Fault Ride-through Demand of Large-scale Islanded

Renewable Energy Connected to VSC-HVDC


System and Its Key Technologies
Yan Li Hongzhi Liu * Yongning Chi
China Electric Power Research Institute China Electric Power Research Institute China Electric Power Research Institute
China State Key Laboratory of Operation and China State Key Laboratory of Operation and China State Key Laboratory of Operation and
Control of Renewable Energy & Storage Control of Renewable Energy & Storage Control of Renewable Energy & Storage Systems
Systems Systems Beijing, China
Beijing, China Beijing, China chiyn@epri.sgcc.com.cn
liyan@epri.sgcc.com.cn *liuhongzhi@epri.sgcc.com.cn

Yiwen Fan Xiangyu Li * Fan Cheng


China Electric Power Research Institute School of Electrical and Electronic China Electric Power Research Institute
China State Key Laboratory of Engineering China State Key Laboratory of Operation
Operation and Control of Renewable North China Electric Power University and Control of Renewable Energy &
Energy & Storage Systems Beijing, China Storage Systems
Beijing, China *cumtlixiangyu@163.com Beijing, China
18810263095@163.com chengfan5566@163.com

Zhibing Wang Chunxia Wei Lijun Xie


China Electric Power Research Institute China Electric Power Research Institute China Electric Power Research Institute
China State Key Laboratory of China State Key Laboratory of China State Key Laboratory of Operation
Operation and Control of Renewable Operation and Control of Renewable and Control of Renewable Energy &
Energy & Storage Systems Energy & Storage Systems Storage Systems
Beijing, China Beijing, China Beijing, China
wangzhibing@epri.sgcc.com.cn weichunxia@epri.sgcc.com.cn liju-xie@163.com

Abstract—The adaptability of renewable energy connected


to the VSC-HVDC grid will become an important issue
affecting grid operation. In particular, the complex interaction I. INTRODUCTION
between renewable power generation and the power grid
brings new challenges to the renewable power generation and When large-scale islanded renewable energy is connected
VSC-HVDC grid to achieve fault ride-through. Therefore, it is to the VSC-HVDC grid and the VSC-HVDC technology is
necessary to study the fault ride-through strategies of the VSC- used for long-distance transmission, the operation
HVDC grid-renewable power generation combined system. characteristics of renewable energy and the VSC-HVDC grid
According to the operating characteristics and adaptability of will affect each other. The adaptability of renewable energy
renewable energy clusters connected to the VSC-HVDC grid connected to the VSC-HVDC grid will become an important
under different faults, this paper proposes technical issue affecting grid operation. In particular, the complex
requirements for high- / low-voltage fault ride-through of interaction between renewable energy power generation and
renewable power plants that are connected to the grid in island the power grid brings new challenges to the renewable power
operation, and analyzes key technologies for renewable power generation and VSC-HVDC power grid. Therefore, it is
generation dealing with AC faults at the sending end of the necessary to study the fault ride-through scheme of the VSC-
grid in island integration mode. It is expected to realize joint HVDC grid-renewable energy generation combined system.
fault ride-through of renewable energy and VSC-HVDC,
According to the operating characteristics and adaptability of
thereby increasing the availability of the system, contributing
renewable energy clusters connected to the VSC-HVDC
to the safe and stable operation of renewable energy and VSC-
HVDC grid, providing technical support for the planning of
power grid under different faults, this paper proposes
large-scale renewable energy delivery methods, and effectively technical requirements for high- / low-voltage fault ride-
guiding the planning and design of renewable energy and VSC- through of renewable power plants that are connected to the
HVDC grid grid in island operation, and analyzes key technologies for
renewable power generation dealing with AC faults at the
Keywords- fault ride-through; islanded large-scale sending end of the grid in island integration mode. It is
renewable energy; VSC-HVDC expected to realize joint fault ride-through of renewable
energy and VSC-HVDC, thereby increasing the availability

978-1-7281-7593-5/20/$31.00 ©2020 IEEE 1248

Authorized licensed use limited to: Rutgers University. Downloaded on May 15,2021 at 15:06:14 UTC from IEEE Xplore. Restrictions apply.
of the system, contributing to the safe and stable operation of operating characteristics of the wind turbine and the grid
renewable energy and VSC-HVDC power grids, providing code requirements, the control up / down voltage limit was
technical support for the planning of large-scale renewable designed to obtain a more ideal fault ride-through effect,
energy delivery methods, and effectively guiding the while further reducing the system cost. Literature [6]
planning and design of renewable energy and VSC-HVDC proposed a nine-switch converter topology for VSC-HVDC
grids. transmission, thereby enhancing the system's fault ride-
through characteristics. Literature [7] proposed a new low-
voltage ride-through control strategy based on power line
II. CURRENT STUDY OF FAULT RIDE-THROUGH FOR communication for the dual-star chopper unit MMC
LARGE-SCALE ISLANDED RENEWABLE ENERGY CONNECTED converter, which had better fault ride-through performance.
TO VSC-HVDC SYSTEM However, the above-mentioned literatures only studied the
The use of VSC-HVDC to connect islanded renewable basic AC fault ride-through strategies of the VSC-HVDC
energy to the grid will form a weakly supported, fast- system, and the specific research strategies for the special
dynamic islanded exchange system dominated by power working condition of the renewable energy islanded system
electronics. The complex electromagnetic transient processes at the sending end converter station were not presented.
of wind farms and power grids make the system's fault Relatively many studies by foreign scholars have been
response extremely complicated. At the same time, it also done on low-voltage ride-through technology for large-scale
brings new challenges to the AC fault ride-through of the renewable power plants connected to the grid via VSC-
remote islanded AC system of renewable energy. HVDC with the flexible control characteristics of the
converter in which the inverter is able to reduce its active
A. Interaction between wind farm and grid-connected power output and increases its reactive output during grid
system under AC fault faults. The following control strategies can be combined to
A series of researches has been done by domestic and obtain the ideal fault ride-through effect:
overseas scholars on the interactive effects of wind farm grid x Install energy dissipation or unloading resistors,
connection under various AC disturbances. Literature [1] energy storage devices, etc., on the DC line to absorb
analyzed and simulated the short-circuit fault characteristics unbalanced power so as to maintain the DC bus
of the system before and after the wind power was connected voltage stability [8].
to the grid. It was found that the short-term oscillation of the x Install energy dissipation or unloading resistors,
system voltage and current caused by the short-circuit failure energy storage devices, etc., on the power station
of the system after the wind power was connected was side to absorb unbalanced power [9].
greater; the harmonic distortion was higher; and the voltage x Improve the power control strategy of wind turbines
occurrence of flicker was also more pronounced. The to reduce the wind turbine active power output and
literature [2] analyzed the basic principles and response increase the reactive power output during the low-
situation of the short-circuit fault of the power grid, the DC voltage ride-through period [10-13].
side fault, the common fault of the generator, the wind At present, the research on low-voltage ride-through
turbine variable distance fault, and the inverter fault. The technology for renewable power plants connected to the grid
literature [3] deeply studied the fault handling and protection via VSC-HVDC is mostly based on the electromagnetic
technology of VSC-HVDC transmission lines. However, the transient modeling and analysis of single machines
above literatures aimed at the system impact of VSC-HVDC connected to infinite systems via VSC-HVDC and multi-
converter stations caused by certain specific faults, but not terminal VSC-HVDC systems. In the application scenario of
the impact of wind farms on grid-connected systems when centralized development of large-scale renewable energy,
AC faults occurred. At the same time, there is also a lack of which is collected through the VSC-HVDC grid and sent
related research on the impact of grid-connected systems on over a long distance, it is obvious that the measures of
wind farm fault ride-through under AC faults. installing energy dissipation or unloading resistance on the
VSC-HVDC side and installing super capacitors on a single
B. AC fault ride-through technology for large-scale VSC-HVDC line are not applicable. The existing GB /
renewable energy integration via VSC-HVDC T19963 "Technical Regulations for Wind Farm Connect to
Some scholars have also conducted research on fault Power System" and GB / T19964 "Technical Regulations for
ride-through technologies for wind farm grid-connection via Connect to Power System for Photovoltaic Power Stations"
VSC-HVDC. Literature [4] proposed a new method to based on AC grid faults may need to be modified when
improve the fault ride-through capability of a VSC-HVDC applied to the VSC-HVDC grid.
based wind farm grid-connection system, that is, for the So far, domestic and foreign scholars have done
current disturbance process. A current limiter that relatively little researches on the dynamic analysis and
dynamically changed the limit was designed to limit the interactive effects of AC faults at the sending terminal of the
overcurrent and maximize the output power. Literature [5] VSC-HVDC grid connected with renewable energy. The
proposed a coordinated control strategy for fault ride-through research of fault ride-through technology is mostly based on
of a VSC-HVDC based grid-connection system of a hybrid the electromagnetic transient modeling and analysis of a
wind farm composed of doubly-fed induction wind turbines single machine connected to an infinite system via VSC-
and asynchronous wind turbines. According to the actual HVDC. There is little discussion on the transmission-side

1249

Authorized licensed use limited to: Rutgers University. Downloaded on May 15,2021 at 15:06:14 UTC from IEEE Xplore. Restrictions apply.
AC fault ride-through technology for a large-scale islanded the power surplus of this faulty working condition, and the
renewable energy connected to VSC-HVDC grid. AC chopper device can simultaneously solve the two types
Because the VSC-HVDC converter station of the DC grid of faulting working conditions: receiving terminal converter
connected to the islanded system adopts a constant AC station failure and sending terminal converter station single
voltage control method, overvoltage and overcurrent are pole failure. Therefore, the AC chopper is recommended in
likely to occur during the AC voltage drop or recovery in the the project to solve the power surplus problem.
islanded system that causes the trip of the converter. 
AC
Choppe r
Renewable power plants will trip off while losing AC
voltage to support. Based on the analysis of the
characteristics of the interaction between the renewable
ℷᵕ
energy clusters and the VSC-HVDC grid, the adaptability of MMC
the fault ride-through capability of the renewable power
plants in the island operation mode under various AC faults
at the sending terminal is studied. At the same time, in the Ѹ⌕㒓䏃
case of large-scale islanded renewable energy integration,
under the premise that the island station is not isolated, in
order to prevent the wind farm from being disconnected from 䋳ᵕ
the grid when the AC fault at the sending terminal is MMC
occurred, the VSC-HVDC grid should take countermeasures.
AC
Chopper

III. KEY TECHNOLOGIES OF FAULT RIDE-THROUGH FOR Figure 1. Configuration diagram of energy dissipation device
LARGE-SCALE ISLAND RENEWABLE ENERGY CONNECTED TO
VSC-HVDC SYSTEM
B. Fault ride-through during AC faults in renewable
A. Energy dissipation devices energy systems
The VSC-HVDC grid adopts a bipolar symmetrical The above has briefly explained the configuration of AC
topology, and the basic operation mode of the sending- chopper in VSC-HVDC power grids. The fault ride-through
terminal converter station is the islanded renewable energy during the occurrence of AC faults in renewable energy
integration. Therefore, there will be a power surplus when systems specifically is related to the safety devices, control
the receiving-terminal converter fails or the sending-terminal and protection devices in the DC power grid system when
converter has a single pole failure. The time taken by the the transmission terminal system fails. When a valve-side
security system to detect the above faults and the system to AC fault in a single pole occurs at the sending terminal
cut off the wind farms is more than 100ms, which is too slow. islanded renewable energy system, the fault is mostly a
If no measures are taken, the DC voltage of the DC grid and permanent serious fault. The control and protection device
the AC line voltage of the converter station connecting will detect a serious overcurrent fault in the faulty pole
islanded renewable energy will increase, which will cause converter and immediately block the faulty pole converter.
grid crash and shut down. The system protection may even At the same time, the AC and DC circuit breakers
damage the power electronic equipment at the converter corresponding to the fault pole converter will be opened. The
station in severe cases. control and protection devices also need to detect the total
The most reasonable solution to the problem of power power transmitted by the converters of the two poles before
surplus is to install energy dissipation devices in the DC grid the fault (that is, the power generated by the renewable
system. When the receiving terminal converter station fails power generation clusters), and a certain number of AC
or the sending terminal converter station has a single pole chopper devices need to be equipped according to a certain
failure (including valve-side AC fault), the surplus power switching strategy to ensure the transmission power of
can be consumed by putting the energy dissipation devices normal pole converter not to be overloaded, thereby ensuring
in service, thereby maintaining system stability. When the that there is no surplus problem in the DC grid system.
system is shut down, the energy dissipation device is out of The control and protection device shall immediately
service after the system is stabilized, and the system resumes upload the dispatching system and security system after
normal operation. detecting a single pole valve-side AC failure in the sending
Energy dissipation devices are divided into DC energy terminal renewable energy island system. The security
dissipation devices (DC chopper) and AC energy dissipation device needs to be processed according to the system
devices (AC chopper). Considering various faults in the DC operating status and fault information of the VSC-HVDC
power grid when a single pole fault occurs at the transmitting grid. The total number of cuts for the renewable power
station of the system, all the power corresponding to the plants and specific cut operation instructions need to be
faulty pole of the converter station will be automatically obtained, such as cutting off several times, and cutting off
transferred to the normal pole of the converter station, which the renewable power plant transmission line total power.
may cause power surplus problem in the normal pole. Under The cut-off action will be completed within 150ms, and the
this working condition, only using DC chopper cannot solve power surplus caused by AC failure at the send terminal's

1250

Authorized licensed use limited to: Rutgers University. Downloaded on May 15,2021 at 15:06:14 UTC from IEEE Xplore. Restrictions apply.
single pole valve side will be completely resolved. At this operation mode. Its fault ride-though curve and
time, the control device can detect the instantaneous decrease strategy meet the fault ride-though requirements and
in the total power of both poles (that is, the power generated qualitative analysis of its adaptive ability to fault
by the renewable power generation clusters) transmitted by ride-though.
the converter station, and perform the chopper quit operation x Finally, considering the typical fault forms,
accordingly. combined with the voltage boundary constraints of
the fault ride-though curve and the adaptability in the
island operation mode, the technical requirements
IV. KEY ISSUES OF FAULT RIDE-THROUGH FOR LARGE- for high and low voltage fault ride-through of island
SCALE ISLANDED RENEWABLE ENERGY CONNECTED TO renewable energy clusters connected to VSC-HVDC
VSC-HVDC SYSTEM grid are proposed.
In order to realize the research on the fault ride-though C. Research on high/low-voltage joint crossing technology
technology for the large-scale islanded renewable energy of islanded renewable energy DC integration system
connected to the VSC-HVDC power grid, the specific
based on source-grid coordination
implementation plan is as follows:
x Firstly, based on typical fault types, the research on
A. Research on the interaction between renewable energy the transient voltage control strategy of the islanded
clusters and VSC-HVDC grid under different faults converter station in the VSC-HVDC grid is carried
x First, classify the fault conditions at the sending out simultaneously. With the voltage constraints of
terminal of VSC-HVDC grid with connection of the high-low voltage crossing curve, the transient
large-scale islanded renewable energy, analyze the control strategy is optimized to improve the response
causes of various types of faults, qualitatively give of the island converter station to AC fault ride-
the development mechanism and trend of different though.
types of AC sending terminal faults, and extract x Then, based on the existing security configuration
typical fault types for subsequent simulation analysis. and AC bleeder of the VSC-HVDC grid, it will
x Then, based on the electromagnetic transient further refine its output power regulation of the
simulation model of the existing VSC-HVDC based renewable power generation system and the
islanded renewable energy connection system, fully switching strategy of the AC bleeder during high and
consider the centralized reactive power low voltage crossings to provide protection for fault
compensation characteristics of the renewable power ride-through.
generation system at the sending terminal, and x Finally, based on the above-mentioned VSC-HVDC
increase the external characteristics of reactive grid islanded converter station, renewable power
power compensation, thereby optimizing and generation system and AC bleeder, the research on
improving the current performance. There are high/low voltage combined ride-though technology
simulation models to establish equivalent for the island renewable energy DC integration
electromagnetic transient models of renewable system sending-terminal converter coordinated with
power generation clusters. the renewable energy station is carried out. In the
x Finally, based on the equivalent electromagnetic energy island integration mode, the transmission
transient model of the renewable power generation terminal AC fault response strategy of the VSC-
cluster, the interaction between the renewable power HVDC grid is simulated and verified.
generation system and the VSC-HVDC power grid
under typical AC faults is simulated and scanned.
V. CONCLUSION
B. Adaptability analysis of renewable power generation The transmission terminal of the VSC-HVDC grid adopts
fault ride-through capability in island operation mode island operation control method. From the grid connection
under different faults point of large-scale renewable power generation systems, it
x First, based on the extraction of fault feature assumes that the important role of providing AC voltage and
quantities and the V-F drooping island operation frequency support is renewable power generation systems.
control strategy adopted at the transmission end of However, due to the current capacity limitation of the
the VSC-HVDC grid, the voltage boundary converter station, its short-circuit capacity is small. In the
constraint conditions of the high- and low-voltage case of AC failures, not only must the safety of its own
fault ride-though curves of the renewable power converter be guaranteed, but also the voltage of the AC
generation system are analyzed to determine the islanded system needs to be restored immediately after the
boundaries of typical influencing factors of fault transient fault ends. If the control strategy is not developed
ride-though curve. properly in this process, it will easily lead to the uncontrolled
x Secondly, it further analyzes whether the current AC system, which will lead to the large-scale disconnection
renewable power generation system connected to the of the renewable power generation system. It is urgent to
VSC-HVDC converter station in V-F island study the transient voltage control strategy in its island

1251

Authorized licensed use limited to: Rutgers University. Downloaded on May 15,2021 at 15:06:14 UTC from IEEE Xplore. Restrictions apply.
operation mode, which is one of the key points of future [3] Liu Jian, Tong Nengling, Fan Chunju, Huang Wenhua. Review of
research. Fault Handling and Protection Technology for Flexible DC
Transmission Lines [J]. Automation of Electric Power Systems, 2015,
20: 158-167.
[4] Sun Shixian, Tian Jie. A new method to improve the fault ride-
ACKNOWLEDGMENT through capability of DC grid-connected wind power [J]. Electric
This work was supported by the Science and Technology Power Automation Equipment, 2013, 08: 137-141.
Foundation of SGCC 4000-201955201A-0-0-00 (Research [5] Deng Qiuling. Continuous operation and variable current control of
on Power Transmission of Large-scale Renewable Energy direct-drive permanent magnet synchronous wind power system
under grid faults [D]. Hunan University, 2012.
Base by VSC-LCC hybrid HVDC).
[6] A. Kirakosyan, M. S. E. Moursi, V. KhadkikarFault. Ride Through
and Grid Support Topology for the VSC-HVDC Connected Offshore
Wind Farms[J]. IEEE Transactions on Power Delivery2017,32(03):
REFERENCES 1592-1604.
[1] Zeng Liqiong, Kuang Honghai, Zhang Shuyun, Qiu Yuyang. Analysis [7] X. Yu, Y. Wei, Q. Jiang, X. Xie, Y. Liu, K. Wang. A Novel Hybrid-
and simulation of system short-circuit fault characteristics before and Arm Bipolar MMC Topology With DC Fault Ride-Through
after wind power grid connection [J]. New Industrialization, 2016, 04: Capability[J]. IEEE Transactions on Power Delivery2017,32(03):
27-33. 1404-1413.
[2] Wang Xufeng. Wind farm fault research under DC grid connection
[D]. Anhui University of Science and Technology, 2015.