Professional Documents
Culture Documents
Emailing 73798 Edm Hrw-s-3gb
Emailing 73798 Edm Hrw-s-3gb
Description of Units
4 optimally compact case sizes, 10 models with a nominal Heat exchanger with brazed stainless steel plates on the
cooling capacity ratings ranging from 5.3 to 30.0 kW. water/refrigerant side, for improved efficiency.
Differential pressure switch for antifreeze protection as
High efficiency horizontal units with high COP values.
standard.
Easy access to the compressor, fan and electronic control box,
Bi-Flow thermostatic expansion valve for a wide operating
through wide removable panels. range.
In-line or perpendicular air blowing. Stand-alone regulation by a STORM 2 electronic board which
Condensate drain pan with anti-corrosion treatment by oven- can be configured to 4 operating modes using the RCL user
remote control, which comprises a digital display and essential
baked epoxy paint, equipped with a float-type safety system
control keys.
to protect against accidental condensate overflow.
The µBMS mini-supervision station, available as an optional
3-speed direct drive fan motor or belt driven fan with extra, enables 32 units in 15 zones to be monitored and
variable pitch pulley. managed, with global or individual area programming.
Finned coil
Liquid receiver
Water/refrigerant
plate-type heat
exchanger
Technical Specifications
Introduction The refrigerant circuit also comprises an HP pressure switch with
The new generation of SYSHRW model reversible water source heat manual reset (range 28-20 bar) and an LP pressure switch with an
pumps is the fruit of our considerable product experience and our automatic reset function (range 1.4-2.4 bar). Two Shrader valves (HP
awareness of the market, all combined with a technology based on & LP) are available for pressure measurement on the refrigerant circuit.
the energy efficiency of machines, in order to provide a market offer The water/refrigerant heat exchanger is of the brazed stainless steel
plate type, for increased efficiency. The anti-freeze safety of the heat
for units with the highest performance in terms of COP.
exchanger is provided , on the one hand, by a water pipe sensor
Range located on the water outlet of the unit and, on the other hand, by a
The SYSHRW horizontal units are designed for installation in specifically water flow protection monitored by the electronic board. Maximum
designed false ceilings or in technical rooms, and are available with a service pressure is 31 bar. The heat exchangers are particularly well
range of nominal cooling capacity ratings of between 5.3 and 30.0 adapted to the operation of reversible heat pumps which have high
kW, with 10 models based on 4 different case sizes. thermal transfer rates for a low water flow-rate.
Operating range The air/refrigerant coil is made up of aluminium fins which are
To enable a much wider operating range and operation using a water mechanically crimped onto copper tubes. The geometry of the coil and
source in an application with a dry cooler, the standard SYSHRW units of the fin profile have been carefully designed to provide maximum
efficiency in the operation of the units.
are designed to operate in a water source temperature range of
The cycle reversal valve is designed to be normally energised in
between 13 and 48 °C (according to the models).
heating mode. This logic enables the heat pump to continue to operate
Casing design in cooling mode if this valve fails.
The casing is made of galvanised sheet steel. To facilitate access to The liquid receiver enables the charge of HFC 407C refrigerant to be
the main components, wide removable panels provide access to the optimised, particularly in cooling mode, in order to maintain a high
compressor, the fan and the electronic control box. COP value.
The condensate drain pan has anti-corrosion treatment consisting of A Bi-Flow expansion valve ensures and enables a wide operating
oven-baked epoxy paint. range with water inlet temperatures which can vary between 13 °C
The inside of the casing, on the fan compartment side, is coated with and 48 °C (according to the models) at the minimum or maximum
closed cell polyurethane foam thermal-acoustic insulation; this lagging flow-rate.
is 15 mm thick and is classified M1. On the compressor compartment
Ventilation section
side, the thermal-acoustic insulation consists of Isofeutre felt, 15 mm
The fan compartment contains the fan-motor assembly, the air/
thick (except on models 096 and 120).
refrigerant coil and the condensate drain pan. The ventilation section
Filtration is completely isolated from fan compartment by a thermally and
All units (except for models 096 & 120 supplied with G2-M1 filter) are acoustically insulated partition wall.
factory equipped with a G2-M3 disposable air filter, 20 or 25 mm thick, Wide removable panels provide access to the various internal
according to the models. Optionally, the units can be fitted with G2-M1 components. The condensate drain pan has an anti-corrosion
or G3-M1 filter. The filter can be removed/installed from the side of treatment and comprises a float-type safety device to prevent
the units without plenum and from the side or from the bottom of the accidental overflow of the pan.
units equipped with plenum, without having to remove the optional The sizes 019 to 072 are equipped with a 3 speed direct-drive
return duct. fan motor with ipsothermal protection against overheating during
operation. The motor ipsothermal protection fault is displayed in the
Hydraulic connections form of a coded signal on the LED of the RCL remote control.
The water source outlet and return connectors are located on the
The 3 fan speeds can be controlled either manually or automatically by
outside of the unit, on the compressor compartment side. They are
the electronic management board of the unit. The fan-motor assembly
female gas type tapped fittings 3/4" or 1"1/4 (male), according to the
is mounted on an independent chassis which is isolated from the
models. The condensate evacuation connection is of the smooth tube
casing by anti-vibration mounts.
type, with an outside diameter of 19 mm for models 019 to 072, 22 Belt type drive with variable pitch pulley is supplied on models 096
mm for models 096 and 120. and 120.
Electronic control box In the standard configuration, the fan blows straight in line with the
The electrical box is located inside the compressor compartment. air intake. The perpendicular blowing option is available on all units
A wide access panel is provided to facilitate the maintenance by switching the side panels and the fan-motor assembly.
operations. Suspension kit
The electrical power supply required for model 019 is 230 V / 1 Ph / In order to facilitate installation on site, a suspension kit consisting
50 Hz, whereas models SYSHRW 027 to 120 require 400 V / 3 Ph / 50 of rubber blocks and washers is supplied with the units (except for
Hz + neutral. The compressors are factory equipped with an internal models 096 and 120).
thermal protection with an automatic reset function.
Optional features
Refrigerant circuit Wired main disconnect switch to be installed on the
casing,
The refrigerant circuit comprises a scroll or rotary type hermetic
compressor, a cycle reversal valve, a water/refrigerant heat exchanger, Electric heater at discharge side,
a liquid receiver, a bi-flow thermostatic expansion valve and a finned General alarms fault report,
coil. Motorized water valve supplied loose.
SYSHRW 3
Control Features
STORM 2 electronic board RCL user remote control
All SYSHRW water source heat pumps are, in their standard version,
equipped with a STORM 2 electronic board which manages their
operation and their safety devices.
Models designation
. SYSHRW 40 . RC . 230V/1~/50Hz . R407C . SYS . SL . G2M1 . + . SOND
1 2 3 4 5 6 7 8
REP. Description
Air
6 configuration
SL : In line ST : Rear blowing
Product Codes
367378 SYSHRW42RC.400V.R407C.SYS.RCL
367379 SYSHRW48RC.400V.R407C.SYS.RCL
6 3
WATER 2
outlet 5
2
WATER
inlet
11
1
8 9
10 12
components
Operating Limits
Temperature limits - SYSHRW 019 to 072
Cooling Heating
Minimum 21 °C dry bulb / 15 °C wet bulb 15 °C
Return air temperature Nominal* 27 °C dry bulb / 19 °C wet bulb 20 °C
Maximum 38 °C dry bulb / 28 °C wet bulb 27 °C
Minimum 18 °C 13 °C
Entering water temperature Nominal* 30 °C 20 °C
Maximum 44 °C 34 °C
* Nominal conditions according to EN 14511-2 standard.
Flow limits - SYSHRW 019 to 072
SYSHRW 019
Nominal air flow : 1250 m3/h Nominal water flow : 920 l/h
1300 1000
950
1200
900
Air flow (m3/h)
1100 850
900 700
650
800 600
700 550
500
600 450
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 027
Nominal air flow : 1190 m3/h Nominal water flow : 1540 l/h
1200 1600
1150 1500
1100 1400
1050
Air flow (m3/h)
1300
1000
Water flow (l/h)
1200
950
1100
900
850 1000
800 900
750 800
700 700
650 600
600
500
550
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 400
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 030
Nominal air flow : 1490 m3/h Nominal water flow : 1764 l/h
1450
1680
1350 1580
Air flow (m3/h)
1250 1480
Water flow (l/h)
1150 1380
1050 1280
1180
950
1080
850
980
750
880
650 780
550 680
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 036
Nominal air flow : 1580 m3/h Nominal water flow : 2030 l/h
2000
1500
1400 1800
Air flow (m3/h)
1300
1600
Water flow (l/h)
1200
1100 1400
1000
900 1200
800
1000
700
600 800
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Air inlet temperature (°C) Water inlet temperature (°C)
8 SYSHRW
2100
SYSHRW 048
Nominal air flow : 2750 m3/h Nominal water flow : 2822 l/h
2800
2600
2600
2400
2400
Air flow (m3/h)
2000 2000
1800 1800
1600 1600
1400 1400
1200 1200
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 060
Nominal air flow : 2840 m3/h Nominal water flow : 3348 l/h
3250
2650
3050
2450 2850
Air flow (m3/h)
2250 2650
2450
2050
2250
1850
2050
1650
1850
1450 1650
1250 1450
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 072
Nominal air flow : 3570 m3/h Nominal water flow : 3924 l/h
3400 3750
3200 3550
3350
Air flow (m3/h)
3000
3150
Water flow (l/h)
2800
2950
2600
2750
2400
2550
2200
2350
2000 2150
1800 1950
1600 1750
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 9
4000
4000
3800
3800 3600
3400
3600
3200
3400 3000
3200 2800
2600
3000
2400
2800 2200
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Air inlet temperature (°C) Water inlet temperature (°C)
SYSHRW 120
Nominal air flow : 5600 m3/h Nominal water flow : 6408 l/h
5600 6400
6200
5400
6000
5200 5800
Water flow (l/h)
Air flow (m3/h)
5600
5000 5400
4800 5200
5000
4600 4800
4400 4600
4400
4200 4200
4000 4000
3800
3800 3600
3400
3600
3200
3400 3000
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Air inlet temperature (°C) Water inlet temperature (°C)
10 SYSHRW
Physical Data
models SYSHRW 019 SYSHRW 027 SYSHRW 030 SYSHRW 036
CAPACITIES
VENTILATION
Air filters - Dimensions / Thickness mm 365 x 300/25 385 x 350/25 385 x 350/25 385 x 350/26
HYDRAULIC CIRCUIT
REFRIGERANT CIRCUIT
Type R407C
Number of circuit 1 1 1 1
ELECTRICAL DATA
Electrical heating coil - Number / Capacity (5) W 2/1500+750 1/3750 1 / 3750 1 / 4500
Power input of electric heating coil (5) W 2250 3750 3750 4500
(1) Nominal cooling capacities based on : entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of
30 °C.
(2) Nominal heating capacities based on : entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of
20 °C.
(3) Protection by differential pressure switch.
(4) Absorbed power (compressor + fan) at nominal conditions.
(5) Electric heating coil is an optional feature available for SH & RH versions.
(6) Nominal currents are given at +/- 5%.
(7) Starting currents are given at +/- 10%.
(8) Total water pressure drop with optional water valve fitted.
SYSHRW 11
CAPACITIES
VENTILATION
Air filters - Dimensions / Thickness mm 450 x 440/25 450 x 440/25 450 x 440/25
HYDRAULIC CIRCUIT
REFRIGERANT CIRCUIT
Type R407C
Number of circuit 1 1 1
ELECTRICAL DATA
(1) Nominal cooling capacities based on : entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of
30 °C.
(2) Nominal heating capacities based on : entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of
20 °C.
(3) Protection by differential pressure switch.
(4) Absorbed power (compressor + fan) at nominal conditions.
(5) Electric heating coil is an optional feature available for SH & RH versions.
(6) Nominal currents are given at +/- 5%.
(7) Starting currents are given at +/- 10%.
(8) Total water pressure drop with optional water valve fitted.
12 SYSHRW
CAPACITIES
VENTILATION
Air filters - Dimensions / Thickness mm 450 x 440 x 25 620 x 650 x 25 620 x 650 x 25
HYDRAULIC CIRCUIT
Hydraulic connections - Inlet / Outlet inches ISO G 3/4" INT ISO G 1"1/4 ISO G 1"1/4
REFRIGERANT CIRCUIT
Type R407C
Number of circuit 1 1 1
ELECTRICAL DATA
(1) Nominal cooling capacities based on : entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of
30 °C.
(2) Nominal heating capacities based on : entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of
20 °C.
(3) Protection by differential pressure switch.
(4) Absorbed power (compressor + fan) at nominal conditions.
(5) Electric heating coil is an optional feature available for SH & RH versions.
(6) Nominal currents are given at +/- 5%.
(7) Starting currents are given at +/- 10%.
(8) Total water pressure drop with optional water valve fitted.
Note : All ratings (cooling and heating capacities and power consumptions) are given according to International Standard ISO 13256-1.
SYSHRW 13
SYSHRW 027
170
160
150
140
130 HS
120
Available pressure (Pa)
110
MS
100 LS
90
80
70
60
50
40
Ductwork curve
30
20
10
0
800 850 900 950 1000 1050 1100 1150 1200 1250
Air flow (m3/h)
SYSHRW 030
280
270
260
250
240 HS
230
220
210
MS
Available pressure (Pa)
200
190
180
170
160 LS
150
140
130
120
110 Ductwork curve
100
90
80
70
60
50
40
30
20
10
0
1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600
Air flow (m3/h)
SYSHRW 036
280
270
260
250
240
230
220 HS
210
Available pressure (Pa)
200
190 MS
180
170
160
150
LS
140
130
120
110
100
90
80 Ductwork curve
70
60
50
40
30
20
10
0
1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650
Air flow (m3/h)
14 SYSHRW
290
280
270
260
250
240 HS
230
220
210
Available pressure (Pa) 200 MS
190
180
170
160 LS
150
140
130
120
110
100
90
80
70
60
50 Ductwork curve
40
30
20
10
0
1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100
Air flow (m3/h)
SYSHRW 048
360
350
340
330
320
310
300
290
280
270
HS
260 MS
Available pressure (Pa)
250
240
230
220
210
200
190
LS
180
170
160
150
140
130
120
110
100
90 Ductwork curve
80
70
60
50
40
30
20
10
0
1850 1900 1950 2000 2050 2100 2150 2200 2250 2300 2350 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850
Air flow (m3/h)
SYSHRW 060
380
370
360
350
340
330
320 HS
310
300
290 MS
Available pressure (Pa)
280
270
260
250
240
230 LS
220
210
200
190
180
170
160 Ductwork curve
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
1850 1900 1950 2000 2050 2100 2150 2200 2250 2300 2350 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850 2900
Air flow (m3/h)
SYSHRW 072
250
HS
200
MS
LS
Available pressure (Pa)
150
100
50
Ductwork curve
0
1950 2050 2150 2250 2350 2450 2550 2650 2750 2850 2950 3050 3150 3250 3350 3450 3550 3650 3750 3850
Air flow (m3/h)
SYSHRW 15
SYSHRW 120
300
280
260
240
220
Available pressure (Pa)
200
180
160 0 : Pulley closed
140
1 : Pulley opened 1 turn
120 0
2 : Pulley opened 2 turns
100
Ductwork curve 1 3 : Pulley opened 3 turns
80
60 2
40
20 3
0
3600 4100 4600 5100 5600 6100 6600 7100 7600 8100 8600
Air flow (m3/h)
Total cooling capacity 0.972 0.982 0.993 1.00 1.007 1.010 1.013
Sensible cooling capacity 0.926 0.948 0.974 1.00 1.027 1.055 1.066
Power input - Cooling 0.977 0.984 0.993 1.00 1.011 1.018 1.028
Power input - Heating 1.009 1.006 1.003 1.00 0.997 0.995 0.993
16 SYSHRW
Acoustical Data
Sound power levels Lw - SYSHRW 019
Frequency Global
Speeds Type
125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz dB(A)
Lw radiated inlet + casing (Config. A) 48.9 50.4 52.2 54.9 51.3 40.4 59.1
LS
Lw radiated casing only (Config. B) 44.2 43.1 44.7 45.7 41.5 30.1 51.1
Lw radiated inlet + casing (Config. A) 51.4 53.8 55.0 57.7 52.7 43.3 61.7
MS
Lw radiated casing only (Config. B) 47.1 46.6 47.4 49.1 45.5 35.5 54.4
Lw radiated inlet + casing (Config. A) 53.9 57.1 57.8 60.6 54.0 46.2 64.5
HS
Lw radiated casing only (Config. B) 50.0 50.2 50.1 52.5 49.5 40.9 57.7
Lw radiated inlet + casing (Config. A) 51.5 50.5 50.1 53.9 51.7 41.9 58.8
LS
Lw radiated casing only (Config. B) 46.8 47.1 45.9 48.8 44.5 33.4 53.9
Lw radiated inlet + casing (Config. A) 51.7 52.6 49.7 55.2 53.6 44.1 60.1
MS
Lw radiated casing only (Config. B) 47.4 47.9 48.1 51.4 47.9 37.7 55.9
Lw radiated inlet + casing (Config. A) 54.3 54.2 53.1 57.5 56.1 46.7 62.5
HS
Lw radiated casing only (Config. B) 48.4 48.5 49.4 53.4 49.8 40.2 57.4
Lw radiated inlet + casing (Config. A) 45.6 51.1 52.3 53.9 47.0 43.2 58.2
LS
Lw radiated casing only (Config. B) 45.4 45.7 45.0 48.4 40.8 29.3 52.7
Lw radiated inlet + casing (Config. A) 48.2 51.7 55.2 56.2 50.2 43.2 60.3
MS
Lw radiated casing only (Config. B) 46.3 44.7 48.3 49.9 43.0 32.7 54.2
Lw radiated inlet + casing (Config. A) 50.5 54.3 58.1 59.0 54.0 48.1 63.3
HS
Lw radiated casing only (Config. B) 48.4 48.4 51.5 51.3 46.4 38.7 56.7
Configuration A Configuration B
(*) Unit suspended at 1 metre from ground. (*) Unit suspended at 1 metre from ground.
(**) 1.5 metre long acoustic duct. (**) 1.5 metre long acoustic duct.
SYSHRW 17
Lw radiated inlet + casing (Config. A) 49,4 50,4 54,4 55,0 49,3 40,7 59,5
LS
Lw radiated casing only (Config. B) 46,9 44,6 47,1 46,9 40,1 30,1 52,8
Lw radiated inlet + casing (Config. A) 52,6 52,6 56,3 58,3 54,5 47,2 62,6
MS
Lw radiated casing only (Config. B) 48,4 47,1 50,5 50,0 45,6 37,2 55,7
Lw radiated inlet + casing (Config. A) 53,2 56,1 58,7 61,6 58,1 50,9 65,6
HS
Lw radiated casing only (Config. B) 49,5 50,5 52,7 52,0 49,9 42,1 58,2
Lw radiated inlet + casing (Config. A) 49,5 55,7 56,5 56,6 53,0 46,5 62,1
LS
Lw radiated casing only (Config. B) 45,7 48,4 48,6 47,4 41,6 36,7 54,0
Lw radiated inlet + casing (Config. A) 52,6 55,8 58,7 60,7 58,8 52,7 65,3
MS
Lw radiated casing only (Config. B) 47,1 49,3 51,1 49,6 46,2 40,1 56,1
Lw radiated inlet + casing (Config. A) 53,7 57,6 60,8 63,6 60,7 54,2 67,6
HS
Lw radiated casing only (Config. B) 47,7 51,2 52,9 52,6 49,2 43,6 58,3
Lw radiated inlet + casing (Config. A) 50,8 55,3 60,1 59,1 57,7 49,3 64,7
LS
Lw radiated casing only (Config. B) 46,1 48,4 51,1 48,6 44,8 35,3 55,4
Lw radiated inlet + casing (Config. A) 54,4 58,8 62,8 63,6 62,2 54,8 68,6
MS
Lw radiated casing only (Config. B) 48,3 51,7 53,2 52,8 49,5 43,2 58,6
Lw radiated inlet + casing (Config. A) 56,8 62,6 65,0 66,9 65,4 58,5 71,6
HS
Lw radiated casing only (Config. B) 52,2 57,3 57,1 56,9 52,9 46,5 62,9
Configuration A Configuration B
(*) Unit suspended at 1 metre from ground. (*) Unit suspended at 1 metre from ground.
(**) 1.5 metre long acoustic duct. (**) 1.5 metre long acoustic duct.
18 SYSHRW
Lw radiated inlet + casing (Config. A) 54,8 54,5 56,8 56,0 53,0 46,6 62,3
LS
Lw radiated casing only (Config. B) 52,7 49,7 51,3 49,2 44,4 38,2 57,3
Lw radiated inlet + casing (Config. A) 56,7 58,3 60,1 59,8 56,9 52,4 65,8
MS
Lw radiated casing only (Config. B) 53,5 51,7 53,7 53,6 49,4 41,1 59,7
Lw radiated inlet + casing (Config. A) 57,4 62,7 64,5 65,1 61,8 58,9 70,3
HS
Lw radiated casing only (Config. B) 54,4 55,7 56,5 58,6 53,8 46,7 63,2
Lw radiated inlet + casing (Config. A) 62,7 67,2 71,9 76,8 71,5 69,1 79,7
0 turn
Lw radiated casing only (Config. B) 59,1 62,1 63,4 67,2 60,9 54,8 70,6
Lw radiated inlet + casing (Config. A) 62,0 65,9 70,5 75,0 70,8 68,3 78,3
1 turn
Lw radiated casing only (Config. B) 58,5 61,2 62,7 66,4 60,1 54,6 69,8
Lw radiated inlet + casing (Config. A) 62,4 65,2 70,8 74,9 70,0 67,3 78,0
2 turns
Lw radiated casing only (Config. B) 57,8 60,4 62,0 65,1 58,6 52,7 68,7
Lw radiated inlet + casing (Config. A) 60,3 64,2 69,9 73,1 68,6 65,5 76,5
3 turns
Lw radiated casing only (Config. B) 56,4 59,4 61,2 64,3 57,7 51,7 67,8
Lw radiated inlet + casing (Config. A) 68,1 70,9 73,9 76,5 73,6 67,0 80,6
0 turn
Lw radiated casing only (Config. B) 62,9 64,9 66,2 67,1 61,0 53,3 72,0
Lw radiated inlet + casing (Config. A) 66,5 69,2 73,1 74,3 71,9 65,2 79,0
1 turn
Lw radiated casing only (Config. B) 62,9 64,9 65,6 66,7 60,1 52,5 71,6
Lw radiated inlet + casing (Config. A) 65,8 68,1 72,2 73,3 70,8 63,7 78,0
2 turns
Lw radiated casing only (Config. B) 62,2 62,3 63,4 63,8 57,2 49,5 69,3
Lw radiated inlet + casing (Config. A) 65,9 66,6 68,4 71,3 67,7 60,3 75,6
3 turns
Lw radiated casing only (Config. B) 61,0 61,2 64,0 64,5 57,8 51,4 69,4
Configuration A Configuration B
(*) Unit suspended at 1 metre from ground. (*) Unit suspended at 1 metre from ground.
(**) 1.5 metre long acoustic duct. (**) 1.5 metre long acoustic duct.
SYSHRW 19
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
20 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
22 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
24 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
26 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
28 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
30 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
32 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
34 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
36 SYSHRW
TEA : Entering air temperature (dry bulb/wet bulb). Pabs : Compressor power input.
Pt : Total cooling capacity. CR : Total heat rejection.
Ps : Sensible cooling capacity.
38 SYSHRW
Dimensions (mm)
SYSHRW 019 to 072
B
A
C
SYSHRW sizes A B C
U
N
CONDENSATES OUTLET
Ø 3/4
R
S
T
Q
26
SYSHRW sizes N P Q R S T U
Weight (kg)
SYSHRW sizes 019 027 030 036 042 048 060 072
D
F
F
E E
G H
REAR BLOWING
IN LINE BLOWING
(STANDARD CONFIGURATION)
SYSHRW sizes D E F G H
K
47
M
J
SYSHRW sizes J K M
955
0
168
770
180
1" 1/4 MALE GAS
WATER OUTLET
479
88.5
Ø 7/8 (22.2mm)
90 170 ELECTRICAL CONNECTIONS
286
Weight (kg)
REPRISE D’AIR
349
349
230
230
A A
SOUFFLAGE EN LIGNE
151 B (CONFIGURATION STANDARD)
SOUFFLAGE
ARRIERE
96 120
A 317 403
B 345 259
0
6.5
119
419
SYSHRW 43
600 mm
600 mm
600 mm
600 mm
200 mm
44 SYSHRW
Notes
www.systemair.fr
Systemair AC SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13
july 2017
Systemair · EDM HRW-S-3GB/07.17 - Supersedes EDM HRW-S-2GB/04.15
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.