Professional Documents
Culture Documents
RXYSQ TV9, RXYSQ TY9, RXYSQ T8V, RXYSQ T8Y 4PEN482275 1B Installation and Operation Manual English 2
RXYSQ TV9, RXYSQ TY9, RXYSQ T8V, RXYSQ T8Y 4PEN482275 1B Installation and Operation Manual English 2
RXYSQ4T8VB(*)
RXYSQ5T8VB(*)
RXYSQ6T8VB(*)
RXYSQ4T8YB(*)
RXYSQ5T8YB(*) Installation and operation manual
English
RXYSQ6T8YB(*) VRV IV-S system air conditioner
(mm)
A~E HB HD HU
a b c d e eB eD
B — ≥100
eB
A, B, C — ≥100 ≥100 ≥100
E B, E — ≥100 ≥1000 ≤500
eD
A, B, C, E — ≥150 ≥150 ≥150 ≥1000 ≤500
e
D — ≥500
D, E — ≥1000 ≥1000 ≤500
C HU B, D — ≥100 ≥500
B
c b HB B, D, E HB<HD HB≤½HU ≥250 ≥750 ≥1000 ≤500
½HU<HB≤HU ≥250 ≥1000 ≥1000 ≤500
HB>HU
d 1
a HB>HD HD≤½HU ≥100 ≥1000 ≥1000 ≤500
D A
HD ½HU<HD≤HU ≥200 ≥1000 ≥1000 ≤500
HD>HU ≥200 ≥1700 ≥1000 ≤500
≥100 HB HU b (mm)
≥100 HB≤½HU b≥250
≥100 ½HU<HB≤HU b≥300
≥100 ≥100
HB HB>HU
≥2000 b
≥200 ≥100 ≥3000
≥1000 ≥100
HU ≥600
≥1500
A1 A2
≥100 ≥100
A2 A2
≥300
≥1000
B1 B2
≥100 ≥100
B2 B2
≥100 ≥100
≥300
≥1000
3
CE - DECLARATION-OF-CONFORMITY CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - IZJAVA-O-USKLAĐENOSTI CE - IZJAVA O SKLADNOSTI CE - ATITIKTIES-DEKLARACIJA
CE - KONFORMITÄTSERKLÄRUNG CE - DICHIARAZIONE-DI-CONFORMITA CE - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ CE - ILMOITUS-YHDENMUKAISUUDESTA CE - MEGFELELŐSÉGI-NYILATKOZAT CE - VASTAVUSDEKLARATSIOON CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - DECLARATION-DE-CONFORMITE CE - ΔHΛΩΣΗ ΣΥΜΜΟΡΦΩΣΗΣ CE - OVERENSSTEMMELSESERKLÆRING CE - PROHLÁŠENÍ-O-SHODĚ CE - DEKLARACJA-ZGODNOŚCI CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - VYHLÁSENIE-ZHODY
CE - CONFORMITEITSVERKLARING CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - DECLARAŢIE-DE-CONFORMITATE CE - UYGUNLUK-BEYANI
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions: 08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de 16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß acordo com as nossas instruções: 17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami:
unseren Anweisungen eingesetzt werden: 09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям: 18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: 10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser: instrucţiunile noastre:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze 11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att 19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
instructies: användning sker i överensstämmelse med våra instruktioner: 20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras 12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i 21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции:
instrucciones: henhold til våre instrukser: 22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni: 13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: 23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
07 είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται 14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům: 24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade s našim
σύμφωνα με τις οδηγίες μας: 15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama: návodom:
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
EN60335-2-40,
01 following the provisions of: 10 under iagttagelse af bestemmelserne i: 19 ob upoštevanju določb: 01 Directives, as amended. 10 Direktiver, med senere ændringer. 18 Directivelor, cu amendamentele respective.
02 gemäß den Vorschriften der: 11 enligt villkoren i: 20 vastavalt nõuetele: 02 Direktiven, gemäß Änderung. 11 Direktiv, med företagna ändringar. 19 Direktive z vsemi spremembami.
03 conformément aux stipulations des: 12 gitt i henhold til bestemmelsene i: 21 следвайки клаузите на: 03 Directives, telles que modifiées. 12 Direktiver, med foretatte endringer. 20 Direktiivid koos muudatustega.
04 overeenkomstig de bepalingen van: 13 noudattaen määräyksiä: 22 laikantis nuostatų, pateikiamų: Low Voltage 2014/35/EU 04 Richtlijnen, zoals geamendeerd. 13 Direktiivejä, sellaisina kuin ne ovat muutettuina. 21 Директиви, с техните изменения.
05 siguiendo las disposiciones de: 14 za dodržení ustanovení předpisu: 23 ievērojot prasības, kas noteiktas: Machinery 2006/42/EC ** 05 Directivas, según lo enmendado. 14 v platném znění. 22 Direktyvose su papildymais.
06 secondo le prescrizioni per: 15 prema odredbama: 24 održiavajúc ustanovenia: 06 Direttive, come da modifica. 15 Smjernice, kako je izmijenjeno. 23 Direktīvās un to papildinājumos.
07 με τήρηση των διατάξεων των: 16 követi a(z): 25 bunun koşullarına uygun olarak: Electromagnetic Compatibility 2014/30/EU * 07 Οδηγιών, όπως έχουν τροποποιηθεί. 16 irányelv(ek) és módosításaik rendelkezéseit. 24 Smernice, v platnom znení.
08 de acordo com o previsto em: 17 zgodnie z postanowieniami Dyrektyw: 08 Directivas, conforme alteração em. 17 z późniejszymi poprawkami. 25 Değiştirilmiş halleriyle Yönetmelikler.
09 в соответствии с положениями: 18 în urma prevederilor: 09 Директив со всеми поправками.
01 Note* as set out in <A> and judged positively by <B> 06 Nota* delineato nel <A> e giudicato positivamente da <B> 11 Information* enligt <A> och godkänts av <B> enligt 16 Megjegyzés* a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z) 21 Забележка* както е изложено в <A> и оценено положително от <B>
according to the Certificate <C>. secondo il Certificato <C>. Certifikatet <C>. <C> tanúsítvány szerint. съгласно Сертификата <C>.
02 Hinweis* wie in <A> aufgeführt und von <B> positiv 07 Σημείωση* όπως καθορίζεται στο <A> και κρίνεται θετικά 12 Merk* som det fremkommer i <A> og gjennom positiv 17 Uwaga* zgodnie z dokumentacją <A>, pozytywną 22 Pastaba* kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal
beurteilt gemäß Zertifikat <C>. από το <B> σύμφωνα με το Πιστοποιητικό <C>. bedømmelse av <B> ifølge Sertifikat <C>. opinią <B> i Świadectwem <C>. Sertifikatą <C>.
03 Remarque* tel que défini dans <A> et évalué positivement par <B> 08 Nota* tal como estabelecido em <A> e com o parecer positivo 13 Huom* jotka on esitetty asiakirjassa <A> ja jotka <B> 18 Notă* aşa cum este stabilit în <A> şi apreciat pozitiv de <B> 23 Piezīmes* kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam <A> DAIKIN.TCF.030A29/04-2017
conformément au Certificat <C>. de <B> de acordo com o Certificado <C>. on hyväksynyt Sertifikaatin <C> mukaisesti. în conformitate cu Certificatul <C>. saskaņā ar sertifikātu <C>.
04 Bemerk* zoals vermeld in <A> en positief beoordeeld door <B> 09 Примечание* как указано в <A> и в соответствии с положительным 14 Poznámka* jak bylo uvedeno v <A> a pozitivně zjištěno 19 Opomba* kot je določeno v <A> in odobreno s strani <B> 24 Poznámka* ako bolo uvedené v <A> a pozitívne zistené <B> v súlade <B> TÜV (NB1856)
overeenkomstig Certificaat <C>. решением <B> согласно Свидетельству <C>. <B> v souladu s osvědčením <C>. v skladu s certifikatom <C>. s osvedčením <C>.
05 Nota* como se establece en <A> y es valorado 10 Bemærk* som anført i <A> og positivt vurderet af <B> i henhold til 15 Napomena* kako je izloženo u <A> i pozitivno ocijenjeno od strane 20 Märkus* nagu on näidatud dokumendis <A> ja heaks kiidetud 25 Not* <A>’da belirtildiği gibi ve <C> Sertifikasına göre <B> <C> 12080901.T30
positivamente por <B> de acuerdo con el Certifikat <C>. <B> prema Certifikatu <C>. <B> järgi vastavalt sertifikaadile <C>. tarafından olumlu olarak değerlendirildiği gibi.
Certificado <C>.
01** Daikin Europe N.V. is authorised to compile the Technical Construction File. 07** Η Daikin Europe N.V. είναι εξουσιοδοτημένη να συντάξει τον Τεχνικό φάκελο κατασκευής. 13** Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan. 19** Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
02** Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen. 08** A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico. 14** Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce. 20** Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
03** Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique. 09** Компания Daikin Europe N.V. уполномочена составить Комплект технической документации. 15** Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji. 21** Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
04** Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen. 10** Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata. 16** A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására. 22** Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
05** Daikin Europe N.V. está autorizado a compilar el Archivo de Construcción Técnica. 11** Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen. 17** Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej. 23** Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
06** Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruzione. 12** Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen. 18** Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie. 24** Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
25** Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir.
Shigeki Morita
Director
Ostend, 3rd of May 2017
3P397286-4E
Table of contents
8.2.13 Symptom: The units can give off odours...................... 14
Table of contents 8.2.14 Symptom: The outdoor unit fan does not spin ............. 14
8.2.15 Symptom: The display shows "88"............................... 14
8.2.16 Symptom: The compressor in the outdoor unit does
1 About the documentation 5 not stop after a short heating operation ....................... 15
1.1 About this document.................................................................. 5 8.2.17 Symptom: The inside of an outdoor unit is warm
even when the unit has stopped .................................. 15
2 Specific installer safety instructions 5 8.2.18 Symptom: Hot air can be felt when the indoor unit is
stopped ........................................................................ 15
9 Relocation 15
For the user 6
10 Disposal 15
3 User safety instructions 6
3.1 General...................................................................................... 7
3.2 Instructions for safe operation ................................................... 7 For the installer 15
4 About the system 8 11 About the box 15
4.1 System layout............................................................................ 9
11.1 About ............................................................................ 15
5 User interface 9 11.2 Outdoor unit................................................................................ 15
11.2.1 To remove the accessories from the outdoor unit........ 15
6 Operation 9
6.1 Operation range ........................................................................ 9 12 About the units and options 15
6.2 Operating the system ................................................................ 9 12.1 About the outdoor unit ................................................................ 15
6.2.1 About operating the system ........................................ 9 12.2 System layout............................................................................. 15
6.2.2 About cooling, heating, fan only, and automatic
operation ..................................................................... 9 13 Unit installation 16
6.2.3 About the heating operation........................................ 9 13.1 Preparing the installation site ..................................................... 16
6.2.4 To operate the system (WITHOUT cool/heat 13.1.1 Installation site requirements of the outdoor unit ......... 16
changeover remote control switch) ............................. 9 13.1.2 Additional installation site requirements of the
6.2.5 To operate the system (WITH cool/heat changeover outdoor unit in cold climates ........................................ 16
remote control switch)................................................. 10 13.2 Opening and closing the unit...................................................... 16
6.3 Using the dry program............................................................... 10 13.2.1 About opening the units ............................................... 16
6.3.1 About the dry program ................................................ 10 13.2.2 To open the outdoor unit.............................................. 16
6.3.2 To use the dry program (WITHOUT cool/heat 13.2.3 To close the outdoor unit ............................................. 16
changeover remote control switch) ............................. 10 13.3 Mounting the outdoor unit........................................................... 16
6.3.3 To use the dry program (WITH cool/heat changeover 13.3.1 About mounting the outdoor unit.................................. 16
remote control switch)................................................. 10 13.3.2 Precautions when mounting the outdoor unit............... 17
6.4 Adjusting the air flow direction................................................... 10 13.3.3 To provide the installation structure ............................. 17
6.4.1 About the air flow flap ................................................. 10 13.3.4 To install the outdoor unit............................................. 17
6.5 Setting the master user interface .............................................. 11 13.3.5 To provide drainage ..................................................... 17
6.5.1 About setting the master user interface ...................... 11 13.3.6 To prevent the outdoor unit from falling over ............... 17
6.5.2 To designate the master user interface (VRV DX)...... 11
6.5.3 To designate the master user interface (RA DX) ........ 11 14 Piping installation 18
14.1 Preparing refrigerant piping........................................................ 18
7 Maintenance and service 11 14.1.1 Refrigerant piping requirements................................... 18
7.1 About the refrigerant.................................................................. 12 14.1.2 Refrigerant piping material........................................... 18
7.2 After-sales service and warranty ............................................... 12 14.1.3 To select the piping size .............................................. 18
7.2.1 Warranty period .......................................................... 12 14.1.4 To select refrigerant branch kits................................... 19
7.2.2 Recommended maintenance and inspection.............. 12 14.2 Connecting the refrigerant piping ............................................... 19
14.2.1 About connecting the refrigerant piping ....................... 19
8 Troubleshooting 12
14.2.2 Precautions when connecting the refrigerant piping .... 19
8.1 Error codes: Overview............................................................... 13
14.2.3 Guidelines when connecting the refrigerant piping ...... 19
8.2 Symptoms that are NOT system malfunctions .......................... 13
14.2.4 Pipe bending guidelines............................................... 20
8.2.1 Symptom: The system does not operate .................... 13
14.2.5 To flare the pipe end .................................................... 20
8.2.2 Symptom: Cool/Heat cannot be changed over ........... 14
14.2.6 To braze the pipe end .................................................. 20
8.2.3 Symptom: Fan operation is possible, but cooling and
heating do not work..................................................... 14 14.2.7 Using the stop valve and service port .......................... 20
8.2.4 Symptom: The fan speed does not correspond to the 14.2.8 To connect the refrigerant piping to the outdoor unit ... 21
setting ......................................................................... 14 14.2.9 To connect the refrigerant branching kit ...................... 22
8.2.5 Symptom: The fan direction does not correspond to 14.3 Checking the refrigerant piping .................................................. 22
the setting ................................................................... 14 14.3.1 About checking the refrigerant piping .......................... 22
8.2.6 Symptom: White mist comes out of a unit (Indoor 14.3.2 Checking refrigerant piping: General guidelines .......... 23
unit) ............................................................................. 14 14.3.3 Checking refrigerant piping: Setup............................... 23
8.2.7 Symptom: White mist comes out of a unit (Indoor 14.3.4 To perform a leak test .................................................. 23
unit, outdoor unit) ........................................................ 14 14.3.5 To perform vacuum drying ........................................... 23
8.2.8 Symptom: The user interface reads "U4" or "U5" and 14.3.6 To insulate the refrigerant piping ................................. 24
stops, but then restarts after a few minutes ................ 14
14.4 Charging refrigerant ................................................................... 24
8.2.9 Symptom: Noise of air conditioners (Indoor unit)........ 14
14.4.1 Precautions when charging refrigerant ........................ 24
8.2.10 Symptom: Noise of air conditioners (Indoor unit,
14.4.2 To determine the additional refrigerant amount ........... 24
outdoor unit)................................................................ 14
14.4.3 To charge refrigerant ................................................... 24
8.2.11 Symptom: Noise of air conditioners (Outdoor unit) ..... 14
14.4.4 Error codes when charging refrigerant......................... 25
8.2.12 Symptom: Dust comes out of the unit ......................... 14
17 Commissioning 33
2 Specific installer safety
17.1 Precautions when commissioning ............................................. 33 instructions
17.2 Checklist before commissioning................................................ 33
Always observe the following safety instructions and regulations.
17.3 Checklist during commissioning ................................................ 34
17.3.1 About the test run........................................................ 34 WARNING
17.3.2 To perform a test run (7-LEDs display)....................... 34
Tear apart and throw away plastic packaging bags so that
17.3.3 Correcting after abnormal completion of the test run.. 34
nobody, especially children, can play with them. Possible
17.3.4 Operating the unit ....................................................... 34
risk: suffocation.
18 Hand-over to the user 34
CAUTION
19 Troubleshooting 34 Appliance not accessible to the general public, install it in a
19.1 Solving problems based on error codes.................................... 34 secured area, protected from easy access.
19.1.1 Error codes: Overview ................................................ 35
This unit, both indoor and outdoor, is suitable for
20 Technical data 36 installation in a commercial and light industrial
20.1 Service space: Outdoor unit ...................................................... 36 environment.
20.2 Piping diagram: Outdoor unit..................................................... 37
CAUTION
20.3 Wiring diagram: Outdoor unit .................................................... 37
Excessive refrigerant concentrations in a closed room can
21 Disposal 38 lead to oxygen deficiency.
1 About the documentation Do NOT leave the unit unattended when the service cover
is removed.
INFORMATION WARNING
This appliance is intended to be used by expert or trained Take sufficient precautions in case of refrigerant leakage. If
users in shops, in light industry and on farms, or for refrigerant gas leaks, ventilate the area immediately.
commercial use by lay persons. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
Documentation set can lead to oxygen deficiency.
This document is part of a documentation set. The complete set ▪ Toxic gas might be produced if refrigerant gas comes
consists of: into contact with fire.
▪ General safety precautions:
WARNING
▪ Safety instructions that you must read before installing
ALWAYS recover the refrigerant. Do NOT release them
▪ Format: Paper (in the box of the outdoor unit) directly into the environment. Use a vacuum pump to
▪ Outdoor unit installation and operation manual: evacuate the installation.
▪ Installation and operation instructions
▪ Format: Paper (in the box of the outdoor unit)
Any gas or oil remaining inside the stop valve may blow off WARNING
the spun piping.
ALWAYS use multicore cable for power supply cables.
If these instructions are NOT followed correctly it may
result in property damage or personal injury, which may be CAUTION
serious depending on the circumstances.
▪ When connecting the power supply: connect the earth
cable first, before making the current-carrying
WARNING
connections.
▪ When disconnecting the power supply: disconnect the
current-carrying cables first, before separating the earth
connection.
▪ The length of the conductors between the power supply
stress relief and the terminal block itself must be as
NEVER remove the spun piping by brazing. such that the current-carrying wires are tautened before
Any gas or oil remaining inside the stop valve may blow off the earth wire is in case the power supply is pulled
the spun piping. loose from the stress relief.
WARNING CAUTION
▪ ONLY use R410A as refrigerant. Other substances Do NOT perform the test operation while working on
may cause explosions and accidents. the indoor units.
▪ R410A contains fluorinated greenhouse gases. Its When performing the test operation, NOT only the outdoor
global warming potential (GWP) value is 2087.5. Do unit, but the connected indoor unit will operate as well.
NOT vent these gases into the atmosphere. Working on an indoor unit while performing a test operation
is dangerous.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses. CAUTION
CAUTION Do NOT insert fingers, rods or other objects into the air
inlet or outlet. Do NOT remove the fan guard. When the
Do NOT push or place redundant cable length in the unit.
fan is rotating at high speed, it will cause injury.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING WARNING
Never touch the air outlet or the Stop operation and shut off the
horizontal blades while the swing flap power if anything unusual occurs
is in operation. Fingers may become (burning smells etc.).
caught or the unit may break down. Leaving the unit running under such
CAUTION circumstances may cause breakage,
electric shock or fire. Contact your
Do NOT insert fingers, rods or other dealer.
objects into the air inlet or outlet. Do
NOT remove the fan guard. When the WARNING
fan is rotating at high speed, it will The refrigerant in the system is safe
cause injury. and normally does not leak. If the
CAUTION: Pay attention to the fan! refrigerant leaks in the room, contact
with a fire of a burner, a heater or a
It is dangerous to inspect the unit while cooker may result in a harmful gas.
the fan is running.
Turn off any combustible heating
Be sure to turn off the main switch devices, ventilate the room and contact
before executing any maintenance the dealer where you purchased the
task. unit.
CAUTION Do not use the system until a service
After a long use, check the unit stand person confirms that the portion where
and fitting for damage. If damaged, the the refrigerant leaks is repaired.
unit may fall and result in injury. CAUTION
WARNING NEVER expose little children, plants or
NEVER replace a fuse with a fuse of a animals directly to the airflow.
wrong ampere ratings or other wires
when a fuse blows out. Use of wire or
copper wire may cause the unit to 4 About the system
break down or cause a fire. The indoor unit part of this VRV heat pump system can be used for
heating/cooling applications. The type of indoor unit which can be
used depends on the outdoor units series.
WARNING
NOTICE
▪ Do NOT modify, disassemble,
Do NOT use the system for other purposes. In order to
remove, reinstall or repair the unit avoid any quality deterioration, do NOT use the unit for
yourself as incorrect dismantling or cooling precision instruments, food, plants, animals, or
works of art.
installation may cause an electric
shock or fire. Contact your dealer. NOTICE
leaks, make sure there are no naked A full overview of allowable combinations (for future
system extensions) is available in technical engineering
flames. The refrigerant itself is data and should be consulted. Contact your installer to
entirely safe, non-toxic and non- receive more information and professional advice.
combustible, but it will generate toxic INFORMATION
gas when it accidentally leaks into a ▪ Combination of VRV DX and RA DX indoor units is not
room where combustible air from fan allowed.
heaters, gas cookers, etc. is present. ▪ Combination of RA DX and AHU indoor units is not
allowed.
Always have qualified service
▪ Combination of RA DX and aircurtain indoor units is not
personnel confirm that the point of allowed.
leakage has been repaired or
corrected before resuming operation.
d d
6.2.2 About cooling, heating, fan only, and
g g
automatic operation
a VRV IV-S Heat pump outdoor unit
b Refrigerant piping ▪ Changeover cannot be made with a user interface whose display
c VRV direct expansion (DX) indoor unit
d User interface (dedicated depending on indoor unit type) shows "change-over under centralised control" (refer to
e BP box (required to connect Residential Air (RA) or Sky Air installation and operation manual of the user interface).
(SA) direct expansion (DX) indoor units)
f Residential Air (RA) direct expansion (DX) indoor units ▪ When the display "change-over under centralised control"
g User interface (wireless, dedicated depending on indoor flashes, refer to "About setting the master user interface" 4
[ 11].
unit type)
▪ The fan may keep on running for about 1 minute after the heating
operation stops.
▪ The air flow rate may adjust itself depending on the room
5 User interface temperature or the fan may stop immediately. This is not a
malfunction.
CAUTION
▪ NEVER touch the internal parts of the controller. 6.2.3 About the heating operation
▪ Do NOT remove the front panel. Some parts inside are It may take longer to reach the set temperature for general heating
dangerous to touch and appliance problems may operation than for cooling operation.
happen. For checking and adjusting the internal parts,
contact your dealer. The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.
This operation manual offers a non-exhaustive overview of the main
functions of the system. Defrost operation
Detailed information on required actions to achieve certain functions In heating operation, freezing of the outdoor unit's air cooled coil
can be found in the dedicated installation and operation manual of increases over time, restricting the energy transfer to the outdoor
the indoor unit. unit's coil. Heating capability decreases and the system needs to go
into defrost operation to be able to remove frost from the outdoor
Refer to the operation manual of the installed user interface. unit’s coil. During defrost operation the heating capacity on the
indoor unit side will temporarily drop until defrosting is completed.
After defrosting, the unit will regain its full heating capacity.
6 Operation The indoor unit will stop fan operation, the refrigerant cycle will
reverse and energy from inside the building will be used to defrost
the outdoor unit coil.
6.1 Operation range
The indoor unit will indicate defrost operation on the display .
Use the system in the following temperature and humidity ranges for
Hot start
safe and effective operation.
In order to prevent cold air from blowing out of an indoor unit at the
Cooling Heating
start of heating operation, the indoor fan is automatically stopped.
Outdoor –5~46°C DB –20~21°C DB The display of the user interface shows . It may take some
temperature time before the fan starts. This is not a malfunction.
–20~15.5°C WB
Indoor 21~32°C DB 15~27°C DB
temperature 6.2.4 To operate the system (WITHOUT cool/
14~25°C WB
heat changeover remote control switch)
Indoor humidity ≤80%(a)
(a)
1 Press the operation mode selector button on the user interface
To avoid condensation and water dripping out of the unit. If the
temperature or the humidity is beyond these conditions, safety
several times and select the operation mode of your choice.
devices may be put in action and the air conditioner may not Cooling operation
operate.
Heating operation
Above operation range is only valid in case direct expansion indoor Fan only operation
units are connected to the VRV system.
Special operation ranges are valid in case of using AHU. They can 2 Press the ON/OFF button on the user interface.
be found in the installation/operation manual of the dedicated unit. Result: The operation lamp lights up and the system starts
Latest information can be found in the technical engineering data. operating.
6.2.5 To operate the system (WITH cool/heat 6.3.2 To use the dry program (WITHOUT cool/
changeover remote control switch) heat changeover remote control switch)
Overview of the changeover remote control switch To start
a FAN ONLY/AIR CONDITIONING 1 Press the operation mode selector button on the user interface
SELECTOR SWITCH several times and select (program dry operation).
a
Set the switch to for fan only 2 Press the ON/OFF button of the user interface.
operation or to for heating or Result: The operation lamp lights up and the system starts
cooling operation. operating.
b COOL/HEAT CHANGEOVER SWITCH 3 Press the air flow direction adjust button (only for double-flow,
Set the switch to for cooling or to multi-flow, corner, ceiling-suspended and wall-mounted). Refer
b for heating to "6.4 Adjusting the air flow direction" 4
[ 10] for details.
To stop
4 Press the ON/OFF button on the user interface once again.
Note: In case a cool/heat changeover remote control switch is used, Result: The operation lamp goes out and the system stops
the position of DIP switch 1 (DS1-1) on the main PCB needs to be operating.
switched to the ON position.
NOTICE
To start
Do not turn off power immediately after the unit stops, but
1 Select operation mode with the cool/heat changeover switch as
wait for at least 5 minutes.
follows:
Cooling operation Heating operation Fan only operation
6.3.3 To use the dry program (WITH cool/heat
changeover remote control switch)
To start
1 Select cooling operation mode with the cool/heat changeover
remote control switch.
1 1 1
1 1
a WARNING
NEVER replace a fuse with a fuse of a wrong ampere
ratings or other wires when a fuse blows out. Use of wire
or copper wire may cause the unit to break down or cause
b c c e e a fire.
f f CAUTION
Do NOT insert fingers, rods or other objects into the air
d d g g inlet or outlet. Do NOT remove the fan guard. When the
a VRV IV-S Heat pump outdoor unit fan is rotating at high speed, it will cause injury.
b Refrigerant piping
c VRV direct expansion (DX) indoor unit CAUTION
d User interface (dedicated depending on indoor unit type)
e BP box (required to connect Residential Air (RA) or Sky Air After a long use, check the unit stand and fitting for
(SA) direct expansion (DX) indoor units) damage. If damaged, the unit may fall and result in injury.
f Residential Air (RA) direct expansion (DX) indoor units
g User interface (wireless, dedicated depending on indoor
unit type)
When the system is installed as shown in the figure above, it is
necessary to designate one of the user interfaces as the master user
interface.
NOTICE 8 Troubleshooting
Applicable legislation on fluorinated greenhouse gases
If one of the following malfunctions occur, take the measures shown
requires that the refrigerant charge of the unit is indicated
below and contact your dealer.
both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent WARNING
tonnes: GWP value of the refrigerant × total refrigerant Stop operation and shut off the power if anything
charge [in kg] / 1000 unusual occurs (burning smells etc.).
Please contact your installer for more information. Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
WARNING
The system MUST be repaired by a qualified service person.
The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire Malfunction Measure
of a burner, a heater or a cooker may result in a harmful If a safety device such as a fuse, a Turn OFF the main power
gas. breaker or an earth leakage breaker switch.
Turn off any combustible heating devices, ventilate the frequently actuates or the ON/OFF
room and contact the dealer where you purchased the unit. switch does NOT properly work.
Do not use the system until a service person confirms that If water leaks from the unit. Stop the operation.
the portion where the refrigerant leaks is repaired. The operation switch does NOT work Turn OFF the power
well. supply.
If the user interface display indicates the Notify your installer and
7.2 After-sales service and warranty unit number, the operation lamp flashes report the malfunction
and the malfunction code appears. code.
7.2.1 Warranty period
If the system does NOT operate properly except for the above
▪ This product includes a warranty card that was filled in by the mentioned cases and none of the above mentioned malfunctions is
dealer at the time of installation. The completed card has to be evident, investigate the system in accordance with the following
checked by the customer and stored carefully. procedures.
▪ If repairs to the product are necessary within the warranty period, Malfunction Measure
contact your dealer and keep the warranty card at hand. If the system does not ▪ Check if there is no power failure. Wait
operate at all. until power is restored. If power failure
7.2.2 Recommended maintenance and occurs during operation, the system
inspection automatically restarts immediately after
power is restored.
Since dust collects when using the unit for several years,
performance of the unit will deteriorate to some extent. As taking ▪ Check if no fuse has blown or breaker is
apart and cleaning interiors of units requires technical expertise and activated. Change the fuse or reset the
in order to ensure the best possible maintenance of your units, we breaker if necessary.
recommend to enter into a maintenance and inspection contract on If the system goes into ▪ Check if air inlet or outlet of outdoor or
top of normal maintenance activities. Our network of dealers has fan only operation, but indoor unit is not blocked by obstacles.
access to a permanent stock of essential components in order to as soon as it goes into Remove any obstacles and make sure
keep your unit in operation as long as possible. Contact your dealer heating or cooling the air can flow freely.
for more information. operation, the system
▪ Check if the user interface display shows
stops.
When asking your dealer for an intervention, always state: (time to clean the air filter). (Refer to
▪ The complete model name of the unit. "7 Maintenance and service" 4 [ 11] and
"Maintenance" in the indoor unit manual.)
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
▪ The system does not start immediately after the power supply is
turned on. Wait one minute until the micro computer is prepared 8.2.9 Symptom: Noise of air conditioners
for operation. (Indoor unit)
▪ A "zeen" sound is heard immediately after the power supply is
8.2.2 Symptom: Cool/Heat cannot be changed turned on. The electronic expansion valve inside an indoor unit
over starts working and makes the noise. Its volume will reduce in
about one minute.
▪ When the display shows (change-over under centralized
control), it shows that this is a slave user interface. ▪ A continuous low "shah" sound is heard when the system is in
cooling operation or at a stop. When the drain pump (optional
▪ When the cool/heat changeover remote control switch is installed accessories) is in operation, this noise is heard.
and the display shows (change-over under centralized
control), this is because cool/heat changeover is controlled by the ▪ A "pishi-pishi" squeaking sound is heard when the system stops
cool/ heat changeover remote control switch. Ask your dealer after heating operation. Expansion and contraction of plastic parts
where the remote control switch is installed. caused by temperature change make this noise.
▪ A low "sah", "choro-choro" sound is heard while the indoor unit is
8.2.3 Symptom: Fan operation is possible, but stopped. When another indoor unit is in operation, this noise is
cooling and heating do not work heard. In order to prevent oil and refrigerant from remaining in the
system, a small amount of refrigerant is kept flowing.
Immediately after the power is turned on. The micro computer is
getting ready to operate and is performing a communication check 8.2.10 Symptom: Noise of air conditioners
with all indoor units. Please wait 12 minutes maximally until this
(Indoor unit, outdoor unit)
process is finished.
▪ A continuous low hissing sound is heard when the system is in
8.2.4 Symptom: The fan speed does not cooling or defrost operation. This is the sound of refrigerant gas
correspond to the setting flowing through both indoor and outdoor units.
▪ A hissing sound which is heard at the start or immediately after
The fan speed does not change even if the fan speed adjustment
stopping operation or defrost operation. This is the noise of
button is pressed. During heating operation, when the room
refrigerant caused by flow stop or flow change.
temperature reaches the set temperature, the outdoor unit goes off
and the indoor unit changes to whisper fan speed. This is to prevent
cold air blowing directly on occupants of the room. The fan speed 8.2.11 Symptom: Noise of air conditioners
will not change even when another indoor unit is in heating (Outdoor unit)
operation, if the button is pressed.
When the tone of operating noise changes. This noise is caused by
the change of frequency.
8.2.5 Symptom: The fan direction does not
correspond to the setting 8.2.12 Symptom: Dust comes out of the unit
The fan direction does not correspond with the user interface When the unit is used for the first time in a long time. This is
display. The fan direction does not swing. This is because the unit is because dust has gotten into the unit.
being controlled by the micro computer.
b c c e e
f f
d d g g
e f g
1× 1× 1× a VRV IV-S Heat pump outdoor unit
b Refrigerant piping
c VRV direct expansion (DX) indoor unit
+
d User interface (dedicated depending on indoor unit type)
a General safety precautions e BP box (required to connect Residential Air (RA) or Sky Air
b Outdoor unit installation and operation manual (SA) direct expansion (DX) indoor units)
c Fluorinated greenhouse gases label f Residential Air (RA) direct expansion (DX) indoor units
d Multilingual fluorinated greenhouse gases label g User interface (wireless, dedicated depending on indoor
e Gas piping accessory 1 + copper gasket (only for unit type)
RXYSQ6)
f Gas piping accessory 2 (only for RXYSQ6)
g Gas piping accessory 3 (only for RXYSQ6)
Mind the spacing guidelines. See the "Technical data" chapter, and
DANGER: RISK OF BURNING/SCALDING
the figures on the inside of the front cover.
CAUTION
Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.
This unit is suitable for installation in a commercial and
light industrial environment.
45°~90°
13.1.2 Additional installation site requirements 3
of the outdoor unit in cold climates (4)
2
NOTICE
When operating the unit in heating in a low outdoor
ambient temperature with high humidity conditions, make 1×
sure to take precautions to keep the drain holes of the unit
free by using proper equipment.
In heating:
1
20
15.5
15
0
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
–5
–10
–15
–20
3
10 15 20 25 27 30
TAI (°C DB) 1
13.3.2 Precautions when mounting the outdoor 13.3.4 To install the outdoor unit
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
4× M12
13.3.3 To provide the installation structure
Prepare 4 sets of anchor bolts, nuts and washers (field supply) as
follows:
4× M12 NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150 mm under the outdoor unit.
0
35
62
0
(3
45
≥150 mm
-3
55
)
>150
a
(mm)
a Make sure not to cover the drain holes. Drain holes (dimensions in mm)
INFORMATION a a a
45 376 191
a Drain holes
2 A 2 A
B-1 B-2 D D
2 2 4 4
14 Piping installation
C-1 C-2 C-3 C-4 E E E E
14.1 Preparing refrigerant piping 3-1 3-2 3-3 3-4 5 5 5 5
1 Outdoor unit
14.1.1 Refrigerant piping requirements 2 Refrigerant branch kits
3-1~3-4 VRV DX indoor units
4 BP units
NOTICE
5 RA DX indoor units
Refrigerant R410A requires strict cautions for keeping the A Piping between outdoor unit and (first) refrigerant branch
system clean and dry. Foreign materials (including mineral kit
B-1 B-2 Piping between refrigerant branch kits
oils or moisture) should be prevented from getting mixed C-1~C-4 Piping between refrigerant branch kit and indoor unit
into the system. D Piping between refrigerant branch kit and BP unit
E Piping between BP unit and RA DX indoor unit
NOTICE In case the required pipe sizes (inch sizes) are not available, it is
The piping and other pressure-containing parts shall be also allowed to use other diameters (mm sizes), taken the following
suitable for refrigerant. Use phosphoric acid deoxidised into account:
seamless copper for refrigerant. ▪ Select the pipe size nearest to the required size.
▪ Foreign materials inside pipes (including oils for fabrication) must ▪ Use the suitable adapters for the change-over from inch to mm
be ≤30 mg/10 m. pipes (field supply).
▪ The additional refrigerant calculation has to be adjusted as
14.1.2 Refrigerant piping material mentioned in "To determine the additional refrigerant
▪ Piping material: Phosphoric acid deoxidised seamless copper. amount" 4
[ 24].
▪ Flare connections: Only use annealed material. A: Piping between outdoor unit and (first)
▪ Piping temper grade and thickness: refrigerant branch kit
Outer diameter Temper grade Thickness (t)(a) When the equivalent pipe length between outdoor unit and the
(Ø) furthest indoor unit is 90 m or more (b+d), the size of the main gas
6.4 mm (1/4") Annealed (O) ≥0.80 mm Ø pipe (b) must be increased (size-up). If the recommended gas pipe
t (size-up) is not available, you must use the standard size (which
9.5 mm (3/8")
might result in a small capacity decrease).
12.7 mm (1/2")
a e
15.9 mm (5/8") Annealed (O) ≥0.99 mm d
19.1 mm (3/4") Half hard (1/2H) ≥0.80 mm
(a)
Depending on the applicable legislation and the maximum b c
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
a Outdoor unit
b Main gas pipe (increase piping size if length b+d ≥ 90 m)
14.1.3 To select the piping size c First refrigerant branch kit
d Piping between indoor unit and first refrigerant branch kit
Determine the proper size using the following tables and reference e Furthest indoor unit
figure (only for indication).
INFORMATION
Outdoor unit Piping outer diameter size (mm)
▪ Combination of VRV DX and RA DX indoor units is not capacity type (HP) Gas pipe Liquid pipe
allowed.
Standard Size-up
▪ Combination of RA DX and AHU indoor units is not
4+5 15.9 19.1 9.5
allowed.
6 19.1 22.2
▪ Combination of RA DX and aircurtain indoor units is not
allowed.
Example: Downstream capacity for B-1 = capacity index of unit 3-1 14.2 Connecting the refrigerant piping
+ capacity index of unit 3-2
DANGER: RISK OF BURNING/SCALDING
C: Piping between refrigerant branch kit and
indoor unit
14.2.1 About connecting the refrigerant piping
Use the same diameters as the connections (liquid, gas) on the
indoor units. The diameters of the indoor units are as follows: Before connecting the refrigerant piping
Indoor unit capacity Piping outer diameter size (mm) Make sure the outdoor and indoor units are mounted.
index Gas pipe Liquid pipe Typical workflow
15~50 12.7 6.4
Connecting the refrigerant piping involves:
63~140 15.9 9.5
▪ Connecting the refrigerant piping to the outdoor unit
D: Piping between refrigerant branch kit and BP ▪ Connecting refrigerant branch kits
unit ▪ Connecting the refrigerant piping to the indoor units (see the
installation manual of the indoor units)
Total capacity index Piping outer diameter size (mm)
of connected indoor Gas pipe Liquid pipe ▪ Insulating the refrigerant piping
units ▪ Keeping in mind the guidelines for:
15~62 12.7 6.4
▪ Pipe bending
63~149 15.9 9.5
▪ Flaring pipe ends
150~182 19.1
▪ Brazing
E: Piping between BP unit and RA DX indoor unit ▪ Using the stop valves
a Torque wrench
b Spanner
CAUTION ▪ Set the nitrogen pressure to 20 kPa (0.2 bar) (just enough so it
can be felt on the skin) with a pressure-reducing valve.
▪ Incomplete flaring may cause refrigerant gas leakage.
a b c d e
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage. f f
1 Cut the pipe end with a pipe cutter.
a Refrigerant piping
2 Remove burrs with the cut surface facing down so that the b Part to be brazed
c Taping
chips do NOT enter the pipe.
d Manual valve
e Pressure-reducing valve
f Nitrogen
▪ Do NOT use anti-oxidants when brazing pipe joints.
Counterclockwise to open
Clockwise to close
Result: The valve is now open/closed.
b b b a b
▪ Remove the knockout hole (a) in the bottom plate or
cover plate by tapping on the attachment points with a
flat head screwdriver and a hammer.
To handle the service port ▪ Optionally, cut out the slits (b) with a metal saw.
▪ Always use a charge hose equipped with a valve depressor pin, NOTICE
since the service port is a Schrader type valve.
Precautions when making knockout holes:
▪ After handling the service port, make sure to tighten the service
▪ Avoid damaging the casing and underlying piping.
port cover securely. For the tightening torque, refer to the table
below. ▪ After making the knockout holes, we recommend to
remove the burrs and paint the edges and areas
▪ Check for refrigerant leaks after tightening the service port cover.
around the edges using repair paint to prevent rusting.
Tightening torques ▪ When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
Stop valve Tightening torque N•m (turn clockwise to close)
damage.
size (mm) Shaft
3 Do the following:
Valve body Hexagonal Cap (valve Service
wrench lid) port ▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.
Ø9.5 5.4~6.6 4 mm 13.5~16.5 11.5~13.9
Ø15.9 13.5~16.5 6 mm 22.5~27.5
c c
a
b c
d
a c
b
b c
A A
±30°
c c A
e
d e1 e f e1 a
B
f
A
a Horizontal surface
b Refnet joint mounted vertically
c Refnet joint mounted horizontally
Yes
Use procedure:
"Method 2: After power ON".
a
WARNING
It is very important that all refrigerant piping work is done before the
Provide adequate measures to prevent that the unit can be units (outdoor or indoor) are powered on. When the units are
used as a shelter by small animals. Small animals that powered on, the expansion valves will initialise. This means that the
make contact with electrical parts can cause malfunctions, valves will close.
smoke or fire.
NOTICE
NOTICE Leak test and vacuum drying of field piping and indoor
Make sure to open the stop valves after installing the units is impossible when field expansion valves are closed.
refrigerant piping and performing vacuum drying. Running
the system with the stop valves closed may break the Method 1: Before power ON
compressor. If the system has not yet been powered on, no special action is
required to perform the leak test and the vacuum drying.
14.2.9 To connect the refrigerant branching kit Method 2: After power ON
For installation of the refrigerant branching kit, refer to the installation If the system has already been powered on, activate setting [2‑21]
manual delivered with the kit. (refer to "To access mode 1 or 2" 4[ 29]). This setting will open field
expansion valves to guarantee a refrigerant piping pathway and
▪ Mount the refnet joint so that it branches either horizontally or
make it possible to perform the leak test and the vacuum drying.
vertically.
▪ Mount the refnet header so that it branches horizontally. DANGER: RISK OF ELECTROCUTION
NOTICE
Make sure that all indoor units connected to the outdoor
unit are powered on.
NOTICE
Wait to apply setting [2‑21] until the outdoor unit has
finished the initialisation.
14.3.2 Checking refrigerant piping: General To check for leaks: Pressure leak test
guidelines 1 Test for leaks by applying a bubble test solution to all piping
Connect the vacuum pump through a manifold to the service port of connections.
all stop valves to increase efficiency (refer to "Checking refrigerant 2 Discharge all nitrogen gas.
piping: Setup" 4
[ 23]).
3 Break the vacuum by pressurising with nitrogen gas to a
NOTICE minimum gauge pressure of 0.2 MPa (2 bar). Never set the
gauge pressure higher than the maximum operation pressure of
Use a 2-stage vacuum pump with a non-return valve or a
the unit, i.e. 4.0 MPa (40 bar).
solenoid valve that can evacuate to a gauge pressure of
–100.7 kPa (−1.007 bar)(5 Torr absolute). NOTICE
After finishing the leak test and vacuum drying, the piping must be Make sure all connected indoor units are recognised
insulated. Take into account the following points: (setting [1‑5]).
▪ Make sure to insulate the connection piping and refrigerant branch NOTICE
kits entirely.
Close the front panel before any refrigerant charge
▪ Be sure to insulate the liquid and gas piping (for all units). operation is executed. Without the front panel attached the
▪ Use heat resistant polyethylene foam which can withstand a unit cannot judge correctly whether it is operating properly
temperature of 70°C for liquid piping and polyethylene foam which or not.
can withstand a temperature of 120°C for gas piping.
NOTICE
▪ Reinforce the insulation on the refrigerant piping according to the
In case of maintenance and the system (outdoor unit+field
installation environment.
piping+indoor units) does not contain any refrigerant any
▪ If there is a possibility that condensation on the stop valve might more (e.g., after refrigerant reclaim operation), the unit has
drip down into the indoor unit through gaps in the insulation and to be charged with its original amount of refrigerant (refer
piping because the outdoor unit is located higher than the indoor to the nameplate on the unit) and the determined additional
unit, this must be prevented by sealing up the connections. See refrigerant amount.
below figure.
14.4.2 To determine the additional refrigerant
amount
INFORMATION
b For final charge adjustment in a test laboratory, contact
a your dealer.
INFORMATION
c
15 Electrical installation
DANGER: RISK OF ELECTROCUTION V Y
WARNING
F1/F2
ALWAYS use multicore cable for power supply cables. (16 V)
d
F1/F2
(16 V)
15.1 About electrical compliance e
a Main switch
Only for RXYSQ4~6_V b Earth connection
Equipment complying with EN/IEC 61000‑3‑12 (European/ c Power supply wiring (including earth) (shielded cable)
F1/F2 Transmission wiring (shielded cable)
International Technical Standard setting the limits for harmonic
V Outdoor unit (RXYSQ4~6_V)
currents produced by equipment connected to public low-voltage Y Outdoor unit (RXYSQ4~6_Y)
systems with input current >16 A and ≤75 A per phase.). d Indoor unit
e User interface
Transmission wiring
Transmission wiring specification and limits(a)
Vinyl cords with 0.75 to 1.25 mm² sheath or cables (2‑core wires) F1 F2 F1 F2 F1 F2
L N X1M L1 L2 L3 N X1M
NOTICE
Precautions when making knockout holes:
▪ Avoid damaging the casing and underlying piping.
▪ After making the knockout holes, we recommend to
X1M remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
X2M
▪ When passing electrical wiring through the knockout
a holes, wrap the wiring with protective tape to prevent
X2M a damage.
X1M
6 Reattach the service cover.
a 7 Connect an earth leakage circuit breaker and fuse to the power
a
supply line.
a Cable tie
b Attachment plate
X1M Power supply
X2M Transmission wiring
5 Route the wiring through the frame and connect it to it. a Liquid pipe
b Gas pipe
c Insulator
d Transmission wiring (F1/F2)
S1
B
B
S1
S1
B
7‑LEDs display
S1
[5
B
s]
The display gives feedback about the field settings, which are
defined as [Mode-Setting]=Value. b c
H1P Shows the mode
a Default situation (H1P OFF)
H2P~H7P Shows the settings and values, represented in binary code
b Mode 1 (H1P flashing)
H8P NOT used for field settings, but used during initialisation
c Mode 2 (H1P ON)
Example: BS1 Press BS1.
BS1 [5 s] Press BS1 for at least 5 s.
[H1P - 32 + 16 + 8 + 4 + 2 + 1]
Description
H1P H2P H3P H4P H5P H6P H7P INFORMATION
Default situation If you get confused in the middle of the process, press BS1
(H1P OFF) to return to the default situation.
Mode 1
(H1P flashing)
16.1.5 To use mode 1
Mode 2 In mode 1 (and in default situation) you can read out some
information.
(H1P ON)
Setting 8 Example: 7‑LEDs display – Default situation
0 + 0 + 8 + 0 + 0 + 0
(in mode 2) You can read out the status of low noise operation as follows:
(H2P~H7P = binary 8) # Action Button/display
Value 4 1 Make sure the LEDs are
0 + 0 + 0 + 4 + 0 + 0
(in mode 2) showing the default situation.
(H2P~H7P = binary 4) (H1P OFF)
2 Check the status of LED
16.1.4 To access mode 1 or 2 H6P.
H6P OFF: Unit is currently
After the units are turned ON, the display goes to its default not operating under low noise
situation. From there, you can access mode 1 and mode 2. restrictions.
3 Select setting 8. BS2 [X×] Unit is currently not operating under power
consumption limitations.
("X×" depends on the setting
ON
that you want to select.)
(= binary 8) Unit is currently operating under power consumption
4 Select value 4 (= 8°C). a BS3 [1×] limitation.
a: Display the current value. Power consumption limitation reduces the power
b BS2 [X×] consumption of the unit compared to nominal operating
b: Change to 4. ("X×" conditions.
depends on the current
value, and the value that you c BS3 [1×] Power consumption limitation can be set in mode 2. There
want to select.) are two methods to activate power consumption limitation of
d BS3 [1×] the outdoor unit system.
c: Enter the value in the
system. ▪ The first method is to enable a forced power consumption
limitation by field setting. The unit will always operate at
d: Confirm. The system starts the selected power consumption limitation.
operating according to the
setting. ▪ The second method is to enable power consumption
limitation based on an external input. For this operation
5 Quit mode 2. BS1 [1×]
an optional accessory is required.
▪ The second method is to enable low noise operation To obtain more detailed
based on an external input. For this operation an optional information about the malfunction
accessory is required. code, press BS2 up to 3 times.
20 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin Business Portal (authentication required).
3 Refer to the installation or service manual on how to use A1P Printed circuit board (main)
BS1~BS5 push buttons, and DS1‑1 and DS1‑2 DIP switches. A2P Printed circuit board (filter)
4 Do not operate the unit by short-circuiting protection device A3P Printed circuit board (cool/heat selector) (option)
S1PH. BS* Push buttons (mode, set, return, test, reset) (A1P)
5 Refer to the installation manual for indoor-outdoor C1 Capacitor (A1P)
transmission F1-F2 wiring.
DS1 DIP switch (A1P)
6 When using the central control system, connect outdoor-
outdoor transmission F1-F2. F1U Fuse (T 56 A / 250 V) (A2P)
F3U, F4U Fuse (T 6.3 A / 250 V) (A2P)
Notes for RXYSQ4~6_Y:
F6U Fuse (T 5.0 A / 250 V) (A1P)
1 Symbols (see below).
H*P LED (service monitor orange) (A1P)
2 For X37A refer to the installation manual of the option.
HAP Running LED (service monitor green) (A1P)
3 Refer to the installation or service manual on how to use
HBP Frequency LED (service monitor green) (A1P)
BS1~BS4 push buttons, and DS1‑1 and DS1‑2 DIP switches.
K11M Magnetic contactor (A1P)
4 Do not operate the unit by short-circuiting protection device
S1PH. K*R Magnetic relay (A1P)
5 Refer to the installation manual for indoor-outdoor L*R Reactor (A1P)
transmission F1-F2 wiring. M1C Motor (compressor)
6 When using the central control system, connect outdoor- M1F Motor (upper fan)
outdoor transmission F1-F2.
M2F Motor (lower fan)
Symbols: PS Switching power supply (A1P)
X1M Main terminal Q1DI Earth leakage circuit breaker (field supply)
Earth wiring R* Resistor (A1P)
15 Wire number 15 R1T Thermistor (air)
Field wire R2T Thermistor (discharge)
Field cable R3T Thermistor (suction 1)
4P482275-1B 2020.10
Verantwortung für Energie und Umwelt