Professional Documents
Culture Documents
Eaton - DC - Global E-Catalogue - Sept2009 (1) .918
Eaton - DC - Global E-Catalogue - Sept2009 (1) .918
DC Power Solutions
September2009
SMARTER ENERGY
Eaton DC Power Solutions
Contents
Eaton® Telecommunications Power Solutions - Capabilities Overview
DC Power Solutions
EPS2-3G Enterprise Power Solutions
EPS5-3G Enterprise Power Solutions
Enterprise Extended Battery Module
APS3/APS6-3G Access Power Solutions
APS3-3G Access Power Solutions (UL Series)
APS12-3G Access Power Solutions
Flexi-3G Access Power Solutions
DV2 3G Access Power Solutions with Batteries
DV2-3G Metro Power Solutions
DV2-3G Core Power Solutions
Rectifier Modules
EPR48-3G Enterprise Power Rectifier
APR24-3G Access Power Rectifier
APR48-3G Access Power Rectifier
APR48-ES Access Power Energy Saver Rectifier
CR48-3G Core Power Rectifier
NPR24 Network Power Rectifier
NPR48 Network Power Rectifier
Outdoor Enclosures
Whisper Cabinet™
Pedestal Enclosure™
Eaton DC Power Solutions
Our Business Environmental Standards We've also set tough Comprehensive Range
Eaton Corporation is a global Eaton strives for the highest performance goals for Our telecom power solution
diversified industrial environmental standards across ourselves, like reducing our range includes AC and DC
manufacturer and a leader in both our operations and greenhouse gas emissions by power systems, power and
electrical power quality, products and our commitment 18 percent (adjusted for ancillary equipment
distribution and control. Eaton goes beyond compliance with production) by 2012. management software,
serves the needs of customers existing regulations. We wish to cabinets and enclosures, and
located in over 125 countries. become recognized as an Unsurpassed Experience other products. Eaton also
industry leader in creating safe Eaton has in excess of 40 years offers a wide range of DC
Eaton’s telecommunications workplaces and conserving experience of working closely services including design,
power solutions business world resources. with customers to deliver installation and commissioning
provides telecommunications Eaton is committed to tailored power management remote monitoring, turnkey
and related sectors with world- environmental stewardship and solutions. for communications integration and site support, to
leading infrastructure products participates in a number of networks around the world. provide a seamless solution.
and services. volunteer government
partnership programs Customer led Solutions Delivery
Global Presence worldwide. Eaton’s insight into customer Eaton’s global scale
Headquarters are located in needs is demonstrated through manufacturing and logistic
Raleigh, North Carolina and We were among the first its products in terms of capability means that products
regional sales headquarters are diversified industrial companies reliability, efficiency, smart and services can be delivered
located in USA, Asia and Europe to pursue global ISO 14001 energy features, power density, with maximum cost-
with offices in over 30 certification - a rigorous and ease of installation, effectiveness and with the
additional countries and with standard for managing and delivery speed and flexibility
representation in over 100 improving environmental Intelligent monitoring and that you expect.
countries it is one of the few performance. Today, virtually all control capabilities add
telecommunications of Eaton's facilities worldwide flexibility, precision, reliability,
infrastructure providers with a have earned this designation. and automation - without added
truly global presence. complexity.
Eaton DC Power Solutions
Email: dc.info@eaton.com
Internet: www.eaton.com/telecompower
Eaton DC Power Solutions
Features
• 19” rack mounting
• High power density
• Intelligent system controls
• Pre-configured software
• Onboard secure web server
• Push-in easy to fit circuit breakers
• Low Voltage Disconnect
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Easy to use menu & full color display
• Optional batteries
Technical Specifications
Input Options
AC Supply Nominal: 120V, 240V Battery* Eaton Extended Battery Module (EBM)
Operating Range: 90V – 275V PW5130 48V EBM RM
Power Factor † >0.99 (50 – 100% Output Current) P/N 103006587-6591
Efficiency † 92% (50 – 100% Output Current)
Weight: 29.5kg [65lb]
Output Dimensions (H,W,D*): 85mm (2U), 432mm (19”
DC Output 43 – 57.5V mounting), 487mm
Voltage Range *Additional space is required at the rear for cables.
DC Output 240V AC: APR48-3G: 3.6kW
Power EPR48-3G: 1.8kW Typical Run time values* (see graph).
(maximum*) †
Battery Run Time (minutes)
120V AC: APR48-3G: 2.2kW
EPR48-3G: 1.1kW
Environmental
Operating Rated: -10°C to +50°C [-14°F to +122°F]
Temperature Extended*: -40°C to +70°C [-40°F to +158°F]
Range
*Output current is derated above 50°C [122°F]
Mechanical
Dimensions 2U , 19” mounting, 13.2” [335mm]*
H,W,D
* Additional clear depth space is required for
exhaust air.
System
System SC200 Equipment Power (watts))
Controller
Α = Required number of battery modules.
DC Distribution 12-way circuit breakers (2 x Battery, 10 x Load)
Module Circuit breaker type: Magnetic/Hydraulic, push fit
*Battery times are approximate and vary depending
on factors such as:
Battery circuit breakers: Heinemann AC1R Series
- load configuration
Typical ranges available: 30A, 40A, 50A, 60A, 70A
- battery charge
- battery age and temperature.
Load circuit Breakers: Heinemann JC1S Series
Typical ranges available: 6A,10A, 15A, 20A, 25A,
* Other battery options available - consult your local
30A
Eaton agent.
Communication USB direct
Battery Cables CKBATT-02 Eaton EBM 5130 connection cable,
Features 10BaseT Ethernet, TCP/IP, SNMP, On board web
2000mm long
server
or CKBATT-01 ‘other batteries’ connection cable,
RS232 to external PSTN or GSM modem (modem
2000mm long
not included)
Equipment Customer Equipment Connection Cable
Rectifier Blank For unused rectifier positions
Cable CKLOAD-00 10-way connection loom, 1000mm long
Panels
EBM Rack Included with EBM5130 as standard
Mounting Kit
Software
DCTools Configuration software.
Certifications
Free download from:
All products comply with International Standards.
www.powerware.com/downloads
PowerManagerII Remote control and monitoring software
North America UL (Canada, USA), FCC Class B
Europe CE
† Power factor, efficiency and DC output power are dependant on Australia and New Zealand C-Tick
rectifier model fitted. Refer to the rectifier data sheet for further
In the interests of continual product improvement all specifications are
details.
subject to change without notice.
Features
• 19” rack mounting
• High power density
• Intelligent system controls
• Pre-configured software
• Onboard secure web server
• Push-in easy to fit circuit breakers
• Low voltage disconnect
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Easy to use menu & full color display
• Optional batteries
Technical Specifications
Input Options
AC Supply Nominal: 120V, 240V Battery* Eaton Extended Battery Module (EBM)
Operating range: 90V – 275V PW5130 48V EBM RM
Power Factor † >0.99 (50 – 100% output current) P/N 103006587-6591
Efficiency † 91% (50 – 100% output current)
Weight: 29.5kg [65lb]
Output Dimensions (H,W,D*): 85mm (2U), 432mm (19”
DC Output 43 – 57.5V mounting), 487mm
Voltage Range *Additional space is required at the rear for cables.
DC Output 240V AC: 4.5kW
Power 120V AC: 2.25kW Typical run time values* (see graph).
(maximum*) †
Battery Run Time (minutes)
* Based on five rectifiers fitted, refer to EPR48-3G
rectifier data sheets.
Environmental
Operating Rated: -10°C to +50°C [-14°F to +122°F]
Temperature Extended*: -40°C to +70°C [-40°F to +158°F]
Range
*Output current is derated above 50°C [122°F]
Mechanical
Dimensions 3U, 19” mounting, 13.2” [335mm]*
H,W,D
* Additional clear depth space is required for
exhaust air.
Equipment Power (watts))
System
System
Controller
SC200 • = Required number of battery modules.
Software
Certifications
DCTools Configuration software.
All products comply with international standards.
Free download from:
www.powerware.com/downloads
North America UL (Canada, USA), FCC Class B
PowerManagerII Remote control and monitoring software
Europe CE
Australia and New Zealand C-Tick
† Power factor, efficiency and DC output power are dependant on
rectifier model fitted. Refer to the rectifier data sheet for further In the interests of continual product improvement all specifications are
details. subject to change without notice.
Features
• Easy to install
• Slimline 19” rack mounting
• Extended runtime -18Ahr capacity
• Modular and scaleable
• Service maintenance free VLRA batteries
Technical Specifications
Output
DC Output 48V nominal
Voltage
DC Output 18Ahr
Capacity Maximum input/output current should not exceed
55Amps
Mechanical
Weight 29.5kg
Dimensions 85mm (2U), 432mm (19” mounting), 487mm*
H,W,D
* Additional space is required at the rear for cables.
Battery
Certifications
All products comply with international standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
North America UL listed
Europe CE
Environmental
Operating -40°C to +70°C [-40°F to +158°F]
Temperature * Refer to rectifier data sheet for more information.
Range* Output current is derated above 50°C [122°F] and
below -10°C [14°F]
Mechanical
Dimensions APS3-300: 3U, 19” mounting, 306mm [12”]*
H,W,D APS6-300: 6U, 19” mounting, 306mm [12”]*
APS6-500: 6U, 19” mounting, 306mm [12”]*
System
System SC200 or SC100
Controller
DC Distribution APS3-300: 12-way circuit breakers
Module (2 x battery, 10 x load)
APS6-300: 20-way circuit breakers
(4 x battery, 16 x load)
APS6-500: 20-way circuit breakers
(4 x battery, 16 x load)
Communication USB direct
Features 10BaseT Ethernet, TCP/IP, SNMP, On board web
server
RS232 to external PSTN or GSM modem (modem
not included)
Low Voltage APS3-300: optional battery LVD
Disconnect APS6-300: optional 200A LVD’s for battery
(LVD) or load, or both.
APS6-500: optional 400A LVD’s for battery
or load, or both.
Rectifier Blank For unused rectifier positions
Panels
Options External Surge Protection
Environmental
Temperature Rated: -10°C – +50°C [14°F – +122°F]
Range Extended: -40°C – +65°C [-40°F – 149°F]*
Mechanical
Dimensions 3U [5.25”, 133mm], 19” [483mm] mounting,
H,W,D 14” [356mm]*
System
System SC200 as standard.
Controller SC100 optional.
DC Distribution 10-way circuit breakers (2 x Battery, 8 x Load).
Module Load circuit breakers: Heinemann AMIR Series
5A,10A, 20A, 30A, 40A, 50A, 70A, 80A, 100A.
Battery circuit breakers: Heinemann AMIR 100A or
AMIP 120A.
Communication USB direct.
Features of 10BaseT Ethernet, TCP/IP, SNMP, On board web
SC200 server.
RS232 to external PSTN or GSM modem (modem
not included).
Low Voltage Battery disconnect: 200A internal.
Disconnect
(LVD)
Rectifier Blank For unused rectifier positions.
Panels
Options Relay Rack
Batteries.
Features
• Compact 9U, 19” sub-rack
• Up to 12 rectifier modules
• Pre-configured software
• High power density (450A/9U)
• Dual AC input
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Priority and non priority options for DC distributions
Technical Specifications
Input Software
AC Supply 100 – 240V, 50 – 60Hz (nominal) DCTools Configuration software.
175 – 275V full power output upto 50°C [122°F] Free download from:
90 – 175V reduced power output www.powerware.com/downloads
Dual AC input - 1Ø, 2Ø or 3Ø (one supply feed per PowerManagerII Remote control and monitoring software
6-rectifier shelf)
Power Factor >0.99 (50 – 100% Output Current) † Certifications
Efficiency 92% (50 – 100% Output Current) † All products comply with international standards. Contact your local
Eaton DC representative for details on the specific product versions
Output available with these safety and EMC approvals:
DC Output 43 – 58V
Voltage Range Europe CE
DC Output 21.6kW @ 48V Australia / C-tick
Power New Zealand
(maximum) †
In the interests of continual product improvement all specifications are
subject to change without notice.
Environmental
Operating -40°C to +70°C [-40°F to +158°F]
Temperature Output current is derated above 50°C [122°F] and
Range below -10°C [14°F]
Mechanical
Dimensions 9U, 19” mounting, 306mm [12”]*
H,W,D
* Additional clear space is required for exhaust air.
System
System SC200 or SC100
Controller
DC Distribution 20-way circuit breakers (4 x Battery, 16 x Load)
Module
Communication USB direct
Features 10BaseT Ethernet, TCP/IP, SNMP, On board web
server
RS232 to external PSTN or GSM modem (modem
not included)
Low Voltage Optional battery LVD, or non priority LVD, or battery
Disconnect and non priority LVD’s. (Contactors 400A
(LVD) rated)
Rectifier Blank For unused rectifier positions
Panels
Options External Surge Protection
Features
• Innovative system design reduces shipping costs and is easily
assembled on-site
• Integrated batteries with optional rack heights
• Reduced rack-depth option (450mm) ideal for installations with
restricted space
• Integral DC distribution
• Wide AC input voltage range
• Hot swappable rectifiers
• High power density
• Pre-configured software
• Flexible modular design
• Remote monitoring and control
• Ethernet communications offering SNMP
Technical Specifications
Input Options
AC Supply 230/400 3Ø+N+PE (cabinets may be supplied Battery Rack Extension kit for extending battery rack from
from 230V single-phase) Extension 450mm to 600mm depth, is available for 1150 and
120/208 3Ø+PE (specific version with protection 1350mm battery racks
in each phase) DC Distribution 22 Load MCB (18mm) positions *
230/400 dual, single or 3-phase connection 4 Battery MCB (27mm) positions *
(specific version)
Frequency 50/60Hz (nominal) *other configurations available
Power Factor >0.99 (50 – 100% Output Current) Cabinet Doors Optional doors available for battery racks and
Efficiency 92% (50 – 100% Output Current) Power Box
Rectifier Blank For unused rectifier positions
Output Panels
DC Output 43 – 57.5V
Voltage Range Software
Maximum DC 16.2kW PowerManagerII Remote control and monitoring for small to large
Output Power networks
DCTools Configuration Software. Free download from
Environmental www.powerware.com/downloads
Operating -40°C to +70°C Maximum output power is
Temperature derated below -10°C and above 50°C Certifications
Range All products comply with International Standards. Contact your local
Eaton DC product representative for details on the specific product
Mechanical versions available with these safety and EMC approvals:
Dimensions Combined battery rack / Power Box: Europe CE
H,W,D 1800/2000mm, 600mm, 450mm
2121mm, 600mm, 600mm In the interests of continual product improvement all specifications are
subject to change without notice.
Battery Rack:
1150mm – Maximum 4 Battery Shelves (258mm
min. space)
1350mm – Maximum 4 Battery Shelves (308mm
min. space)
1471mm – Maximum 5 Battery Shelves (262mm
min. space)
Weight System cabinet: <110kg (excluding rectifiers and
batteries)
Rectifiers : APR48-3G: 1.7kg
Finish Cabinet is constructed with a galvanised finish
(unpainted)
System
System Controller Extended functionality: SC200
Features
• Intelligent system management features
• Pre-Configured Software
• High Power Density
• Fast On-Line Expansion of Rectifiers (Hot-Swap)
• High Efficiency and Unity Power Factor
• Range of DC distribution configurations
• Integrated batteries
• Battery condition monitoring
• Wide AC input voltage range
• Seismic rated cabinet
• Remote monitoring and control
• Full length security door (optional)
Technical Specification
Input Options
AC Supply 3P+N+PE, 3P+PE, 2P+PE, 1P+N+PE AC Distribution Coordinated transient protection up to 40kA, 8/20μs
50/60Hz (nominal) Incoming isolator
Power Factor >0.99* (20 – 100% Maximum System Current) Individual rectifier MCBs
Efficiency up to 92%* DC Distribution Up to 4 groups of MCBs or fuses. Each group
comprises up to:
Output 9 x 18mm MCBs (1-63A), or
DC Output 20 – 58V 6 x 27mm MCBs (10-125A), or
Voltage Range 4 x DIN00 HRC fuses (20-160A)
Typical DC 14.4kW (500A @ 28.8V) † or
Output Power 18 kW (375A @ 48V) † Custom options available on request.
Low Voltage Single or dual LVD configured as battery
Disconnect disconnect.
Environmental
(LVD)
Operating -25°C to +50°C*
Rectifier Blank For unused rectifier positions
Temperature
Panels
Range
SiteSure Input/output modules to monitor and control
external equipment
Mechanical CellSure Comprehensive battery monitoring and fault
Dimensions 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”] diagnosis system with patented state-of-health
H,W,D algorithms.
Weight 870kg [1914lb]
Typical maximum with 10 rectifier modules and 4
Software
x 48V/150Ah battery strings.
PowerManagerII Remote control and monitoring software
DCTools Configuration Software. Free download from
System www.powerware.com/downloads
System Controller SC100/SC200
Communications 10BaseT Ethernet port TCP/IP*
Certifications
On-board web server*
All products comply with International Standards. Contact your local
SNMP agent*
Powerware DC representative for details on the specific product
Dial up modem
versions available with these safety and EMC approvals:
GSM modem
China MII
Europe CE
*SC200 only
Australia / C-tick, Seismic rating to NZS4203
Batteries Typically up to 4 strings @ 48V, or 8 strings @ 24V,
New Zealand
600Ah total capacity.
Other battery configurations available.
In the interests of continual product improvement all specifications are
subject to change without notice.
* Refer to rectifier specifications for more information.
† System output power will vary depending on rectifiers and batteries
selected.
Features
• Intelligent system management features
• Pre-Configured Software
• High Power Density
• Fast On-Line Expansion of Rectifiers (Hot-Swap)
• High Efficiency and Unity Power Factor
• Range of DC distribution configurations
• Battery condition monitoring
• Wide AC input voltage range
• Seismic rated cabinet
• Remote monitoring and control
• Full length security door (optional)
Technical Specification
Input Options
AC Supply 3P+N+PE, 3P+PE, 2P+PE, 1P+N+PE AC Distribution Coordinated transient protection up to 40kA, 8/20μs
50/60Hz (nominal) Incoming isolator
Individual rectifier MCBs
Other options available depending on system DC Distribution A wide range of DC distribution elements are
capacity. available including:
Power Factor >0.99* (20 – 100% Maximum System Current) 24 x 18mm MCBs (1-63A)
Efficiency up to 92%* 16 x 27mm MCBs (10-125A)
10 x DIN00 type HRC fuses (20-160A)
Output 6 x DIN1 type HRC fuses (63-250A)
DC Output 40 – 58V 6 x DIN2 type HRC fuses (100-400A)
Voltage Range 4 x DIN3 type HRC fuses (400-630A)
Typical DC 72kW (1500A @ 48V) † 4 x DIN4 type HRC fuses (800-1200A)
Output Power Low Voltage Single or dual LVD can be configured as battery or
Disconnect load disconnect including non-priority load
(LVD) disconnect.
Environmental
Rectifier Blank For unused rectifier positions
Operating -25°C to +50°C*
Panels
Temperature
SiteSure Input/output modules to monitor and control
Range
external equipment
CellSure Comprehensive battery monitoring and fault
Mechanical diagnosis system with patented state-of-health
Dimensions 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”] algorithms.
H,W,D
Weight 200kg [443lb]
Software
Typical configuration with 40 APR-3G rectifier
PowerManagerII Remote control and monitoring software
modules.
DCTools Configuration Software. Free download from
www.powerware.com/downloads
System
System Controller SC100/SC200
Certifications
All products comply with International Standards. Contact your local
* Refer to rectifier specifications for more information. Powerware DC representative for details on the specific product
† System output power will vary depending on rectifiers and batteries versions available with these safety and EMC approvals:
selected. China MII
Europe CE
Australia / C-tick, Seismic rating to NZS4203
New Zealand
Features
• Intelligent system management features
• Pre-Configured Software
• High Power Density
• Fast On-Line Expansion of Rectifiers (Hot-Swap)
• High Efficiency and Unity Power Factor
• Range of DC distribution configurations
• Battery condition monitoring
• Wide AC input voltage range
• Seismic rated cabinet
• Remote monitoring and control
• Full length security door (optional)
Technical Specifications
Input Options
Nominal AC 3P+PE, Δ 208VAC AC Distribution Coordinated transient protection up to 40kA, 8/20μs
Supply 3P+N+PE, Y 230/400VAC Incoming isolator
50/60Hz Individual rectifier MCBs
Power Factor >0.99* (20 – 100% Maximum System Current) DC Distribution A wide range of DC distribution elements are
Efficiency up to 92%* available including:
24 x 18mm MCBs (1-63A)
Output 16 x 27mm MCBs (10-125A)
DC Output 40 – 58V 10 x DIN00 type HRC fuses (20-160A)
Voltage Range 6 x DIN1 type HRC fuses (63-250A)
Typical DC 46kW - 750kW † 6 x DIN2 type HRC fuses (100-400A)
Output Power 4 x DIN3 type HRC fuses (400-630A)
4 x DIN4 type HRC fuses (800-1200A)
Low Voltage Single or dual LVD can be configured as battery or
Environmental
Disconnect load disconnect including non-priority load
Operating -25°C to +50°C*
(LVD) disconnect.
Temperature
Rectifier Blank For unused rectifier positions
Range
Panels
SiteSure Input/output modules to monitor and control
Mechanical external equipment
Dimensions 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”] CellSure Comprehensive battery monitoring and fault
H,W,D diagnosis system with patented state-of-health
Weight 200kg [443lb] algorithms.
Typical configuration with 16 CR48-3G rectifier
modules.
Software
PowerManagerII Remote control and monitoring software
System DCTools Configuration Software. Free download from
System Controller SC200 www.powerware.com/downloads
Features
• Ultimate high power density reducing space demand
• Hot-pluggable connection allows module addition or removal
without interruption to AC supply
• Versatile modular design allows a variety of configurations for
different power needs
• Capacity up to 18kVA when configured without the optional
Static Transfer Switch n+x redundancy
• Single phase 120Vac or 230Vac output options
• High efficiency, >89%
• Comprehensive LCD/LED display provides system status, and
user-friendly panel eases program settings
• Optional Maintenance Bypass Switch with integrated AC
distribution
• Optional USB/RS232/RS485 communication for local and
remote management
Technical Specifications
Modules Mechanical
INV-4810E 1000VA/800W inverter module Inverter (DxWxH) 270mm x 215mm x 43.8mm (10.6 in. x 8.5
Input:48Vdc,Output:230VAC,1U*5U Module in. x 1.7 in.), Weight 2.5kg (5.5lb)
INV-4810 1000VA/800W inverter module STS Module (DxWxH) 270mm x 215mm x 43.8mm (10.6in x 8.5in
Input:48Vdc,Output:120VAC,1U*5U x 1.7in.), Weight 2.1kg (4.6lb)
INV-4815E 1500VA/1200W inverter module Controller (DxWxH) 277mm x 87.9mm x 43.5mm (10.8 in. x 3.4
Input:48Vdc,Output:230VAC,1U*5U Module in. x 1.7 in.), Weight 0.5kg (1.1lb)
INV-4815 1500VA/1200W inverter module Interface (DxWxH) 79.7mm x 129.5mm x 43.5mm (3.1 in. x
Input:48Vdc,Output:120VAC,1U*5U Module 5.1 in. x 1.7 in.), Weight 0.25kg (0.55 lb)
STS-050 12KVA static transfer switch module Inverter (1U x 19”): (DxWxH) 330mm x 483mm x 43.8mm
50A, 1U*5U Chassis (13 in. x 19 in. x 1.7 in.), Weight 2.7kg (6 lb)
MC-1000 Controller module Controller (1U x 19”): (DxWxH) 330mm x 483mm x 43.8mm
LCD, 3*LED, 4*function key, 1U*2U /Interface/STS (13 in. x 19 in. x 1.7 in.), Weight 2.7kg (6 lb)
IFC-1000-NS RS232/USB/RS485 interface module, 1U*3U Chassis
INVSS-2EA-1U- 19" inverter hot-swap chassis, 1U MBS / PD (DxWxH) 330mm x 483mm x 88mm (13in x 19in x
19 Chassis 3.5in), Weight 7.0kg (15.4lb)
STSSS-C-1EA- 19" controller/STS chassis, 1U (2U x 19”)
1U-19
MBSDU-50-2U- 19" Maintenance Bypass, Power Distribution Certifications
19 chassis, 2U All products comply with international standards including CE and UL.
DC Input
Nominal 48Vdc In the interests of continual product improvement all specifications are
Voltage subject to change without notice.
Operating 40.5Vdc ~ 58Vdc
Range
Surge Telcordia GR-1089 CORD, ANSI C62.41-IEEE, STD
Protection 587-1980
Input Reverse polarity protection
Protection
Psophometric ≤1.0mV ITU-T O.41 (16.66~6000Hz) Maximum Number of Inverter Modules for Parallel Operation
Noise (Max Power)
Peak to Peak 150mV up to 100MHz Model With STS-050 Without STS-050
Noise INV-4810 6 (6kVA) 12 (12kVA)
INV-4810E 12 (12kVA) 12 (12kVA)
AC Output INV-4815 4 (6kVA) 12 (18kVA)
Output Pure sine wave INV-4815E 8 (12kVA) 12 (18kVA)
Waveform
Output power INV-4810E, INV-4810: 1000VA/800W
INV-4815E, INV-4815: 1500VA/1200W
Power factor 0.8
Nominal INV-4810, INV-4815: 110/115/120Vac
Output Voltage INV-4810E, INV-4815E: 208/220/230/240Vac
(Single Phase) Max ±2%
Frequency 50/60Hz ±0.5%
Crest factor 3:1
THD, resistive <3%, linear load
load <5%, non-linear load
Efficiency Min 88% at rated load
Dynamic Max±10%
Response
Overload 1.5*Inom >20s
Protection 1.25*Inom temperature controlled
Short Circuit 16A for INV4810E
Current 30A for INV4810
Features The Eaton® Matrix™ 2000 The Matrix 2000 solution uses
Standalone Inverter is digital microprocessor control to
• Designed for telecom applications designed for use in provide maximum performance
• Pure sine wave output telecommunications under all operating conditions.
applications where a very The built-in controller gives real-
• Unity power factor (full 2000 watt output power) reliable AC supply is required. time system status through
• Significant overload capability, 120% continuously, 200% for 5 The high efficiency and comprehensive LCD/LED
seconds compact size makes the Matrix displays, and allows program
2000 Inverter an outstanding setting through a keypad panel.
• High efficiency, >91% solution for powering all types
• High power density of critical AC equipment. The Matrix 2000 Standalone
Inverter includes a built in USB
• Built in Static Transfer Switch (STS)
The Matrix 2000 Standalone interface for monitoring and
• DSP design for improved reliability and performance Inverter provides 2000W of control.
• Single phase 120Vac or 230Vac output options reliable AC power in a 1U x 19”
rack mount package that
• Comprehensive LCD/LED with keypad includes a built-in Static
• USB interface for connecting to PC Transfer Switch (STS). The
STS automatically and
• Wide selection of configurable parameters.
instantaneously switches the
• International certifications AC output, from the DC inverter
to an alternative source such as
AC mains (and back again),
providing extra security of the
AC supply to the load
equipment.
Technical Specifications
DC Input Certifications
Operating 48V: 40Vdc ~ 60Vdc All products comply with international standards.
Range
Safety EN60950-1 / UL60950-1
Europe CE
AC Input (to Transfer Switch)
Voltage Range: INV-4820SA: 89Vac to 138Vac In the interests of continual product improvement all specifications are
(50/60Hz) INV-4820ESA: 176Vac to 276Vac subject to change without notice.
Transfer Time <10ms
AC Output
Power Output 2000VA / 2000W
Wave Form Pure sine wave
Power Factor 1.0
Nominal Output INV-4820SA: 110/115/120Vac
Voltage INV-4820ESA: 208/220/230/240Vac
(selectable)
Output 50,60Hz
Frequency
Efficiency >91% at rated load
Over Load 2*Inom, 5sec max
Protection 1.5*Inom, 10sec max
1.25*Inom, temperature controlled
Environmental
Requirements
Operating -20°C to 60°C (-4°F to 140°F)
Temperature -20°C to 50 °C (-4°F to 122°F), full performance
Range
Cooling Fan Cooled
Features
• DC power system configuration software
• Windows® compatible
• Easy to use graphical display
• Operates with all Eaton DC power systems, CellSure™ and
SiteSure™
• Local (RS232 serial) or remote (dialup modem or Ethernet)
connection
• Downloadable from the Internet at no charge
Technical Specifications
Computer
Minimum
Requirements
Operating Windows 98, Windows NT 4.0 or later
System
RAM 16Mb Ram Windows 98, 24Mb Windows NT
Interfaces
Communications RS232, Ethernet, or modem
interfaces
supported
Availability
Free download www.powerware.com/downloads
Alarms and
Indicators
Controller Status LED, 4 String Alarm LEDs
module
indicators
Controller Voltage free relay contacts (Urgent and Non-urgent)
module alarms
Inputs
Cell/monobloc ±0.5% accuracy
voltage
String current ±1% accuracy
Ambient ±1°C accuracy
temperature
String ±1°C accuracy
temperature
Data Output
Alarm Cell/monobloc voltage low, Cell/monobloc
conditions divergence, Discharge voltage low, String
temperature, String overcharge, Low capacity, Low
charge.
Measured Actual capacity, Reserve charge, Reserve time,
values “State of Health”
Data Weekly log: 7day x 24hour cell/monobloc data
Yearly log: 365day cell/monobloc data (averaged)
Last two partial discharges.
Last full discharge.
Certifications
All products comply with International Standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
North America UL, FCC Verification
Canada IC
Europe CE
Australia / C-tick
New Zealand
SiteSure™
Input/Output
Certifications
All products comply with International Standards. Contact your local
Powerware DC representative for details on the specific product
versions available with these safety and EMC approvals:
Europe CE
Australia /
New Zealand C-tick
SiteSure-3G™
Features
• Remote control and monitoring
• Expandable
• Modular
• Real time data collection
• Compliance with international standards
Technical Specifications
Operation
Supply Voltage 19 to 60V
Range
Rated Operating -10°C to +80°C [+14°F to +176°F]
Range
Input/Output
Bus voltage Number: 1
input Range: -60V to +60V
Current inputs Number: 3
Range: -50mV to +50mV
Temperature Number: 2
inputs Range: 2.53V to 3.23V
(-20°C to +70°C with TS02 temperature sensor)
Digital inputs Number: 10
General Number: 4
purpose analog Range: 0V to +10V
inputs
Digital Outputs Number: 6
(Relays) Type: Voltage free, NO-C-NC
0.3A @ 60VDC / 1A @ 30VDC
Certifications
All products comply with international standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
Features
• Fast on-line expansion of rectifiers (hot-swap)
• Automatic set-up from system controller
• Intelligent microprocessor controlled
• High efficiency and unity power factor
• Universal AC supply input
• Wide output voltage ranges
• Constant power output
• Compliance with international standards
Technical Specifications
Input
AC Supply Nominal: 220/240V, 50/60Hz
Extended Operating Range: 90V – 275V
Power Factor >0.98 (50 – 100% Output Current)
Efficiency 91% (50 – 100% Output Current)
Output
DC Output 48V: 43 – 57.5V
Voltage Range
DC Output 900W (240V AC nominal)
(maximum) 550W (120V AC nominal)
Environmental
Operating -40°C – +70°C [-40°F – +158°F]
Temperature Output current is derated above 50°C [122°F]
Range
Cooling Temperature controlled, variable speed, high
reliability fans
Mechanical
Dimensions 3U: 133mm [5.25”], 42mm [1.65”],
H,W,D 266mm [10.45”] overall
Weight 1.7kg [3.7 lb]
Certifications
North America UL, FCC Verification
Europe CE
Australia / C-tick, Telepermit
New Zealand
Features
• Fast on-line expansion of rectifiers (hot-swap)
• Automatic set-up from system controller
• Intelligent microprocessor controlled
• High power density
• High efficiency and unity power factor
• Wide AC supply conditions
• Wide output voltage ranges
• Constant current output
• NiCad battery compatible
• Compliance with international standards
Technical Specifications
Input
AC Supply 220/240V, 50/60Hz (nominal)
175-275V full output power up to 50°C [122°F]
Power Factor >0.98 (50 – 100% Output Current)
Efficiency 89% (50 – 100% Output Current)
Output
DC Output 24V: 20 – 32V
Voltage Range
DC Output Constant power 1440W, 28.8 - 32V
(maximum) Constant current 50A, 20 - 28.8V
Environmental
Operating -40°C – +70°C [-40°F – +158°F]
Temperature Output current is derated above 50°C [122°F] and
Range below -10°C [14°F]
Cooling Temperature controlled, high reliability fans
Mechanical
Dimensions 3U: 133mm [5.25”], 42mm [1.65”],
H,W,D 266mm [10.45”] overall
Weight 1.7kg [3.7 lb]
Certifications
North America UL, FCC Verification, CSA, IC
Europe CE
Australia / C-tick, Telepermit
New Zealand
Features
• Fast on-line expansion of rectifiers (hot-swap)
• Automatic set-up from system controller
• Intelligent microprocessor controlled
• Industry leading power density
• High efficiency and unity power factor
• Wide AC supply conditions
• Wide output voltage ranges
• Constant power output
• Compliance with international standards
Technical Specifications
Input
AC Supply 220/240V, 50/60Hz (nominal)
175-275V full output power up to 50°C [122°F]
Power Factor >0.99 (50 – 100% Output Current)
Efficiency 92% (50 – 100% Output Current)
Output
DC Output 48V: 43 – 57.5V
Voltage Range
DC Output 1800W @ 48V
(maximum)
Environmental
Operating -40°C – +70°C [-40°F – +158°F]
Temperature Output current is derated above 50°C [122°F] and
Range below -10°C [14°F]
Cooling Temperature controlled, high reliability fans
Mechanical
Dimensions 3U: 133mm [5.25”], 42mm [1.65”],
H,W,D 266mm [10.45”] overall
Weight 1.7kg [3.7 lb]
Certifications
North America UL, FCC Verification, CSA, IC
Europe CE
Australia / C-tick, Telepermit
New Zealand
Features
• 2000W output power
• Energy saving efficiency greater than 96%
• Wide efficiency curve
• Industry leading power density
• Fast on-line expansion of rectifiers (hot-swap)
• Simple ‘plug and go’ insert
• Unity power factor
• Digital signal processing for enhanced control
• Wide AC supply conditions
• Wide output voltage range
• Constant power output
• Compliance with international standards
Technical Specifications
Input
AC Supply 120V/208-240V, 50/60Hz (nominal)
185-275V full output power up to 50°C [122°F]
90-185V reduced output power
Power Factor >0.99 (50 – 100% output current)
Efficiency >96% peak
>95% (30 – 100% output power)
Output
DC Output
Voltage Range 43 – 57.5V
DC Output
(maximum) 2000W @ 48V
Environmental
Operating
Temperature -40°C – +70°C [-40°F – +158°F]
Range Output power derates above 50°C [122°F]
Cooling Temperature controlled, variable speed, high reliability
fan
Mechanical
Dimensions 3U: 133mm [5.25”], 42mm [1.65”],
H,W,D 266mm [10.45”] overall
Weight 1.7kg [3.7 lb]
Certifications
North America UL (pending), FCC Verification, CSA, IC
Europe CE
Australia /
New Zealand C-tick
Features
• Fast on-line expansion of rectifiers (hot-swap)
• Automatic set-up from system controller
• Intelligent microprocessor controlled
• Industry leading power density
• High efficiency and unity power factor
• 3Ø AC supply
• Wide AC supply conditions
• Wide output voltage ranges
• Constant power output
• Compliance with international standards
Technical Specifications
Input
AC Supply 208V, 50/60Hz (nominal) 3-phase Δ
400V, 50/60Hz (nominal) 3-phase Y
323-510V full output power up to 50°C [122°F]
Power Factor >0.99 (50 – 100% Output Current)
Efficiency 92% (50 – 100% Output Current)
Output
DC Output 43 – 58V
Voltage Range
DC Output 5800W @ 48V
(maximum)
Environmental
Operating -40°C – +70°C [-40°F – +158°F]
Temperature Output current is derated above 50°C [122°F] and
Range below -10°C [14°F]
Cooling Temperature controlled, high reliability fan
Mechanical
Dimensions 3U: 130mm [5.25”], 121mm [4.8”],
H,W,D 321mm [12.6”] overall
Weight 4.4kg [9.7 lb]
Certifications
North America UL, FCC Verification, CSA, IC
Europe CE
Australia / C-tick, Telepermit
New Zealand
Features
• Fast on-line expansion of rectifiers (hot-swap)
• Automatic set-up from supervisory module
• Intelligent microprocessor controlled
• High power density
• High efficiency and unity power factor
• Wide AC supply conditions
• Wide output voltage range
• Constant power or constant current output modes
• Compliance with international standards
Technical Specifications
Input
AC Supply 240V, 50/60Hz (nominal)
Power Factor > 0.99 (20 – 100% Output Current)
Efficiency > 88% 30-100% Output Current
> 89% @ 50% Output Current
Output
DC Output 20 – 29V
Voltage Range
DC Output Constant power mode: 1740W (66.6A@ 26V)
(maximum) Constant current mode: 60A @ 29V
Power Density 6 Rectifiers: 400A in 5U/19-inch
Environmental
Operating -25°C – +70°C [-13°F – +158°F ]
Temperature Maximum output current is derated above 40°C
Range [104°F] (66.6A @ 40°C [104°F])
Cooling Dual, temperature controlled, high reliability fans
Mechanical
Dimensions 5U: 220mm [8.75”], 70mm [2.75”], 360mm [14.2”]
H,W,D overall
Weight 4.5kg [9.9lb]
Certifications
North America UL (USA, Canada), FCC Verification, CSA, IC
Europe CE
Features
• Fast on-line replacement of rectifiers (hot-swap)
• Automatic set-up from supervisory module
• Intelligent microprocessor controlled
• High power density
• High efficiency and unity power factor
• Wide AC supply conditions
• Wide output voltage range
• Constant power or constant current output modes
• Compliance with international standards
Technical Specifications
Input
AC Supply 240V, 50/60Hz (nominal)
Power Factor > 0.99 (20 – 100% Output Current)
Efficiency > 90% for 20 – 100% Output Current
> 92% @ 50% Output Current
Output
DC Output 40 – 58V
Voltage Range
DC Output Constant power mode: 3000W (62.5A @48V)
(maximum) Constant current mode: 52A
Power Density 6 Rectifiers: 375A in 5U/19-inch (10W/cu.inch)
Environmental
Operating -25°C – +70°C [-13°F – +158°F ]
Temperature
Range Output current is derated above 50°C [122°F]
Cooling Dual, temperature controlled, high reliability fans
Mechanical
Dimensions 5U: 220mm [8.75”], 70mm [2.75”], 360mm [14.2”]
H,W,D overall
Weight 4.5kg [9.9lb]
Certifications
All products comply with international standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
Europe CE
Australia/New Zealand
C-tick
Features
• Ethernet interface built-in
• SNMP agent
• Battery mid-point monitoring
• Eaton Fuel Saver
• SMS alarm messages (with GSM modem)
• Comprehensive system control functions
• Color display with user-friendly menus
• Complies with international standards
• Setup via web, keypad or DCTools configuration software
• Language options
• Optional extra I/O boards or SiteSure-3G modules for expansion
Technical Specification
Operation Options
Supply Voltage 18 to 60Vdc Input/Output With IOBSS module (SiteSure-3G):
Range Analog inputs: 48
Operating Range Standard: -10 to +50°C [14 to 122 °F] Digital inputs: 108
Extended: -25 to 70°C [-13 to 158 °F] Digital outputs: 32
Modem PSTN or GSM. Requires external modem.
Input/Output communications
Standard
Analog inputs Current sensor (3), Bus voltage (1), Temperature Certifications
(2) China MII
Digital inputs 4 Internal (pre-defined), 6 external (user-defined) North America UL, FCC Verification, IC
LVD contactor 2 Europe CE
outputs Australia / C-tick
Relay outputs 6 Voltage free, NO-C-NC, 0.1A @ 60VDC New Zealand
Screw terminal block, 0.5mm2 - 2.0mm2
conductors In the interests of continual product improvement all specifications are
subject to change without notice.
Communications
Interfaces
Physical Ethernet, USB and RS232
Software IP, https (secure web), S3P
Management DCTools configuration / local management
software software.
PowerManagerII remote management software.
SNMP version V1, V2c or V3. Supports standard
Network Management System software including
HP OpenView Network Node Manager.
User Interface
Display Back-lit color dot matrix LCD 160 x 128 pixel
Adjustable viewing angle
Keypad 6 keys
Language English: Standard
Options Spanish, German and Chinese available on
request.
Other language software upgrades by
arrangement.
Indicators Power on, Critical/Major alarm, Minor alarm
Mechanical
Dimensions SC200: 133.5mm (3U), 44.5mm, 70mm
H,W,D IOBGP: 106mm, 175mm, 18mm
Mounting SC200: rectifier slot or flush panel mount
Orientation: vertical or horizontal
IOBGP: panel mount
Datalogging
Event Log 10,000 records
Data Log 10,000 records
Features
• Comprehensive system control functions
• Supports PSTN and GSM external modems
• User-friendly menus
• Pre-loaded customized configuration file
• Complies with international standards
• Setup via DCTools configuration software
• Language options
• Low cost
Technical Specifications
Operation Options
Supply Voltage 19 to 60Vdc Modem PSTN or GSM. Requires external modem.
Range communications
Operating Range -10 to +70 °C [14 to 158 °F]
Certifications
Input/Output China MII
with IOBGP-00 North America FCC Verification, IC
Analog inputs Current sensor (3), Bus voltage (1), Temperature Europe CE
(2) Australia / C-tick
Digital inputs 4 Internal (pre-defined), 6 external (user-defined) New Zealand
LVD contactor 2
outputs In the interests of continual product improvement all specifications are
Relay outputs 6 Voltage free, NO-C-NC, 0.5A @ 100VDC subject to change without notice.
Screw terminal block, 0.5mm2 - 2.0mm2
conductors
Communications
Interfaces
Physical RS232
Software S3P, MII
Management DCTools configuration / local management
software software.
PowerManagerII remote management software.
User Interface
Display Back-lit dot matrix LCD 128 x 128 pixel
Adjustable viewing angle
Keypad 4 keys
Language English: Standard
Options Other languages by arrangement.
Indicators Power on, Critical/major alarm, Minor alarm
Mechanical
Dimensions SC100: 133.5mm (3U), 44.5mm, 60mm
H,W,D IOBGP: 106mm, 175mm, 18mm
Mounting SC100: rectifier slot or flush panel mount
Orientation: vertical or horizontal
IOBGP: panel mount
Datalogging
Event Log 100 records
Indicators Power on
Urgent alarm
Non-Urgent alarm
Data Logging 10,000 record event log
10,000 record data log
Single Bay
Technical Specification
Dimensions
(H, W, D)
Overall Single bay: 1500mm x 1650mm x 600mm
Double bay: 1500mm x 2240mm x 600mm
Equipment bay(s) 1330mm x 660mm x 500mm
Single bay: 1 x 27RU 19”/23”, 1 x 48SU, 21”
(ETSI)
Double bay: 2 x 27RU 19”/23”, 2 x 48SU, 21”
(ETSI)
MDF bay 1330mm, 630mm, 300mm
1 x 48SU (ETSI 21”)
Space 2000 pairs R&M disconnect
Battery bay 1330mm, 300mm, 630mm
Suits 2 x 48V x 150Ah FT type
Cable access
Cable Entry 3 x removable panels
Environmental
Thermal 1300W per 10°C above ambient (in equipment
Performance chamber)
External Ambient -40°C to +45°C
Temperature
IP Rating IP56 (equipment bay)
IP54 (MDF and battery bay)
Seismic Rating 2g in any direction
Construction
Cabinet 2.5mm marine grade aluminum
Base 5mm MS hot dipped galvanized
Color/Finish Anti-graffiti green or beige, powder-coat
Pedestal Enclosure™
Typical applications include micro- Features
rollouts or expansion for
Broadband, POTS and IP. It is • No concrete plinth - single
ideally suited where the existing visit installation
cabinet infrastructure is full to • Low audible noise
capacity.
• Dual skin design to enhance
The design of the base eliminates environmental protection
the need for a concrete plinth,
• Sealed air to air heat exchanger
reducing installation time and cost.
designed with thermostatically
The double skin equipment bay, controlled DC fans giving
with internal heat exchangers, is 450W heat dissipation with
ideal where equipment is being only 10°C internal temperature
installed in a hostile environment. rise
When fitted with the Eaton® range • 12RU Equipment bay (300mm
of power and site monitoring deep)
hardware, full visibility and control • Up to 400 line Krone
is possible. connections
• Battery space in base
• AC Switchboard
Technical Specification
Mechanical
Dimensions 1100mm(H) x 720mm(W) x 600mm(D)
Weight 60kg
Internal space
Rack Units 19” ANSI, 16RU total
IP Rating IP56 protection to equipment chamber
Construction
Outer Roto molded Polyethylene, UV Stabilized
Base Material Roto molded Polyethylene, UV Stabilized
Inner Marine Grade Aluminum
Colors Off-white, Green
Options
DC Power System Eaton EPS DC Power System
Batteries Eaton front terminal batteries