CO2 latent heat of fusion 247 btu/lb. (@ 1 Atm.

) latent heat of fusion is for dry ice


50lb bottle of CO2 yeilds 12350 btu/bottle liquid to gas =122 btu/lb

Walk-in Size:
Width 20 ft
Depth 40 ft
Height 8 ft
Wall surface area 960 ft^2
Floor/ceiling surface area 1600 ft^2
Total Surface Area 2560 ft^2

Insulation "R" Value 20


0.05 btu/(h*ft^2*°F)

Exterior temp: 75 °F
Walk-in temp: 32 °F
Delta T is: 43 °F

Heat loss is: 5504 btu/hr

CO2 usage is: 2.24382267442 hr/bottle


or.... 0.44566801619 bottles/hr

24 hour protection... 10.6960323887 50lb. bottles