MSD Electricity Approved Drawings MMR Block-I

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

NOTES

COVERED AREA & FEES SCHEDULE PLOT LIMIT 1. ALL DIMENSIONS ARE IN METERS, UNLESS OTHERWISE SHOWN.
COORDINATES 2.ALL LEVELS AND COORDINATES ARE IN METERS.

N
S/S 1 346517.1582 2800166.7612
33/11 K.V
7275 2 346511.5086 2800158.5110

10.00M 3 346508.9076 2800172.4117

4 346503.2580

10.00M
2800164.1614
10.00M

PLOT 7676
7130 MMR
10.00M
67.00m WIDE ROAD MEET ME ROOM
COORDINATES
A 346513.2708 2800166.3934

B 346510.1635 2800161.8562

C 346509.1452 2800169.2189

D 346506.0381 2800164.6815

10.00
PLOT LIMIT
PLOT LIMIT
2.00 5.50 2.50
Proposed Boundary Wall
4 3

GRAVEL
2.00

INTERLOCK CAT LADDER

D C

CASE ID: 1080269008


GENERAL ELECTRICAL LEGEND
NOTE: - LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR
- ALL LIGHT FIXTURE MUST BE AS PER CLIENT APPROVAL

+6.05m SYMBOL DESCRIPTION REMARKS


+6.05m
TOP OF PARAPET
Proposed Boundary Wall

GRAVEL

Proposed Boundary Wall


ADVISABLE
TOP OF PARAPET TRANSFORMER

M.D.B. 2000mm FROM FFL


(MAIN DISTRIBUTION BOARD)

S.M.D.B.

PROPOSED MMR (SUB MAIN DISTRIBUTION BOARD)


2000mm FROM FFL
Plot 7130

D.B. 2000mm FROM FFL


( DISTRIBUTION BOARD)
5.00

"GROUND FLOOR ONLY" GRAVEL ISOLATOR W/P SINGLE PH. & 3 PH.
2000mm FROM FFL
10.00

KWH KILO WATT-HOUR METER 2000mm FROM FFL


INTERLOCK INTERLOCK CT 1,3PH
+4950 13 A. SWITCHED SOCKET OUTLET, DOUBLEX 450mm FROM FFL
13 A. REFRIGRETOR SOCKET OUTLET 1250mm FROM FFL
SSL. 13A. SWITCHED SOCKET & SHAVER OUTLET
WEATHER PROOF (W/P) IP 65
1500mm FROM FFL
(IN & NEAR WET AREA)

15A. SWITCHED SOCKET & COOKER OUTLET


450mm FROM FFL

FLOOR BOX CONTAINS 13A DOUBLE SOCKET, TEL & SMATV SOCKET FLOOR FLUSH

WATER HEATER WITH FLEXIBLE OUTLET BELOW CEILING

MDB−MMR ONE, TWO, THREE, GANG LIGHTING SWITCH, DP SWITCH


TIMER SWITCH ,45A COOKER SWITCH, BELL SWITCH 1400mm FROM FFL

ONE, TWO, THREE GANG TOW WAY LIGHTING SWITCH

A
1400mm FROM FFL

B EARTH PIT DIMMER SWITCH 1400mm FROM FFL


Rev By Checked Approved Date Description
+0.300 INTERLOCK
EP
CANOPY MOTION SENSOR @360 DEGREE COVERING 12M C E I L ING

60x60x80CM MANHOLE MH S B SIGNBOARD ISOLATOR ADVISABLE


PROJECT:
INTERLOCK TYPE WITH H.D 1X20WATT @ 2FT LED SURFACE/BATTEN FITTING WITH

RECESS COVER
+0.300 BUILT IN LED DRIVER, HOUSING MADE OF HEAT-RESISTANT PC MATERIAL
LUMINIARE WITH PC DIFFUSER,230V AC,IP-44,IP-55, 35000 HOURS.
SURFACE CEILING/
WALL MOUNTED
PAVEMENT
PROPOSED MMR+ COMP. WALL
MANUFACTURER MUST BE SEWA VENDOR LIST
AS PER CLIENT APPROVAL
3.00

2X20WATT @ 2FT LED SURFACE/BATTEN FITTING WITH


60mm THK. BUILT IN LED DRIVER, HOUSING MADE OF HEAT-RESISTANT PC MATERIAL SURFACE CEILING/
2x100mm uPVC DUCT LUMINIARE WITH PC DIFFUSER,230V AC,IP-44,IP-55, 35000 HOURS.
WALL MOUNTED
H.D UPVC PIPES MANUFACTURER MUST BE SEWA VENDOR LIST

+0.200
GRAVEL
UP
40W, LED LIGHT 230V AC ,RAYTEC SPZ LINEAR LIGHT

52W LED 4000K, POLYCARBONATE FITTING IP66


SURFACE MOUNTED

LOCATION: AL JADA DEVELOPMENT


SUSPENDED BELOW
RZB Germany , Model No: PLANOX 451166.009 CABLE LADDER

23W LED 4000K, POLYCARBONATE FITTING IP66,

RZB Germany , Model No: PLANOX 451161.009 SURFACE MOUNTED


AUTHORITY/CLIENT:
M PROPOSED METER
1% SLOPE

2 Proposed Boundary Wall


ENCLOSURE IP 65
1 22W LED 4000K, DIE CAST ALUMINUM IP65,

RZB Germany , Model No: ROUNDED MAXI 581639.004.1


WALL MOUNTED
1.00

1.00

+0.150
(WITH ALU.W/P COVER)
3.40
+0.150 10W LED WALL MOUNTED IMPACT
RESISTANCE, ANTI-CORROSIVE IP-56 LUMINAIRE
WALL MOUNTED
ABOVE MIRROR
PLOT LIMIT FOOTPATH LVL. FOOTPATH LVL. PLOT LIMIT 40 WATTS. 60X60 CM LED PANEL 230V AC,IP-44, 50,000 H
HOUSING MADE OF DIE-CASTED ALUMINIUM WITH POWDER COATING RECESSED CEILING
MAIN LUMINAIRE USES HIGH QUALITY REFLECTOR, LED DRIVER, MOUNTED

INCOMING CABLE ENTRANCE


LOUVER DIFFUSER

20W RECESSED 4000K LED DOWNLIGHT W/ CAST


±0.00 ALUMINUM BODY,WHITE IP 55
RECESSED CEILING

ROAD LVL. FROM SEW MOUNTED

ROAD 10W RECESSED/SURFACE MOUNT, 4000K LED SPOT LIGHT


W/ CAST ALUMINUM BODY,WHITE IP 55
RECESSED CEILING
MOUNTED

CHANDELIER LIGHT 100W LED


5X20W LED LIGHT 3000K/4000K LED SURFACED CEILING
MOUNTED
DEVELOPER:
20W RECESSED MOUNTED 3000K/4000K LED DOWNLIGHT
BODY, WHITE POLYCARBONATE BEZEL & WITH CAST RECESSED CEILING
ALUMINUM INTEGRAL LIGHT, IP-44 MOUNTED

20 W SURFACED DOWNLIGHT LUMINAIRE WITH


230V, 50HZ, WITH 20W LED LIGHT, WITH OPAL RING, IP-20 SURFACED CEILING
MOUNTED

SCALE 1:100mts 10W LED SURFACE MOUNTED DOWNLIGHT WITH SPUME ALUMINUM
AND PURE ALUMINUM DIAMOND FACED REFLECTOR,IP-44
SURFACED CEILING
MOUNTED

20W SURFACE MOUNTED DOWNLIGHT WITH SPUM ALUMINIUM


SURFACED CEILING
AND PURE ALUMINIUM DIAMONED FACED REFLECTOR,IP-44
MOUNTED

20W, LED, 230V ,HANSAGREEN SOLACE SOLID LIGHT ADVISABLE

40W, LED, 230V ,HANSAGREEN LUMIBROOK TP LIGHT


ADVISABLE

100 W LED HIGH-BAY (W/P) / STANDARD SURFACED CEILING


LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR

20W LED SPOT LIGHT (W/P) / STANDARD


MOUNTED

RECESSED CEILING
CIVIL DESIGN CONSULTANT:

INVESTMENT
LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR MOUNTED
114 WATT LED EXTERNAL WALL MOUNTED LIGHT W/P IP 65 4000K, DIE CASR ALUMINUM
6 METER HIGH FROM F.F.L
MAKE: RZB Germany Model No: LIGHTSTREAM MIDI 721720.114.1

200 W LED POLE LIGHT W/P , LUX CALCULATION ADVISABLE


SHALL BE SUBMITTED BY THE CONTRACTOR

150 W LED EXTERNAL LANDSCPAE LIGHT W/P IP 56, LUX


ADVISABLE
CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR

10 WATT/M LED STRIP LIGHT , LUX CALCULATION RECESSED IN


SHALL BE SUBMITTED BY THE CONTRACTOR

Engineering Consultancy
FALSE CEILING

CEILING FAN W/ OR W/O REGULATOR C E I L ING


F

TEL : +971 6 5737979 FAX : +971 6 5737779


INDUSTRIAL STEEL EXHAUST FAN 12''INCH DIA ADVISABLE P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae
INLINE EXHAUST FAN , AIR FLOW TO BE CALCULATION ABOVE FLASE
TO BE SUBMITTED FOR CONSULTANT APPROVAL CEILING
WALL/WINDOW MOUNTED
ADVISABLE
MANAGEMENT CONSULTANT:
EXHAUST FAN 6''/8''

R1 V V
S
VOLT METER WITH SELECTOR ADVISABLE

A A
S AMMETER WITH SELECTOR ADVISABLE

PILOT LIGHTS ADVISABLE

COOKER HOOD 100WATT AS PER KITCHEN


CABINET LAYOUT

DOOR BELL CHIME 10WATT 2000mm AFFL

FIRE RESISTANCE ADVISABLE

WEATHER PROOF ADVISABLE

ADVISABLE
MAIN CONTRACTOR:
LIGHTS GRID SWITCH

ADVISABLE , Subject to
LIGHTS GRID SWITCH engineer's approval

TRACK LIGHT , LED 10W FOR EACH LIGHT, IP20 ADVISABLE , Subject to
engineer's approval

DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/01 INV 329
IMPORTANT NOTE:
1− LIGHT FIXTURES SHALL BE FIXED BELOW
CABLE LADDER BY USING THREAD ROD.

10.00
PLOT LIMIT PLOT LIMIT GENERAL ELECTRICAL LEGEND
NOTE: - LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR
PLOT BOUNDARY - ALL LIGHT FIXTURE MUST BE AS PER CLIENT APPROVAL

5.50 SYMBOL DESCRIPTION REMARKS

A B C TRANSFORMER

M.D.B.
ADVISABLE

2000mm FROM FFL


GRAVEL (MAIN DISTRIBUTION BOARD)

S.M.D.B. 2000mm FROM FFL


(SUB MAIN DISTRIBUTION BOARD)
+0.30m LEVEL
INTERLOCK 0.94 1.61 D.B.
( DISTRIBUTION BOARD)
2000mm FROM FFL

2000mm FROM FFL


ISOLATOR W/P SINGLE PH. & 3 PH.
CAT LADDER WP
+0.30m LEVEL KWH KILO WATT-HOUR METER 2000mm FROM FFL
CT 1,3PH
INTERLOCK 2.55
0.40 1.40 1.45 1.15 2.55 13 A. SWITCHED SOCKET OUTLET, DOUBLEX 450mm FROM FFL

01
13 A. REFRIGRETOR SOCKET OUTLET 1250mm FROM FFL
13A. SWITCHED SOCKET & SHAVER OUTLET 1500mm FROM FFL
WEATHER PROOF (W/P) IP 65 (IN & NEAR WET AREA)

0.70 15A. SWITCHED SOCKET & COOKER OUTLET

0.85
450mm FROM FFL

FLOOR BOX CONTAINS 13A DOUBLE SOCKET, TEL & SMATV SOCKET FLOOR FLUSH

1.70
ODF−6
ODF−2

ODF−1

ODF−5
WATER HEATER WITH FLEXIBLE OUTLET BELOW CEILING

PLOT BOUNDARY
ONE, TWO, THREE, GANG LIGHTING SWITCH, DP SWITCH

5.00
TIMER SWITCH ,45A COOKER SWITCH, BELL SWITCH 1400mm FROM FFL

GRAVEL
ONE, TWO, THREE GANG TOW WAY LIGHTING SWITCH 1400mm FROM FFL

1.45

OPEN RACK−2

OPEN RACK−2
OPEN RACK−1

OPEN RACK−1
DIMMER SWITCH 1400mm FROM FFL

MOTION SENSOR @360 DEGREE COVERING 12M C E I L ING

MMR ROOM

5.00
S B SIGNBOARD ISOLATOR ADVISABLE
10.00
F.F.L +0.75m

GRAVEL
FINISH AS PER SCHED. 1X20WATT @ 2FT LED SURFACE/BATTEN FITTING WITH
BUILT IN LED DRIVER, HOUSING MADE OF HEAT-RESISTANT PC MATERIAL SURFACE CEILING/
LUMINIARE WITH PC DIFFUSER,230V AC,IP-44,IP-55, 35000 HOURS. WALL MOUNTED
MANUFACTURER MUST BE SEWA VENDOR LIST

Y1/DB-GF

ODF−3

ODF−8
ODF−4

ODF−7
1.45
2X20WATT @ 2FT LED SURFACE/BATTEN FITTING WITH
BUILT IN LED DRIVER, HOUSING MADE OF HEAT-RESISTANT PC MATERIAL SURFACE CEILING/
2.55
02
LUMINIARE WITH PC DIFFUSER,230V AC,IP-44,IP-55, 35000 HOURS.
WALL MOUNTED
MANUFACTURER MUST BE SEWA VENDOR LIST

2.55 40W, LED LIGHT 230V AC ,RAYTEC SPZ LINEAR LIGHT SURFACE MOUNTED

+0.30m LEVEL
R1/DB-GF INTERLOCK 52W LED 4000K, POLYCARBONATE FITTING IP66
SUSPENDED BELOW
0.65

0.85
RZB Germany , Model No: PLANOX 451166.009 CABLE LADDER

MDB−MMR 23W LED 4000K, POLYCARBONATE FITTING IP66,

DB−U−GF DB−GF
0.85 CANOPY RZB Germany , Model No: PLANOX 451161.009 SURFACE MOUNTED

03 0.60 0.45 0.45


22W LED 4000K, DIE CAST ALUMINUM IP65,

RZB Germany , Model No: ROUNDED MAXI 581639.004.1


WALL MOUNTED

10W LED WALL MOUNTED IMPACT WALL MOUNTED


RESISTANCE, ANTI-CORROSIVE IP-56 LUMINAIRE ABOVE MIRROR
F.F.L +0.75m
FINISH AS PER SCHED.
CANOPY 40 WATTS. 60X60 CM LED PANEL 230V AC,IP-44, 50,000 H
HOUSING MADE OF DIE-CASTED ALUMINIUM WITH POWDER COATING RECESSED CEILING
LUMINAIRE USES HIGH QUALITY REFLECTOR, LED DRIVER, MOUNTED
LOUVER DIFFUSER

5.50 RAMP 20W RECESSED 4000K LED DOWNLIGHT W/ CAST


ALUMINUM BODY,WHITE IP 55
RECESSED CEILING
MOUNTED

+0.30m 10W RECESSED/SURFACE MOUNT, 4000K LED SPOT LIGHT


RECESSED CEILING
W/ CAST ALUMINUM BODY,WHITE IP 55
PAVEMENT MOUNTED
+0.20m LEVEL
GRAVEL 60mm THK. LIGHT FIXTURE MOUNTED CHANDELIER LIGHT 100W LED
B1/DB-GF 5X20W LED LIGHT 3000K/4000K LED SURFACED CEILING
ON BOUNDARY WALL WITH MOUNTED
(CONTROLLED VIA TIMER &
DEOCRATIVE POLES (IP65) 20W RECESSED MOUNTED 3000K/4000K LED DOWNLIGHT
MANUAL OVERRIDE SWITCH) BODY, WHITE POLYCARBONATE BEZEL & WITH CAST
ALUMINUM INTEGRAL LIGHT, IP-44
RECESSED CEILING
MOUNTED

20 W SURFACED DOWNLIGHT LUMINAIRE WITH


230V, 50HZ, WITH 20W LED LIGHT, WITH OPAL RING, IP-20 SURFACED CEILING

± 0.00m UP MOUNTED

1% SLOPE
10W LED SURFACE MOUNTED DOWNLIGHT WITH SPUME ALUMINUM
SURFACED CEILING
ROAD LVL. AND PURE ALUMINUM DIAMOND FACED REFLECTOR,IP-44
MOUNTED

1.00
20W SURFACE MOUNTED DOWNLIGHT WITH SPUM ALUMINIUM
SURFACED CEILING

PLOT LIMIT 3.40 +0.150


FOOTPATH LVL. PLOT LIMIT
AND PURE ALUMINIUM DIAMONED FACED REFLECTOR,IP-44
MOUNTED

20W, LED, 230V ,HANSAGREEN SOLACE SOLID LIGHT ADVISABLE


MAIN
ENTRANCE 40W, LED, 230V ,HANSAGREEN LUMIBROOK TP LIGHT
ADVISABLE
±0.00
ROAD LVL. ROAD 100 W LED HIGH-BAY (W/P) / STANDARD
LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR
SURFACED CEILING
MOUNTED

20W LED SPOT LIGHT (W/P) / STANDARD RECESSED CEILING


LUX CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR MOUNTED
114 WATT LED EXTERNAL WALL MOUNTED LIGHT W/P IP 65 4000K, DIE CASR ALUMINUM
6 METER HIGH FROM F.F.L
MAKE: RZB Germany Model No: LIGHTSTREAM MIDI 721720.114.1

200 W LED POLE LIGHT W/P , LUX CALCULATION ADVISABLE


SHALL BE SUBMITTED BY THE CONTRACTOR

150 W LED EXTERNAL LANDSCPAE LIGHT W/P IP 56, LUX


ADVISABLE

MMR ROOM PLAN


CALCULATION SHALL BE SUBMITTED BY THE CONTRACTOR

10 WATT/M LED STRIP LIGHT , LUX CALCULATION RECESSED IN


SHALL BE SUBMITTED BY THE CONTRACTOR FALSE CEILING

CEILING FAN W/ OR W/O REGULATOR C E I L ING

CASE ID: 1080269008


F

INDUSTRIAL STEEL EXHAUST FAN 12''INCH DIA ADVISABLE

INLINE EXHAUST FAN , AIR FLOW TO BE CALCULATION ABOVE FLASE


TO BE SUBMITTED FOR CONSULTANT APPROVAL CEILING
WALL/WINDOW MOUNTED
ADVISABLE
EXHAUST FAN 6''/8''

R1 V V
S
VOLT METER WITH SELECTOR ADVISABLE

A A
S AMMETER WITH SELECTOR ADVISABLE

PILOT LIGHTS ADVISABLE

COOKER HOOD 100WATT AS PER KITCHEN


CABINET LAYOUT

DOOR BELL CHIME 10WATT 2000mm AFFL

FIRE RESISTANCE ADVISABLE

WEATHER PROOF ADVISABLE

LIGHTS GRID SWITCH ADVISABLE

ADVISABLE , Subject to
LIGHTS GRID SWITCH engineer's approval

10.00 TRACK LIGHT , LED 10W FOR EACH LIGHT, IP20 ADVISABLE , Subject to
engineer's approval

PLOT LIMIT PLOT LIMIT


Rev By Checked Approved Date Description
PLOT BOUNDARY
5.50 PROJECT:
A B C
GRAVEL PROPOSED MMR+ COMP. WALL
B3/DB-GF +0.30m LEVEL
ISO FOR SPLIT AC
AC-MMR 02
32A ISO
INTERLOCK
FOR ACCESS
CONTROL PANEL
C6/DB-U-GF
FOR CCTV SYSTEM SERVER LOCATION: AL JADA DEVELOPMENT
C7/DB-U-GF CAT LADDER
+0.30m LEVEL
INTERLOCK
WP
AUTHORITY/CLIENT:
Y3/DB-GF

1.80
01 AC-MMR 01
32A ISO ACP
CCTV RACK
32A SERVER Y8/DB-GF
RYB5/DB-GF ISO
32A ISO C5/DB-U-GF
RYB6/DB-GF
ODF−6
ODF−2

ODF−1

ODF−5

C1/DB-U-GF
WP
PLOT BOUNDARY

5.00
GRAVEL

R7/DB-GF SPLIT UNIT A/C DUTY /


OPEN RACK−2

OPEN RACK−2
OPEN RACK−1

OPEN RACK−1

STAND BY CONTROL PANEL

DEVELOPER:
MMR ROOM
5.00
10.00

F.F.L +0.75m
GRAVEL

FINISH AS PER SCHED.


ODF−3

ODF−8
ODF−4

ODF−7

C11/DB-U-GF

02 C2/DB-U-GF C8/DB-U-GF
FOR FACP

+0.30m LEVEL
C3/DB-U-GF INTERLOCK
R7/DB-GF WP
C4/DB-U-GF
MDB−MMR FOR EXTERNAL CCTV
DB−U−GF DB−GF CAMERA (TYPICAL) CANOPY
03 WP
CIVIL DESIGN CONSULTANT:
EARTH PIT

INVESTMENT
R8/DB-GF C9/DB-U-GF
F.F.L +0.75m FOR ACCESS CONTROL
FINISH AS PER SCHED.
MH EP CANOPY

RAMP
5.50
2x100mm uPVC
DUCT
+0.30m Engineering Consultancy
PAVEMENT TEL : +971 6 5737979 FAX : +971 6 5737779
+0.20m LEVEL
60mm THK. P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
GRAVEL
www.investmentengineering.ae

C12/DB-U-GF C10/DB-U-GF MANAGEMENT CONSULTANT:


W/P W/P

± 0.00m UP
M METERING CABINET
1% SLOPE

ROAD LVL. PROPOSED METER


1.00

ENCLOSURE IP 65
(WITH ALU.W/P COVER)
PLOT LIMIT 3.40 +0.150
FOOTPATH LVL. PLOT LIMIT
INCOMING CABLE
FROM AUTHORITY MAIN
ENTRANCE
±0.00
ROAD LVL. ROAD
MAIN CONTRACTOR:

MMR ROOM PLAN


DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/02 INV 329
LEGEND:
EP - EQUIPMENT EARTH PIT

LEP - LIGHTNING PROTECTION EARTH PIT


Important Note: - TAPE TO TAPE JOINT

1− contractor to ensure to separate AC and DC Earthing in earthing layout. C - TAPE TO EQUIPMENT JOINT

- BAR COPPER TAPE DOWN CONDUCTOR TERMINATING IN


E
2− Earth pits shall be provided with weather−proof labels mentioning details to where connected. EARTH PIT LOCATED AT GROUND LEVEL.

DC - 3mm(D)x25mm(W) INSULATED COPPER TAPE TO LIGHTNING


3− Earth pit test reports approved by project consultant, where in the resistance being <1 ohm PROTECTION EARTH PIT
- 1CX70sq.mm PVC INSULATED COPPER CONDUCTOR

,shall be submitted as part of handing over documents. - 3mm(D)x25mm(W) BAR COPPER TAPE.

- LIGHTNING ARRESTER

- SQUARE TAPE CLAMP INSTALLED AT EVERY INTERSCECTION

CONCRETE EARTH INSPECTION HOUSING, PT005 (300X310X200mm)

8 WAY EARTH BAR WITH TWIN DISCONNECTING LINK (EDL-1&2)

NOTES:
PLOT LIMIT PLOT LIMIT 1. PROVIDE LABELS INSIDE EACH PIT FOR EARTH RODS SHOWING TYPE
10.00 AND SERIAL NO. OF RESPECTIVE EARTH ROD.
PLOT BOUNDARY
2. OBTAIN SOIL RESISTIVITY REPORT TO DETERMINE WHETHER SOIL
5.50 TREATMENT IS NECESSARY TO IMPROVE EARTH ELECTRODE CONTACT
A B C 1M LONG COPPER AIR TERMINAL ROD (RA225)
MULTI POINT (RA600) SUPPORTED WITH BASE (SD 105−H)
RESISTANCE IN COMPLIANCE WITH BS EN 62305 PARTS 1-4 FOR
LIGHTNING PROTECTION AND BS EN 62305 1-4: 2006 FOR EARTHING.
GRAVEL CONNECTED TO THE AIR TERMINATION NETWORK.
SEE DETAILS "B" 3. PROVIDE DEEP DRIVEN SOLID COPPER EARTH ROD ELECTRODES
+0.30m LEVEL WHERE CONDITIONS ALLOW TO ACHIEVE A LOW ELECTRICAL
INTERLOCK RESISTANCE.
ELP EP1
4. LIGHTNING CONDUCTORS SUPPORT SHOULD BE THROUGH BRASS
CAT LADDER ACCESSORIES.
+0.30m LEVEL 1C x 70mm ² PVC INSULATED
INTERLOCK 25x3mm COPPER TAPE COPPER CONDUCTOR DC 5. TAPE TO BE FIXED TO BACKGROUND USING PROPRIETARY FIXING,
25x3mm INSULATED COPPER INSPECTION PITS TO BE CAST IN TO THE GROUND, CONNECTIONS
01 TAPE TO LIGHTNING
PROTECTION EARTH PIT
TO MECH. EQUIPMENT.

EDL-02
DC

ODF−6
ODF−2

ODF−1

ODF−5
8 WAY EARTH BAR WITH
DISCONNECTING LINK TYPICAL
PLOT BOUNDARY

( SEE DETAIL−A )

5.00
GRAVEL

OPEN RACK−2

OPEN RACK−2
OPEN RACK−1

OPEN RACK−1
8 WAY EARTH BAR WITH
DISCONNECTING LINK TYPICAL
( SEE DETAIL−A ) EDL-01 MMR ROOM
F.F.L +0.75m

5.00

GRAVEL
FINISH AS PER SCHED.
EP2
10.00

ODF−3

ODF−8
ODF−4

ODF−7
+0.30m LEVEL
02 INTERLOCK SEE DETAILS "C"

1C x 70mm ² PVC INSULATED


COPPER CONDUCTOR 1M LONG COPPER AIR TERMINAL ROD (RA225)
MULTI POINT (RA600) SUPPORTED WITH BASE (SD 105−H)
MDB−MMR
CONNECTED TO THE AIR TERMINATION NETWORK. CANOPY
03 SEE DETAILS "B"

F.F.L +0.75m
EP3 EP4 FINISH AS PER SCHED.
CANOPY

RAMP
5.50
+0.30m
PAVEMENT
+0.20m LEVEL 60mm THK.
GRAVEL

CASE ID: 1080269008


UP
± 0.00m

1% SLOPE
ROAD LVL.

1.00
PLOT LIMIT 3.40 +0.150
FOOTPATH LVL. PLOT LIMIT
MAIN
ENTRANCE
±0.00
ROAD LVL. ROAD

MMR ROOM PLAN


Rev By Checked Approved Date Description

PROJECT:

PROPOSED MMR+ COMP. WALL


LOCATION: AL JADA DEVELOPMENT
AUTHORITY/CLIENT:

DEVELOPER:

CONNECTIONS TO EARTH PIT CONNECTIONS TO THE


EARTH BUS BAR
CABLE LUG
8WAY EARTH BAR CIVIL DESIGN CONSULTANT:
DISCONNECTING INVESTMENT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

TO CABLE TRAYS MANAGEMENT CONSULTANT:

CONNECTION TO RACKS

8WAY TWIN DISCONNECTING LINK TO THE EARTH BAR MAIN CONTRACTOR:

DETAIL-A

DRAWING TITLE

SQUARE TAPE CLAMP


DETAIL-B DETAIL-C
MULK - BLOCK:- SCALE:- 1/100
PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/03 INV 329
CASE ID: 1080269008

Rev By Checked Approved Date Description

PROJECT:

PROPOSED MMR+ COMP. WALL


LOCATION: AL JADA DEVELOPMENT
AUTHORITY/CLIENT:

DEVELOPER:

CIVIL DESIGN CONSULTANT:

INVESTMENT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

MANAGEMENT CONSULTANT:

MAIN CONTRACTOR:

DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/04 INV 329
CASE ID: 1080269008

Rev By Checked Approved Date Description

PROJECT:

PROPOSED MMR+ COMP. WALL


LOCATION: AL JADA DEVELOPMENT
AUTHORITY/CLIENT:

DEVELOPER:

CIVIL DESIGN CONSULTANT:

INVESTMENT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

MANAGEMENT CONSULTANT:

M
MAIN CONTRACTOR:

DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/05 INV 329
LEGEND

SYMBOLS DESCRIPTION

DOME TYPE FIXED CCTV CAMERA

Note: Contractor shall make only provisions for Access Control and CCTV. WALL MOUNTED WEATHER PROOF
DOME TYPE CAMERA

CR CARD READER

DC DOOR CONTACT

M MAGNETIC LOCK

BG BREAK GLASS

13 A SINGLE SOCKET NORMAL / WEATHER PROOF

20mm PVC CONDUIT FOR CCTV DATA CABLE

20mm PVC CONDUIT FOR CCTV SOCKET

ACP ACCESS CONTROL PANEL

NOTE:
· FOR CCTV & ACCESS CONTROL SYSTEM CONTAINMENT (PROVISION) ONLY.
· NECESSARY CONTAINMENT FOR SNMP CABLING SHOULD BE PROVIDED FOR
CCTV & ACCESS CONTROL SYSTEM REMOTE MONIROTING.

PLOT LIMIT PLOT LIMIT PLOT LIMIT PLOT LIMIT


10.00 10.00
PLOT BOUNDARY PLOT BOUNDARY

A B C A B C
GRAVEL GRAVEL
C6 DB−U−GF
+0.30m LEVEL SOCKET FOR CCTV +0.30m LEVEL C7 DB−U−GF
INTERLOCK SYSTEM SERVER INTERLOCK SOCKET FOR ACCESS
1X20mm GI CONTROL PANEL
FLEXIBLE CONDUIT CAT LADDER CAT LADDER
2X20mm PVC CONDUIT
+0.30m LEVEL 0.20 +0.30m LEVEL
INTERLOCK
FOR CCTV DATA CABLE INTERLOCK
0.40 0.20 1X20mm GI

01 FLEXIBLE CONDUIT
01 ACP
0.95

ACCESS CONTROL
PANEL 1.03
2.07 1.23 C5 DB−U−GF
C1 DB−U−GF 2X20mm PVC CONDUIT

ODF−6

ODF−6
ODF−2

ODF−1

ODF−5

ODF−2

ODF−1

ODF−5
2X20mm PVC CONDUIT FOR ACCESS CONTROL
CCTV RACK/ FOR CCTV SOCKET DATA CABLE
PLOT BOUNDARY

PLOT BOUNDARY
SERVER
GRAVEL

GRAVEL
1X20mm PVC CONDUIT
5X20mm PVC CONDUIT
FOR SOCKET OUTLET
OPEN RACK−2

OPEN RACK−2

OPEN RACK−2

OPEN RACK−2
FOR CCTV DATA CABLE
OPEN RACK−1

OPEN RACK−1

OPEN RACK−1

OPEN RACK−1
1X20mm PVC CONDUIT
FOR CCTV SOCKET MMR ROOM
F.F.L +0.75m
MMR ROOM
F.F.L +0.75m
C8 DB−U−GF
CASE ID: 1080269008

5.00

5.00
GRAVEL

GRAVEL
FINISH AS PER SCHED. FINISH AS PER SCHED.
10.00

10.00
0.65
BG
ODF−3

ODF−8

ODF−3

ODF−8
ODF−4

ODF−7

ODF−4

ODF−7

0.15
CR

0.15
+0.30m LEVEL +0.30m LEVEL
02 INTERLOCK
02 M DC
0.15 INTERLOCK

0.15
CR

C2 DB−U−GF C4 DB−U−GF
SOCKET FOR
DB−U−GF
CCTV CAMERA
0.40 1.30
BG
0.65
0.35

1.63 CR

03 DB−U−GF
1X20mm GI 03 0.15
CR
M DC

1.51 FLEXIBLE CONDUIT


0.22 1X20mm GI 0.66 F.F.L +0.75m
WP
F.F.L +0.75m
1X20mm GI FLEXIBLE CONDUIT 0.21 FINISH AS PER SCHED.
CANOPY 1X20mm PVC CONDUIT FINISH AS PER SCHED.
CANOPY
FLEXIBLE CONDUIT 3X20mm PVC CONDUIT FOR SOCKET OUTLET
C9 DB−U−GF
FOR CCTV SOCKET FLEX OUTLET FOR
ACCESS CONTROL
5.50 5.50
+0.30m +0.30m
2X20mm PVC CONDUIT
PAVEMENT PAVEMENT
+0.20m LEVEL +0.20m LEVEL FOR ACCESS CONTROL
GRAVEL 60mm THK. GRAVEL 60mm THK. Rev By Checked Approved Date Description
DATA CABLE

PROJECT:
WP DC C12 DB−U−GF W/P DC WP

UP UP
± 0.00m ± 0.00m 0.15 CR WP
PROPOSED MMR+ COMP. WALL
1% SLOPE

1% SLOPE
0.15 C10 DB−U−GF
ROAD LVL. ROAD LVL.
1.00

1.00
0.15

PLOT LIMIT 3.40 +0.150


FOOTPATH LVL. PLOT LIMIT PLOT LIMIT 3.40 +0.150
FOOTPATH LVL. PLOT LIMIT LOCATION: AL JADA DEVELOPMENT
MAIN MAIN
ENTRANCE ENTRANCE
±0.00 ±0.00 AUTHORITY/CLIENT:
ROAD LVL. ROAD ROAD LVL. ROAD

MMR ROOM PLAN MMR ROOM PLAN


GROUND FLOOR PLAN GROUND FLOOR PLAN DEVELOPER:

CCTV LAYOUT ACCESS CONTROL LAYOUT

CIVIL DESIGN CONSULTANT:

INVESTMENT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

MANAGEMENT CONSULTANT:

MAIN CONTRACTOR:

DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/06 INV 329
INSULATION TAP ELEC WIRE
LIQUID PIPE

GAS PIPE
200

1" RUBBER PIPE


INSULATION

CONDENSING UNIT
WALL MOUNTED

DETAIL−’B’

1/2"RUBBER PAD
FCU WALL MOUNTED TYPE
REMOTE 50x50x6mm ANGLE
1 DUTY +1 STANDBY AC UNIT CONTROL SPU−GF−01

CAPACITY 2TON EACH

10.00
50x50x6mm ANGLE
PLOT LIMIT PLOT LIMIT
(FOR LOCK)
PLOT BOUNDARY

A B C 5.50
50x50x6mm ANGLE
WALL MOUNTED
GRAVEL

+0.30m LEVEL 110mm Ø RWP (T/B)


CASE ID: 1080269008
CONDENSING UNIT INTERLOCK
SOAK PIT
32mm Ø CDP
Ø 300mm CAT LADDER

0.50
+0.30m LEVEL 110mm Ø RWP (F/A)
INTERLOCK FREE DISCHARGE
32mm Ø CDP T/B

01 SPU MMR 02
0.41

SPU MMR 01
(STANDBY) +0.750
CONDENSATE
(DUTY) CONDENSATE
GF LEVEL
ODF−6
ODF−2

ODF−1

ODF−5

DRAIN PAN
DRAIN PAN
PLOT BOUNDARY

0
10
SPLIT UNIT A/C DUTY / 1:
GRAVEL

STAND BY CONTROL PANEL PE

5.00
O
OPEN RACK−2

OPEN RACK−2

SL
OPEN RACK−1

OPEN RACK−1

+0.300
MMR ROOM
5.00

PAV. LEVEL
10.00

F.F.L +0.75m
GRAVEL

FINISH AS PER SCHED.


REMOTE
CONTROLLER
ODF−3

ODF−8
ODF−4

ODF−7

Rev By Checked Approved Date Description

02 PROJECT:
+0.30m LEVEL
INTERLOCK

PROPOSED MMR+ COMP. WALL


03 CANOPY SECTION-A LOCATION: AL JADA DEVELOPMENT
F.F.L +0.75m
FINISH AS PER SCHED.
CANOPY AUTHORITY/CLIENT:

5.50
+0.30m RAMP
+0.20m LEVEL PAVEMENT
GRAVEL 60mm THK.

± 0.00m UP
DEVELOPER:
1% SLOPE

ROAD LVL.
1.00

PLOT LIMIT 3.40 +0.150


FOOTPATH LVL. PLOT LIMIT AC LAYOUT
MAIN
ENTRANCE
±0.00
ROAD LVL. ROAD

CIVIL DESIGN CONSULTANT:


MMR ROOM PLAN INVESTMENT
AC LAYOUT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

MANAGEMENT CONSULTANT:

MAIN CONTRACTOR:

DRAWING TITLE

MULK - BLOCK:- SCALE:- 1/100


PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/08 INV 329
PLOT LIMIT PLOT LIMIT
10.00
PLOT BOUNDARY

A B C 10.00
GRAVEL

+0.30m LEVEL 3.00 5.00 2.00


A INTERLOCK
-
450mm GI. H.D CABLE LADDER AT
0.76 0.30 0.30 0.80 0.30 0.30
CAT LADDER HIGH LEVEL FOR DATA (TYPICAL)
+0.30m LEVEL 2.34
INTERLOCK

01

0.60
0.80
0.30
OSP CABL ENTRY

D54 DUCT PIPE 6 NOS (TYPICAL)

0.60

0.60
ODF−6
ODF−2

ODF−1

ODF−5
PLOT BOUNDARY

B B
-

-
GRAVEL

1.20
1000mm GI. H.D CABLE

OPEN RACK−2

OPEN RACK−2
OPEN RACK−1

OPEN RACK−1
LADDER RISER (TYP)

4.80
1.00

450mm GI. H.D CABLE LADDER AT


MMR ROOM HIGH LEVEL FOR DATA (TYPICAL)
F.F.L +0.75m
0.90 1.20 1.00 1.20 0.30

5.00

GRAVEL
FINISH AS PER SCHED.

3.40
10.00

450mm GI. H.D CABLE


ODF−3

ODF−8
ODF−4

ODF−7
1.20

+0.30m LEVEL LADDER RISER (TYP.)

02 ODF−3 OPEN RACK−1 ODF−1

2.20
INTERLOCK
0.94

1000mm GI. H.D CABLE

1.00
LADDER RISER (TYP.) MMR ROOM
0.90

1000mm GI. H.D CABLE


LADDER RISER (TYP)

0.30
03
-

1.00
D54 DUCT PIPE F.F.L +0.75m
6 NOS (TYPICAL) A FINISH AS PER SCHED.
CANOPY 1000mm (MIN.)
TURNING RADIUS BEND
OSP CABLE ENTRY

5.50
+0.30m D54 DUCT PIPE 6 NOs
PAVEMENT (TYPICAL)
+0.20m LEVEL
GRAVEL 60mm THK. 2 SECTION A-A
- SCALE: 1:50

UP
± 0.00m
1% SLOPE

ROAD LVL.
1.00

PLOT LIMIT 3.40 +0.150


FOOTPATH LVL. PLOT LIMIT
MAIN
ENTRANCE
±0.00
ROAD LVL. ROAD
CASE ID: 1080269008
MMR ROOM PLAN
DATA CONTAINMENT LAYOUT

Rev By Checked Approved Date Description

PROJECT:

10.50 PROPOSED MMR+ COMP. WALL


3.00 5.50 2.00 LOCATION: AL JADA DEVELOPMENT
SCREWED EXPANSION AUTHORITY/CLIENT:

450mm GI. H.D CABLE LADDER AT


INSERT
0.60

HIGH LEVEL FOR DATA (TYPICAL)


0.80

THREADED SUSPENSION
ROD SUPPORTS
0.60

600MM
1.20

0.30 0.30
0.76 0.30 0.80 0.30 2.34
HEAVY DUTY DEVELOPER:
CABLE LADDER
4.80

4.00

GALVANIZED 'L' CHANNEL


450mm GI. H.D CABLE
LADDER RISER (TYP.)
ODF−6
ODF−1
ODF−2

ODF−5

2.20

1000mm GI. H.D CABLE


1.00

MMR ROOM LADDER RISER (TYP.)

CIVIL DESIGN CONSULTANT:


0.30

5
-
CABLE LADDER HANGING DETAIL
SCALE: N.T.S
INVESTMENT
D54 DUCT PIPE 6 NOS
(TYPICAL)

Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

2 SECTION B-B MANAGEMENT CONSULTANT:


- SCALE: 1:50

MAIN CONTRACTOR:

DRAWING TITLE

MMR ROM PLAN


DATA CONTAINMENT LAYOUT
MULK - BLOCK:- SCALE:- 1/100
PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/07 INV 329
CASE ID: 1080269008

Rev By Checked Approved Date Description

PROJECT:

PROPOSED MMR+ COMP. WALL


LOCATION: AL JADA DEVELOPMENT
AUTHORITY/CLIENT:

DEVELOPER:

CIVIL DESIGN CONSULTANT:

INVESTMENT
Engineering Consultancy
TEL : +971 6 5737979 FAX : +971 6 5737779
P.O.BOX : 1388, SHARJAH , UAE EMAIL : investment.shj@gmail.com
www.investmentengineering.ae

MANAGEMENT CONSULTANT:

MAIN CONTRACTOR:

DRAWING TITLE

PREVIOUS APPROVED MODEL


MULK - BLOCK:- SCALE:- 1/100
PLOT NO:-
GOV. 7676 MUWAILEH COMM'L. SHEET SIZE: A2
DESIGNED BY:- CORDINATED BY:- APPROVED BY:- DATE:-
E. JALAL E.ALAA OUSAMA E.KHALID ALZ 11-2022
DRAWN BY:- DRAWING NO. :- JOB NO. :-
INEC TEAM EL/MMR/08 INV 329