions in ambient temperature within the range
specified in (1).
Rated (3) Temperature tests may be made at ambi-
Continuous ent temperatures outside the range specified, if
Current,
Amperes Size of Leads suitable and agreed upon correction factors are
available.
Up t o 50 AWG N o 6 solid
70-100 AWG No 210 stranded 6.11.3.3 Determination of the Ambient
140-200 AU'G N o 410 stranded Temperature .
280 250 000 cmil ( 1 2 5 mm2) 6.11.3.3.1 Placing of Thermocouples.
400 400 000 cmil ( 200 mm2)
560 600 000 cmil ( 300 mmz) The ambient temperature shall be determined
800 1 000 000 cmil ( 500 mm2) by taking the average of the readings of three
1120 2 000 000 cmil(1000 mm2l thermocouples (thermometers) placed 1 2 in
(30 cm) to one side of the device and vertically
located as follows:
For sectionalizers with separable cable con-
nection bushings, the connecting conductors (I)One thermocouple 1 2 in (30 cm) above
shall have a minimum length of 4 f t (1.2 m) the device
and shall be of aluminum with sizes as shown (2) One thermocouple 1 2 in (30 cm) below
in Table 8 (or equivalent). the device
(3) One thermocouple midway between the
Table 8 above two positions
Size of Aluminum Cable Leads
6.11.3.3.2 Use of Oil Cup. To avoid errors
Rated due to the time lag between the temperature of
Continuous apparatus and the variations in the ambient
Current,
Amperes Size of Leads temperature, all reasonable precautions shall be
taken t o reduce these variations and the errors
200 AWG No 4/0 stranded arising therefrom. Thus, when the ambient
560 1 000 000 cmil(500 mm2)
- temperature is subject to such variations that
error in taking the temperature rise might
6.11.3 Test Procedure. The rated continuous result, the thermocouple for determining the
current of a sectionalizer at rated frequency ambient temperature should be immersed in a
shall be applied continuously until the temper- suitable liquid (such as oil) in a suitable heavy
ature becomes constant. The temperature shall cup.
be considered constant when three consecutive A convenient form for such an oil cup con-
values of temperature rise taken at one-half- sists of a metal cylinder with a hole drilled
hour intervals at all points where readings are partly through it. This hole is filled with oil
being taken shows a maximum variation of one and the thermocouple is placed therein. The
degree. If the temperature rise after the second response of the thermocouple t o various rates
interval is equal to the established limits, and if of temperature change will depend largely
the temperature rise has increased since the last upon the size, kind of material, and the mass of

22
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

the containing cup and may be further regu- any other connected element external to the
lated by adjusting the amount of oil in the cup. control cabinet, and shall be applied between
The larger the apparatus under test, the larger each pair of terminals and between each terrni-
the metal cylinder employed as an oil cup in nal and ground. During these tests, the section-
the determination of the cooling temperature alizer and control elements shall be connected
should be. The smallest size of oil cup employed for normal operation and shall be energized at
in any case shall consist of a metal cylinder, 1 rated voltage.
in (2.5 cm) in diameter and 2 in (5 cm) high. 6.13.2 Simulated Surge Arrester Operation
Test. This test simulates a surge arrester opera-
6.12 Mechanical Operation Test. The sectional- tion and the resulting voltage changes that
izer shall meet the conditions of environment appear on the sectionalizer and control ele-
and mechanical duty when tested in accordance ments due to the rate of current change and
with 6.1 and as follows : the impedance of the ground connection.
6.12.1 Mechanical Duty Test. The sectionali- 6.13.2.1 Test Procedure. A gap connected
zers shall be subjected to 500 automatic lock- from one source bushing terminal to the sec-
out operations without maintenance. The tionalizer ground lead shall be used to simulate
interval between operations shall be the short- a surge arrester. See Fig 4(a). The gap shall be
est allowed by the reset time of the counting set to flashover at 80% ( 4 10%) of the rated
mechanism. impulse withstand voltage of the sectionalizer
6.12.2 Cold Temperature Test. A sectionali- on which the control element is to be applied.
zer shall be tested for proper operation and The surge voltage shall rise to flashover in
reset at the lowest temperature for which it is 1.2 ps (k0.5 11s). The external surge generator
designed. After the sectionalizer has come to a current limiting resistance shall be chosen in
steady temperature, it shall be operated as in order t o provide a surge current following the
6.6.1 with the control set for 1,2, and 3 shots gap flashover having a peak value of 7000 A
to lockout. Heater performance shall be veri- (+lo%).
fied during this test. The sectionalizer ground lead shall be 20 f t
(6 m) of AWG No 12 copper wire. The control
6.13 Control Elements Surge Withstand Capa- cable shall be of equal length and spaced
bility Tests. Control elements supplied with 6 inches from and run parallel to the sectional-
sectionalizers shall withstand, without damage, izer ground lead.
voltage surges originating in the low voltage
energy source, in the current or voltage trans- Fig 4
formers connected to the control elements, or
Surge Withstand Test Circuits-Control
both, or in the control leads connecting the
sectionalizer and the control elements. Either
of the tests described below may be used to
demonstrate this capability.
6.13.1 Oscillatory Surge Tests. The test wave
for this test shall be oscillatory, with a fre-
quency of 1.0 mHz to 1.5 mHz, a crest value of
2.5 kV t o 3.0 kV occurring in the first half cycle,
decaying to 10% of the crest value of the first
peak in not less than 6 ps. The source imped-
ance of the surge generator used to produce the CONTROL
test wave shall be 150 i2. CABLE

NOTES: (1) All voltage and time values refer to the


open circuit condition of the surge generator.
( 2 ) Time period and repetition rate have been chosen
to cover equipment which is used on 50 Hz as well an
GRouNDY
1 1
CONDUCTOR

60 Hz systems.

6.13.1.1 Test Procedure. The test wave shall


be applied to those control element terminals
used to connect the control elements to all in- -
strument transformers, sources of energy, and (a) Control Element with Sectionalizer

23
ANSI/IEEE
C37.63-1984 IEEE STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT,

Fig 4 (3) Dielectric withstand test-1 min dry low


Surge Withstand Test C i r c u i t d o n t r o l frequency
(4) Mechanical operation test
h (5) Leak test-submersible sectionalizersonly

7.1 Counting and Overcurrent Trip Calibration.


Sectionalizersshall be subjected to the following
calibration tests. Calibration may be performed
on the individual control element subassembly
prior to final assembly on the sectionalizer.
When the latter is done, the complete assembly
shall be tested to assure that the control ele-
CONDUCTORS I- ments will operate the sectionalizer. Sinusoidal
wave shape, 60 H current at a convenient volt-
CONDUCTOR age shall be used. The calibration may be per-
formed in any order deemed appropriate by
I I I the manufacturer.
(1)Minimum actuating currerit test (6.6)
(2)Automatic operation tests to assure proper
counting when set for 1,2,or 3 counts
(3) Remote features
(b) Control Element with Transformer (4) Special features

Fifteen positive and fifteen negative surges 7.2 Control, Secondary Wiring, and Accessory
shall be applied to the source bushing with the Devices Check Tests. Control, secondary wiring,
sectionalizer open. Fifteen positive and fifteen and accessory devices shall be checked t o en-
negative surges shall be applied t o the load sure all connections have been made correctly.
bushing with the sectionalizer closed. Devices and relays, if needed, shall be checked
The above tests shall also be applied to a by actual operation where feasible. Those cir-
properly rated transformer connected as shown cuits for which operation is not feasible shall
in Fig 4(b). Fifteen positive and fifteen nega. be checked for continuity.
tive surges shall be applied.
6.13.3 Condition of Control During and After
7.3 Dielectric Withstand Test-1 min Dry Low
Test. The control shall not cause the sectional-
Frequency. The test shall be conducted in
izer t o open or close during the application of
accordance with 6.2.1( 2). The duration of the
surges.
Following the tests, the sectionalizer and test may be 1 second if a voltage of 20% above
that specified in 6.2.1(2) is used.
control apparatus shall be capable of perform-
ing all of its normal functions without impair-
ment. 7.4 Mechanical Operation Tests.
(1)Inspection of the external parts.
(2) Manual tripping by the tripping lever.
(3) Sufficient consecutive operational tests
7. Production Tests without trouble or malfunction, to check per-
formance of the operating mechanism. These
All applicable production tests shall be made tests shall include electrical or manual closing
by the manufacturer on each sectionalizer or and tripping of the sectionalizer, or both, as
representative sample, at the factory after final applicable.
assembly. Production tests shall include the fol-
lowing: 7.5 Leak Test. A suitable leak test shall be per-
(1)Calibration formed on submersible sectionalizers t o ensure
(2) Control, secondary wiring, and accessory that these will operate under service conditions
device test as outlined in 3.1(3).

24
ANSI/IEEE
AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS C37.63-1984

8. Construction Requirements 8.4 Oil Sampling Provisions (Submersible Sec-


tionalizers). When oil is used as an insulating
8.1 Tank Construction. medium, provision shall be made to obtain a
8.1.1 The tank and all appurtenances shall be bottom oil sample.
made of corrosion-resistant material or provided
with an impact and corrosion-resistant finish 8.5 Manual Operating Provision. Sectionalizers
and should also be suitable for storage in un- shall be provided with a manual operating lever
covered areas, which is suitable for operation with a hot line
8.1.2 No external portion of the tank or ac- stick, or other suitable manual operating means.
cessories shall trap and hold water. 8.5.1 Submersible or Dry-Vault Sectionalizer.
8.1.3 Tank support rails shall extend entirely The operating handle on a submersible section-
across the bottom of the tank to increase pro- alizer shall be located such that one man stand-
tection and to provide a firm stable support. ing on the surface can operate it without
The support shall include provision for anchor- standing directly over the sectionalizer.
ing the tank, (Submersible or dry-vault section- 8.5.2 Pad-Mounted Sectionalizers. Pad-mount-
alizers only.) ed sectionalizers with draw-out provisions shall
8.1.4 Lifting lugs shall be provided and so include an interlock that requires manual trip-
positioned that the sectionalizer will remain ping of the sectionalizer before the primary
level when being lifted. They shall be designed connection can be disengaged.
and located on the tank to avoid interference
between lifting slings and any attachments 8.6 Position Indicator. Sectionalizers shall be
(bushings, operating handles, etc) and to avoid provided with a position indicator, or other
scratching or marring the tank finish during suitable means that clearly indicates its closed
handling. or open position, that shall be visible from the
8.1.5 Tank construction shall be such that surface. For pad mounted, submersible, or dry
leaks will not occur and the sectionalizer will vault sectionalizers viewing of the position indi-
remain mechanically operable at the maximum cator may require opening of the enclosure. If
operating pressure generated by the normal colors are used t o indicate an open or closed
operation of the sectionalizer, for example, position, red shall signify closed and green shall
temperature rise, load interrupting, and fault signify open, with the words open or closed in
closing. contrasting colors.
8.2 Grounding Provisions. A sectionalizer with 8.7 Nameplate Markings. The following mini-
a metal housing shall have provisions for the mum information shall be given on the name-
connection of a ground lead. plate:
The grounding connector shall accommodate (1)Manufacturer’s name or trademark.
a ground conductor of a size adequate to con- (2) Manufacturer’s type or identification
duct the rated 1 s current of the sectionalizer number to indicate the design or construction.
for a period of 3 s without damage to the con- Changes in operating characteristics, design, or
ductor or connector, construction, that affect its application or
Pad mounted, dry vault, and submersible service, shall be accompanied by a change in
sectionalizers shall have an additional ground- the identification data.
ing connection for each three-phase set of cable (3) Rated maximum voltage.
entrances. (4)Rated continuous current.
(5) Rated minimum actuating current.
8.3 Insulating Medium Quantity Indicators (6) Rated symmetrical interrupting current.
(Submersible Sectionalizers). Where liquid or (7) Rated impulse withstand voltage.
gas is used as the insulating medium, provision
shall be made for personnel to determine readily For submersible sectionalizers a nameplate of
the insulating liquid level or insulating gas pres- stainless steel or other corrosion-resistant
sure with the sectionalizer energized. Indicator material shall be provided. The nameplate shall
markings shall show the safe operating range of be securely attached to the top of the tank by
levels or pressures. Procedures or devices thht means of stainless steel screws, rivets, or other
require exposing the insulating medium t o the corrosion-resistant fasteners. All letters, sche-
outside environment shall not be used. matics, and numbers shall be permanently

\I 25
stamped, embossed, or engraved on the name- 8.11 Counters. If an operations counter is pro-
plate. vided, it shall indicate the total number of trip-
ping operations of the sectionalizer. The
8.8 Stored Energy Mechanism Charge Indicator. counter shall be visible with the sectionalizer
When indicators are used on stored energy in service.
operating mechanisms, the following colors
should be used: 8.12 Conductor Terminal Sizes. For connec-
(1)Yellow background with charged in black tion of bare conductors, bushing terminals shall
letters for charged mechanism. accommodate conductors of a size adequate to
(2) White background with discharged in conduct the rated continuous current of the
black letters for discharged mechanisms. sectionalizer without exceeding a temperature
rise shown in 5.4.2.
8.9 Safety Provisions. (This paragraph is being For submersible sectionalizers bushings shall
studied by committee and will be published accommodate cable terminations in accordance
when completed.) with ANSIIIEEE Std 386-1977 [ 51.
8.13 Vacuum Interrupters. Where vacuum in-
8.10 Separate Mounting of Control Apparatus. terrupters are used they shall be in accordance
Where applied, control apparatus shall be capa- with ANSI C37.85-1972 (R1978) [l]. X-radia-
ble of being mounted separately from the tion generated shall not exceed the value in
sectionalizer in normal service. Table 1of that standard.

26

You might also like