Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-1
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 52 M Ω 77.5 M Ω 74.9 M Ω OK OK

WH 72.8 M Ω 70.6 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020224
Drawing No DN # Date 25-01-2024
Cable Size & Types 8px1.5mm2 cu/pvc/pvc OA shielded Length 1800M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 23.6 M Ω 25.9 M Ω 27.4 M Ω OK OK

WH 29.4 M Ω 41.4 M Ω OK OK

Pair-2 BK 33.9 M Ω 35.1 M Ω 59.0 M Ω OK OK

WH 40.2 M Ω 60.7 M Ω OK OK

Pair-3 BK 34.5 M Ω 46.1 M Ω 63.2 M Ω OK OK

WH 39.1 M Ω 75.0 M Ω OK OK

Pair-4 BK 29.4 M Ω 37.5 M Ω 57.2 M Ω OK OK

WH 49.3 M Ω 50.3 M Ω OK OK

Pair-5 BK 21.4 M Ω 49.5 M Ω 60.4 M Ω OK OK

WH 48.3 M Ω 58.2 M Ω OK OK

Pair-6 BK 14.4 M Ω 31.9 M Ω 62.0 M Ω OK OK

WH 33.4 M Ω 43.0 M Ω OK OK

Pair-7 BK 18.9 M Ω 29.5 M Ω 45.1 M Ω OK OK

WH 31.5 M Ω 61.4 M Ω OK OK

Pair-8 BK 15.11 M Ω 39.5 M Ω 63.4 M Ω OK OK

WH 40.7 M Ω 49.6 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # NB-04-01-03-ZD1 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 44 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 03
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.7 GΩ 5.46 GΩ 5.3 GΩ OK OK

WH 3.94 GΩ 4.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020208
Drawing No DN # Date 25-01-2024
Cable Size & Types 8P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 54.5 Mohm 247M ohm OK OK

WH 256M ohm OK OK

Pair-2 BK 41 Mohm 149M ohm OK OK

WH 163M ohm OK OK

Pair-3 BK 48.7 Mohm 148M ohm OK OK

WH 191M ohm OK OK

Pair-4 BK 51.5 Mohm 158M ohm OK OK

WH 194M ohm OK OK

Pair-5 BK 40.4 Mohm 204M ohm OK OK

WH 205M ohm OK OK

Pair-6 BK 48.1 Mohm 198M ohm OK OK

WH 205M ohm OK OK

Pair-7 BK 43.1 Mohm 165M ohm OK OK

WH 202M ohm OK OK

Pair-8 BK 43.6 Mohm 200M ohm OK OK

WH 172M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020207
Drawing No DN # Date 25-01-2024
Cable Size & Types 8p*1.5mm2 cu/pvc/pvc OA shielded Length 1300 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500v____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 295 M Ω 382 M Ω 531 M Ω OK OK

WH 430 M Ω 537 M Ω OK OK

Pair-2 BK 247 M Ω 382 M Ω 339 M Ω OK OK

WH 430 M Ω 345 M Ω OK OK

Pair-3 BK 242 M Ω 263 M Ω 355 M Ω OK OK

WH 287 M Ω 369 M Ω OK OK

Pair-4 BK 240 M Ω 307 M Ω 411 M Ω OK OK

WH 329 M Ω 414 M Ω OK OK

Pair-5 BK 217 M Ω 351 M Ω 376 M Ω OK OK

WH 368 M Ω 382 M Ω OK OK

Pair-6 BK 209 M Ω 332 M Ω 343 M Ω OK OK

WH 356 M Ω 490 M Ω OK OK

Pair-7 BK 222 M Ω 360 M Ω 324 M Ω OK OK

WH 323 M Ω 338 M Ω OK OK

Pair-8 BK 222M Ω 312 M Ω 323 M Ω OK OK

WH 319 M Ω 325 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdul Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020206
Drawing No DN # Date 25-01-2024
Cable Size & Types 8p*1.5mm2 cu/pvc/pvc OA shielded Length 1000 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500v____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 156 M Ω 271 M Ω 151M Ω OK OK

WH 254 M Ω 171 M Ω OK OK

Pair-2 BK 148 M Ω 245 M Ω 179 M Ω OK OK

WH 281 M Ω 198 M Ω OK OK

Pair-3 BK 150 M Ω 280 M Ω 198 M Ω OK OK

WH 306 M Ω 211 M Ω OK OK

Pair-4 BK 160 M Ω 311 M Ω 218 M Ω OK OK

WH 326 M Ω 225 M Ω OK OK

Pair-5 BK 105 M Ω 280 M Ω 218 M Ω OK OK

WH 154 M Ω 226 M Ω OK OK

Pair-6 BK 111 M Ω 161 M Ω 188 M Ω OK OK

WH 149 M Ω 193 M Ω OK OK

Pair-7 BK 102 M Ω 141 M Ω 199 M Ω OK OK

WH 166 M Ω 216 M Ω OK OK

Pair-8 BK 121 M Ω 182 M Ω 216 M Ω OK OK

WH 192 M Ω 200 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdul Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020223
Drawing No DN # Date 25-01-2024
Cable Size & Types 12p*1.5mm2 cu/pvc/pvc OA shielded Length 1300M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 218 Mohm 227M ohm 214M ohm OK OK

WH 241M ohm 224M ohm OK OK

Pair-2 BK 206M ohm 261M ohm 249M ohm OK OK

WH 264M ohm 251M ohm OK OK

Pair-3 BK 203M ohm 269M ohm 265M ohm OK OK

WH 277M ohm 256M ohm OK OK

Pair-4 BK 162M ohm 268M ohm 246M ohm OK OK

WH 275M ohm 265M ohm OK OK

Pair-5 BK 163M ohm 304M ohm 264M ohm OK OK

WH 313M ohm 251M ohm OK OK

Pair-6 BK 142M ohm 307M ohm 266M ohm OK OK

WH 298M ohm 235M ohm OK OK

Pair-7 BK 186M ohm 328M ohm 279M ohm OK OK

WH 338M ohm 248M ohm OK OK

Pair-8 BK 162M ohm 332M ohm 227M ohm OK OK

WH 284M ohm 234M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020223
Drawing No DN # Date 25-01-2024
Cable Size & Types 12p*1.5mm2 cu/pvc/pvc OA shielded Length 1300M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-9 BK 203 Mohm 294M ohm 235M ohm OK OK

WH 338M ohm 220M ohm OK OK

Pair-10 BK 188M ohm 264M ohm 232M ohm OK OK

WH 239M ohm 192M ohm OK OK

Pair-11 BK 173M ohm 254M ohm 207M ohm OK OK

WH 269M ohm 220M ohm OK OK

Pair-12 BK 163M ohm 220M ohm 198M ohm OK OK

WH 238M ohm 192M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020223
Drawing No DN # Date 25-01-2024
Cable Size & Types 12p*1.5mm2 cu/pvc/pvc OA shielded Length 1300M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-9 BK 203 Mohm 294M ohm 235M ohm OK OK

WH 338M ohm 220M ohm OK OK

Pair-10 BK 188M ohm 264M ohm 232M ohm OK OK

WH 239M ohm 192M ohm OK OK

Pair-11 BK 173M ohm 254M ohm 207M ohm OK OK

WH 269M ohm 220M ohm OK OK

Pair-12 BK 163M ohm 220M ohm 198M ohm OK OK

WH 238M ohm 192M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020222
Drawing No DN # Date 27-01-2024
Cable Size & Types 3Tx1.5mm2 cu/pvc/pvc 1+OA shielded Length 1000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD1-BK1 RD1 Core to Core 46.0 M Ω 66.4 M Ω OK OK

WH1-RD1 BK1 11.6 M Ω 60.1 M Ω 66.9 M Ω OK OK

BK1-WH1 wH1 11.0 M Ω 60.5 M Ω 61.7 M Ω OK OK

RD1-BK1 RD2 12.1 M Ω 53.2 M Ω 60.3 M Ω OK OK

WH1-RD1 BK2 11.3 M Ω 54.3 M Ω 55.3 M Ω OK OK

BK1-WH1 wH2 11.7 M Ω 42.7 M Ω 61.3 M Ω OK OK

RD1-BK1 RD3 12.3 M Ω 61.4 M Ω 63.4 M Ω OK OK

WH1-RD1 BK3 11.9 M Ω 44.6 M Ω 56.4 M Ω OK OK

BK1-WH1 wH3 11.3 M Ω 53.4 M Ω 56.1 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020223
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 1300 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 218 M Ω 227 M Ω 214 M Ω OK OK

WH 241 M Ω 224 M Ω OK OK

Pair-2 BK 206 M Ω 261 M Ω 249 M Ω OK OK

WH 264 M Ω 251M Ω OK OK

Pair-3 BK 203 M Ω 269 M Ω 265 M Ω OK OK

WH 277 M Ω 256 M Ω OK OK

Pair-4 BK 162 M Ω 268 M Ω 246 M Ω OK OK

WH 275 M Ω 265 M Ω OK OK

Pair-5 BK 163 M Ω 304 M Ω 264 M Ω OK OK

WH 313 M Ω 251 M Ω OK OK

Pair-6 BK 142 M Ω 307 M Ω 266 M Ω OK OK

WH 298 M Ω 235 M Ω OK OK

Pair-7 BK 186 M Ω 328 M Ω 279 M Ω OK OK

WH 338 M Ω 248 M Ω OK OK

Pair-8 BK 162 M Ω 332 M Ω 227 M Ω OK OK

WH 284 M Ω 234 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020223
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 1300 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 218 M Ω 227 M Ω 214 M Ω OK OK

WH 241 M Ω 224 M Ω OK OK

Pair-2 BK 206 M Ω 261 M Ω 249 M Ω OK OK

WH 264 M Ω 251M Ω OK OK

Pair-3 BK 203 M Ω 269 M Ω 265 M Ω OK OK

WH 277 M Ω 256 M Ω OK OK

Pair-4 BK 162 M Ω 268 M Ω 246 M Ω OK OK

WH 275 M Ω 265 M Ω OK OK

Pair-5 BK 163 M Ω 304 M Ω 264 M Ω OK OK

WH 313 M Ω 251 M Ω OK OK

Pair-6 BK 142 M Ω 307 M Ω 266 M Ω OK OK

WH 298 M Ω 235 M Ω OK OK

Pair-7 BK 186 M Ω 328 M Ω 279 M Ω OK OK

WH 338 M Ω 248 M Ω OK OK

Pair-8 BK 162 M Ω 332 M Ω 227 M Ω OK OK

WH 284 M Ω 234 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31023


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020225
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 6Tx1.5mm2 cu/pvc/pvc 1+ OA shielded Length 1000 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Drain Conductor
Core No. Core to Core Core to Ground Core to Shield
Continuity Continuity

Triad-1 RD-BK 204 M Ω RD-GRD 123 M Ω RD-S 132 M Ω OK OK

RD-WH 198 M Ω BK-GRD 119M Ω BK-s 126 M Ω OK OK

BK-WH 181 M Ω WH-GRD 122 M Ω WH-S 124 M Ω OK OK

Triad-2 RD-BK 181 M Ω RD-GRD 110 M Ω RD-S 115 M Ω OK OK

RD-WH 189 M Ω BK-GRD 120M Ω BK-s 125 M Ω OK OK

BK-WH 184 M Ω WH-GRD 134 M Ω WH-S 135 M Ω OK OK

Triad-3 RD-BK 180 M Ω RD-GRD 106 M Ω RD-S 114 M Ω OK OK

RD-WH 184 M Ω BK-GRD 119 M Ω BK-s 124 M Ω OK OK

BK-WH 177 M Ω WH-GRD 131 M Ω WH-S 129 M Ω OK OK

Triad-4 RD-BK 174 M Ω RD-GRD 100 M Ω RD-S 105 M Ω OK OK

RD-WH 177 M Ω BK-GRD 113 M Ω BK-s 117 M Ω OK OK

BK-WH 171 M Ω WH-GRD 116 M Ω WH-S 113 M Ω OK OK

Triad-5 RD-BK 176 M Ω RD-GRD 102 M Ω RD-S 68 M Ω OK OK

RD-WH 174 M Ω BK-GRD 120M Ω BK-s 86.1 M Ω OK OK

BK-WH 167 M Ω WH-GRD 119 M Ω WH-S92.8 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020211
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 139 M Ω 142 M Ω 139 M Ω OK OK

WH 153 M Ω 160 M Ω OK OK

Pair-2 BK 164 M Ω 177 M Ω 190 M Ω OK OK

WH 182 M Ω 179 M Ω OK OK

Pair-3 BK 121 M Ω 151 M Ω 131 M Ω OK OK

WH 180 M Ω 188 M Ω OK OK

Pair-4 BK 111 M Ω 143 M Ω 140 M Ω OK OK

WH 154 M Ω 161 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020214
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 138 M Ω 127 M Ω 101 M Ω OK OK

WH 128 M Ω 111 M Ω OK OK

Pair-2 BK 64.3 M Ω 87 M Ω 78.3M Ω OK OK

WH 96.7 M Ω 91.5 M Ω OK OK

Pair-3 BK 73.1 M Ω 86.3 M Ω 76.3 M Ω OK OK

WH 96.1 M Ω 73.4 M Ω OK OK

Pair-4 BK 81.0 M Ω 116 M Ω 89.2 M Ω OK OK

WH 122 M Ω 86.8 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31025


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020205
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 4Px1.5mm2 cu/pvc/pvc I + OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 19.9 M Ω 28.5 M Ω 43.0 M Ω OK OK

WH 52.0 M Ω 46.1 M Ω OK OK

Pair-2 BK 19.9 M Ω 30.0 M Ω 43.6 M Ω OK OK

WH 39.9 M Ω 40.5 M Ω OK OK

Pair-3 BK 18.2 M Ω 28.3 M Ω 42.8 M Ω OK OK

WH 37.6 M Ω 41.9M Ω OK OK

Pair-4 BK 18.8 M Ω 28.6 M Ω 40.2 M Ω OK OK

WH 38.5 M Ω 41.4 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020211
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 135 M Ω 128 M Ω 163 M Ω OK OK

WH 102 M Ω 123 M Ω OK OK

Pair-2 BK 80 M Ω 108 M Ω 131 M Ω OK OK

WH 121 M Ω 138 M Ω OK OK

Pair-3 BK 108 M Ω 94.1 M Ω 106 M Ω OK OK

WH 104 M Ω 113M Ω OK OK

Pair-4 BK 66.6 M Ω 88.1 M Ω 94.3 M Ω OK OK

WH 92.7 M Ω 96 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020209
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 472 M Ω 397 M Ω 515 M Ω OK OK

WH 261 M Ω 398 M Ω OK OK

Pair-2 BK 300 M Ω 368 M Ω 402 M Ω OK OK

WH 408 M Ω 427 M Ω OK OK

Pair-3 BK 318 M Ω 341 M Ω 408 M Ω OK OK

WH 417 M Ω 429 M Ω OK OK

Pair-4 BK 301 M Ω 282 M Ω 345 M Ω OK OK

WH 323 M Ω 360 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020204
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc 1+ OA shielded Length 500 M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 203 M Ω 157 M Ω 196 M Ω OK OK

WH 185 M Ω 207 M Ω OK OK

Pair-2 BK 196 M Ω 157 M Ω 189 M Ω OK OK

WH 174 M Ω 187 M Ω OK OK

Pair-3 BK 189 M Ω 148 M Ω 188 M Ω OK OK

WH 173 M Ω 195 M Ω OK OK

Pair-4 BK 175 M Ω 141 M Ω 271 M Ω OK OK

WH 173 M Ω 205 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020217
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 32.5 M Ω 54.1 M Ω 59.3 M Ω OK OK

WH 51.0 M Ω 52.0 M Ω OK OK

Pair-2 BK 41.1M Ω 69.4 M Ω 68.0 M Ω OK OK

WH 63.0 M Ω 65.0 M Ω OK OK

Pair-3 BK 29.7 M Ω 93.3 M Ω 94.0 M Ω OK OK

WH 85.0 M Ω 89.4 M Ω OK OK

Pair-4 BK 26.9 M Ω 57.0 M Ω 60.0 M Ω OK OK

WH 56.0 M Ω 58.4 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020213
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 100 M Ω 102 M Ω 104 M Ω OK OK

WH 105 M Ω 100 M Ω OK OK

Pair-2 BK 56.5 M Ω 83.8 M Ω 99 M Ω OK OK

WH 99.4 M Ω 101 M Ω OK OK

Pair-3 BK 56.3 M Ω 80.4 M Ω 90.1 M Ω OK OK

WH 92.5 M Ω 88.1 M Ω OK OK

Pair-4 BK 55.9 M Ω 85.4 M Ω 91.6 M Ω OK OK

WH 96.9 M Ω 98 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020215
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 129 M Ω 76.1 M Ω 98.0 M Ω OK OK

WH 83.4 M Ω 99.8 M Ω OK OK

Pair-2 BK 65.5 M Ω 84.3 M Ω 99.1 M Ω OK OK

WH 86.0 M Ω 97.6 M Ω OK OK

Pair-3 BK 50.2 M Ω 75.6 M Ω 81.4 M Ω OK OK

WH 84.2 M Ω 82.5 M Ω OK OK

Pair-4 BK 50.9 M Ω 82.3 M Ω 85.9 M Ω OK OK

WH 87.0M Ω 85.4M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020212
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 19.1 M Ω 56.4 M Ω 82.6 M Ω OK OK

WH 74.5 M Ω 83.7 M Ω OK OK

Pair-2 BK 27.7 M Ω 67.1 M Ω 78.3 M Ω OK OK

WH 67.5 M Ω 84.6 M Ω OK OK

Pair-3 BK 17.6 M Ω 74.7 M Ω 75.9 M Ω OK OK

WH 74.5 M Ω 81.5 M Ω OK OK

Pair-4 BK 18.8 M Ω 74.8 M Ω 78.4 M Ω OK OK

WH 77.0 M Ω 79.9 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020216
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 24.9 M Ω 47.0 M Ω 44.2 M Ω OK OK

WH 53.3 M Ω 41.6 M Ω OK OK

Pair-2 BK 30.1 M Ω 57.7 M Ω 43.6 M Ω OK OK

WH 59.6 M Ω 47.8 M Ω OK OK

Pair-3 BK 20.5 M Ω 59.6 M Ω 48.5 M Ω OK OK

WH 63.3 M Ω 50.2 M Ω OK OK

Pair-4 BK 15.8 M Ω 66.1 M Ω 52.7 M Ω OK OK

WH 68.9 M Ω 56.8 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020211
Drawing No DN # Date 27-01-2024
Cable Size & Types 4p*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 135 Mohm 128M ohm 163M ohm OK OK

WH 102M ohm 123M ohm OK OK

Pair-2 BK 80M ohm 121M ohm 131M ohm OK OK

WH 264M ohm 138M ohm OK OK

Pair-3 BK 68.1M ohm 94.1M ohm 106M ohm OK OK

WH 104M ohm 113M ohm OK OK

Pair-4 BK 66.6M ohm 88.1M ohm 94.3M ohm OK OK

WH 92.7M ohm 96M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31023


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020225
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 6Tx1.5mm2 cu/pvc/pvc OA shielded Length 1000 M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Drain Conductor
Core No. Core to Core Core to Ground Core to Shield
Continuity Continuity

Triad-6 RD-BK 169 M Ω RD-GRD 98 M Ω RD-S 64.9 M Ω OK OK

RD-WH 166 M Ω BK-GRD 117 M Ω BK-s 85.4 M Ω OK OK

BK-WH 161 M Ω WH-GRD 116 M Ω WH-S 91.6 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-21
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 500M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 185 M Ω 221 M Ω 197 M Ω OK OK

WH 353 M Ω 378 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-20
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 274 M Ω 183 M Ω 212 M Ω OK OK

WH 115 M Ω 148 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-19
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 160 M Ω 94.1 M Ω 125 M Ω OK OK

WH 117 M Ω 133 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-18
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 309 M Ω 232 M Ω 270 M Ω OK OK

WH 129 M Ω 152 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-17
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 231 M Ω 158 M Ω 193 M Ω OK OK

WH 111 M Ω 131 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-16
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 143 M Ω 115 M Ω 141 M Ω OK OK

WH 162 M Ω 189 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-15
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 121 M Ω 104 M Ω 130 M Ω OK OK

WH 85.4 M Ω 109 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-13
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 213 M Ω 167 M Ω 196 M Ω OK OK

WH 118 M Ω 155 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-12
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 124 M Ω 110 M Ω 73.2 G Ω OK OK

WH 92.0 M Ω 33.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-11
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 188 M Ω 134 M Ω 162 M Ω OK OK

WH 112 M Ω 135 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-10
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 94.1 M Ω 87.7 M Ω 105 M Ω OK OK

WH 102 M Ω 111 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-9
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 154 M Ω 149 M Ω 534 M Ω OK OK

WH 97.0 M Ω 164 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-8
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 200 M Ω 191 M Ω 216 M Ω OK OK

WH 91.9 M Ω 108 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-7
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 218 M Ω 169 M Ω 154 M Ω OK OK

WH 102 M Ω 98.4 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-6
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 313 M Ω 277 M Ω 301 M Ω OK OK

WH 135 M Ω 151 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-5
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 155 M Ω 127 M Ω 152 M Ω OK OK

WH 106 M Ω 134 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-4
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 165 M Ω 97.8 M Ω 129 M Ω OK OK

WH 113 M Ω 146 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-3
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 229 M Ω 115 M Ω 204 M Ω OK OK

WH 163 M Ω 133 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-2
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 186 M Ω 125 M Ω 133 M Ω OK OK

WH 128 M Ω 125 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-1
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 266 M Ω 190 M Ω 180 M Ω OK OK

WH 132 M Ω 230 M Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-1__
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 143 Mohm 115M ohm 141M ohm OK OK

WH 162M ohm 189M ohm OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020227
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 2.75 G Ω OK

BK-GRND 2.83 G Ω OK

RD-GRND 2.27 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020228
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 3.41 G Ω OK

BK-GRND 3.93 G Ω OK

RD-GRND 3.62 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020229
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage _________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 3.03 G Ω OK

BK-GRND 3.22 G Ω OK

RD-GRND 2.20 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020230
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 2.69 G Ω OK

BK-GRND 5.79 G Ω OK

RD-GRND 2.72 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum#16023-020231
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 2.86 G Ω OK

BK-GRND 2.26 G Ω OK

RD-GRND 1.25 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020232
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:____________6000/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 3.02 G Ω OK

BK-GRND 3.47 G Ω OK

RD-GRND 3.15 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31024


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 2.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020233
Drawing No DN # 63179 Date 27-01-2024
Cable Size & Types 3Cx2.5mm2 cu/xLpE/pvc Length 2000M

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________1000V_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

RD-BK 3.23 G Ω OK

BK-GRND 3.82 G Ω OK

RD-GRND 3.36 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No
Tag Description Tag# Cable No
Drawing No Date
Cable Size & Types Length

Cable from _______In drum____________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK OK OK

WH OK OK

Pair-2 BK OK OK

WH OK OK

Pair-3 BK OK OK

WH OK OK

Pair-4 BK OK OK

WH OK OK

Pair-5 BK OK OK

WH OK OK

Pair-6 BK OK OK

WH OK OK

Pair-7 BK OK OK

WH OK OK

Pair-8 BK OK OK

WH OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 4-400W2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 77 M

Cable from WTL control panel RIO 4-X6 Cable To, WTL Field FIELD_RIO 4-AIT-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 16.3 G Ω 43.16 G Ω 48.2 G Ω OK OK

WH 35.76 G Ω 52.02 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO4-508-WO Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 103 M

Cable from WTL control panel RIO 4-X13 Cable To, WTL Field FIELD_RIO 4-VM-08-30_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

PAIR-1 BK 964 M Ω 1.35 G Ω 1.1 G Ω OK OK

WH 1.42 G Ω 4.2 G Ω OK OK

PAIR-2 BK 423 M Ω 1.11 G Ω 2.5 G Ω OK OK

WH 1.32 G Ω 3.5 G Ω OK OK

PAIR-3 BK 340 M Ω 1.29 G Ω 9.4 G Ω OK OK

WH 1.02 G Ω 28.1 G Ω OK OK

PAIR-4 BK 313 M Ω 901 M Ω 54.2 G Ω OK OK

WH 824 G Ω 21.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-11-VD1M Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 22 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

PAIR-1 BK 16.6 G Ω 49.5 G Ω 19.1 G Ω OK OK

WH 46.5 G Ω 24.2 G Ω OK OK

PAIR-2 BK 17.0 G Ω 30.0 G Ω 32.5 G Ω OK OK

WH 27.9 G Ω 30.5 G Ω OK OK

PAIR-3 BK 15.5 G Ω 26.9 G Ω 29.4 G Ω OK OK

WH 23.3 G Ω 28.1 G Ω OK OK

PAIR-4 BK 17.4 G Ω 28.1 G Ω 54.2 G Ω OK OK

WH 21.6 G Ω 21.2 G Ω OK OK

PAIR-5 BK 16.7 G Ω 24.8 G Ω 25.6 G Ω OK OK

WH 22.9 G Ω 26 G Ω OK OK

PAIR-6 BK 15.4 G Ω 29.1 G Ω 28.2 G Ω OK OK

WH 28.1 G Ω 27.2 G Ω OK OK

PAIR-7 BK 18.2 G Ω 26.7 G Ω 26.1 G Ω OK OK

WH 28.0 G Ω 28.2 G Ω OK OK

PAIR-8 BK 18.0 G Ω 23.8 G Ω 24.1 G Ω OK OK

WH 25.1 G Ω 25.7 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-02013
Drawing No Tag # RIO-3-511W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 60 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-42_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.23 G Ω 1.87 G Ω 2.10 G Ω OK OK

WH 2.18 G Ω 3.00 G Ω OK OK

Pair-2 BK 1.57 G Ω 1.71 G Ω 1.99 G Ω OK OK

WH 2.21 G Ω 2.31 G Ω OK OK

Pair-3 BK 1.76 G Ω 2.00 G Ω 1.44 G Ω OK OK

WH 2.44 G Ω 2.33 G Ω OK OK

Pair-4 BK 1.73 G Ω 2.81 G Ω 1.05 G Ω OK OK

WH 2.39 G Ω 1.54 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO-3-504W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 311 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-23_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 849 M Ω 895 M Ω 6.35 G Ω OK OK

WH 951 M Ω 5.87 G Ω OK OK

Pair-2 BK 526 M Ω 942 M Ω 5.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 559 M Ω 6.35 G Ω 690 M Ω OK OK

WH 5.87 G Ω 901 M Ω OK OK

Pair-4 BK 624 M Ω 5.45 G Ω 994 M Ω OK OK

WH 5.11 G Ω 1.09 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-02013
Drawing No Tag # RIO-3-510W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 58 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-41_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 819 M Ω 690 M Ω 6.35 G Ω OK OK

WH 901 M Ω 5.87 G Ω OK OK

Pair-2 BK 446 M Ω 994 M Ω 5.45 G Ω OK OK

WH 1.09 G Ω 5.11 G Ω OK OK

Pair-3 BK 487 M Ω 895 M Ω 4.9 G Ω OK OK

WH 951 M Ω 5.11 G Ω OK OK

Pair-4 BK 424 M Ω 942 M Ω 4.97 G Ω OK OK

WH 1.05 G Ω 5.14 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO-3-504W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 310 M

Cable from WTL control panel RIO 3-X13 Cable To, WTL Field FIELD_RIO 3-VM-08-23_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.49 G Ω 25.8 G Ω 6.35 G Ω OK OK

WH 31.5G Ω 5.87 G Ω OK OK

Pair-2 BK 2.21 G Ω 6.5 G Ω 5.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 2.26 G Ω 3.35 G Ω 6.3 G Ω OK OK

WH 4.87 G Ω 9.5 G Ω OK OK

Pair-4 BK 1.38 G Ω 5.5 G Ω 6.4G Ω OK OK

WH 9.87 G Ω 3.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO3-505W5 Date 18/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 45 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-23_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.37 G Ω 1.25 G Ω 1.21 G Ω OK OK

WH 1.29 G Ω 1.47 G Ω OK OK

Pair-2 BK 1.51 G Ω 1.52 G Ω 1.06 G Ω OK OK

WH 1.51 G Ω 1.25 G Ω OK OK

Pair-3 BK 1.01 G Ω 1.37 G Ω 1.01 G Ω OK OK

WH 1.38 G Ω 1.51 G Ω OK OK

Pair-4 BK 977 M Ω 1.21 G Ω 1.37 G Ω OK OK

WH 1.5 G Ω 1.38 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO3-505W0 Date 18/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 44 M

Cable from WTL control panel RIO 3-X13 Cable To, WTL Field FIELD_RIO 3-VM-08-23_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.06 G Ω 1.5 G Ω 1.14 G Ω OK OK

WH 1.38 G Ω 1.55 G Ω OK OK

Pair-2 BK 1.47 G Ω 1.37 G Ω 1.21 G Ω OK OK

WH 1.02 G Ω 1.65 G Ω OK OK

Pair-3 BK 1.21 G Ω 1.19 G Ω 1.35 G Ω OK OK

WH 1.72 G Ω 1.06 G Ω OK OK

Pair-4 BK 1.17 G Ω 1.36 G Ω 1.67 G Ω OK OK

WH 1.07 G Ω 1.35 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO4-501W5 Date 18/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 88 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-21_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.12 G Ω 2.07 G Ω 3.97 G Ω OK OK

WH 1.5 G Ω 4.71 G Ω OK OK

Pair-2 BK 3.29 G Ω 3.11 G Ω 5.58 G Ω OK OK

WH 3.26 G Ω 7.8 G Ω OK OK

Pair-3 BK 2.07 G Ω 2.76 G Ω 4.87 G Ω OK OK

WH 2.37 G Ω 4.11 G Ω OK OK

Pair-4 BK 2.12 G Ω 2.65 G Ω 6.45 G Ω OK OK

WH 2.91 G Ω 5.23 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO4-501W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.50 Length 29 M

Cable from WTL control panel RIO 4-X13 Cable To, WTL Field FIELD_RIO 4-VM-08-21_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.9 G Ω 2.48 G Ω 8.97 G Ω OK OK

WH 2.25 G Ω 8.71 G Ω OK OK

Pair-2 BK 3.33 G Ω 3.31 G Ω 6.58 G Ω OK OK

WH 5.91 G Ω 11.8 G Ω OK OK

Pair-3 BK 2.22 G Ω 6.22 G Ω 8.87 G Ω OK OK

WH 9.11 G Ω 9.11 G Ω OK OK

Pair-4 BK 2.34 G Ω 9.45 G Ω 9.45 G Ω OK OK

WH 8.44 G Ω 11.2 G Ω

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO4-509W5 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 107 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-41_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.09 G Ω 2.56 G Ω 3.11 G Ω OK OK

WH 2.19 G Ω 2.24 G Ω OK OK

Pair-2 BK 1.81 G Ω 2.39 G Ω 4.22 G Ω OK OK

WH 2.62 G Ω 3.77 G Ω OK OK

Pair-3 BK 1.67 G Ω 2.23 G Ω 2.10 G Ω OK OK

WH 1.68 G Ω 2.09 G Ω OK OK

Pair-4 BK 1.50 G Ω 1.69 G Ω 4.16 G Ω OK OK

WH 2.55 G Ω 2.81 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO4-404W2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 80 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-FQIT-08-10_08

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.45 G Ω 1.77 G Ω 3.97 G Ω OK OK

WH 1.78 G Ω 1.24 G Ω OK OK

Pair-2 BK 1.56 G Ω 2.54 G Ω 3.20 G Ω OK OK

WH 2.20 G Ω 3.77 G Ω OK OK

Pair-3 BK 1.48 G Ω 1.81 G Ω 2.10 G Ω OK OK

WH 2.09 G Ω 2.09 G Ω OK OK

Pair-4 BK 1.68 G Ω 2.51 G Ω 4.16 G Ω OK OK

WH 3.16 G Ω 2.81 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO4-404W2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 80 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-FQIT-08-10_08

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.45 G Ω 1.77 G Ω 3.97 G Ω OK OK

WH 1.78 G Ω 1.24 G Ω OK OK

Pair-2 BK 1.56 G Ω 2.54 G Ω 3.20 G Ω OK OK

WH 2.20 G Ω 3.77 G Ω OK OK

Pair-3 BK 1.48 G Ω 1.81 G Ω 2.10 G Ω OK OK

WH 2.09 G Ω 2.09 G Ω OK OK

Pair-4 BK 1.68 G Ω 2.51 G Ω 4.16 G Ω OK OK

WH 3.16 G Ω 2.81 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO4-508W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 104 M

Cable from WTL control panel RIO 4-X10 Cable To, WTL Field FIELD_RIO 4-VM-08-30_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.23 G Ω 3.12 G Ω 2.99 G Ω OK OK

WH 3.26 G Ω 3.11 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO4-409W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 83 M

Cable from WTL control panel RIO 4-X6 Cable To, WTL Field FIELD_RIO 4-PISH-08-10_08

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.11 G Ω 2.90 G Ω 3.97 G Ω OK OK

WH 1.24 G Ω 1.24 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO4-310W1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 319 M

Cable from FIELD_RIO 2 Cable To, Blower Group controller FIELD_RIO 4-MCP-X15

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.3 G Ω 8.82 G Ω 8.97 G Ω OK OK

WH 7.79 G Ω 8.71 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO3-310W1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 281 M

Cable from WTL control panel RIO 3-X4 Cable To, Blower Group controller FIELD_RIO 3-MCP-X14

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 14.6G Ω 8.09 G Ω 9.82 G Ω OK OK

WH 7.46 G Ω 12.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO2-311W1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 216 M

Cable from WTL control panel RIO 2-X4 Cable To, Blower Group controller FIELD_RIO 2-MCP-X13

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 14.4 G Ω 7.17 G Ω 9.12 G Ω OK OK

WH 8.27 G Ω 8.93 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO1-312W1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 137 M

Cable from WTL control panel RIO 1-X4 Cable To, Blower Group controller FIELD_RIO 1-MCP-X11

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.2 G Ω 7.87 G Ω 9.13 G Ω OK OK

WH 8.14G Ω 8.77 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag #Rio1-313W1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 138 M

Cable from WTL control panel RIO 1-X4 Cable To, Blower Group controller FIELD_RIO 1-MCP-X12

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 14.6 G Ω 8.64 G Ω 5.99 G Ω OK OK

WH 7.72G Ω 9.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO2-310W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 215 M

Cable from WTL control panel RIO 2-X4 Cable To, WTL Field FIELD_RIO 2-MCC - QV-08-40_02

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 32.8 G Ω 20.8 G Ω 15.99 G Ω OK OK

WH 17.2 G Ω 21.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO1-310W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 132 M

Cable from WTL control panel RIO 1-X4 Cable To, WTL Field FIELD_RIO 1-MCC - QV-08-40_01

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 19.9 G Ω 19.9 G Ω 15.99 G Ω OK OK

WH 16.1 G Ω 21.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-13-VD2 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 27.5 G Ω 22.6 G Ω 24.1 G Ω OK OK

WH 21.1 G Ω 23.7 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-23-VD2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.8 G Ω 20.5 G Ω 22.1 G Ω OK OK

WH 21.2 G Ω 23 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-04-31-ZD1 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 119 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 28.2 G Ω 36.3 G Ω 47.5G Ω OK OK

WH 39.1 G Ω 96.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_03-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.11 GΩ 4.41GΩ 3.72 GΩ OK OK

WH 3.94 GΩ 3.91 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # AF-08-03-42-VD2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.50 Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 24.9 G Ω 22.8 G Ω 24.1 G Ω OK OK

WH 17.3 G Ω 22.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 4-506W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 98 M

Cable from WTL control panel RIO 4-X10 Cable To, WTL Field FIELD_RIO 4-VM-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.33 G Ω 4.11 G Ω 4.58 G Ω OK OK

WH 3.33 G Ω 6.02 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 4-400W2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 77 M

Cable from WTL control panel RIO 4-X6 Cable To, WTL Field FIELD_RIO 4-AIT-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.8 G Ω 4.16 G Ω 4.78 G Ω OK OK

WH 3.76 G Ω 5.02 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273341-20
Drawing No Tag # RIO 3-508W6 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 54 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-VM-08-30_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.10 G Ω 3.41 G Ω 4.38 G Ω OK OK

WH 3.11 G Ω 5.22 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273341-20
Drawing No Tag # RIO 3-507W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 50 M

Cable from WTL control panel RIO 3-X10 Cable To, WTL Field FIELD_RIO 3-VM-08-30_32

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.93 G Ω 3.12 G Ω 5.38 G Ω OK OK

WH 2.79 G Ω 5.12 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273341-20
Drawing No Tag # RIO 3-508W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 53 M

Cable from WTL control panel RIO 3-X10 Cable To, WTL Field FIELD_RIO 3-VM-08-30_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 10.6 G Ω 3.43 G Ω 4.38 G Ω OK OK

WH 1.10 G Ω 5.16 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 3-507W6 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 51 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-VM-08-30_32

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.10 G Ω 1.61 G Ω 4.18 G Ω OK OK

WH 2.84 G Ω 5.56 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 4-406W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 82 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-PT-08-40_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.46 G Ω 1.86 G Ω 5.18 G Ω OK OK

WH 3.48 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-10
Drawing No Tag # RIO 3-400W2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 35 M

Cable from WTL control panel RIO 3-X6 Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.03 G Ω 3.28 G Ω 7.28 G Ω OK OK

WH 1.58 G Ω 6.56 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-20
Drawing No Tag # RIO1-406W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 10 M

Cable from WTL control panel RIO 1-X9 Cable To, WTL Field FIELD_RIO 1-PT-08-40_10

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 54.3 G Ω 5.11 G Ω 6.99 G Ω OK OK

WH 4.77 G Ω 7.21 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-20
Drawing No Tag # RIO1-409WO Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 11 M

Cable from WTL control panel RIO 1-X9 Cable To, WTL Field FIELD_RIO 1-TIT-08-31_10

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 31.7 G Ω 6.43 G Ω 4.8 G Ω OK OK

WH 4.93 G Ω 5.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-20
Drawing No Tag # RIO1-405WO Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 9M

Cable from WTL control panel RIO 1-X9 Cable To, WTL Field FIELD_RIO 1-PT-08-30_10

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.21 G Ω 3.63 G Ω 4.33 G Ω OK OK

WH 2.75 G Ω 3.11G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-20
Drawing No Tag # RIO4-507W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 101 M

Cable from WTL control panel RIO 4-X10 Cable To, WTL Field FIELD_RIO 4-VM-08-30_42

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 9.51 G Ω 8.28 G Ω 7.99 G Ω OK OK

WH 7.93 G Ω 8.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-16
Drawing No Tag # RIO4-507W6 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 102 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-VM-08-30_42

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.29 G Ω 5.37 G Ω 5.99 G Ω OK OK

WH 5.21 G Ω 6.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-16
Drawing No Tag # RIO 4-405W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 81 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-PT-08-40_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.01 G Ω 7.10 G Ω 7.99 G Ω OK OK

WH 6.97 G Ω 8.43 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-409WO Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 296 M

Cable from WTL control panel RIO 3-X6 Cable To, WTL Field FIELD_RIO 3-PISH-08-10_06

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.47 G Ω 2.21 G Ω 2.69 G Ω OK OK

WH 2.14 G Ω 2.55 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273334161-6
Drawing No Tag # RIO1-301W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 5M

Cable from WTL control panel RIO 1-X4 Cable To, WTL Field FIELD_RIO 1-MCC - AF-08-03_12

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.57 G Ω 2.39 G Ω 3.4 G Ω OK OK

WH 2.71 G Ω 2.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273334161-6
Drawing No Tag # RIO1-300W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 3M

Cable from WTL control panel RIO 1-X4 Cable To, WTL Field FIELD_RIO 1-MCC - AF-08-03_11

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.61 G Ωs 2.44 G Ω 3.4 G Ω OK OK

WH 2.39G Ω 2.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BT-08-10-07-ZD1 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 81 M

Cable from Primary clarifiers and Biological MCC Cable To, LUCAS 04A SLUDGE SCREW PUMP

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 33.3 G Ω 22.7 G Ω 22.4 G Ω OK OK

WH 21.4 G Ω 12.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BT-08-10-07-REM Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 82 M

Cable from Primary clarifiers and Biological MCC Cable To, LUCAS 04A SLUDGE SCREW PUMP

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 33.13 G Ω 22.8 G Ω 14.76 G Ω OK OK

WH 22.6 G Ω 16.87 G Ω OK OK

Pair-2 BK 22.5 G Ω 21.2 G Ω 14.41 G Ω OK OK

WH 23.2 G Ω 13.97 G Ω OK OK

Pair-3 BK 21.3G Ω 24.1 G Ω 14.11 G Ω OK OK

WH 21.2 G Ω 14.97 G Ω OK OK

Pair-4 BK 17.5 G Ω 20.2 G Ω 14.61 G Ω OK OK

WH 21.3 G Ω 14.59 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO 4-502W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 89 M

Cable from WTL control panel RIO 4-X13 Cable To, WTL Field FIELD_RIO 4-VM-08-22_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.54 G Ω 3.22 G Ω 4.76 G Ω OK OK

WH 4.48 G Ω 4.87 G Ω OK OK

Pair-2 BK 4.05 G Ω 3.66 G Ω 4.41 G Ω OK OK

WH 3.98 G Ω 3.97 G Ω OK OK

Pair-3 BK 3.43 G Ω 4.02 G Ω 4.11 G Ω OK OK

WH 4.11 G Ω 4.97 G Ω OK OK

Pair-4 BK 3.48 G Ω 4.17 G Ω 4.61 G Ω OK OK

WH 4.10 G Ω 4.59 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag #RIO 4-502W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 90 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-22_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.98 G Ω 5.45 G Ω 6.35 G Ω OK OK

WH 4.87 G Ω 5.87 G Ω OK OK

Pair-2 BK 3.86 G Ω 4.79 G Ω 5.45 G Ω OK OK

WH 5.07 G Ω 5.11 G Ω OK OK

Pair-3 BK 3.36 G Ω 4.91 G Ω 4.9 G Ω OK OK

WH 5.21 G Ω 5.11 G Ω OK OK

Pair-4 BK 3.32 G Ω 5.31 G Ω 4.97 G Ω OK OK

WH 5.41 G Ω 5.14 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO 3-400W.1 Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 101 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.02 G Ω 1.16 G Ω 2.55 G Ω OK OK

WH 1.46 G Ω 3.72 G Ω OK OK

Pair-2 BK 2.4 G Ω 1.54 G Ω 2.91 G Ω OK OK

WH 1.71 G Ω 3.2 G Ω OK OK

Pair-3 BK 2.23 G Ω 1.63 G Ω 3.9 G Ω OK OK

WH 1.43 G Ω 2.45 G Ω OK OK

Pair-4 BK 2.26 G Ω 1.7 G Ω 3.28 G Ω OK OK

WH 1.39 G Ω 3.21 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-401W0.1 Date 17/3/2024
Cable Size & Types PVC/ISH/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 287 M

Cable from WTL Field FIELD_RIO 3-JB8-X Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.83 G Ω 3.51 G Ω 4.15 G Ω OK OK

WH 4.12 G Ω 4.22 G Ω OK OK

Pair-2 BK 6.08 G Ω 4.21 G Ω 3.51 G Ω OK OK

WH 4.35 G Ω 4.2 G Ω OK OK

Pair-3 BK 5.79 G Ω 5.13 G Ω 3.9 G Ω OK OK

WH 4.76 G Ω 3.95 G Ω OK OK

Pair-4 BK 5.89 G Ω 4.79 G Ω 3.88 G Ω OK OK

WH 4.91 G Ω 3.75 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-402W0.1 Date 17/3/2024
PVC/ISH/OSH/PVC/SWA/PVC FRLS
Cable Size & Types Length 290 M
500V - 4P x 1.50
Cable from WTL Field FIELD_RIO 3-JB9-X Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.02 G Ω 1.72 G Ω 2.15 G Ω OK OK

WH 1.51 G Ω 3.22 G Ω OK OK

Pair-2 BK 3.22 G Ω 2.01 G Ω 2.51 G Ω OK OK

WH 1.71 G Ω 3.2 G Ω OK OK

Pair-3 BK 2.91 G Ω 1.63 G Ω 3.9 G Ω OK OK

WH 1.91 G Ω 2.95 G Ω OK OK

Pair-4 BK 3.07 G Ω 1.89 G Ω 3.08 G Ω OK OK

WH 1.75 G Ω 3.41 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 4-503W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 92 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-22_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.67 G Ω 1.85 G Ω 2.5 G Ω OK OK

WH 2.9 G Ω 3.2 G Ω OK OK

Pair-2 BK 1.87 G Ω 1.66 G Ω 2.9 G Ω OK OK

WH 1.71 G Ω 4.2 G Ω OK OK

Pair-3 BK 1.35 G Ω 1.63 G Ω 3.9 G Ω OK OK

WH 1.66 G Ω 2.55 G Ω OK OK

Pair-4 BK 1.72 G Ω 2.35 G Ω 2.08 G Ω OK OK

WH 2.44 G Ω 3.11 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO-4-5-503W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 110 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.17 G Ω 2.45 G Ω 3.5 G Ω OK OK

WH 2.65 G Ω 3.8 G Ω OK OK

Pair-2 BK 3.62 G Ω 3.70 G Ω 4.4 G Ω OK OK

WH 3.72 G Ω 4.2 G Ω OK OK

Pair-3 BK 3.21 G Ω 3.51 G Ω 4.9 G Ω OK OK

WH 3.81 G Ω 2.55 G Ω OK OK

Pair-4 BK 3.36 G Ω 3.25 G Ω 5 1.08 G Ω OK OK

WH 3.35 G Ω 3.11 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # AF-08-03-32-VD2 Date 19/03/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 186 G Ω 21.5 G Ω 22.3 G Ω OK OK

WH 10.4 G Ω 20.7 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_11-VD3- Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 26.4 G Ω 22.4 G Ω 23.1 G Ω OK OK

WH 24.0 G Ω 21.01 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-11-VD2 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 40.3 G Ω 23.6 G Ω 22.2 G Ω OK OK

WH 21.2 G Ω 21.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag #BS-08-20-41-VD2 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.1 G Ω 16.6 G Ω 11.22 G Ω OK OK

WH 13.2 G Ω 12.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-21-VD2 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.0 G Ω 18.6 G Ω 22.1 G Ω OK OK

WH 5.87 G Ω 21.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-21-VD3 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 23.8 G Ω 18.9 G Ω 17.44 G Ω OK OK

WH 12.1 G Ω 23.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-23-VD3 Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 28.6 G Ω 20.5 G Ω 22.1 G Ω OK OK

WH 19.6 G Ω 21.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO3-307W7 Date 28/3/2024
Cable Size & Types 1P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 18 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.71 G Ω 2.66 G Ω 3.4 G Ω OK OK

WH 2.51 G Ω 2.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273334161-6
Drawing No Tag # RIO3-302W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 23 M

Cable from WTL control panel RIO 3-X4 Cable To, WTL Field FIELD_RIO 3-MCC - AF-08-03_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.79 G Ω 2.59 G Ω 3.4 G Ω OK OK

WH 2.72 G Ω 2.45 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273334161-6
Drawing No Tag # RIO2-301W7 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from WTL control panel RIO 2-X4 Cable To, WTL Field FIELD_RIO 2-MCC - AF-08-03_22

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.9 G Ω 19.5 G Ω 20.5 G Ω OK OK

WH 19.4 G Ω 21.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273334161-6
Drawing No Tag # RIO2-302W7 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 17 M

Cable from WTL control panel RIO 2-X4 Cable To, WTL Field FIELD_RIO 2-MCC - AF-08-03_23

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 27.5 G Ω 23.0G Ω 26.5G Ω OK OK

WH 18.4 G Ω 22.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-43-ZD1 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 108 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 4C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.3 G Ω 19.3 G Ω 24.5G Ω OK OK

WH 18.1 G Ω 23.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-8
Drawing No Tag # RIO4-300W7 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 22 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-MCC - AF-08-03_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.66 G Ω 2.51 G Ω 2.5G Ω OK OK

WH 2.45 G Ω 3.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-8
Drawing No Tag #RIO4-301W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 18 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-MCC - AF-08-03_42

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.33 G Ω 2.66 G Ω 3.2 G Ω OK OK

WH 2.71 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO2-301W7 Date 28/3/2024
Cable Size & Types 1P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 100 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.9 G Ω 19.5 G Ω 20.5 G Ω OK OK

WH 19.4 G Ω 21.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-8
Drawing No Tag #RIO4-302W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 18 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-MCC - AF-08-03_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.33 G Ω 2.66 G Ω 3.2 G Ω OK OK

WH 2.71 G Ω 5.4 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-8
Drawing No Tag # RIO4-303W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 18 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-MCC - AF-08-04_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.71 G Ω 2.47 G Ω 1.9 G Ω OK OK

WH 2.54 G Ω 2.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # AF-08-03-21-VD2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.50 Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 32.9 G Ω 22.4 G Ω 19 G Ω OK OK

WH 9.75 G Ω 21.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-04-33-ZD1 Date 28/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 26.2 G Ω 48.3 G Ω 49.5G Ω OK OK

WH 38.1 G Ω 56.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 1-306W1 Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 17 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 24.4 G Ω 45.9 G Ω 33.1 G Ω OK OK

WH 33.7 G Ω 33.4 G Ω OK OK

Pair-2 BK 24.8 G Ω 34.6 G Ω 31.3 G Ω OK OK

WH 33.2 G Ω 33.1 G Ω OK OK

Pair-3 BK 23.7 G Ω 23.8 G Ω 31.2 G Ω OK OK

WH 23 G Ω 33.1 G Ω OK OK

Pair-4 BK 15.9 G Ω 18 G Ω 26.9 G Ω OK OK

WH 35.2 G Ω 27.3 G Ω OK OK

Pair-5 BK 16.7 G Ω 29.1 G Ω 30.0 G Ω OK OK

WH 20.3 G Ω 31.1 G Ω OK OK

Pair-6 BK 10.7 G Ω 26.0 G Ω 33.3 G Ω OK OK

WH 33.5 G Ω 34.1 G Ω OK OK

Pair-7 BK 24.6 G Ω 37.3 G Ω 33.3 G Ω OK OK

WH 36.2 G Ω 33.2 G Ω OK OK

Pair-8 BK 25.7 G Ω 25.2 G Ω 32.5 G Ω OK OK

WH 25.4 G Ω 31.3 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-23-VD1M Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 22 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.4 G Ω 34.9 G Ω 31.1 G Ω OK OK

WH 31.2 G Ω 32.4 G Ω OK OK

Pair-2 BK 15.8 G Ω 29.7 G Ω 32.3 G Ω OK OK

WH 18.6 G Ω 33.1 G Ω OK OK

Pair-3 BK 18.3 G Ω 23.8 G Ω 31.2 G Ω OK OK

WH 23 G Ω 33.1 G Ω OK OK

Pair-4 BK 15.9 G Ω 18 G Ω 26.9 G Ω OK OK

WH 35.2 G Ω 27.3 G Ω OK OK

Pair-5 BK 16.7 G Ω 29.1 G Ω 30.0 G Ω OK OK

WH 20.3 G Ω 31.1 G Ω OK OK

Pair-6 BK 10.7 G Ω 26.0 G Ω 33.3 G Ω OK OK

WH 33.1 G Ω 34.1 G Ω OK OK

Pair-7 BK 14.5 G Ω 21.1 G Ω 33.3 G Ω OK OK

WH 33.1 G Ω 31.2 G Ω OK OK

Pair-8 BK 14.1 G Ω 35.1 G Ω 32.1 G Ω OK OK

WH 32.2 G Ω 32.3 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-21-VD1M Date 19/03/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 22 M

Cable from BIOLOGICAL TREATMENT MAIN SYSTEM CONTROL PA Cable To, Primary clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 28.6 G Ω 29.7 G Ω 33.1 G Ω OK OK

WH 23.1 G Ω 32.5 G Ω OK OK

Pair-2 BK 17.8 G Ω 25.2 G Ω 32.1 G Ω OK OK

WH 18.6 G Ω 33.2 G Ω OK OK

Pair-3 BK 16.3 G Ω 23.8 G Ω 31.2 G Ω OK OK

WH 23 G Ω 33.1 G Ω OK OK

Pair-4 BK 16.9 G Ω 18 G Ω 26.9 G Ω OK OK

WH 15.2 G Ω 27.3 G Ω OK OK

Pair-5 BK 16.7 G Ω 17.1 G Ω 30.0 G Ω OK OK

WH 20.3 G Ω 31.1 G Ω OK OK

Pair-6 BK 10.7 G Ω 26.0 G Ω 33.3 G Ω OK OK

WH 33.1 G Ω 34.1 G Ω OK OK

Pair-7 BK 13.9 G Ω 21.1 G Ω 33.3 G Ω OK OK

WH 23.1 G Ω 33.2 G Ω OK OK

Pair-8 BK 14.6 G Ω 25.1 G Ω 32.1 G Ω OK OK

WH 22.2 G Ω 31.3 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020205
Drawing No Tag # RIO 3-301W1 Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 18 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.2 G Ω 31 G Ω 33.1 G Ω OK OK

WH 32.1 G Ω 32.2 G Ω OK OK

Pair-2 BK 20.4 G Ω 27.2 G Ω 33.3 G Ω OK OK

WH 25.7 G Ω 34.2 G Ω OK OK

Pair-3 BK 19.1 G Ω 23.8 G Ω 31.2 G Ω OK OK

WH 24.8 G Ω 33.1 G Ω OK OK

Pair-4 BK 18.6 G Ω 29.0 G Ω 26.9 G Ω OK OK

WH 30.4 G Ω 27.3 G Ω OK OK

Pair-5 BK 17.2 G Ω 29.2 G Ω 30.0 G Ω OK OK

WH 27.3 G Ω 31.1 G Ω OK OK

Pair-6 BK 16 G Ω 26.0 G Ω 33.3 G Ω OK OK

WH 33.1 G Ω 35.1 G Ω OK OK

Pair-7 BK 18.8G Ω 27.3 G Ω 32.3 G Ω OK OK

WH 26.3 G Ω 33.2 G Ω OK OK

Pair-8 BK 21.9 G Ω 25.4 G Ω 32.1 G Ω OK OK

WH 23.3 G Ω 32.3 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020205
Drawing No Tag # RIO 3-300W1 Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 18 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 22.6 G Ω 30.6 G Ω 36.1 G Ω OK OK

WH 35.1 G Ω 32.2 G Ω OK OK

Pair-2 BK 15.8 G Ω 17.9 G Ω 33.1 G Ω OK OK

WH 18.6 G Ω 39.2 G Ω OK OK

Pair-3 BK 15.9 G Ω 23.8 G Ω 31.2 G Ω OK OK

WH 24.8 G Ω 33.1 G Ω OK OK

Pair-4 BK 18.6 G Ω 29.0 G Ω 26.9 G Ω OK OK

WH 30.4 G Ω 27.3 G Ω OK OK

Pair-5 BK 17.2 G Ω 30.7 G Ω 30.0 G Ω OK OK

WH 27.5 G Ω 31.1 G Ω OK OK

Pair-6 BK 16.6 G Ω 26.0 G Ω 33.3 G Ω OK OK

WH 33.1 G Ω 35.1 G Ω OK OK

Pair-7 BK 17.6 G Ω 32.7 G Ω 32.3 G Ω OK OK

WH 26.1 G Ω 37.2 G Ω OK OK

Pair-8 BK 16.2 G Ω 27.5 G Ω 35.1 G Ω OK OK

WH 24.8 G Ω 33.3 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020205
Drawing No Tag # RIO 4-301W1 Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 18 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 22.4 G Ω 30.3 G Ω 35.2 G Ω OK OK

WH 35.8 G Ω 29.4 G Ω OK OK

Pair-2 BK 23 G Ω 20 G Ω 31.1 G Ω OK OK

WH 24.4 G Ω 33 G Ω OK OK

Pair-3 BK 23 G Ω 28.8 G Ω 36.1 G Ω OK OK

WH 33.1 G Ω 32 G Ω OK OK

Pair-4 BK 26.6 G Ω 32.7 G Ω 26.9 G Ω OK OK

WH 33.9 G Ω 32.7 G Ω OK OK

Pair-5 BK 21.6 G Ω 33.9 G Ω 33.1 G Ω OK OK

WH 38.5 G Ω 33.3 G Ω OK OK

Pair-6 BK 19.8 G Ω 33.6 G Ω 33.1 G Ω OK OK

WH 33.9 G Ω 32.1 G Ω OK OK

Pair-7 BK 20.1 G Ω 29.5 G Ω 32.5 G Ω OK OK

WH 33.1 G Ω 33.2 G Ω OK OK

Pair-8 BK 24.7 G Ω 33.6 G Ω 32.7 G Ω OK OK

WH 30.2 G Ω 33.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # BT-08-10-03-VD1M Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.5 G Ω 19.9 G Ω 29.1 G Ω OK OK

WH 23.7 G Ω 29.4 G Ω OK OK

Pair-2 BK 18 G Ω 22.1 G Ω 31.1 G Ω OK OK

WH 22.4 G Ω 32 G Ω OK OK

Pair-3 BK 17.7 G Ω 27 G Ω 35.1 G Ω OK OK

WH 31.1 G Ω 32 G Ω OK OK

Pair-4 BK 18.6 G Ω 32.3 G Ω 26.9 G Ω OK OK

WH 27.5 G Ω 28.7 G Ω OK OK

Pair-5 BK 17.7 G Ω 26.1 G Ω 33.1 G Ω OK OK

WH 30.6 G Ω 33.3 G Ω OK OK

Pair-6 BK 16.5 G Ω 24.2 G Ω 30.1 G Ω OK OK

WH 23.6 G Ω 32.1 G Ω OK OK

Pair-7 BK 17.1 G Ω 25.3 G Ω 34.5 G Ω OK OK

WH 21.7 G Ω 32.5 G Ω OK OK

Pair-8 BK 19.3 G Ω 23.4 G Ω 30.4 G Ω OK OK

WH 21.7 G Ω 31.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # BT-08-10-06-VD1M Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 38.8 G Ω 33.8 G Ω 39.1 G Ω OK OK

WH 39.8 G Ω 29.4 G Ω OK OK

Pair-2 BK 36. G Ω 22 G Ω 33.1 G Ω OK OK

WH 22.4 G Ω 32 G Ω OK OK

Pair-3 BK 30.1 G Ω 27 G Ω 35.1 G Ω OK OK

WH 31.1 G Ω 32 G Ω OK OK

Pair-4 BK 31.8 G Ω 32.3 G Ω 26.9 G Ω OK OK

WH 27.5 G Ω 32.7 G Ω OK OK

Pair-5 BK 31.2 G Ω 26.1 G Ω 33.1 G Ω OK OK

WH 30.6 G Ω 33.3 G Ω OK OK

Pair-6 BK 30.7 G Ω 40.2 G Ω 33.1 G Ω OK OK

WH 33.6 G Ω 32.1 G Ω OK OK

Pair-7 BK 32 G Ω 41.3 G Ω 34.5 G Ω OK OK

WH 41.7 G Ω 33.5 G Ω OK OK

Pair-8 BK 27.9 G Ω 43.4 G Ω 33.4 G Ω OK OK

WH 39.7 G Ω 35.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # BT-08-10-05-VD1M Date 19/03/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 42.7 G Ω 28.4 G Ω 39 G Ω OK OK

WH 30.1 G Ω 28.4 G Ω OK OK

Pair-2 BK 33.6 G Ω 39 G Ω 32.1 G Ω OK OK

WH 34 G Ω 33 G Ω OK OK

Pair-3 BK 29.9 G Ω 27 G Ω 36.1 G Ω OK OK

WH 31.1 G Ω 32 G Ω OK OK

Pair-4 BK 24 G Ω 32.3 G Ω 26.9 G Ω OK OK

WH 27.5 G Ω 32.7 G Ω OK OK

Pair-5 BK 21.5 G Ω 26.1 G Ω 33.1 G Ω OK OK

WH 30.6 G Ω 33.3 G Ω OK OK

Pair-6 BK 23.7 G Ω 35.1 G Ω 33.1 G Ω OK OK

WH 33.1 G Ω 32.1 G Ω OK OK

Pair-7 BK 26.9 G Ω 31.1 G Ω 32.5 G Ω OK OK

WH 33.2 G Ω 33.1 G Ω OK OK

Pair-8 BK 26.7 G Ω 32.5 G Ω 32.4 G Ω OK OK

WH 32.2 G Ω 34.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO 3-501W5 Date 18/03/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 41 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-21_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.25 G Ω 1.38 G Ω 1.65 G Ω OK OK

WH 1.53 G Ω 1.37 G Ω OK OK

Pair-2 BK 1.67 G Ω 1.33 G Ω 1.41 G Ω OK OK

WH 1.24 G Ω 1.51 G Ω OK OK

Pair-3 BK 1.21 G Ω 1.17 G Ω 1.23 G Ω OK OK

WH 1.29 G Ω 1.29 G Ω OK OK

Pair-4 BK 1.06 G Ω 1.11 G Ω 1.36 G Ω OK OK

WH 1.17 G Ω 1.21 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO-3-410W4-1 Date 17/3/2024
PVC/ISH/OSH/PVC/SWA/PVC FRLS
Cable Size & Types Length 297 M
500V - 4P x 1.50
Cable from WTL Field FIELD_RIO 3-JB19-X Cable To, WTL Field FIELD_AIT_SB_L3L4-AIT-SB-L3-pH/ORP/CON

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.44 G Ω 1.81 G Ω 3.10 G Ω OK OK

WH 1.15 G Ω 2.00 G Ω OK OK

Pair-2 BK 1.15 G Ω 1.11 G Ω 2.99 G Ω OK OK

WH 1.17 G Ω 1.31 G Ω OK OK

Pair-3 BK 1.86 G Ω 1.39 G Ω 2.44 G Ω OK OK

WH 1.32 G Ω 2.33 G Ω OK OK

Pair-4 BK 1.84 G Ω 1.79 G Ω 2.05 G Ω OK OK

WH 1.41 G Ω 2.54 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO 3-503W5 Date 18/03/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 43 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-22_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.21 G Ω 1.36 G Ω 2.1 G Ω OK OK

WH 1.27 G Ω 1.81 G Ω OK OK

Pair-2 BK 2.55 G Ω 1.33 G Ω 1.91 G Ω OK OK

WH 1.21 G Ω 1.39 G Ω OK OK

Pair-3 BK 1.14 G Ω 1.71 G Ω 1.47 G Ω OK OK

WH 1.52 G Ω 1.54 G Ω OK OK

Pair-4 BK 1.07 G Ω 1.45 G Ω 1.83 G Ω OK OK

WH 1.32 G Ω 1.94 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO-3-500W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 307 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-21_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.49 G Ω 25.8 G Ω 6.35 G Ω OK OK

WH 31.5G Ω 5.87 G Ω OK OK

Pair-2 BK 29.21 G Ω 6.5 G Ω 5.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 26.26 G Ω 6.35 G Ω 6.3 G Ω OK OK

WH 5.87 G Ω 9.5 G Ω OK OK

Pair-4 BK 13.38 G Ω 5.45 G Ω 6.4G Ω OK OK

WH 5.11 G Ω 3.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO3-500 -WO Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 32 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 781 M Ω 1.66 G Ω 3.5 G Ω OK OK

WH 1.72 G Ω 3.8 G Ω OK OK

Pair-2 BK 1.08 G Ω 1.79 G Ω 2.4 G Ω OK OK

WH 1.83 G Ω 2.2 G Ω OK OK

Pair-3 BK 756 M Ω 1.41 G Ω 2.9 G Ω OK OK

WH 1.56 G Ω 2.55 G Ω OK OK

Pair-4 BK 631 M Ω 908 M Ω 1.08 G Ω OK OK

WH 1.11 G Ω 1.11 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-400W0 Date 17/3/2024
Cable Size & Types XLPE/PVC/SWA/PVC 0,6/1kV (AC) - 2C x 2.50 Length 34 M

Cable from WTL control panel RIO 3-X8 Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 143 G Ω OK

RD-GND 144 G Ω OK

BK-GND 137 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020227
Drawing No Tag # RIO 3-403W0 Date 17/3/2024
Cable Size & Types XLPE/PVC/SWA/PVC 0,6/1kV (AC) - 2C x 2.50 Length 293 M

Cable from WTL control panel RIO 3-X8 Cable To, WTL Field FIELD_RIO 3-FQIT-08-10_05

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 99.5 G Ω OK

RD-GND 106 G Ω OK

BK-GND 109 G Ω OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020210
Drawing No Tag # RIO 3-403W2 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 294 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-FQIT-08-10_05

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.33 G Ω 3.19 G Ω 4.35 G Ω OK OK

WH 2.22 G Ω 3.87 G Ω OK OK

Pair-2 BK 2.26 G Ω 2.26 G Ω 3.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 2.33 G Ω 2.41 G Ω 6.3 G Ω OK OK

WH 2.27 G Ω 3.5 G Ω OK OK

Pair-4 BK 1.70 G Ω 2.29 G Ω 3.4G Ω OK OK

WH 2.31 G Ω 2.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO-3-502W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 308 M

Cable from WTL control panel RIO 3-X13 Cable To, WTL Field FIELD_RIO 3-VM-08-22_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.54 G Ω 1.57 G Ω 3.35 G Ω OK OK

WH 1.62 G Ω 3.87 G Ω OK OK

Pair-2 BK 1.92 G Ω 1.45 G Ω 4.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 1.61 G Ω 2.41 G Ω 6.3 G Ω OK OK

WH 2.27 G Ω 5.5 G Ω OK OK

Pair-4 BK 1.71 G Ω 1.61 G Ω 3.5G Ω OK OK

WH 1.59 G Ω 4.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 3-309W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 33 M

Cable from WTL control panel RIO 3-X4 Cable To, WTL Field FIELD_RIO 3-CM-08-01_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.6 G Ω 2.71 G Ω 2.85 G Ω OK OK

WH 2.79 G Ω 3.17 G Ω OK OK

Pair-2 BK 2.77 G Ω 2.17 G Ω 3.25 G Ω OK OK

WH 1.05 G Ω 3.11 G Ω OK OK

Pair-3 BK 2.66 G Ω 2.41 G Ω 3.31 G Ω OK OK

WH 3.13 G Ω 2.53 G Ω OK OK

Pair-4 BK 2.54 G Ω 2.79 G Ω 3.13G Ω OK OK

WH 2.73 G Ω 3.17 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 4-309W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 75 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-CM-08-01_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.79 G Ω 2.78 G Ω 2.55 G Ω OK OK

WH 2.71 G Ω 3.27 G Ω OK OK

Pair-2 BK 2.79 G Ω 3.17 G Ω 3.25 G Ω OK OK

WH 1.05 G Ω 3.11 G Ω OK OK

Pair-3 BK 2.66 G Ω 2.41 G Ω 3.31 G Ω OK OK

WH 3.13 G Ω 2.53 G Ω OK OK

Pair-4 BK 2.71 G Ω 2.77 G Ω 3.03G Ω OK OK

WH 2.72 G Ω 4.17 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 4-309W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 74 M

Cable from WTL control panel RIO 4-X3 Cable To, WTL Field FIELD_RIO 4-CM-08-01_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.54 G Ω 2.66 G Ω 3.55 G Ω OK OK

WH 2.57 G Ω 3.47 G Ω OK OK

Pair-2 BK 2.513 G Ω 3.17 G Ω 3.25 G Ω OK OK

WH 1.05 G Ω 3.11 G Ω OK OK

Pair-3 BK 2.47 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 3.13 G Ω 2.5 G Ω OK OK

Pair-4 BK 2.59 G Ω 2.55 G Ω 3.63G Ω OK OK

WH 2.71 G Ω 4.12 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 3-309W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 32 M

Cable from WTL control panel RIO 3-X3 Cable To, WTL Field FIELD_RIO 3-CM-08-01_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.61 G Ω 3.44 G Ω 3.15 G Ω OK OK

WH 3.21 G Ω 3.87 G Ω OK OK

Pair-2 BK 3.33 G Ω 3.17 G Ω 3.25 G Ω OK OK

WH 1.05 G Ω 3.11 G Ω OK OK

Pair-3 BK 3.10 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 3.13 G Ω 2.5 G Ω OK OK

Pair-4 BK 3.13 G Ω 2.91 G Ω 3.13G Ω OK OK

WH 3.14 G Ω 3.12 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-401W0 Date 17/3/2024
Cable Size & Types PVC/ISH/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 286 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 937 M Ω 789 M Ω 2.25 G Ω OK OK

WH 810 M Ω 1.17 G Ω OK OK

Pair-2 BK 944 M Ω 841 M Ω 2.55 G Ω OK OK

WH 791 M Ω 1.21 G Ω OK OK

Pair-3 BK 911 M Ω 1.41 G Ω 2.01 G Ω OK OK

WH 2.07 G Ω 2.5 G Ω OK OK

Pair-4 BK 917 M Ω 1.74 G Ω 1.1 G Ω OK OK

WH 889 M Ω 1.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-400W4 Date 17/3/2024
PVC/ISH/OSH/PVC/SWA/PVC FRLS
Cable Size & Types Length 282 M
500V - 4P x 1.50
Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 897 M Ω 686 M Ω 1.25 G Ω OK OK

WH 710 M Ω 2.17 G Ω OK OK

Pair-2 BK 908 M Ω 821 M Ω 2.25 G Ω OK OK

WH 791 M Ω 3.21 G Ω OK OK

Pair-3 BK 827 M Ω 1.41 G Ω 2.3 G Ω OK OK

WH 2.27 G Ω 2.5 G Ω OK OK

Pair-4 BK 870 M Ω 1.61 G Ω 3.1 G Ω OK OK

WH 887 M Ω 2.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 4-402W0 Date 17/3/2024
PVC/ISH/OSH/PVC/SWA/PVC FRLS
Cable Size & Types Length 327 M
500V - 4P x 1.50
Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-AIT-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 798 M Ω 688 M Ω 1.35 G Ω OK OK

WH 711 M Ω 2.87 G Ω OK OK

Pair-2 BK 856 M Ω 810 M Ω 2.45 G Ω OK OK

WH 1.05 G Ω 3.11 G Ω OK OK

Pair-3 BK 788 M Ω 2.41 G Ω 2.3 G Ω OK OK

WH 2.27 G Ω 2.5 G Ω OK OK

Pair-4 BK 872 M Ω 1.61 G Ω 3.5G Ω OK OK

WH 895 M Ω 2.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-20
Drawing No Tag # RIO 4-508W6 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 105 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-VM-08-30_43

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.71 G Ω 2.99 G Ω 3.51 G Ω OK OK

WH 3.14 G Ω 3.59 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273341-20
Drawing No Tag # RIO 3-506W4 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 47 M

Cable from WTL control panel RIO 3-X10 Cable To, WTL Field FIELD_RIO 3-VM-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.97 G Ω 2.64 G Ω 3.11 G Ω OK OK

WH 2.87 G Ω 2.59 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #273341-20
Drawing No Tag # RIO 3-506W6 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 48 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-VM-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.10 G Ω 2.77 G Ω 3.71 G Ω OK OK

WH 3.05 G Ω 2.99 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-16
Drawing No Tag # RIO 3-405W0 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 37 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-PT-08-40_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.16 G Ω 3.10 G Ω 3.9 G Ω OK OK

WH 3.39 G Ω 2.29 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #2733416-8
Drawing No Tag # RIO4-304W7 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRSL 500V - 1P x 1.50 Length 71 M

Cable from WTL control panel RIO 4-X4 Cable To, WTL Field FIELD_RIO 4-MCC - AF-08-04_42 [43]

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.36 G Ω 2.41 G Ω 1.9 G Ω OK OK

WH 2.23 G Ω 2.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO 4-500W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 86 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-21_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.4 G Ω 4.57 G Ω 3.55 G Ω OK OK

WH 4.31G Ω 4.57 G Ω OK OK

Pair-2 BK 3.56 G Ω 4.21 G Ω 3.65 G Ω OK OK

WH 4.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 3.87 G Ω 2.41 G Ω 5.3 G Ω OK OK

WH 3.27 G Ω 5.5 G Ω OK OK

Pair-4 BK 4.11 G Ω 4.17 G Ω 3.4 G Ω OK OK

WH 4.26 G Ω 3.8 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020217
Drawing No Tag # RIO-3-502W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 309 M

Cable from WTL control panel RIO 3-X14 Cable To, WTL Field FIELD_RIO 3-VM-08-22_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.06 G Ω 2.01 G Ω 3.35 G Ω OK OK

WH 2.10 G Ω 4.87 G Ω OK OK

Pair-2 BK 2.13 G Ω 2.12 G Ω 3.45 G Ω OK OK

WH 1.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 2.03 G Ω 2.41 G Ω 6.3 G Ω OK OK

WH 2.27 G Ω 5.5 G Ω OK OK

Pair-4 BK 1.89 G Ω 2.65 G Ω 3.4G Ω OK OK

WH 2.33 G Ω 3.0 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO 4-504W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 94 M

Cable from WTL control panel RIO 4-X14 Cable To, WTL Field FIELD_RIO 4-VM-08-23_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.86 G Ω 3.68 G Ω 4.75 G Ω OK OK

WH 3.72 G Ω 4.57 G Ω OK OK

Pair-2 BK 5.76 G Ω 4.21 G Ω 3.65 G Ω OK OK

WH 4.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 3.40 G Ω 2.41 G Ω 5.3 G Ω OK OK

WH 3.27 G Ω 5.5 G Ω OK OK

Pair-4 BK 3.40 G Ω 3.66 G Ω 4.43 G Ω OK OK

WH 3.79 G Ω 4.28 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 4-400W4 Date 17/3/2024
PVC/ISH/OSH/PVC/SWA/PVC FRLS
Cable Size & Types Length 320 M
500V - 4P x 1.50

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-AIT-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 775 M Ω 688 M Ω 1.15 G Ω OK OK

WH 691 M Ω 1.37 G Ω OK OK

Pair-2 BK 805 M Ω 686 M Ω 1.15 G Ω OK OK

WH 791 M Ω 1.21 G Ω OK OK

Pair-3 BK 722 M Ω 855 M Ω 2.21 G Ω OK OK

WH 697 G Ω 2.15 G Ω OK OK

Pair-4 BK 741 M Ω 696 M Ω 1.27 G Ω OK OK

WH 687 M Ω 1.25 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 4-401W0 Date 17/3/2024
Cable Size & Types PVC/ISH/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 324 M

Cable from WTL control panel RIO 4-X9 Cable To, WTL Field FIELD_RIO 4-AIT-08-30_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 732 M Ω 700 M Ω 2.15 G Ω OK OK

WH 701 M Ω 1.17 G Ω OK OK

Pair-2 BK 762 M Ω 686 M Ω 1.15 G Ω OK OK

WH 791 M Ω 1.21 G Ω OK OK

Pair-3 BK 703 M Ω 855 M Ω 2.21 G Ω OK OK

WH 697 G Ω 2.15 G Ω OK OK

Pair-4 BK 723 M Ω 690 M Ω 1.17 G Ω OK OK

WH 683 M Ω 1.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-402W0 Date 17/3/2024
Cable Size & Types PVC/ISH/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 289 M

Cable from WTL control panel RIO 3-X9 Cable To, WTL Field FIELD_RIO 3-AIT-08-30_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 919 M Ω 739 M Ω 2.05 G Ω OK OK

WH 811 M Ω 1.47 G Ω OK OK

Pair-2 BK 974 M Ω 686 M Ω 1.15 G Ω OK OK

WH 791 M Ω 1.21 G Ω OK OK

Pair-3 BK 937 M Ω 855 M Ω 2.21 G Ω OK OK

WH 1.17 G Ω 2.15 G Ω OK OK

Pair-4 BK 954 M Ω 1.54 G Ω 1.17 G Ω OK OK

WH 879 M Ω 1.4 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 3-307W5 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 29 M

Cable from WTL control panel RIO 3-X4 Cable To, WTL Field FIELD_RIO 3-CM-08-01_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.35 G Ω 2.31 G Ω 2.65 G Ω OK OK

WH 2.27 G Ω 2.47 G Ω OK OK

Pair-2 BK 2.41 G Ω 2.26 G Ω 2.65 G Ω OK OK

WH 1.05 G Ω 2.11 G Ω OK OK

Pair-3 BK 2.23 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 1.27 G Ω 2.5 G Ω OK OK

Pair-4 BK 2.12 G Ω 2.21 G Ω 3.43 G Ω OK OK

WH 2.17 G Ω 2.6 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020212
Drawing No Tag # RIO 3-307W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 28 M

Cable from WTL control panel RIO 3-X3 Cable To, WTL Field FIELD_RIO 3-CM-08-01_31

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.63 G Ω 1.43 G Ω 2.75 G Ω OK OK

WH 1.39 G Ω 2.57 G Ω OK OK

Pair-2 BK 1.57 G Ω 1.21 G Ω 3.65 G Ω OK OK

WH 1.05 G Ω 2.11 G Ω OK OK

Pair-3 BK 1.51 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 1.27 G Ω 2.5 G Ω OK OK

Pair-4 BK 1.24 G Ω 1.22 G Ω 3.4 G Ω OK OK

WH 1.25 G Ω 2.8 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-02013
Drawing No Tag # RIO 3-308W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 30 M

Cable from WTL control panel RIO 3-X3 Cable To, WTL Field FIELD_RIO 3-CM-08-01_32

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.51 G Ω 2.41 G Ω 2.35 G Ω OK OK

WH 2.39 G Ω 2.45 G Ω OK OK

Pair-2 BK 2.36 G Ω 2.36 G Ω 2.55 G Ω OK OK

WH 2.33 G Ω 2.11 G Ω OK OK

Pair-3 BK 2.39 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 1.27 G Ω 2.45 G Ω OK OK

Pair-4 BK 2.25 G Ω 2.32 G Ω 2.13 G Ω OK OK

WH 2.30 G Ω 2.41 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-02013
Drawing No Tag # RIO 3-308W5 Date 17/3/2024 0
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 31 M

Cable from WTL control panel RIO 3-X4 Cable To, WTL Field FIELD_RIO 3-CM-08-01_32

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.73 G Ω 2.58 G Ω 2.45 G Ω OK OK

WH 2.41 G Ω 2.45 G Ω OK OK

Pair-2 BK 2.31 G Ω 2.47 G Ω 2.35 G Ω OK OK

WH 2.33 G Ω 2.11 G Ω OK OK

Pair-3 BK 2.39 G Ω 2.41 G Ω 3.3 G Ω OK OK

WH 1.27 G Ω 2.45 G Ω OK OK

Pair-4 BK 2.09 G Ω 2.16 G Ω 3.13 G Ω OK OK

WH 2.11 G Ω 2.51 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020211
Drawing No Tag # RIO 4-504W0 Date 17/3/2024
Cable Size & Types PVC/OSH/PVC/SWA/PVC FRLS 500V - 4P x 1.50 Length 93 M

Cable from WTL control panel RIO 4-X13 Cable To, WTL Field FIELD_RIO 4-VM-08-23_41

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.33 G Ω 5.15 G Ω 3.75 G Ω OK OK

WH 4.81G Ω 3.57 G Ω OK OK

Pair-2 BK 3.89 G Ω 4.21 G Ω 3.65 G Ω OK OK

WH 4.05 G Ω 5.11 G Ω OK OK

Pair-3 BK 3.53 G Ω 2.41 G Ω 5.3 G Ω OK OK

WH 3.27 G Ω 5.5 G Ω OK OK

Pair-4 BK 3.11 G Ω 4.69 G Ω 4.4 G Ω OK OK

WH 4.72 G Ω 4.8 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-021-11-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 19.3 GΩ 14.4 GΩ OK OK

WH 32.3 GΩ OK OK

Pair-2 BK 17.0 GΩ 21.6 GΩ OK OK

WH 25.2 GΩ OK OK

Pair-3 BK 19.2 GΩ 31.5 GΩ OK OK

WH 32.7 GΩ OK OK

Pair-4 BK 16.5 GΩ 18.9 GΩ OK OK

WH 22.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-021-11-ZD1- Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 19.3 GΩ 14.4 GΩ OK OK

WH 32.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-21-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length

SCUM PIT SUBMERSIBLE PUMP LUCAS 2A


Cable from Primary clarifiers and Biological MCC Cable To,
& 3A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.93 GΩ 26.67 GΩ OK OK

WH 1.24 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-04-41-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 78 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 4A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.10 GΩ 2.92 GΩ OK OK

WH 2.75 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-04-33-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 716 MΩ 550 MΩ OK OK

WH 226 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-41-ZD1- Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.60 GΩ 3.04 GΩ 3.74 GΩ OK OK

WH 3.27 GΩ 3.64 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-42-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.67 GΩ 2.75 GΩ 3.84 GΩ OK OK

WH 3.77 GΩ 3.74 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-43-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.22 GΩ 1.91 GΩ 3.44 GΩ OK OK

WH 2.15 GΩ 3.54 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # BS-08-20-21-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.01 GΩ 2.55 GΩ 2.22 GΩ OK OK

WH 2.14 GΩ 2.15 GΩ OK OK

Pair-2 BK 1.95 GΩ 1.50 GΩ 1.59 GΩ OK OK

WH 1.84 GΩ 1.95 GΩ OK OK

Pair-3 BK 2.17 GΩ 1.95 GΩ 2.11 GΩ OK OK

WH 2.69 GΩ 2.31 GΩ OK OK

Pair-4 BK 1.91 GΩ 1.75 GΩ 1.87 GΩ OK OK

WH 1.61 GΩ 2.01 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # 08-JBD-15-VDM Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.93 GΩ 2 GΩ 2.12 GΩ OK OK

WH 1.73 GΩ 2.14 GΩ OK OK

Pair-2 BK 1.37 GΩ 1.65 GΩ 1.69 GΩ OK OK

WH 1.73 GΩ 1.95 GΩ OK OK

Pair-3 BK 1.56 GΩ 1.90 GΩ 2.11 GΩ OK OK

WH 2.13 GΩ 2.11 GΩ OK OK

Pair-4 BK 1.30 GΩ 1.59 GΩ 1.67 GΩ OK OK

WH 1.72 GΩ 2.11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # E-Stop-Blower4-VFD Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 20.7 GΩ 13.7 GΩ 13.44 GΩ OK OK

WH 8.28 GΩ 16.54 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # BLOWER4-BOV1VFD NO4 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 16.6 GΩ 13.9 GΩ 12.12 GΩ OK OK

WH 11.8 GΩ 12.44 GΩ OK OK

Pair-2 BK 11.3 GΩ 12.7 GΩ 11.69 GΩ OK OK

WH 15 GΩ 13.95 GΩ OK OK

Pair-3 BK 17.3 GΩ 12.7 GΩ 12.11 GΩ OK OK

WH 14.7 GΩ 12.11 GΩ OK OK

Pair-4 BK 11.6 GΩ 10.6 GΩ 13.67 GΩ OK OK

WH 12.2 GΩ 12.11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # BLOWER4-Temperature Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.17 GΩ 3.18 GΩ 4.12 GΩ OK OK

WH 4.2 GΩ 5.44 GΩ OK OK

Pair-2 BK 5.38 GΩ 5.11 GΩ 4.69 GΩ OK OK

WH 3.8 GΩ 3.95 GΩ OK OK

Pair-3 BK 5.02 GΩ 2.15 GΩ 4.11 GΩ OK OK

WH 2.57 GΩ 2.11 GΩ OK OK

Pair-4 BK 5.05 GΩ 3.95 GΩ 3.67 GΩ OK OK

WH 3.38 GΩ 4.11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # BLOWER4-DC Supply Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 16.2 GΩ 13.7 GΩ 14.12 GΩ OK OK

WH 11.5 GΩ 15.44 GΩ OK OK

Pair-2 BK 11 GΩ 12.9 GΩ 13.69 GΩ OK OK

WH 11.1 GΩ 13.95 GΩ OK OK

Pair-3 BK 11.06 GΩ 10.8 GΩ 14.11 GΩ OK OK

WH 11.4 GΩ 12.11 GΩ OK OK

Pair-4 BK 11.3 GΩ 12.2 GΩ 13.67 GΩ OK OK

WH 13.4 GΩ 14.11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # E-stopVFDBLOWER4 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 15.8 GΩ 13.6 GΩ 13.12 GΩ OK OK

WH 10.3 GΩ 12.44 GΩ OK OK

Pair-2 BK 11.2 GΩ 14.9 GΩ 13.69 GΩ OK OK

WH 12.5 GΩ 13.5 GΩ OK OK

Pair-3 BK 14.5 GΩ 14.7 GΩ 14.11 GΩ OK OK

WH 13.3 GΩ 12.11 GΩ OK OK

Pair-4 BK 11.4 GΩ 10.8 GΩ 12.65 GΩ OK OK

WH 9.14 GΩ 13.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-03-33-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 277 MΩ 854 MΩ 844 MΩ OK OK

WH 774 MΩ 842 MΩ OK OK

Pair-2 BK 314 MΩ 810 MΩ 821 MΩ OK OK

WH 726 MΩ 789 MΩ OK OK

Pair-3 BK 250 MΩ 790 MΩ 765 MΩ OK OK

WH 594 MΩ 811 MΩ OK OK

Pair-4 BK 240 MΩ 556 MΩ 844 MΩ OK OK

WH 466 MΩ 823 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-04-33-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 278 MΩ 950 MΩ 814 MΩ OK OK

WH 800 MΩ 822 MΩ OK OK

Pair-2 BK 326 MΩ 835 MΩ 811 MΩ OK OK

WH 795 MΩ 789 MΩ OK OK

Pair-3 BK 261 MΩ 790 MΩ 765 MΩ OK OK

WH 694MΩ 841 MΩ OK OK

Pair-4 BK 237 MΩ 670 MΩ 814 MΩ OK OK

WH 515 MΩ 833 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-03-43-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 976 MΩ 1.35 GΩ 892 MΩ OK OK

WH 1.22 GΩ 882 MΩ OK OK

Pair-2 BK 521 MΩ 778 MΩ 871 MΩ OK OK

WH 809 MΩ 789 MΩ OK OK

Pair-3 BK 481 MΩ 790 MΩ 765 MΩ OK OK

WH 694 MΩ 849 MΩ OK OK

Pair-4 BK 475 MΩ 787 MΩ 854 MΩ OK OK

WH 901 MΩ 843 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-04-43-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 883 MΩ 1.35 GΩ 882 MΩ OK OK

WH 1.12 GΩ 872 MΩ OK OK

Pair-2 BK 622 MΩ 1.16 GΩ 881 MΩ OK OK

WH 1.18 GΩ 789 MΩ OK OK

Pair-3 BK 507 MΩ 790 MΩ 865 MΩ OK OK

WH 1.03 GΩ 849 MΩ OK OK

Pair-4 BK 454 MΩ 809 MΩ 874 MΩ OK OK

WH 778 MΩ 883 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-04-41-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.45 GΩ 1.98 GΩ 997 MΩ OK OK

WH 1.97 GΩ 972 MΩ OK OK

Pair-2 BK 945 MΩ 1.80 GΩ 981 MΩ OK OK

WH 2.15 GΩ 989 MΩ OK OK

Pair-3 BK 765 MΩ 1.20 GΩ 965 MΩ OK OK

WH 1.36 GΩ 849 MΩ OK OK

Pair-4 BK 759 MΩ 1.12 GΩ 974 MΩ OK OK

WH 1.59 GΩ 983 MΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # RIO 1-311-W6 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 11.8 GΩ 8.7 GΩ 8.67 GΩ OK OK

WH 9.39 GΩ 9.04 GΩ OK OK

Pair-2 BK 8.9 GΩ 8.35 GΩ 8.45 GΩ OK OK

WH 9.9 GΩ 8.71 GΩ OK OK

Pair-3 BK 10.3 GΩ 9.20 GΩ 8.65 GΩ OK OK

WH 10.8 GΩ 9.11 GΩ OK OK

Pair-4 BK 7.56 GΩ 8.76 GΩ 9.13 GΩ OK OK

WH 8.72 GΩ 8.75 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-32-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.88 GΩ 2.80 GΩ 3.14 GΩ OK OK

WH 1.25 GΩ 2.64 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-03-41-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.05 GΩ 1.65 GΩ 1.25 GΩ OK OK

WH 1.74 GΩ 1.15 GΩ OK OK

Pair-2 BK 749 MΩ 1.70 GΩ 1.35 GΩ OK OK

WH 1.92 GΩ 1.55 GΩ OK OK

Pair-3 BK 621 MΩ 1.45 GΩ 1.17 GΩ OK OK

WH 1.62 GΩ 1.35 GΩ OK OK

Pair-4 BK 591 MΩ 1.04 GΩ 1.05 GΩ OK OK

WH 1.24 GΩ 1.16 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-04-31-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.21 GΩ 1.70 GΩ 1.5 GΩ OK OK

WH 1.91 GΩ 1.12 GΩ OK OK

Pair-2 BK 1.05 GΩ 1.18 GΩ 1.15 GΩ OK OK

WH 1.21 GΩ 1.25 GΩ OK OK

Pair-3 BK 809 MΩ 1.11 GΩ 1.17 GΩ OK OK

WH 1.19 GΩ 1.35 GΩ OK OK

Pair-4 BK 958 MΩ 1.28 GΩ 1.15 GΩ OK OK

WH 1.38 GΩ 1.26 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-03-31-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 935 MΩ 1.19 GΩ 1.02 GΩ OK OK

WH 1.22 GΩ 1.1 GΩ OK OK

Pair-2 BK 858 MΩ 850 MΩ 1.12 GΩ OK OK

WH 920 MΩ 1.25 GΩ OK OK

Pair-3 BK 706 MΩ 809 MΩ 1.07 GΩ OK OK

WH 868 MΩ 1.11 GΩ OK OK

Pair-4 BK 710 MΩ 868 MΩ 1.05 GΩ OK OK

WH 891 MΩ 1.16 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # AF-08-03-42-RE-M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 200 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 1A

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.76 GΩ 2.81 GΩ 1.22 GΩ OK OK

WH 2.23 GΩ 1.17 GΩ OK OK

Pair-2 BK 1.29 GΩ 2.15 GΩ 1.32 GΩ OK OK

WH 2.37 GΩ 1.15 GΩ OK OK

Pair-3 BK 1.18 GΩ 2.35 GΩ 1.27 GΩ OK OK

WH 2.65 GΩ 1.21 GΩ OK OK

Pair-4 BK 1.08 GΩ 1.83 GΩ 1.25 GΩ OK OK

WH 1.52 GΩ 1.26 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-33-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.72 GΩ 1.55 GΩ 1.14 GΩ OK OK

WH 1.34 GΩ 1.64 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 3-410W0 Date 3/4/2024
Cable Size & Types 2CX2.5 mm2, XLPE/PVC Length M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 80.3 GΩ 84.2 GΩ OK

70.8 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # RIO 4-410W0 Date 3/4/2024
Cable Size & Types 2CX2.5 mm2, XLPE/PVC Length M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 70.9 GΩ OK

RD-GND 91.2 GΩ OK

BK-GND 59.9 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # AF-08-03-31-ZD1 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 149 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.24 GΩ 4.31 GΩ 2.14 GΩ OK OK

WH 1.57 GΩ 2.64 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 06-JBD-01-VD-M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 12P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Distribution Chamber JB Digital

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.33 GΩ 3.67 GΩ 3.57 GΩ OK OK

WH 3.51 GΩ 3.52 GΩ OK OK

Pair-2 BK 2.97 GΩ 3.59 GΩ 3.65 GΩ OK OK

WH 3.62 GΩ 3.47 GΩ OK OK

Pair-3 BK 3.17 GΩ 3.21 GΩ 3.43 GΩ OK OK

WH 3.71 GΩ 3.41 GΩ OK OK

Pair-4 BK 3.11 GΩ 3.29 GΩ 3.39 GΩ OK OK

WH 3.18 GΩ 3.51 GΩ OK OK

Pair-5 BK 3.27 GΩ 3.23 GΩ 3.64 GΩ OK OK

WH 3.27 GΩ 3.72 GΩ OK OK

Pair-6 BK 3.08 GΩ 3.31 GΩ 3.55 GΩ OK OK

WH 3.37 GΩ 3.57 GΩ OK OK

Pair-7 BK 3.15 GΩ 3.41 GΩ 3.56 GΩ OK OK

WH 3.35 GΩ 3.52 GΩ OK OK

Pair-8 BK 3.33 GΩ 3.32 GΩ 3.47 GΩ OK OK

WH 3.36 GΩ 3.67 GΩ OK OK

Pair-9 BK 2.95GΩ 3.31 GΩ 3.51 GΩ OK OK

WH 3.37 GΩ 3.41 GΩ OK OK

Pair-10 BK 2.87 GΩ 3.51 GΩ 3.33 GΩ OK OK

WH 3.45 GΩ 3.17 GΩ OK OK

Pair-11 BK 3.11 GΩ 3.15 GΩ 3.67 GΩ OK OK

WH 3.31 GΩ 3.53 GΩ OK OK

Pair-12 BK 3.17 GΩ 3.14 GΩ 3.53 GΩ OK OK

WH 3.21 GΩ 3.55 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 08-JBD-15-VD-M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Lucas Biological Reactor JB Digital

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.67 GΩ 2.17 GΩ 2.43 GΩ OK OK

WH 2.23 GΩ 2.39 GΩ OK OK

Pair-2 BK 1.91 GΩ 1.91 GΩ 2.26 GΩ OK OK

WH 2.07 GΩ 2.25 GΩ OK OK

Pair-3 BK 2.11 GΩ 2.25 GΩ 3.43 GΩ OK OK

WH 2.21 GΩ 2.31 GΩ OK OK

Pair-4 BK 2.22 GΩ 2.31 GΩ 2.33 GΩ OK OK

WH 2.27 GΩ 2.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 08-JBD-16-VD-M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Lucas Biological Reactor JB Digital

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.25 GΩ 2.26 GΩ 2.13 GΩ OK OK

WH 2.21 GΩ 2.17 GΩ OK OK

Pair-2 BK 2.29 GΩ 2.27 GΩ 2.12 GΩ OK OK

WH 2.07 GΩ 2.25 GΩ OK OK

Pair-3 BK 2.33 GΩ 2.25 GΩ 3.43 GΩ OK OK

WH 2.21 GΩ 2.27 GΩ OK OK

Pair-4 BK 2.41 GΩ 2.25 GΩ 2.31 GΩ OK OK

WH 2.27 GΩ 2.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01-01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.41 GΩ 3.22 GΩ 3.24 GΩ OK OK

WH 3.27 GΩ 3.21 GΩ OK OK

Pair-2 BK 3.39 GΩ 3.31 GΩ 3.25 GΩ OK OK

WH 3.17 GΩ 3.21 GΩ OK OK

Pair-3 BK 3.33 GΩ 3.27 GΩ 3.19 GΩ OK OK

WH 3.17 GΩ 3.01 GΩ OK OK

Pair-4 BK 3.47 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.57 GΩ 3.41 GΩ 3.33 GΩ OK OK

WH 3.31 GΩ 3.43 GΩ OK OK

Pair-6 BK 3.37 GΩ 3.29 GΩ 3.23 GΩ OK OK

WH 3.31 GΩ 3.13 GΩ OK OK

Pair-7 BK 3.27 GΩ 3.25 GΩ 3.37 GΩ OK OK

WH 3.21 GΩ 3.29 GΩ OK OK

Pair-8 BK 3.33 GΩ 3.23 GΩ 3.31 GΩ OK OK

WH 3.27 GΩ 3.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01-03-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.67 GΩ 3.04 GΩ 3.14 GΩ OK OK

WH 3.15 GΩ 3.2 GΩ OK OK

Pair-2 BK 3.11 GΩ 3.21 GΩ 3.15 GΩ OK OK

WH 3.17 GΩ 3.21 GΩ OK OK

Pair-3 BK 2.61 GΩ 3.27 GΩ 3.12 GΩ OK OK

WH 3.17 GΩ 3.01 GΩ OK OK

Pair-4 BK 2.51 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 2.74 GΩ 3.41 GΩ 3.31 GΩ OK OK

WH 3.31 GΩ 3.13 GΩ OK OK

Pair-6 BK 2.93 GΩ 3.21 GΩ 3.23 GΩ OK OK

WH 3.19 GΩ 3.13 GΩ OK OK

Pair-7 BK 3.05 GΩ 3.21 GΩ 3.17 GΩ OK OK

WH 3.15 GΩ 3.19 GΩ OK OK

Pair-8 BK 3.13 GΩ 3.13 GΩ 3.11 GΩ OK OK

WH 3.17 GΩ 3.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02-01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.67 GΩ 4.47 GΩ 4.37 GΩ OK OK

WH 4.37 GΩ 4.21 GΩ OK OK

Pair-2 BK 5.13 GΩ 4.35 GΩ 4.33 GΩ OK OK

WH 4.31 GΩ 4.35 GΩ OK OK

Pair-3 BK 4.57 GΩ 4.34 GΩ 3.12 GΩ OK OK

WH 3.17 GΩ 4.01 GΩ OK OK

Pair-4 BK 3.69 GΩ 3.22 GΩ 4.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.74 GΩ 4.41 GΩ 3.31 GΩ OK OK

WH 3.31 GΩ 4.13 GΩ OK OK

Pair-6 BK 4.07 GΩ 4.21 GΩ 3.23 GΩ OK OK

WH 3.19 GΩ 3.13 GΩ OK OK

Pair-7 BK 4.21 GΩ 4.26 GΩ 4.21 GΩ OK OK

WH 4.35 GΩ 4.25 GΩ OK OK

Pair-8 BK 4.13 GΩ 4.33 GΩ 4.31 GΩ OK OK

WH 3.07 GΩ 3.37 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02-02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.67 GΩ 2.51 GΩ 4.37 GΩ OK OK

WH 2.45 GΩ 3.21 GΩ OK OK

Pair-2 BK 2.81 GΩ 2.54 GΩ 3.33 GΩ OK OK

WH 4.31 GΩ 4.35 GΩ OK OK

Pair-3 BK 2.72 GΩ 4.34 GΩ 3.12 GΩ OK OK

WH 3.17 GΩ 4.01 GΩ OK OK

Pair-4 BK 3.69 GΩ 3.22 GΩ 4.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.74 GΩ 4.41 GΩ 3.31 GΩ OK OK

WH 3.31 GΩ 4.13 GΩ OK OK

Pair-6 BK 2.79 GΩ 4.21 GΩ 3.23 GΩ OK OK

WH 3.19 GΩ 3.13 GΩ OK OK

Pair-7 BK 2.82 GΩ 2.23 GΩ 3.21 GΩ OK OK

WH 1.95 GΩ 4.25 GΩ OK OK

Pair-8 BK 2.72 GΩ 2.11 GΩ 3.31 GΩ OK OK

WH 3.27 GΩ 3.37 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02-04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.87 GΩ 3.17 GΩ 3.21 GΩ OK OK

WH 3.13 GΩ 3.13 GΩ OK OK

Pair-2 BK 2.69 GΩ 3.19 GΩ 3.23 GΩ OK OK

WH 3.31 GΩ 3.35 GΩ OK OK

Pair-3 BK 2.55 GΩ 3.34 GΩ 3.12 GΩ OK OK

WH 3.07 GΩ 3.01 GΩ OK OK

Pair-4 BK 3.69 GΩ 3.22 GΩ 4.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.15 GΩ 3.21 GΩ 3.31 GΩ OK OK

WH 3.31 GΩ 3.13 GΩ OK OK

Pair-6 BK 3.05 GΩ 3.21 GΩ 3.23 GΩ OK OK

WH 3.19 GΩ 3.13 GΩ OK OK

Pair-7 BK 2.91 GΩ 3.36 GΩ 3.13 GΩ OK OK

WH 3.41 GΩ 3.23 GΩ OK OK

Pair-8 BK 2.83 GΩ 3.27 GΩ 3.17 GΩ OK OK

WH 3.23 GΩ 3.31 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_11-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.87 GΩ 3.37 GΩ 3.41 GΩ OK OK

WH 3.33 GΩ 3.33 GΩ OK OK

Pair-2 BK 3.69 GΩ 3.29 GΩ 3.33 GΩ OK OK

WH 3.35 GΩ 3.35 GΩ OK OK

Pair-3 BK 3.55 GΩ 3.34 GΩ 3.32 GΩ OK OK

WH 3.27 GΩ 3.01 GΩ OK OK

Pair-4 BK 3.59 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.55 GΩ 3.21 GΩ 3.31 GΩ OK OK

WH 3.41 GΩ 3.03 GΩ OK OK

Pair-6 BK 3.05 GΩ 3.21 GΩ 3.23 GΩ OK OK

WH 3.19 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.91 GΩ 3.46 GΩ 3.23 GΩ OK OK

WH 3.51 GΩ 3.33 GΩ OK OK

Pair-8 BK 3.83 GΩ 3.37 GΩ 3.37 GΩ OK OK

WH 3.33 GΩ 3.23 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_13-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.67 GΩ 3.47 GΩ 3.51 GΩ OK OK

WH 3.35 GΩ 3.53 GΩ OK OK

Pair-2 BK 3.79 GΩ 3.49 GΩ 3.43 GΩ OK OK

WH 3.45 GΩ 3.35 GΩ OK OK

Pair-3 BK 3.65 GΩ 3.34 GΩ 3.32 GΩ OK OK

WH 3.37 GΩ 3.41 GΩ OK OK

Pair-4 BK 3.69 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.65 GΩ 3.21 GΩ 3.31 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.75 GΩ 3.21 GΩ 3.23 GΩ OK OK

WH 3.39 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.71 GΩ 3.46 GΩ 3.43 GΩ OK OK

WH 3.55 GΩ 3.23 GΩ OK OK

Pair-8 BK 3.93 GΩ 3.57 GΩ 3.47 GΩ OK OK

WH 3.43 GΩ 3.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_21-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.17 GΩ 3.37 GΩ 3.41 GΩ OK OK

WH 3.25 GΩ 3.23 GΩ OK OK

Pair-2 BK 3.66 GΩ 3.19 GΩ 3.41 GΩ OK OK

WH 3.45 GΩ 3.25 GΩ OK OK

Pair-3 BK 3.55 GΩ 3.44 GΩ 3.32 GΩ OK OK

WH 3.37 GΩ 3.41 GΩ OK OK

Pair-4 BK 3.69 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.75 GΩ 3.21 GΩ 3.31 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.65 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.39 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.76 GΩ 3.46 GΩ 3.23 GΩ OK OK

WH 3.35 GΩ 3.23 GΩ OK OK

Pair-8 BK 3.87 GΩ 3.37 GΩ 3.27 GΩ OK OK

WH 3.33 GΩ 3.23 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-01_02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.37 GΩ 3.27 GΩ 3.44 GΩ OK OK

WH 3.25 GΩ 3.33 GΩ OK OK

Pair-2 BK 3.57 GΩ 3.19 GΩ 3.21 GΩ OK OK

WH 3.25 GΩ 3.25 GΩ OK OK

Pair-3 BK 3.45 GΩ 3.44 GΩ 3.32 GΩ OK OK

WH 3.37 GΩ 3.41 GΩ OK OK

Pair-4 BK 3.59 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.13 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.45 GΩ 3.21 GΩ 3.31 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.35 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.39 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.56 GΩ 3.16 GΩ 3.23 GΩ OK OK

WH 3.25 GΩ 3.23 GΩ OK OK

Pair-8 BK 3.57 GΩ 3.32 GΩ 3.39 GΩ OK OK

WH 3.23 GΩ 3.43 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-01_03-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.67 GΩ 3.29 GΩ 3.21 GΩ OK OK

WH 3.35 GΩ 3.39 GΩ OK OK

Pair-2 BK 3.41 GΩ 3.49 GΩ 3.25 GΩ OK OK

WH 3.25 GΩ 3.55 GΩ OK OK

Pair-3 BK 3.49 GΩ 3.54 GΩ 3.32 GΩ OK OK

WH 3.37 GΩ 3.41 GΩ OK OK

Pair-4 BK 3.39 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.65 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.55 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.39 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.36 GΩ 3.36 GΩ 3.53 GΩ OK OK

WH 3.27 GΩ 3.13 GΩ OK OK

Pair-8 BK 3.67 GΩ 3.52 GΩ 3.49 GΩ OK OK

WH 3.43 GΩ 3.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-01_04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.55 GΩ 3.21 GΩ 3.55 GΩ OK OK

WH 3.15 GΩ 3.19 GΩ OK OK

Pair-2 BK 3.37 GΩ 3.29 GΩ 3.35 GΩ OK OK

WH 3.15 GΩ 3.65 GΩ OK OK

Pair-3 BK 3.19 GΩ 3.54 GΩ 3.37 GΩ OK OK

WH 3.37 GΩ 3.49 GΩ OK OK

Pair-4 BK 3.29 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.45 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.54 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.39 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.16 GΩ 3.26 GΩ 3.33 GΩ OK OK

WH 3.37 GΩ 3.63 GΩ OK OK

Pair-8 BK 3.27 GΩ 3.12 GΩ 3.29 GΩ OK OK

WH 3.23 GΩ 3.53 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-02_01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.25 GΩ 3.31 GΩ 3.65 GΩ OK OK

WH 3.65 GΩ 3.49 GΩ OK OK

Pair-2 BK 3.17 GΩ 3.39 GΩ 3.45 GΩ OK OK

WH 3.17 GΩ 3.75 GΩ OK OK

Pair-3 BK 3.39 GΩ 3.74 GΩ 3.37 GΩ OK OK

WH 3.57 GΩ 3.49 GΩ OK OK

Pair-4 BK 3.59 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.83 GΩ OK OK

Pair-5 BK 3.25 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.74 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.19 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.66 GΩ 3.26 GΩ 3.53 GΩ OK OK

WH 3.31 GΩ 3.83 GΩ OK OK

Pair-8 BK 3.57 GΩ 3.52 GΩ 3.19 GΩ OK OK

WH 3.53 GΩ 3.43 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-02_02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.25 GΩ 3.81 GΩ 3.55 GΩ OK OK

WH 3.75 GΩ 3.41 GΩ OK OK

Pair-2 BK 3.87 GΩ 3.30 GΩ 3.25 GΩ OK OK

WH 3.47 GΩ 3.65 GΩ OK OK

Pair-3 BK 3.69 GΩ 3.74 GΩ 3.37 GΩ OK OK

WH 3.57 GΩ 3.49 GΩ OK OK

Pair-4 BK 3.79 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.71 GΩ OK OK

Pair-5 BK 3.65 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.94 GΩ 3.31 GΩ 3.53 GΩ OK OK

WH 3.19 GΩ 3.37 GΩ OK OK

Pair-7 BK 3.66 GΩ 3.16 GΩ 3.53 GΩ OK OK

WH 3.61 GΩ 3.63 GΩ OK OK

Pair-8 BK 3.77 GΩ 3.76 GΩ 3.39 GΩ OK OK

WH 3.73 GΩ 3.73 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-02_03-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.25 GΩ 3.61 GΩ 3.15 GΩ OK OK

WH 3.45 GΩ 3.11 GΩ OK OK

Pair-2 BK 3.67 GΩ 3.39 GΩ 3.35 GΩ OK OK

WH 3.27 GΩ 3.25 GΩ OK OK

Pair-3 BK 3.49 GΩ 3.74 GΩ 3.37 GΩ OK OK

WH 3.47 GΩ 3.49 GΩ OK OK

Pair-4 BK 3.29 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.23 GΩ OK OK

Pair-5 BK 3.35 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.53 GΩ OK OK

Pair-6 BK 3.55 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.61 GΩ 3.46 GΩ 3.23 GΩ OK OK

WH 3.65 GΩ 3.13 GΩ OK OK

Pair-8 BK 3.27 GΩ 3.36 GΩ 3.19 GΩ OK OK

WH 3.23 GΩ 3.43 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-02_04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.45 GΩ 3.68 GΩ 3.17 GΩ OK OK

WH 3.25 GΩ 3.31 GΩ OK OK

Pair-2 BK 3.37 GΩ 3.19 GΩ 3.15 GΩ OK OK

WH 3.37 GΩ 3.25 GΩ OK OK

Pair-3 BK 3.69 GΩ 3.74 GΩ 3.27 GΩ OK OK

WH 3.47 GΩ 3.49 GΩ OK OK

Pair-4 BK 3.19 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.55 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.25 GΩ OK OK

Pair-6 BK 3.35 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.60 GΩ 3.16 GΩ 3.23 GΩ OK OK

WH 3.05 GΩ 3.13 GΩ OK OK

Pair-8 BK 3.57 GΩ 3.26 GΩ 3.29 GΩ OK OK

WH 3.33 GΩ 3.23 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_23-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.25 GΩ 3.28 GΩ 3.37 GΩ OK OK

WH 3.29 GΩ 3.32 GΩ OK OK

Pair-2 BK 3.17 GΩ 3.39 GΩ 3.25 GΩ OK OK

WH 3.37 GΩ 3.25 GΩ OK OK

Pair-3 BK 3.49 GΩ 3.74 GΩ 3.27 GΩ OK OK

WH 3.47 GΩ 3.39 GΩ OK OK

Pair-4 BK 3.19 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.54 GΩ OK OK

Pair-5 BK 3.55 GΩ 3.21 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.23 GΩ OK OK

Pair-6 BK 3.35 GΩ 3.31 GΩ 3.37 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.45 GΩ 3.16 GΩ 3.23 GΩ OK OK

WH 3.25 GΩ 3.23 GΩ OK OK

Pair-8 BK 3.51 GΩ 3.46 GΩ 3.49 GΩ OK OK

WH 3.23 GΩ 3.13 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_41-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.76 GΩ 3.22 GΩ 3.17 GΩ OK OK

WH 3.39 GΩ 3.39 GΩ OK OK

Pair-2 BK 3.53 GΩ 3.29 GΩ 3.27 GΩ OK OK

WH 3.33 GΩ 3.15 GΩ OK OK

Pair-3 BK 3.14 GΩ 3.74 GΩ 3.27 GΩ OK OK

WH 3.47 GΩ 3.39 GΩ OK OK

Pair-4 BK 3.34 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.21 GΩ OK OK

Pair-5 BK 3.15 GΩ 3.23 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.03 GΩ OK OK

Pair-6 BK 3.25 GΩ 3.31 GΩ 3.33 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.49 GΩ 3.56 GΩ 3.23 GΩ OK OK

WH 3.45 GΩ 3.53 GΩ OK OK

Pair-8 BK 3.31 GΩ 3.41 GΩ 3.44 GΩ OK OK

WH 3.43 GΩ 3.53 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20_43-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.26 GΩ 3.42 GΩ 3.27 GΩ OK OK

WH 3.29 GΩ 3.49 GΩ OK OK

Pair-2 BK 3.23 GΩ 3.27 GΩ 3.17 GΩ OK OK

WH 3.13 GΩ 3.19 GΩ OK OK

Pair-3 BK 3.34 GΩ 3.74 GΩ 3.27 GΩ OK OK

WH 3.47 GΩ 3.39 GΩ OK OK

Pair-4 BK 3.14 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.43 GΩ OK OK

Pair-5 BK 3.25 GΩ 3.23 GΩ 3.37 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.15 GΩ 3.31 GΩ 3.13 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.19 GΩ 3.26 GΩ 3.29 GΩ OK OK

WH 3.35 GΩ 3.51 GΩ OK OK

Pair-8 BK 3.11 GΩ 3.49 GΩ 3.54 GΩ OK OK

WH 3.54 GΩ 3.63 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-01_01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.19 GΩ 3.22 GΩ 3.47 GΩ OK OK

WH 3.19 GΩ 3.25 GΩ OK OK

Pair-2 BK 3.31 GΩ 3.31 GΩ 3.57 GΩ OK OK

WH 3.17 GΩ 3.59 GΩ OK OK

Pair-3 BK 3.24 GΩ 3.74 GΩ 3.27 GΩ OK OK

WH 3.47 GΩ 3.39 GΩ OK OK

Pair-4 BK 3.34 GΩ 3.22 GΩ 3.32 GΩ OK OK

WH 3.33 GΩ 3.83 GΩ OK OK

Pair-5 BK 3.15 GΩ 3.23 GΩ 3.47 GΩ OK OK

WH 3.41 GΩ 3.33 GΩ OK OK

Pair-6 BK 3.37 GΩ 3.31 GΩ 3.53 GΩ OK OK

WH 3.19 GΩ 3.27 GΩ OK OK

Pair-7 BK 3.23 GΩ 3.56 GΩ 3.19 GΩ OK OK

WH 3.45 GΩ 3.41 GΩ OK OK

Pair-8 BK 3.41 GΩ 3.29 GΩ 3.14 GΩ OK OK

WH 3.51 GΩ 3.43 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.25 GΩ 2.22 GΩ 3.17 GΩ OK OK

WH 2.19 GΩ 3.05 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.45 GΩ 2.31 GΩ 2.24 GΩ OK OK

WH 2.27 GΩ 2.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_03-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.41 GΩ 2.33 GΩ 2.44 GΩ OK OK

WH 2.37 GΩ 2.25 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_03-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.74 GΩ 2.13 GΩ 2.54 GΩ OK OK

WH 2.37 GΩ 2.45 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02_02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.65 GΩ 2.46 GΩ 2.24 GΩ OK OK

WH 2.27 GΩ 2.49 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02_03-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.5 mm2 Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.11 GΩ 2.26 GΩ 2.29 GΩ OK OK

WH 2.27 GΩ 2.19 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO 1-311VD2 Date 27/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 4P x 1.50 Length 29 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 14.3 G Ω 10.2 G Ω 8.97 G Ω OK OK

WH 9.25 G Ω 8.71 G Ω OK OK

Pair-2 BK 9.36 G Ω 9.31 G Ω 6.58 G Ω OK OK

WH 8.91 G Ω 11.8 G Ω OK OK

Pair-3 BK 8.89 G Ω 8.87 G Ω 8.87 G Ω OK OK

WH 9.11 G Ω 9.11 G Ω OK OK

Pair-4 BK 9.62 G Ω 9.45 G Ω 9.45 G Ω OK OK

WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # MC-07-02_04-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.01 GΩ 2.11 GΩ 2.25 GΩ OK OK

WH 2.13 GΩ 3.02 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_11-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.79 GΩ 1.91 GΩ 1.57 GΩ OK OK

WH 1.66 GΩ 1.71 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_41-ZD1 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.12 GΩ 2.62 GΩ 3.24 GΩ OK OK

WH 2.74 GΩ 3.33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_13-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.17 GΩ 1.92 GΩ 3.14 GΩ OK OK

WH 1.74 GΩ 3.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-08-20-41-RE-M Date 27/3/2024
Cable Size & Types 4P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 55 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.3 G Ω 6.2 G Ω 4.97 G Ω OK OK

WH 5.25 G Ω 4.71 G Ω OK OK

Pair-2 BK 4.36 G Ω 5.31 G Ω 5.58 G Ω OK OK

WH 4.91 G Ω 4.8 G Ω OK OK

Pair-3 BK 5.89 G Ω 4.87 G Ω 5.87 G Ω OK OK

WH 5.11 G Ω 5.11 G Ω OK OK

Pair-4 BK 4.62 G Ω 4.45 G Ω 6.45 G Ω OK OK

WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # BS-24-02_01-VD1M Date 27/3/2024
Cable Size & Types 8P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 15 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.3 G Ω 8.2 G Ω 6.97 G Ω OK OK

WH 7.89 G Ω 5.71 G Ω OK OK

Pair-2 BK 8.36 G Ω 6.31 G Ω 7.58 G Ω OK OK

WH 4.91 G Ω 6.8 G Ω OK OK

Pair-3 BK 6.89 G Ω 6.87 G Ω 5.87 G Ω OK OK

WH 5.11 G Ω 6.11 G Ω OK OK

Pair-4 BK 6.62 G Ω 5.45 G Ω 7.45 G Ω OK OK

WH 5.55 G Ω 6.41 G Ω OK OK

Pair-5 BK 6.82 G Ω 5.95 G Ω 7.35 G Ω OK OK

WH 6.45 G Ω 7.75 G Ω OK OK

Pair-6 BK 7.62 G Ω 7.45 G Ω 5.15 G Ω OK OK

WH 5.45 G Ω 7.35 G Ω OK OK

Pair-7 BK 5.12 G Ω 6.75 G Ω 6.65 G Ω OK OK

WH 5.65 G Ω 7.15 G Ω OK OK

Pair-8 BK 6.57 G Ω 7.45 G Ω 7.21 G Ω OK OK

WH 8.45 G Ω 7.32 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-02_03-VD1M Date 27/3/2024
Cable Size & Types 8P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.23 G Ω 4.56 G Ω 4.17 G Ω OK OK

WH 3.19 G Ω 3.91 G Ω OK OK

Pair-2 BK 3.11 G Ω 3.31 G Ω 3.58 G Ω OK OK

WH 2.93 G Ω 3.65 G Ω OK OK

Pair-3 BK 4.05 G Ω 3.57 G Ω 3.97 G Ω OK OK

WH 3.45 G Ω 4.11 G Ω OK OK

Pair-4 BK 3.91 G Ω 4.65 G Ω 4.45 G Ω OK OK

WH 5.05 G Ω 3.41 G Ω OK OK

Pair-5 BK 4.22 G Ω 5.15 G Ω 3.35 G Ω OK OK

WH 4.45 G Ω 3.25 G Ω OK OK

Pair-6 BK 4.19 G Ω 3.85 G Ω 4.15 G Ω OK OK

WH 3.45 G Ω 3.35 G Ω OK OK

Pair-7 BK 3.82 G Ω 3.75 G Ω 3.15 G Ω OK OK

WH 3.65 G Ω 4.35 G Ω OK OK

Pair-8 BK 3.33 G Ω 3.25 G Ω 3.21 G Ω OK OK

WH 4.15 G Ω 4.62 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_04-VD1M Date 27/3/2024
Cable Size & Types 8P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 20 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.13 G Ω 7.56 G Ω 6.37 G Ω OK OK

WH 7.19 G Ω 5.91 G Ω OK OK

Pair-2 BK 6.11 G Ω 6.31 G Ω 6.58 G Ω OK OK

WH 5.93 G Ω 6.65 G Ω OK OK

Pair-3 BK 6.55 G Ω 5.57 G Ω 5.97 G Ω OK OK

WH 5.45 G Ω 6.11 G Ω OK OK

Pair-4 BK 6.72 G Ω 5.65 G Ω 7.45 G Ω OK OK

WH 5.25 G Ω 6.41 G Ω OK OK

Pair-5 BK 6.22 G Ω 5.95 G Ω 6.35 G Ω OK OK

WH 6.45 G Ω 7.25 G Ω OK OK

Pair-6 BK 5.19 G Ω 7.45 G Ω 5.15 G Ω OK OK

WH 5.45 G Ω 6.35 G Ω OK OK

Pair-7 BK 5.82 G Ω 6.75 G Ω 6.15 G Ω OK OK

WH 5.65 G Ω 7.35 G Ω OK OK

Pair-8 BK 6.33 G Ω 6.25 G Ω 6.21 G Ω OK OK

WH 7.15 G Ω 7.62 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-01_02-VD1M Date 27/3/2024
Cable Size & Types 8P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.63 G Ω 4.26 G Ω 4.76 G Ω OK OK

WH 4.14 G Ω 4.61 G Ω OK OK

Pair-2 BK 4.41 G Ω 4.71 G Ω 4.8 G Ω OK OK

WH 5.63 G Ω 4.15 G Ω OK OK

Pair-3 BK 4.15 G Ω 3.67 G Ω 5.15 G Ω OK OK

WH 3.45 G Ω 5.11 G Ω OK OK

Pair-4 BK 4.17G Ω 4.25 G Ω 4.45 G Ω OK OK

WH 4.25 G Ω 5.41 G Ω OK OK

Pair-5 BK 4.24 G Ω 5.25 G Ω 4.35 G Ω OK OK

WH 4.45 G Ω 5.25 G Ω OK OK

Pair-6 BK 4.29 G Ω 4.45 G Ω 4.65 G Ω OK OK

WH 5.25 G Ω 4.35 G Ω OK OK

Pair-7 BK 4.35 G Ω 5.75 G Ω 5.15 G Ω OK OK

WH 4.75 G Ω 4.35 G Ω OK OK

Pair-8 BK 4.63 G Ω 4.35 G Ω 4.21 G Ω OK OK

WH 4.55 G Ω 4.22 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MC-07-04_04-VD1M Date 27/3/2024
Cable Size & Types 8P x 1.5 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 20 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.33 G Ω 5.56 G Ω 5.37 G Ω OK OK

WH 5.44 G Ω 5.41 G Ω OK OK

Pair-2 BK 4.71 G Ω 4.11 G Ω 6.08 G Ω OK OK

WH 4.63 G Ω 6.15 G Ω OK OK

Pair-3 BK 4.85 G Ω 4.67 G Ω 5.77 G Ω OK OK

WH 4.45 G Ω 4.11 G Ω OK OK

Pair-4 BK 5.72 G Ω 5.15 G Ω 4.45 G Ω OK OK

WH 4.25 G Ω 4.41 G Ω OK OK

Pair-5 BK 6.04 G Ω 5.25 G Ω 4.35 G Ω OK OK

WH 4.45 G Ω 4.25 G Ω OK OK

Pair-6 BK 5.29 G Ω 4.45 G Ω 4.65 G Ω OK OK

WH 5.25 G Ω 4.35 G Ω OK OK

Pair-7 BK 5.12 G Ω 4.75 G Ω 4.15 G Ω OK OK

WH 4.65 G Ω 5.35 G Ω OK OK

Pair-8 BK 4.43 G Ω 4.25 G Ω 5.21 G Ω OK OK

WH 5.15 G Ω 4.62 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_41-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.23 GΩ 6.45 GΩ 6.55 GΩ OK OK

WH 6.14 GΩ 6.13 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_43-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.79 GΩ 5.11 GΩ 6.45 GΩ OK OK

WH 5.42 GΩ 5.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-08-20_43-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.19 GΩ 5.61 GΩ 6.15 GΩ OK OK

WH 4.94 GΩ 5.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_01-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.24 GΩ 3.12 GΩ 3.65 GΩ OK OK

WH 3.34 GΩ 4.35 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_01-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.55 GΩ 3.87 GΩ 3.85 GΩ OK OK

WH 3.74 GΩ 4.09 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_02-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.71 GΩ 3.43 GΩ 3.76 GΩ OK OK

WH 3.54 GΩ 4.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_03-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.76 GΩ 3.45 GΩ 3.61 GΩ OK OK

WH 3.49 GΩ 3.93 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_04-VD2 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.75 GΩ 3.78 GΩ 3.69 GΩ OK OK

WH 3.64 GΩ 3.83 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_04-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.66 GΩ 4.18 GΩ 4.63 GΩ OK OK

WH 3.84 GΩ 3.79 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-20_11-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.29 GΩ 2.58 GΩ 3.05 GΩ OK OK

WH 3.54 GΩ 3.11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # BS-24-02_02-VD3 Date 6/4/2024
Cable Size & Types 1P x 1.5 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 15 M

Cable from Biological Treatment Main System Control Panel Cable To, Primary Clarifiers and Biological MCC

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.49 GΩ 2.88 GΩ 3.65 GΩ OK OK

WH 3.14 GΩ 3.71 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # RIO-501W0 Date 18/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 1P x 1.50 Length 180 M

Cable from WTL control panel RIO 3-X13 Cable To, WTL Field FIELD_RIO 3-VM-08-21_33

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.39 G Ω 1.20 G Ω 1.59 G Ω OK OK

WH 1.22 G Ω 1.71 G Ω OK OK

Pair-2 BK 1.39 G Ω 1.17 G Ω 1.69 G Ω OK OK

WH 1.11 G Ω 1.59 G Ω OK OK

Pair-3 BK 1.07 G Ω 1.14 G Ω 1.45 G Ω OK OK

WH 1.41 G Ω 1.57 G Ω OK OK

Pair-4 BK 1.07 G Ω 1.36 G Ω 1.01 G Ω OK OK

WH 1.69 G Ω 1.76 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020208
Drawing No Tag # HC-10-01-01-W-BOX-FT1 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 115 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.28 GΩ 4.69 GΩ 4.8 GΩ OK OK

WH 6.1 GΩ 7.84 GΩ OK OK

Pair-2 BK 1.74 GΩ 4.6 GΩ 5.1 GΩ OK OK

WH 2.4 GΩ 3.2 GΩ OK OK

Pair-3 BK 6.24 GΩ 8.5 GΩ 10.4 GΩ OK OK

WH 11.8 GΩ 6.8 GΩ OK OK

Pair-4 BK 5.13 GΩ 3.9 GΩ 8.4 GΩ OK OK

WH 4.7 GΩ 3.4 GΩ OK OK

Pair-5 BK 3.4 GΩ 8.2 GΩ 5.8 GΩ OK OK

WH 10.2 GΩ 11.4 GΩ OK OK

Pair-6 BK 14.5 GΩ 15.7 GΩ 11.8 GΩ OK OK

WH 6.2 GΩ 4.6 GΩ OK OK

Pair-7 BK 9.4 GΩ 11.4 GΩ 12.6 GΩ OK OK

WH 5.2 GΩ 13.89 GΩ OK OK

Pair-8 BK 11.2 GΩ 12.2 GΩ 9.11 GΩ OK OK

WH 13.4 GΩ 4.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020209
Drawing No Tag # HC-10-01-02-W-BOX-FT2 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 113 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.52 GΩ 5.71 GΩ 9.4 GΩ OK OK

WH 2.96 GΩ 2.5 GΩ OK OK

Pair-2 BK 5.61 GΩ 5.26 GΩ 7.1 GΩ OK OK

WH 3.91 GΩ 2.4 GΩ OK OK

Pair-3 BK 3.22 GΩ 4.11 GΩ 9.1 GΩ OK OK

WH 6.22 GΩ 8.5 GΩ OK OK

Pair-4 BK 4.15 GΩ 5.24 GΩ 7.2 GΩ OK OK

WH 3.12 GΩ 2.1 GΩ OK OK

Pair-5 BK 5.26 GΩ 5.78 GΩ 9.4 GΩ OK OK

WH 9.44 GΩ 7.5 GΩ OK OK

Pair-6 BK 1.99 GΩ 2.76 GΩ 2.4 GΩ OK OK

WH 1.82 GΩ 1.2 GΩ OK OK

Pair-7 BK 2.98 GΩ 3.24 GΩ 3.1 GΩ OK OK

WH 2.99 GΩ 2.8 GΩ OK OK

Pair-8 BK 3.67 GΩ 4.16 GΩ 6.3 GΩ OK OK

WH 8.92 GΩ 5.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020210
Drawing No Tag # HC-10-01-03-W-BOX-FT3 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 110 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.38 GΩ 4.76 GΩ 6.2 GΩ OK OK

WH 5.4 GΩ 3.1 GΩ OK OK

Pair-2 BK 3.32 GΩ 3.4 GΩ 5.4 GΩ OK OK

WH 6.9 GΩ 6.3 GΩ OK OK

Pair-3 BK 4.4 GΩ 6.2 GΩ 3.9 GΩ OK OK

WH 9.1 GΩ 4.5 GΩ OK OK

Pair-4 BK 4.1 GΩ 6.1 GΩ 3.1 GΩ OK OK

WH 5.2 GΩ 6.2 GΩ OK OK

Pair-5 BK 3.8 GΩ 5.6 GΩ 3.1 GΩ OK OK

WH 4.7 GΩ 3.6 GΩ OK OK

Pair-6 BK 4.1 GΩ 1.5 GΩ 2.9 GΩ OK OK

WH 3.8 GΩ 4.9 GΩ OK OK

Pair-7 BK 9.2 GΩ 1.2 GΩ 13.8 GΩ OK OK

WH 7.2 GΩ 11.2 GΩ OK OK

Pair-8 BK 5.2 GΩ 1.9 GΩ 11.1 GΩ OK OK

WH 7.8 GΩ 13.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020211
Drawing No Tag # HC-10-01-04-W-BOX-FT4 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 107 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.20 GΩ 3.6 GΩ 6.5 GΩ OK OK

WH 2.1 GΩ 6.2 GΩ OK OK

Pair-2 BK 3.6 GΩ 4.0 GΩ 5.2 GΩ OK OK

WH 2.8 GΩ 6.8 GΩ OK OK

Pair-3 BK 2.4 GΩ 5.9 GΩ 7.3 GΩ OK OK

WH 2.6 GΩ 4.1 GΩ OK OK

Pair-4 BK 7.1 GΩ 6.4 GΩ 6.1 GΩ OK OK

WH 8.4 GΩ 5.8 GΩ OK OK

Pair-5 BK 3.9 GΩ 6.4 GΩ 3.9 GΩ OK OK

WH 9.1 GΩ 8.4 GΩ OK OK

Pair-6 BK 1.1 GΩ 5.2 GΩ 9.3 GΩ OK OK

WH 6.2 GΩ 2.4 GΩ OK OK

Pair-7 BK 6.2 GΩ 4.5 GΩ 7.1 GΩ OK OK

WH 5.3 GΩ 6.2 GΩ OK OK

Pair-8 BK 2.9 GΩ 8.9 GΩ 6.2 GΩ OK OK

WH 11.1 GΩ 12.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020212
Drawing No Tag # HC-10-01-05-W-BOX-FT5 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 93 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.06 GΩ 2.25 GΩ 2.9 GΩ OK OK

WH 3.52 GΩ 5.6 GΩ OK OK

Pair-2 BK 1.41 GΩ 2.9 GΩ 1.6 GΩ OK OK

WH 2.6 GΩ 3.4 GΩ OK OK

Pair-3 BK 2.5 GΩ 3.1 GΩ 5.2 GΩ OK OK

WH 2.4 GΩ 3.8 GΩ OK OK

Pair-4 BK 6.8 GΩ 8.8 GΩ 7.0 GΩ OK OK

WH 2.8 GΩ 6.2 GΩ OK OK

Pair-5 BK 9.2 GΩ 3.8 GΩ 4.1 GΩ OK OK

WH 4.9 GΩ 6.2 GΩ OK OK

Pair-6 BK 11.3 GΩ 10.8 GΩ 11.2 GΩ OK OK

WH 2.4 GΩ 13.8 GΩ OK OK

Pair-7 BK 3.3 GΩ 11.8 GΩ 7.7 GΩ OK OK

WH 4.0 GΩ 11.2 GΩ OK OK

Pair-8 BK 5.2 GΩ 2.2 GΩ 8.4 GΩ OK OK

WH 6.0 GΩ 7.8 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020213
Drawing No Tag # HC-10-01-05-W-BOX-FT6 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 104 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.88 GΩ 4.24 GΩ 6.0 GΩ OK OK

WH 3.4 GΩ 5.22 GΩ OK OK

Pair-2 BK 9.54 GΩ 9.1 GΩ 2.88 GΩ OK OK

WH 8.4 GΩ 12.1 GΩ OK OK

Pair-3 BK 3.85 GΩ 4.55 GΩ 5.0 GΩ OK OK

WH 5.3 GΩ 6.6 GΩ OK OK

Pair-4 BK 2.11 GΩ 3.5 GΩ 11.2 GΩ OK OK

WH 4.11 GΩ 5.3 GΩ OK OK

Pair-5 BK 5.4 GΩ 6.4 GΩ 6.4 GΩ OK OK

WH 8.2 GΩ 11.1 GΩ OK OK

Pair-6 BK 6.9 GΩ 7.1 GΩ 7.6 GΩ OK OK

WH 7.77 GΩ 11.4 GΩ OK OK

Pair-7 BK 8.4 GΩ 6.8 GΩ 8.3 GΩ OK OK

WH 6.0 GΩ 9.1 GΩ OK OK

Pair-8 BK 7.22 GΩ 7.8 GΩ 11.2 GΩ OK OK

WH 8.8 GΩ 12.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # HC-10-01-05-W-BOX-FT7 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 80 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.18 GΩ 4.87 GΩ 4.9 GΩ OK OK

WH 3.8 GΩ 5.2 GΩ OK OK

Pair-2 BK 2.19 GΩ 4.97 GΩ 5.1 GΩ OK OK

WH 9.1 GΩ 8.2 GΩ OK OK

Pair-3 BK 3.2 GΩ 5.2 GΩ 6.4 GΩ OK OK

WH 2.9 GΩ 3.4 GΩ OK OK

Pair-4 BK 4.1 GΩ 3.2 GΩ 5.1 GΩ OK OK

WH 5.5 GΩ 6.2 GΩ OK OK

Pair-5 BK 5.22 GΩ 6.4 GΩ 7.1 GΩ OK OK

WH 7.3 GΩ 7.8 GΩ OK OK

Pair-6 BK 9.84 GΩ 8.3 GΩ 8.2 GΩ OK OK

WH 8.4 GΩ 3.4 GΩ OK OK

Pair-7 BK 2.7 GΩ 3.91 GΩ 3.7 GΩ OK OK

WH 3.8 GΩ 5.6 GΩ OK OK

Pair-8 BK 3.4 GΩ 3.8 GΩ 4.4 GΩ OK OK

WH 2.8 GΩ 2.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020215
Drawing No Tag # HC-10-01-05-W-BOX-FT8 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 80 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.99 GΩ 3.99 GΩ 4.5 GΩ OK OK

WH 4.0 GΩ 4.0 GΩ OK OK

Pair-2 BK 1.7 GΩ 1.1 GΩ 3.2 GΩ OK OK

WH 2.5 GΩ 7.4 GΩ OK OK

Pair-3 BK 2.4 GΩ 3.0 GΩ 5.9 GΩ OK OK

WH 4.9 GΩ 9.1 GΩ OK OK

Pair-4 BK 11.2 GΩ 13.4 GΩ 11.6 GΩ OK OK

WH 6.2 GΩ 13.4 GΩ OK OK

Pair-5 BK 10.5 GΩ 8.5 GΩ 7.1 GΩ OK OK

WH 9.0 GΩ 8.4 GΩ OK OK

Pair-6 BK 6.7 GΩ 8.0 GΩ 7.8 GΩ OK OK

WH 7.6 GΩ 6.8 GΩ OK OK

Pair-7 BK 11.8 GΩ 10.3 GΩ 11.4 GΩ OK OK

WH 12.4 GΩ 10.4 GΩ OK OK

Pair-8 BK 3.2 GΩ 6.2 GΩ 9.1 GΩ OK OK

WH 4.5 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020216
Drawing No Tag # HC-10-01-05-W-BOX-FT9 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 86 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.59 GΩ 7.03 GΩ 7.5 GΩ OK OK

WH 6.4 GΩ 8.09 GΩ OK OK

Pair-2 BK 5.5 GΩ 7.8 GΩ 6.8 GΩ OK OK

WH 6.9 GΩ 9.2 GΩ OK OK

Pair-3 BK 6.2 GΩ 6.8 GΩ 8.3 GΩ OK OK

WH 5.0 GΩ 9.7 GΩ OK OK

Pair-4 BK 9.1 GΩ 10.4 GΩ 11.2 GΩ OK OK

WH 6.4 GΩ 9.4 GΩ OK OK

Pair-5 BK 2.8 GΩ 3.4 GΩ 7.2 GΩ OK OK

WH 6.4 GΩ 2.8 GΩ OK OK

Pair-6 BK 11.0 GΩ 10.2 GΩ 3.88 GΩ OK OK

WH 8.6 GΩ 9.2 GΩ OK OK

Pair-7 BK 6.2 GΩ 6.6 GΩ 11.9 GΩ OK OK

WH 9.1 GΩ 8.3 GΩ OK OK

Pair-8 BK 4.11 GΩ 6.8 GΩ 3.8 GΩ OK OK

WH 5.6 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020217
Drawing No Tag # HC-10-01-05-W-BOX-FT10 Date 5/17/2024
Cable Size & Types 8P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 89 M

Cable from Disc Filters Local Control Panel Cable To, Disc Filter Local Control Box

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.36 GΩ 4.64 GΩ 5.44 GΩ OK OK

WH 6.22 GΩ 3.69 GΩ OK OK

Pair-2 BK 3.4 GΩ 6.2 GΩ 7.99 GΩ OK OK

WH 3.99 GΩ 5.6 GΩ OK OK

Pair-3 BK 2.11 GΩ 3.69 GΩ 4.2 GΩ OK OK

WH 11.2 GΩ 10.5 GΩ OK OK

Pair-4 BK 3.6 GΩ 4.97 GΩ 6.8 GΩ OK OK

WH 9.11 GΩ 8.5 GΩ OK OK

Pair-5 BK 9.1 GΩ 6.25 GΩ 11.2 GΩ OK OK

WH 4.2 GΩ 6.4 GΩ OK OK

Pair-6 BK 8.5 GΩ 9.43 GΩ 6.9 GΩ OK OK

WH 7.3 GΩ 5.5 GΩ OK OK

Pair-7 BK 5.7 GΩ 6.2 GΩ 6.4 GΩ OK OK

WH 11.4 GΩ 9.2 GΩ OK OK

Pair-8 BK 3.45 GΩ 8.71 GΩ 7.7 GΩ OK OK

WH 5.29 GΩ 6.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-01-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 107 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 1 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.8 GΩ 1.53 GΩ 2.3 GΩ OK OK

WH 4.95 GΩ 1.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-02-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 109 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 2 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.94 GΩ 1.63 GΩ 2.4 GΩ OK OK

WH 3.90 GΩ 3.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-03-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 111 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 3 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.59 GΩ 1.69 GΩ 1.9 GΩ OK OK

WH 3.19 GΩ 1.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-04-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 113 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 4 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.71 GΩ 1.58 GΩ 1.69 GΩ OK OK

WH 3.02 GΩ 2.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-05-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 115 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 5 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.18 GΩ 1.54 GΩ 2.65 GΩ OK OK

WH 3.27 GΩ 2.31 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 10-JBS-06-VD-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 6 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.38 GΩ 3.34 GΩ 2.68 GΩ OK OK

WH 4.01 GΩ 3.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-07-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 83 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 7 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.78 GΩ 5.95 GΩ 4.9 GΩ OK OK

WH 5.75 GΩ 6.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-08-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 87 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 8 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.45 GΩ 2.57 GΩ 3.6 GΩ OK OK

WH 4.62 GΩ 2.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-09-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 91 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 9 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.80 GΩ 6.35 GΩ 5.98 GΩ OK OK

WH 5.05 GΩ 6.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-10-VD-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 93 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 10 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.51 GΩ 2.39 GΩ 3.6 GΩ OK OK

WH 5.15 GΩ 4.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-01-VC-- Date 13/4/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 107 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 1 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.01 GΩ 1.92 GΩ 3.6 GΩ OK OK

WH 3.75 GΩ 4.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-02-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 109 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 2 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.82 GΩ 1.64 GΩ 2.65 GΩ OK OK

WH 4.23 GΩ 3.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-03-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 111 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 3 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.81 GΩ 1.59 GΩ 2.65 GΩ OK OK

WH 4.28 GΩ 2.45 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-04-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 113 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 4 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.97 GΩ 1.81 GΩ 3.67 GΩ OK OK

WH 2.60 GΩ 3.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-05-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 115 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 5 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.91 GΩ 1.70 GΩ 2.45 GΩ OK OK

WH 2.31 GΩ 2.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 10-JBS-06-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 6 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.16 GΩ 3.36 GΩ 2.45 GΩ OK OK

WH 5.20 GΩ 3.45 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # 10-JBS-07-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 7 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.98 GΩ 2.49 GΩ 2.45 GΩ OK OK

WH 5.24 GΩ 3.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-08-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 87 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 8 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.23 GΩ 4.07 GΩ 3.45 GΩ OK OK

WH 3.70 GΩ 3.98 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-09-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 91 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 9 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.19 GΩ 5.25 GΩ 4.52 GΩ OK OK

WH 3.95 GΩ 6.24 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # 10-JBS-09-VC-- Date 13/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 93 M

Cable from Disc Filters Local Control Panel Cable To, Disc Cloth Filter 10 JB

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.37 GΩ 2.17 GΩ 4.95 GΩ OK OK

WH 7.94 GΩ 3.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-01-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 7M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 70.09 GΩ 35.1 GΩ 40.36 GΩ OK OK

WH 57.9 GΩ 52.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-02-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 67.1 GΩ 39.7 GΩ 45.6 GΩ OK OK

WH 5.9 GΩ 6.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-03-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 9.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 45.3 GΩ 30.5 GΩ 45.6 GΩ OK OK

WH 46.7 GΩ 45.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-04-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 11.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 76.9 GΩ 45.3 GΩ 34.6 GΩ OK OK

WH 53.9 GΩ 65.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-05-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 14.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 47.3 GΩ 29.0 GΩ 34.6 GΩ OK OK

WH 43.7 GΩ 26.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-06-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 45.7 GΩ 25.9 GΩ 36.5 GΩ OK OK

WH 81.0 GΩ 70.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-07-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 64.8 GΩ 35.2 GΩ 47.6 GΩ OK OK

WH 91.0 GΩ 46.8 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-08-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 7.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 58.0 GΩ 20.6 GΩ 30.6 GΩ OK OK

WH 47.0 GΩ 36.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-09-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 10.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 33.2 GΩ 13.5 GΩ 18.9 GΩ OK OK

WH 27.0 GΩ 26.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-10-VD1 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 12.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 26.9 GΩ 12.3 GΩ 20.0 GΩ OK OK

WH 15.9 GΩ 19.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-01-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 7M

Cable from Disc Cloth Filtration JB Digital # Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 55.1 GΩ 29.7 GΩ 33.3 GΩ OK OK

WH 47.9 GΩ 22.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-02-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 45.1 GΩ 69.2 GΩ 70.5 GΩ OK OK

WH 89.3 GΩ 69.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-03-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 9.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 77.1 GΩ 25.9 GΩ 39.9 GΩ OK OK

WH 35.5 GΩ 45.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-04-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 11.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 65.6 GΩ 55.9 GΩ 65.4 GΩ OK OK

WH 70.3 GΩ 62.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-05-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 14.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 55.1 GΩ 26.3 GΩ 39.6 GΩ OK OK

WH 44.5 GΩ 35.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-06-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 59.5 GΩ 35.3 GΩ 45.6 GΩ OK OK

WH 75.1 GΩ 65.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-07-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 6M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 62.1 GΩ 40.1 GΩ 45.9 GΩ OK OK

WH 61.3 GΩ 38.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-08-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 7.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 57.7 GΩ 19.9 GΩ 39.6 GΩ OK OK

WH 50.1 GΩ 56.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-08-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 10.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 36.9 GΩ 13.3 GΩ 18.9 GΩ OK OK

WH 27.2 GΩ 26.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-10-WI-WQ-31132


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-4
Drawing No Tag # CM-10-01-10-VD2 Date 14/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 10.5 M

Cable from Disc Cloth Filtration JB Digital Cable To, Disc Cloth Filters Inlet Penstock

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 28.0 GΩ 14.1 GΩ 25.6 GΩ OK OK

WH 15.3 GΩ 18.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # NB-04-01-01-ZD1 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 50 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 01
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.769 GΩ 5.20 GΩ 5.1 GΩ OK OK

WH 5.3 GΩ 5.7 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # NB-04-01-02-ZD1 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 48 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 02
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.4 GΩ 7.4 GΩ 6.7 GΩ OK OK

WH 4.29 GΩ 5.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # NB-04-01-04-ZD1 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 41 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 04
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.92 GΩ 5.74 GΩ 6.2 GΩ OK OK

WH 4.07 GΩ 5.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # NB-04-01-05-ZD1 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 39 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 05
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 9.45 GΩ 6.10 GΩ 6.2 GΩ OK OK

WH 4.47 GΩ 7.5 GΩ OK OK

5.3 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # NB-04-01-01-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 50 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 01
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.45 GΩ 6.52 GΩ 9.1 GΩ OK OK

WH 6.64 GΩ 6.3 GΩ OK OK

Pair-2 BK 4.18 GΩ 4.31 GΩ 5.1 GΩ OK OK

WH 5.53 GΩ 5.2 GΩ OK OK

Pair-3 BK 3.73 GΩ 4.34 GΩ 4.7 GΩ OK OK

WH 5.23 GΩ 5.12 GΩ OK OK

Pair-4 BK 4.67 GΩ 5.79 GΩ 6.2 GΩ OK OK

WH 6.29 GΩ 6.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # NB-04-01-02-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 48 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 02
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 5.39 GΩ 5.02 GΩ 6.1 GΩ OK OK

WH 6.30 GΩ 5.2 GΩ OK OK

Pair-2 BK 3.16 GΩ 4.58 GΩ 5.4 GΩ OK OK

WH 5.34 GΩ 6.2 GΩ OK OK

Pair-3 BK 2.86 GΩ 4.11 GΩ 4.8 GΩ OK OK

WH 5.27 GΩ 5.7 GΩ OK OK

Pair-4 BK 3.20 GΩ 4.85 GΩ 5.3 GΩ OK OK

WH 5.3 GΩ 6.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # NB-04-01-03-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 47 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 03
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 9.8 GΩ 8.91 GΩ 6.5 GΩ OK OK

WH 7.52 GΩ 7.1 GΩ OK OK

Pair-2 BK 5.95 GΩ 5.59 GΩ 5.8 GΩ OK OK

WH 6.51 GΩ 6.6 GΩ OK OK

Pair-3 BK 5.06 GΩ 5.57 GΩ 6.71 GΩ OK OK

WH 7.01 GΩ 7.2 GΩ OK OK

Pair-4 BK 5.94 GΩ 6.68 GΩ 6.21 GΩ OK OK

WH 7.49 GΩ 6.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # NB-04-01-04-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 44 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 04
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.78 GΩ 7.46 GΩ 8.1 GΩ OK OK

WH 6.98 GΩ 7.2 GΩ OK OK

Pair-2 BK 6.61 GΩ 7.6 GΩ 7.2 GΩ OK OK

WH 9.35 GΩ 8.5 GΩ OK OK

Pair-3 BK 5.25 GΩ 6.21 GΩ 7.1 GΩ OK OK

WH 8.18 GΩ 7.9 GΩ OK OK

Pair-4 BK 4.69 GΩ 4.95 GΩ 5.2 GΩ OK OK

WH 5.66 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # NB-04-01-05-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRLS 500V Length 42 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Aeration Blower 05
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.57 GΩ 5.82 GΩ 6.1 GΩ OK OK

WH 6.19 GΩ 5.9 GΩ OK OK

Pair-2 BK 4.38 GΩ 6.45 GΩ 6.1 GΩ OK OK

WH 8.10 GΩ 7.8 GΩ OK OK

Pair-3 BK 4.44 GΩ 6.36 GΩ 5.8 GΩ OK OK

WH 7.76 GΩ 6.3 GΩ OK OK

Pair-4 BK 3.96 GΩ 5.3 GΩ 5.7 GΩ OK OK

WH 5.72 GΩ 5.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # QW-04-01-01-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 28 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 2) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.9 GΩ 7.83 GΩ 8.2 GΩ OK OK

WH 6.64 GΩ 7.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # QW-04-01-03-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 28 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 2) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.6 GΩ 7.18 GΩ 6.8 GΩ OK OK

WH 6.41 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # QW-04-01-04-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 28 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 2) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.6 GΩ 10.1 GΩ 9.3 GΩ OK OK

WH 5.47 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # DT-04-01-02-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 30 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 1) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.8 GΩ 6.34 GΩ 5.9 GΩ OK OK

WH 8.49 GΩ 7.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # DT-04-01-04-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 30 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 1) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.2 GΩ 6.12 GΩ 5.9 GΩ OK OK

WH 8.08 GΩ 6.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # MO-04-01-02-ZD Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 53 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Oil And Grease Separator 02
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.44 GΩ 3.7 GΩ 4.1 GΩ OK OK

WH 5.62 GΩ 5.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020214
Drawing No Tag # MO-04-01-02-RE-M Date 15/04/2024
Cable Size & Types 4P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 53 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, Oil And Grease Separator 02
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.63 GΩ 4.77 GΩ 5.15 GΩ OK OK

WH 5.65 GΩ 5.38 GΩ OK OK

Pair-2 BK 1.82 GΩ 3.77 GΩ 5.76 GΩ OK OK

WH 4.97 GΩ 6.12 GΩ OK OK

Pair-3 BK 2.19 GΩ 3.86 GΩ 5.94 GΩ OK OK

WH 4.53 GΩ 5.81 GΩ OK OK

Pair-4 BK 2.9 GΩ 5.49 GΩ 6.09 GΩ OK OK

5.78 GΩ 6.01 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # DA-04-01-03-VD2 Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 30 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 1) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 15.1 GΩ 9.71 GΩ 8.7 GΩ OK OK

WH 6.15 GΩ 6.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # DS-04-01202-VD2- Date 15/04/2024
Cable Size & Types 1P x 1.50 mm2, PVC/OSH/PVC/PVC FRSL 500V Length 30 M

380 LV Distribution Switchboard


Cable from Pretreatment Main System Control Panel (Part 1) Cable To,
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.2 GΩ 6.17 GΩ 5.9 GΩ OK OK

WH 9.12 GΩ 7.8 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # DA-04-01-02-VD1M Date 28/2/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 31 M

Cable from PRETREATMENT MAIN SYSTEM CONTROL PANEL (PART 1) Cable To, 380 LV Distribution Switchboard Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Drain Remarks
Tagging Core to Conductor
Core No. Core to Core Core to Ground Continuit
Shield Continuity
y
Pair-1 BK 19.3 G Ω 29.1 G Ω 20.2 G Ω OK OK

WH 28.6 G Ω 29.2 G Ω OK OK

Pair-2 BK 18.1 G Ω 16.8 G Ω 17.1 G Ω OK OK

WH 16.1 G Ω 20.5 G Ω OK OK

Pair-3 BK 17.9 G Ω 16.7 G Ω 17.5 G Ω OK OK

WH 17.2 G Ω 18.1 G Ω OK OK

Pair-4 BK 16.9 G Ω 19.2 G Ω 19.5 G Ω OK OK

WH 19.9 G Ω 22.3 G Ω OK OK

Pair-5 BK 13.2 G Ω 21.8 G Ω 25.2 G Ω OK OK

WH 20.7 G Ω 20.1 G Ω OK OK

Pair-6 BK 11.8 G Ω 19.2 G Ω 12 G Ω OK OK

WH 19.0 G Ω 18.5 G Ω OK OK

Pair-7 BK 15.4 G Ω 22.6 G Ω 25.5 G Ω OK OK

WH 20.2 G Ω 21.2 G Ω OK OK

Pair-8 BK 14.8 G Ω 19.7 G Ω 22.0 G Ω OK OK

WH 18.9 G Ω 18.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # DT-04-01-03-VD1M Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 30 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 31.9 G Ω 55.9 G Ω 59.1 G Ω OK OK

WH 28.8 G Ω 29.2 G Ω OK OK

Pair-2 BK 24.1 G Ω 30.1 G Ω 32.4 G Ω OK OK

WH 33.3 G Ω 31.2 G Ω OK OK

Pair-3 BK 27.7 G Ω 25.9 G Ω 26.7 G Ω OK OK

WH 32.1 G Ω 32.5 G Ω OK OK

Pair-4 BK 29.8 G Ω 30.1 G Ω 29.8 G Ω OK OK

WH 28.8 G Ω 28.2 G Ω OK OK

Pair-5 BK 23.6 G Ω 30.3 G Ω 22.5 G Ω OK OK

WH 35.2 G Ω 29.2 G Ω OK OK

Pair-6 BK 25.1G Ω 35.2 G Ω 30.0 G Ω OK OK

WH 31.7 G Ω 33 G Ω OK OK

Pair-7 BK 24.5 G Ω 25.9 G Ω 29.5 G Ω OK OK

WH 31.7 G Ω 37.0 G Ω OK OK

Pair-8 BK 25.1 G Ω 32.1 G Ω 33.2 G Ω OK OK

WH 33.3 G Ω 33.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MO-04-01-02-VD2 Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 29 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 2) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.48 G Ω 16.7 G Ω 74.9 G Ω OK OK

WH 7.92 G Ω 70.6 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # DA-04-01-03-VD1M Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 31 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 16.7 G Ω 24 6 G Ω 22.5 G Ω OK OK

WH 23.9 G Ω 23.9 G Ω OK OK

Pair-2 BK 14.4 G Ω 15 G Ω 15.0 G Ω OK OK

WH 14.3 G Ω 14.3 G Ω OK OK

Pair-3 BK 13.1 G Ω 17.1 G Ω 17.1 G Ω OK OK

WH 19.6 G Ω 19.6 G Ω OK OK

Pair-4 BK 13.2 G Ω 20.8 G Ω 20.8 G Ω OK OK

WH 20.1 G Ω 20.1 G Ω OK OK

Pair-5 BK 12.0 G Ω 20.0 G Ω 20.0 G Ω OK OK

WH 19.6 G Ω 19.6 G Ω OK OK

Pair-6 BK 11.1 G Ω 19 G Ω 19.0 G Ω OK OK

WH 19.8 G Ω 19.8 G Ω OK OK

Pair-7 BK 13.7 G Ω 19.0 G Ω 19 G Ω OK OK

WH 21.3 G Ω 21.3 G Ω OK OK

Pair-8 BK 13.2 G Ω 17.6 G Ω 17.6 G Ω OK OK

WH 17.5 G Ω 17.5 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # LL-04-01-02-VD1M Date 29/2/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 46.4 G Ω 39.2 G Ω 36.4 G Ω OK OK

WH 35.4 G Ω 33.4 G Ω OK OK

Pair-2 BK 33.4 G Ω 29.3 G Ω 39.4 G Ω OK OK

WH 28.6 G Ω 27.5 G Ω OK OK

Pair-3 BK 30.7 G Ω 25.6 G Ω 23.8 G Ω OK OK

WH 28.7 G Ω 24.3 G Ω OK OK

Pair-4 BK 30.1 G Ω 22.42 G Ω 28.4 G Ω OK OK

WH 28.53 G Ω 20.0 G Ω OK OK

Pair-5 BK 28.5 G Ω 34.2 G Ω 27.0 G Ω OK OK

WH 28.9 G Ω 35.2 G Ω OK OK

Pair-6 BK 32.5 G Ω 23.6 G Ω 29.1 G Ω OK OK

WH 26.7 G Ω 29.6 G Ω OK OK

Pair-7 BK 43.3 G Ω 21.2 G Ω 30.5 G Ω OK OK

WH 38.2 G Ω 28.2 G Ω OK OK

Pair-8 BK 29.3 G Ω 34.5 G Ω 35.2 G Ω OK OK

WH 25.50 G Ω 29.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020207
Drawing No Tag # LL-04-02-01-VD1M Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M
PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard
Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 40.8 G Ω 39.2 G Ω 36.4 G Ω OK OK

WH 35.4 G Ω 33.4 G Ω OK OK

Pair-2 BK 30.7 G Ω 29.3 G Ω 39.4 G Ω OK OK

WH 28.6 G Ω 27.5 G Ω OK OK

Pair-3 BK 30.7 G Ω 25.6 G Ω 23.8 G Ω OK OK

WH 28.7 G Ω 24.3 G Ω OK OK

Pair-4 BK 30.1 G Ω 22.42 G Ω 28.4 G Ω OK OK

WH 28.53 G Ω 20.0 G Ω OK OK

Pair-5 BK 28.5 G Ω 34.2 G Ω 27.0 G Ω OK OK

WH 28.9 G Ω 35.2 G Ω OK OK

Pair-6 BK 32.5 G Ω 23.6 G Ω 29.1 G Ω OK OK

WH 26.7 G Ω 29.6 G Ω OK OK

Pair-7 BK 43.3 G Ω 21.2 G Ω 30.5 G Ω OK OK

WH 38.2 G Ω 28.2 G Ω OK OK

Pair-8 BK 29.3 G Ω 34.5 G Ω 35.2 G Ω OK OK

WH 25.50 G Ω 29.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # NB-04-01-01-VD1M Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M
PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard
Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 22.2 G Ω 32 G Ω 35 G Ω OK OK

WH 38.4 G Ω 38 G Ω OK OK

Pair-2 BK 23.3G Ω 19.3 G Ω 20.4 G Ω OK OK

WH 23.6 G Ω 22.2 G Ω OK OK

Pair-3 BK 20.8 G Ω 23.6 G Ω 29.0 G Ω OK OK

WH 29.2 G Ω 29.4 G Ω OK OK

Pair-4 BK 20.8 G Ω 27.2 G Ω 28.4 G Ω OK OK

WH 27.3 G Ω 30.0 G Ω OK OK

Pair-5 BK 19.5 G Ω 33.2 G Ω 27.0 G Ω OK OK

WH 27.2 G Ω 29 G Ω OK OK

Pair-6 BK 18.8 G Ω 28.4 G Ω 29.1 G Ω OK OK

WH 27.7 G Ω 26 G Ω OK OK

Pair-7 BK 22.3 G Ω 27.2 G Ω 29 G Ω OK OK

WH 27.9 G Ω 28.2 G Ω OK OK

Pair-8 BK 21.8 G Ω 34.5 G Ω 35.2 G Ω OK OK

WH 26.0 G Ω 29.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-1
Drawing No DN # Date 27-01-2024
Cable Size & Types 1P*1.5mm2 cu/pvc/pvc OA shielded Length 2000M

Cable from _______In drum___________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 52 M Ω 77.5 M Ω 74.9 M Ω OK OK

WH 72.8 M Ω 70.6 M Ω OK OK

Pair-1 BK
WH
Pair-1 BK
WH
Pair-1 BK
WH
Pair-1 BK
WH
Pair-1 BK
WH
Pair-1 BK
WH
Pair-1 BK
WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# LL-04-01-02-VD1M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.50 Length 32M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 43.5 GΩ 46.4 GΩ 45.1 GΩ OK

WH 57.8 GΩ 57.2 GΩ OK

Pair-2 BK 33.4 GΩ 28.8 GΩ 29.8 GΩ OK

WH 32.8 GΩ 31.1 GΩ OK

Pair-3 BK 33.3 GΩ 31.9 GΩ 34.9 GΩ OK

WH 35.5 GΩ 39.2 GΩ OK

Pair-4 BK 33.2 GΩ 35.3 GΩ 35.2 GΩ OK

WH 35.7 GΩ 39.2 GΩ OK

Pair-5 BK 30.7 GΩ 33.8 GΩ 39.5 GΩ OK

WH 39 GΩ 39.2 GΩ OK

Pair-6 BK 27.9 GΩ 33.2 GΩ 38.2 GΩ OK

WH 38.6 GΩ 39.5 GΩ OK

Pair-7 BK 39.0 GΩ 31.5 GΩ 31.5 GΩ OK

WH 30.7 GΩ 39.1 GΩ OK

Pair-8 BK 35 GΩ 30.8 GΩ 29.0 GΩ OK

WH 31.5 GΩ 28.5 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# DS-04-01-01-VD1M Date 2/4/2024
PVC/OSH/PVC/PVC FRLS
Cable Size & Types Length 30M
500V - 8P x 1.50

PRETREATMENT MAIN 380 LV Distribution Switchboard


Cable from Cable To,
SYSTEM CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 31.8 GΩ 41.5 GΩ 45.2 GΩ OK

WH 37.9 GΩ 30.2 GΩ OK

Pair-2 BK 28 GΩ 23.6 GΩ 20.2 GΩ OK

WH 26.4 GΩ 36.1 GΩ OK

Pair-3 BK 29.9 Ω 23.8 GΩ 29.1 GΩ OK

WH 27.3 GΩ 31.5 GΩ OK

Pair-4 BK 27.9 GΩ 29.5 GΩ 32.1 GΩ OK

WH 27.8 GΩ 29.5 GΩ OK

Pair-5 BK 26.8 GΩ 27.4 GΩ 25.2 GΩ OK

WH 27 GΩ 27.5 GΩ OK

Pair-6 BK 26.9 GΩ 26.7 GΩ 35.1 GΩ OK

WH 27.1 GΩ 28.2 GΩ OK

Pair-7 BK 59.6 GΩ 24.8 GΩ 25.1 GΩ OK

WH 27.8 GΩ 27.4 GΩ OK

Pair-8 BK 48 GΩ 27.6 GΩ 28.1 GΩ OK

WH 27.4 GΩ 29.4 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# LL-04-01-02-VD2 Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 32M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 27 GΩ 18 GΩ 21.4 GΩ OK

WH 11.5 GΩ 12.3 GΩ OK

BK
WH
BK
WH
BK
WH
BK
WH
BK
WH
BK
WH
BK
WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# NB-04-01-05-VD1M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 20.5 GΩ 29.4 GΩ 29.0 GΩ OK OK

WH 31.8 GΩ 33.2 GΩ OK OK

Pair-2 BK 19.6 GΩ 19.7 GΩ 21.5 GΩ OK OK

WH 24.3 GΩ 29.2 GΩ OK OK

Pair-3 BK 16.8 GΩ 18.2 GΩ 21.5 GΩ OK OK

WH 19.4 GΩ 22.2 GΩ OK OK

Pair-4 BK 17.4 GΩ 22.5 GΩ 19.2 GΩ OK OK

WH 23.9 GΩ 24 GΩ OK OK

Pair-5 BK 16.2 GΩ 23 GΩ 23.8 GΩ OK OK

WH 22.5 GΩ 29.1 GΩ OK OK

Pair-6 BK 15.3 GΩ 21.1 GΩ 22.5 GΩ OK OK

WH 19.5 GΩ 18.1 GΩ OK OK

Pair-7 BK 18.7 GΩ 20.2 GΩ 20.2 GΩ OK OK

WH 22.7 GΩ 22 GΩ OK OK

Pair-8 BK 17.6 GΩ 18.8 GΩ 19.7 GΩ OK OK

WH 21.5 GΩ 22.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# LL-04-01-01-VD1M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 35.4 GΩ 37.4 GΩ 34.9 GΩ OK

WH 42.3 GΩ 39.5 GΩ OK

Pair-2 BK 28 GΩ 24.3 GΩ 30.1 GΩ OK

WH 23.9 GΩ 24.0 GΩ OK

Pair-3 BK 33.6 GΩ 22.1 GΩ 25.5 GΩ OK

WH 22.6 GΩ 23.1 GΩ OK

Pair-4 BK 28.3 GΩ 24.9 GΩ 29.5 GΩ OK

WH 28.4 GΩ 20.1 GΩ OK

Pair-5 BK 24 GΩ 27.6 GΩ 28.5 GΩ OK

WH 27.7 GΩ 21.5 GΩ OK

Pair-6 BK 22.9 GΩ 27.4 GΩ 29 GΩ OK

WH 29.8 GΩ 20.1 GΩ OK

Pair-7 BK 25.6 GΩ 27.7 GΩ 29.5 GΩ OK

WH 32.1 GΩ 33.1 GΩ OK

Pair-8 BK 24.6 GΩ 27.6 GΩ 29.2 GΩ OK

WH 28.2 GΩ 29.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DA-04-01-02-VD2- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 30 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 25.6 GΩ 19.3 GΩ 22.4 GΩ OK

WH 9.18 GΩ 22.4 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# NB-04-01-03VD2- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 30 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 29.9 GΩ 15.7 GΩ 21.2 GΩ OK

WH 7.9 GΩ 20.5 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# MO-04-01-01-VD2- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 29 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 2) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 20.7 GΩ 11.9 GΩ 24.5 GΩ OK

WH 10.8 GΩ 22.3 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# NB-04-01-01-VD2- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 32 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 13.9 GΩ 5.99 GΩ 15.1 GΩ OK

BK 6.62 GΩ 12.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# LL-04-02-02-VD1M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.50 Length 29 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 23.7 GΩ 26.2 GΩ 39 GΩ OK

WH 30.6 GΩ 22.1 GΩ OK

Pair-2 BK 19.3 GΩ 17.9 GΩ 21.2 GΩ OK

WH 18.9 GΩ 22.1 GΩ OK

Pair-3 BK 20.4 GΩ 20 GΩ 22.5 GΩ OK

WH 21.3 GΩ 21.9 GΩ OK

Pair-4 BK 19.2 GΩ 23.4 GΩ 29.1 GΩ OK

WH 21.8 GΩ 22.5 GΩ OK

Pair-5 BK 16.7 GΩ 19.6 GΩ 18.2 GΩ OK

WH 16.1 GΩ 15.7 GΩ OK

Pair-6 BK 15.7 GΩ 13.8 GΩ 14.2 GΩ OK

WH 13.6 GΩ 21.1 GΩ OK

Pair-7 BK 16.1 GΩ 14.1 GΩ 17.9 GΩ OK

WH 13.7 GΩ 15.5 GΩ OK

Pair-8 BK 16.2 GΩ 16.5 GΩ 15.2 GΩ OK

WH 17.1 GΩ 18.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733146-13
Drawing No Tag# DS-04-01-01-ZD-- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 64 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 6.68 GΩ 4.26 GΩ 5.1 GΩ OK OK

BK 3.5 GΩ 4.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733146-13
Drawing No Tag# DS-04-01_02-ZD-- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 61 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 7.39 GΩ 3.63 GΩ 5.2 GΩ OK OK

BK 4.31 GΩ 4.93 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# QW-04-01-02-ZD Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 69 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 7.04 GΩ 4.77 GΩ 5.1 GΩ OK OK

BK 5.1 GΩ 5.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# QW-04-01-01-ZD Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 73 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 6.40 GΩ 3.83 GΩ 4.12 GΩ OK OK

BK 3.46 GΩ 3.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# MO-04-01-01-ZD- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 54 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 8.99 GΩ 5.78 GΩ 5.5 GΩ OK OK

BK 4.48 GΩ 6.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020214
Drawing No Tag # DS-04-01_02-RE-M Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 61 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.24 G Ω 3.9 G Ω 4.1 G Ω OK OK

WH 4.31 G Ω 4.3 G Ω OK OK

Pair-2 BK 2.58 G Ω 3.9 G Ω 4.1 G Ω OK OK

WH 5.8 G Ω 5.1 G Ω OK OK

Pair-3 BK 4.24 G Ω 4.63 G Ω 5.2 G Ω OK OK

WH 5.85 G Ω 5.1 G Ω OK OK

Pair-4 BK 2.58 G Ω 4.33 G Ω 4.7 G Ω OK OK

WH 4.3 G Ω 4.4 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020214
Drawing No Tag # QW-04-01_02-RE-M Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 69 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.10 G Ω 3.67 G Ω 4.1 G Ω OK OK

WH 3.76 G Ω 3.92 G Ω OK OK

Pair-2 BK 3.10 G Ω 3.5 G Ω 3.71 G Ω OK OK

WH 5.8 G Ω 5.1 G Ω OK OK

Pair-3 BK 1.28 G Ω 4.63 G Ω 5.2 G Ω OK OK

WH 3.7 G Ω 4.19 G Ω OK OK

Pair-4 BK 1.52 G Ω 4.1 G Ω 4.32 G Ω OK OK

WH 3.8 G Ω 4.29 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020214
Drawing No Tag # QW-04-01_01-RE-M Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 73 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.53 G Ω 1.89 G Ω 2.1 G Ω OK OK

WH 1.87 G Ω 1.86 G Ω OK OK

Pair-2 BK 510 M Ω 1.98 G Ω 1.78 G Ω OK OK

WH 1.66 G Ω 1.9 G Ω OK OK

Pair-3 BK 605 M Ω 1.87 G Ω 1.61 G Ω OK OK

WH 2.14 G Ω 2.3 G Ω OK OK

Pair-4 BK 554 M Ω 2.1 G Ω 1.89 G Ω OK OK

WH 1.8 G Ω 1.71 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020214
Drawing No Tag # 04-JBD-07-VD-M Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 69 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.06 G Ω 1.86 G Ω 2.11 G Ω OK OK

WH 1.98 G Ω 2.21 G Ω OK OK

Pair-2 BK 411 M G Ω 1.79 G Ω 1.91 G Ω OK OK

WH 1.81 G Ω 2.11 G Ω OK OK

Pair-3 BK 487 M Ω 2.38 G Ω 2.31 G Ω OK OK

WH 2.4 G Ω 2.12 G Ω OK OK

Pair-4 BK 436 M Ω 1.64 G Ω 1.94 G Ω OK OK

WH 1.72 G Ω 1.92 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-06-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 104 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 1GΩ 2.11 G Ω 1.35 GΩ OK

WH 2.19 GΩ 1.40 GΩ OK

Pair-2 BK 946 M Ω 2.21 GΩ 1.23 GΩ OK

WH 1.9 GΩ 1.44 GΩ OK

Pair-3 BK 1.01 G Ω 1.13 GΩ 1.69 GΩ OK

WH 1.44 GΩ 1.23 GΩ OK

Pair-4 BK 1.01 G Ω 1.63 GΩ 1.24 G Ω OK

WH 1.23 G Ω 2.5 GΩ OK

Pair-5 BK 893 M Ω 1.61 GΩ 1.2 GΩ OK

WH 1.26 GΩ 1.7 GΩ OK

Pair-6 BK 924 M Ω 1.43 GΩ 1.2 GΩ OK

WH 2.29 GΩ 1.51 GΩ OK

Pair-7 BK 995 M Ω 2.17 GΩ 1.69 GΩ OK

WH 1.93 GΩ 1.14 GΩ OK

Pair-8 BK 1.13 G Ω 2.1 GΩ 1.98 GΩ OK

WH 1.89 GΩ 2.1 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-05-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 87 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 398 M Ω 763 M Ω 1.46 GΩ OK

WH 30.6 GΩ 1.21 GΩ OK

Pair-2 BK 292 M Ω 1.11 GΩ 1.26 GΩ OK

WH 1.42 GΩ 1.19 GΩ OK

Pair-3 BK 306 M Ω 1.13 GΩ 1.69 GΩ OK

WH 1.44 GΩ 1.23 GΩ OK

Pair-4 BK 294 M Ω 1.63 GΩ 943 M Ω OK

WH 764 M Ω 2.5 GΩ OK

Pair-5 BK 265 M Ω 1.61 GΩ 1.2 GΩ OK

WH 1.26 GΩ 1.7 GΩ OK

Pair-6 BK 253 M Ω 1.43 GΩ 1.2 GΩ OK

WH 1.12 GΩ 1.1 GΩ OK

Pair-7 BK 270 M Ω 1.31 GΩ 1.27 GΩ OK

WH 1.26 GΩ 1.17 GΩ OK

Pair-8 BK 267 M Ω 1.01 GΩ 1.11 GΩ OK

WH 1.15 GΩ 1.19 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #16023-020214
Drawing No Tag # DS-04-01_01-RE-M Date 17/3/2024
Cable Size & Types 4P x 1.50 MM2, PVC/OSH/PVC/PVC FRLS 500V Length 64 M

Cable from Cable To,

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.02 G Ω 4.55 G Ω 4.7 G Ω OK OK

WH 4.63 G Ω 4.5 G Ω OK OK

Pair-2 BK 2.33 G Ω 4.55 G Ω 4.8 G Ω OK OK

WH 5.8 G Ω 5.1 G Ω OK OK

Pair-3 BK 2.78 G Ω 4.63 G Ω 5.2 G Ω OK OK

WH 5.85 G Ω 6.1 G Ω OK OK

Pair-4 BK 2.33 G Ω 5.84 G Ω 6.1 G Ω OK OK

WH 5.3 G Ω 5.9 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-03-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 81 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 3.20G Ω 5.22 G Ω 7.41 GΩ OK OK

WH 5.10 GΩ 6.94 GΩ OK OK

Pair-2 BK 3.24 G Ω 4.96 GΩ 7.13 GΩ OK OK

WH 5.15 GΩ 6.97 GΩ OK OK

Pair-3 BK 3.10 G Ω 6.19 GΩ 5.83 GΩ OK OK

WH 3.70 GΩ 5.73 GΩ OK OK

Pair-4 BK 3.37 G Ω 4.89 GΩ 3.24 G Ω OK OK

WH 4.23 G Ω 4.5 GΩ OK OK

Pair-5 BK 2.96 G Ω 3.61 GΩ 4.2 GΩ OK OK

WH 4.26 GΩ 3.7 GΩ OK OK

Pair-6 BK 2.64 G Ω 4.94 GΩ 5.2 GΩ OK OK

WH 4.97 GΩ 5.74 GΩ OK OK

Pair-7 BK 3.29 G Ω 4.62 GΩ 5.79 GΩ OK OK

WH 5.13 GΩ 5.78 GΩ OK OK

Pair-8 BK 2.9 G Ω 3.92 GΩ 5.96 GΩ OK OK

WH 4.07 GΩ 5.37 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-04-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 68 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 2.93 G Ω 4.66 G Ω 5.69 GΩ OK OK

WH 4.51 GΩ 5.21 GΩ OK OK

Pair-2 BK 2.69 G Ω 4.21 GΩ 4.97 GΩ OK OK

WH 3.98 GΩ 3.91 GΩ OK OK

Pair-3 BK 2.89 G Ω 2.59 GΩ 3.69 GΩ OK OK

WH 2.70 GΩ 3.23 GΩ OK OK

Pair-4 BK 2.77 G Ω 2.89 GΩ 3.24 G Ω OK OK

WH 3.23 G Ω 4.5 GΩ OK OK

Pair-5 BK 2.55 G Ω 3.61 GΩ 4.2 GΩ OK OK

WH 3.26 GΩ 3.7 GΩ OK OK

Pair-6 BK 2.32 G Ω 3.94 GΩ 5.2 GΩ OK OK

WH 3.78 GΩ 5.74 GΩ OK OK

Pair-7 BK 2.4 G Ω 3.94 GΩ 4.79 GΩ OK OK

WH 3.91 GΩ 4.59 GΩ OK OK

Pair-8 BK 2.38 G Ω 2.99 GΩ 5.69 GΩ OK OK

WH 3.11 GΩ 5.71 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-02-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 79 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 1.67 G Ω 3.32 G Ω 3.74 GΩ OK OK

WH 3.85 GΩ 3.79 GΩ OK OK

Pair-2 BK 1.67 G Ω 3.79 GΩ 3.18 GΩ OK OK

WH 3.32 GΩ 3.32 GΩ OK OK

Pair-3 BK 1.73 G Ω 2.59 GΩ 3.69 GΩ OK OK

WH 2.70 GΩ 1.23 GΩ OK OK

Pair-4 BK 1.89 G Ω 2.89 GΩ 3.24 G Ω OK OK

WH 1.23 G Ω 2.5 GΩ OK OK

Pair-5 BK 1.76 G Ω 1.61 GΩ 1.2 GΩ OK OK

WH 1.26 GΩ 3.7 GΩ OK OK

Pair-6 BK 1.55 G Ω 3.94 GΩ 1.2 GΩ OK OK

WH 3.84 GΩ 2.81 GΩ OK OK

Pair-7 BK 1.81 G Ω 3.89 GΩ 3.45GΩ OK OK

WH 3.91 GΩ 3.71 GΩ OK OK

Pair-8 BK 1.62 G Ω 3.91 GΩ 3.95 GΩ OK OK

WH 3.88 GΩ 3.84 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020207
Drawing No Tag# 04-JBD-01-VD-M Date 2/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 8P x 1.5 MM2 Length 100 M

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from Cable To,
CONTROL PANEL (PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 1.63 G Ω 2.89 G Ω 2.91 GΩ OK OK

WH 3.26 GΩ 2.99 GΩ OK OK

Pair-2 BK 1.88 G Ω 2.45 GΩ 2.65 GΩ OK OK

WH 2.49 GΩ 2.7 GΩ OK OK

Pair-3 BK 1.46 G Ω 2.59 GΩ 1.69 GΩ OK OK

WH 2.70 GΩ 1.23 GΩ OK OK

Pair-4 BK 1.59 G Ω 2.89 GΩ 1.24 G Ω OK OK

WH 1.23 G Ω 2.5 GΩ OK OK

Pair-5 BK 1.35 G Ω 1.61 GΩ 1.2 GΩ OK OK

WH 1.26 GΩ 1.7 GΩ OK OK

Pair-6 BK 1.31 G Ω 2.71 GΩ 1.2 GΩ OK OK

WH 2.91 GΩ 2.81 GΩ OK OK

Pair-7 BK 1.55 G Ω 3.10 GΩ 2.94 GΩ OK OK

WH 3.17 GΩ 2.87 GΩ OK OK

Pair-8 BK 1.21 G Ω 3.15 GΩ 2.84 GΩ OK OK

WH 2.94 GΩ 2.74 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733146-13
Drawing No Tag# LIT-04-01-00-ZC-- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 110 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 3.06 GΩ 1.76 GΩ 3.5 GΩ OK OK

BK 2.69 GΩ 3.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-8
Drawing No Tag# AIT-04-02_02-ZC-- Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 109 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 4.33 GΩ 3.4 GΩ 4.15 GΩ OK OK

BK 1.27 GΩ 3.81 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-8
Drawing No Tag# AIT-04-02_01-ZC Date 2/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 102 M
500V - 1P x 1.50

PRETREATMENT MAIN SYSTEM 380 LV Distribution Switchboard


Cable from CONTROL PANEL (PART 1) Cable To, Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 WH 3.71 GΩ 2.35 GΩ 3.45 GΩ OK OK

BK 1.77 GΩ 3.65 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# MO-04-01-01-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 56 M

380 LV Distribution Switchboard


Cable from Cable To, OIL AND GREASE SEPARATOR 01
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 3.96 G Ω 6.37 G Ω 4.07 G Ω OK

WH 5.98G Ω 6.1 G Ω OK

Pair-2 BK 2.8 G Ω 4.09 G Ω 4.7 G Ω OK

WH 4.75 G Ω 6.1 G Ω OK

Pair-3 BK 3.54 G Ω 6.37 G Ω 6.2 G Ω OK

WH 4.09 G Ω 5.2 G Ω OK

Pair-4 BK 3.81 G Ω 4.75 G Ω 5.7 G Ω OK

WH 5.1 G Ω 6.2 G Ω

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DA-04-01-02-ZD- Date 3/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 82 M
500V - 1P x 1.50

380 LV Distribution Switchboard


Cable from Transformer 1 Incomer Cable To, COARSE SCREEN CHANNEL 02

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.86 GΩ 2.09 GΩ 2.7 GΩ OK OK

WH 3.33 GΩ 3.14 GΩ 2.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# DA-04-01-01-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 87 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 01
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 4.55 GΩ 4.23 GΩ 2.77 GΩ OK OK

WH 3.81 GΩ 2.33 GΩ OK OK

Pair-2 BK 1.76 GΩ 2.39 GΩ 3.12 GΩ OK OK

WH 2.17 GΩ 2.99 GΩ OK OK

Pair-3 BK 2.37 GΩ 2.88 GΩ 3.44 GΩ OK OK

WH 2.51 GΩ 3.19 GΩ OK OK

Pair-4 BK 2.94 GΩ 2.84 GΩ 2.79 GΩ OK OK

WH 3.61 GΩ 3.42 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DA-04-01-01-ZD-- Date 3/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 87 M
500V - 1P x 1.50

380 LV Distribution Switchboard


Cable from Transformer 1 Incomer Cable To, COARSE SCREEN CHANNEL 01

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 4.33 GΩ 2.52 GΩ 3.28 GΩ OK OK

WH 2.18 GΩ 3.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# DA-04-1-02-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 82 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 02
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 8.13 GΩ 6.68 GΩ 4.86 GΩ OK OK

WH 6.26 GΩ 5.13 GΩ OK OK

Pair-2 BK 3.30 GΩ 3.71 GΩ 4.96 GΩ OK OK

WH 4.08 GΩ 4.87 GΩ OK OK

Pair-3 BK 4.14 GΩ 3.57 GΩ 4.71 GΩ OK OK

WH 4.1 GΩ 5.01 GΩ OK OK

Pair-4 BK 5.04 GΩ 4.23 GΩ 5.11 GΩ OK OK

WH 5.41 GΩ 5.23 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# DA-04-01-04-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 70 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 04
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 9.12 GΩ 7.31 GΩ 6.93 GΩ OK OK

WH 5.88 GΩ 6.71 GΩ OK OK

Pair-2 BK 3.91 GΩ 4.15 GΩ 5.78 GΩ OK OK

WH 4.55 GΩ 5.64 GΩ OK OK

Pair-3 BK 4.72 GΩ 4.93 GΩ 4.94 GΩ OK OK

WH 4.79 GΩ 5.11 GΩ OK OK

Pair-4 BK 5.35 GΩ 5.71 GΩ 5.79 GΩ OK OK

WH 5.91 GΩ 5.89 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# LL-04-01-01-ZD- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 83 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW COARSE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.05 GΩ 3.85 GΩ 3.91 GΩ OK OK

WH 2.67 GΩ 3.79 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# LL-04-02-01-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 75 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW FINE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 9.46 GΩ 5.68 GΩ 6.0 GΩ OK OK

WH 5.41 GΩ 2.6 GΩ OK OK

Pair-2 BK 3.42 GΩ 5.23 GΩ 4.3 GΩ OK OK

WH 5.71 GΩ 6.1 GΩ OK OK

Pair-3 BK 3.87 GΩ 5.31 GΩ 4.2 GΩ OK OK

WH 5.47 GΩ 5.9 GΩ OK OK

Pair-4 BK 4.22 GΩ 4.94 GΩ 5.0 GΩ OK OK

WH 5.07 GΩ 6.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# LL-04-02-01-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 53 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW FINE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.78 GΩ 4.44 GΩ 6.14 GΩ OK OK

WH 4.24 GΩ 6.07 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DT-04-01-01-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 75 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 01
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.94 GΩ 2.9 GΩ 4.32 GΩ OK OK

WH 5.31 GΩ 3.13 GΩ 3.78 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# DT-04-01-01-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 75 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 01
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.09 GΩ 2.87 GΩ 3.63 GΩ OK OK

WH 3.10 GΩ 3.91 GΩ OK OK

Pair-2 BK 2.33 GΩ 3.37 GΩ 4.14 GΩ OK OK

WH 2.95 GΩ 4.23 GΩ OK OK

Pair-3 BK 3.27 GΩ 3.39 GΩ 3.96 GΩ OK OK

WH 3.78 GΩ 4.07 GΩ OK OK

Pair-4 BK 3.01 GΩ 3.57 GΩ 4.24 GΩ OK OK

WH 3.81 GΩ 4.37 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DA-04-01-04-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 70 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 04
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.35 GΩ 4.08 GΩ 5.69 GΩ OK

WH 4.33 GΩ 6.07 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# LL-04-01-01-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 83 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW COARSE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.17 GΩ 4.54 GΩ 5.96 GΩ OK OK

WH 4.78 GΩ 5.87 GΩ OK OK

Pair-2 BK 2.0 GΩ 5.1 GΩ 6.1 GΩ OK OK

WH 5.17 GΩ 6.23 GΩ OK OK

Pair-3 BK 2.42 GΩ 5.23 GΩ 6.39 GΩ OK OK

WH 5.78 GΩ 5.79 GΩ OK OK

Pair-4 BK 2.61 GΩ 5.92 GΩ 5.96 GΩ OK OK

WH 6.07 GΩ 6.13 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-19
Drawing No Tag# DA-04-01-03-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 73 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 03
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 13.0 GΩ 3.11 GΩ 4.09 GΩ OK OK

WH 3.71 GΩ 4.21 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# DA-04-01-03-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 73 M

380 LV Distribution Switchboard


Cable from Cable To, COARSE SCREEN CHANNEL 03
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 4.36 GΩ 4.12 GΩ 4.77 GΩ OK OK

WH 4.12 GΩ 5.01 GΩ OK OK

Pair-2 BK 1.47 GΩ 4.50 GΩ 4.85 GΩ OK OK

WH 1.76 GΩ 4.30 GΩ OK OK

Pair-3 BK 2.0 GΩ 2.50 GΩ 4.73 GΩ OK OK

WH 2.55 GΩ 4.90 GΩ OK OK

Pair-4 BK 2.26 GΩ 2.85 GΩ 4.2 GΩ OK OK

WH 2.91 GΩ 4.01 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-19
Drawing No Tag# DT-04-01-02-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 75 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 02
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.87 GΩ 3.28 GΩ 3.94 GΩ OK

WH 3.11 GΩ 4.07 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020214
Drawing No Tag# DT-04-01-02-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 76 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 02
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.12 GΩ 4.64 GΩ 6.22 GΩ OK

WH 4.70 GΩ 5.79 GΩ OK

Pair-2 BK 1.92 GΩ 3.84 GΩ 5.51 GΩ OK

WH 3.91 GΩ 5.64 GΩ OK

Pair-3 BK 2.62 GΩ 2.87 GΩ 6.17 GΩ OK

WH 3.29 GΩ 5.94 GΩ OK

Pair-4 BK 2.63 GΩ 3.85 GΩ 5.47 GΩ OK

WH 5.32 GΩ 6.09 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020214
Drawing No Tag# LL-04-01-02-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 73 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW COARSE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 2.96 GΩ 4.55 GΩ OK

WH 4.82 GΩ OK

Pair-2 BK 5.40 GΩ 3.91 GΩ OK

WH 2.83 GΩ OK

Pair-3 BK 2.64 GΩ 4.19 GΩ OK

WH 4.78 GΩ OK

Pair-4 BK 2.08 GΩ 2.92 GΩ OK

WH 2.71 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-19
Drawing No Tag# LL-04-02-02-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 70 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW FINE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.73 GΩ 5.30 GΩ 5.96 GΩ OK OK

WH 5.06 GΩ 6.07 GΩ OK OK

Pair-2 BK 2.64 GΩ 3.28 GΩ 6.13 GΩ OK OK

WH 4.16 GΩ 5.87 GΩ OK OK

Pair-3 BK 3.21 GΩ 3.62 GΩ 5.94 GΩ OK OK

WH 3.88 GΩ 6.23 GΩ OK OK

Pair-4 BK 3.33 GΩ 5.0 GΩ 6.47 GΩ OK OK

WH 5.40 GΩ 6.59 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020214
Drawing No Tag# DT-04-01-04-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 68 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 04
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.34 GΩ 3.59 GΩ OK OK

WH 4.92 GΩ OK OK

Pair-2 BK 2.66 GΩ 3.18 GΩ OK OK

WH 3.25 GΩ OK OK

Pair-3 BK 3.29 GΩ 3.67 GΩ OK OK

WH 4.70 GΩ OK OK

Pair-4 BK 3.59 GΩ 5.36 GΩ OK OK

WH 5.13 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.2733416-19
Drawing No Tag# DT-04-01-04-ZD-- Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 68 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 04
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 5.31 GΩ 3.18 GΩ OK OK

WH 2.38 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# LL-04-02-02-ZD Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 50 M

380 LV Distribution Switchboard


Cable from Cable To, CONVEYOR SCREW FINE SCREENS
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 6.34 GΩ 6.81 GΩ 7.09 GΩ OK OK

WH 6.73 GΩ 8.18 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.16023-020214
Drawing No Tag# DT-04-01-03-RE-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 73 M

380 LV Distribution Switchboard


Cable from Cable To, FINE SCREEN CHANNEL 03
Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 10.1 GΩ 8.18 GΩ OK

WH 7.04 GΩ OK

Pair-2 BK 4.78 GΩ 4.81 GΩ OK

WH 6.22 GΩ OK

Pair-3 BK 5.36 GΩ 4.36 GΩ OK

WH 5.37 GΩ OK

Pair-4 BK 5.84 GΩ 5.89 GΩ OK

WH 6.11 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-02-VD1 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 9M

PRETREATMENT CHANNEL 2 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 47.4 GΩ 25.9 GΩ 31.1 GΩ OK OK

WH 28.8 GΩ 33.0 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-01-VD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 12 M

PRETREATMENT CHANNEL 1 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 35.2 GΩ 20.6 GΩ 25.1 GΩ OK OK

WH 18.6 GΩ 32.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-02-VD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 9M

PRETREATMENT CHANNEL 2 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 48.0 GΩ 30 GΩ 27 GΩ OK

WH 26.3 GΩ 31 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-01-VD1 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 12 M

PRETREATMENT CHANNEL 1 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 34.4 GΩ 20.3 GΩ 27 GΩ OK

WH 16.7 GΩ 34.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-03-VD1 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 6M

PRETREATMENT CHANNEL 3 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 75.2 GΩ 54.3 GΩ 41.3 GΩ OK OK

WH 33.9 GΩ 37.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CC-04-02-03-VD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 6M

PRETREATMENT CHANNEL 3 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 74.5 GΩ 51.8 GΩ 57.3 GΩ OK OK

WH 34.3 GΩ 45.7 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-8
Drawing No Tag# CM-04-01-04-VD1 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 4 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 99.8 GΩ 83.1 GΩ 35.2 GΩ OK OK

WH 28.7 GΩ 39.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CM-04-01-04-VD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 4 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 50.4 GΩ 54.2 GΩ 47.1 GΩ OK

WH 33.1 GΩ 41.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CM-04-01-05-VD1 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 16 M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 5 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 27.3 GΩ 19.6 GΩ 27.3 GΩ OK

WH 10.6 GΩ 23.1 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 2733416-10
Drawing No Tag# CM-04-01-05-VD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL 500V - 1P x


Cable Size & Types 1.50 Length 16 M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 5 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 28.3 GΩ 21.0 GΩ 26.1 GΩ OK

WH 10.1 GΩ 29.1 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# 04-JBD-08-VD-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 100 M

PRETREATMENT MAIN SYSTEM


Cable from Cable To, PRETREATMENT JB DIGITAL
CONTROL PANEL (PART 2)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 2.14 GΩ 2.29 GΩ OK OK

WH 2.85 GΩ OK OK

Pair-2 BK 836 GΩ 1.63 GΩ OK OK

WH 2.04 GΩ OK OK

Pair-3 BK 1.29 GΩ 1.84 GΩ OK OK

WH 1.89 GΩ OK OK

Pair-4 BK 1.46 GΩ 3.00 GΩ OK OK

WH 3.58 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # MD-04-01-02-JB-ZD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 56 M

PRETREATMENT MAIN SYSTEM


Cable from Cable To, DEGRITTING BRIDGE 2 JB
CONTROL PANEL (PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 3.58 G Ω 116 G Ω


WH 214 G Ω
Pair-2 BK 3.21 G Ω 288 G Ω
WH 309 G Ω
Pair-3 BK 3.18 G Ω 534 G Ω
WH 534 G Ω
Pair-4 BK 2.88 G Ω 42.4 G Ω
WH 4.07 G Ω
Pair-5 BK 2.34 G Ω 2.97 G Ω
WH 3.88 G Ω
Pair-6 BK 2.25 G Ω 3.53 G Ω
WH 3.35 G Ω
Pair-7 BK 2.49 G Ω 3.88 G Ω
WH 4.47 G Ω
Pair-8 BK 2.46 G Ω 4.47 G Ω
WH 4.24 G Ω

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No.
Drawing No Tag# MD-04-01-05-JB-ZD2 Date 3/4/2024

PVC/OSH/PVC/PVC FRSL
Cable Size & Types 500V - 1P x 1.50 Length 41 M

PRETREATMENT MAIN SYSTEM


Cable from Cable To, DEGRITTING BRIDGE 5 JB
CONTROL PANEL (PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 9.83 GΩ 5.38 GΩ OK OK

WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MD-04-01-04-JB-ZD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 44 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL
Cable from (PART 1) Cable To, DEGRITTING BRIDGE 4 JB
CONTROL PANEL (PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 10.4 G Ω 11.7 G Ω OK OK

WH 1209 G Ω OK OK

Pair-2 BK 6.98 G Ω 7.31 G Ω OK OK

WH 8.25 G Ω OK OK

Pair-3 BK 7.27 G Ω 7.13 G Ω OK OK

WH 8.23 G Ω OK OK

Pair-4 BK 7.37 G Ω 9.25 G Ω OK OK

WH 8.83 G Ω OK OK

Pair-5 BK 6.67 G Ω 8.72 G Ω OK OK

WH 8.81 G Ω OK OK

Pair-6 BK 6.96 G Ω 8.87 G Ω OK OK

WH 9.10 G Ω OK OK

Pair-7 BK 7.43 G Ω 9.52 G Ω OK OK

WH 9.59 G Ω OK OK

Pair-8 BK 6.71 G Ω 9.31 G Ω OK OK

WH 9.64 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020224
Drawing No Tag # 04-GZ-01-ZC2M Date 3/4/2024
Cable Size & Types PVC/ISH/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 100 M

Cable from PRETREATMENT METRING SYSTEM PANEL Cable To, PRETREATMENT METERING ANALYZER SHELTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 439 MΩ 109 GΩ OK OK

WH 95.3 GΩ OK OK

Pair-2 BK 530 MΩ 43.3 GΩ OK OK

WH 25.3 GΩ OK OK

Pair-3 BK 564 MΩ 33.3 GΩ OK OK

WH 26.3GΩ OK OK

Pair-4 BK 642 MΩ 4.69 GΩ OK OK

WH 2.63 GΩ OK OK

Pair-5 BK 579 MΩ 90.6 GΩ OK OK

WH 46.8 GΩ OK OK

Pair-6 BK 740Ω 37.6 GΩ OK OK

WH 15.2 GΩ OK OK

Pair-7 BK 504 MΩ 30.7 GΩ OK OK

WH 21.0 GΩ OK OK

Pair-8 BK 520 MΩ 43.2 GΩ OK OK

WH 19.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MD-04-01-03-JB-ZD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 17 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 3 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 143 GΩ 16.3 GΩ 18.0 GΩ OK OK

WH 18.5 GΩ 24.2 GΩ OK OK

Pair-2 BK 12.9 GΩ 11.6 GΩ 15.9 GΩ OK OK

WH 13.1 GΩ 19.4 GΩ OK OK

Pair-3 BK 13.7 GΩ 13.9 GΩ 14.0 GΩ OK OK

WH 13.1 GΩ 14.4 GΩ OK OK

Pair-4 BK 13.4 GΩ 14.8 GΩ 20.1 GΩ OK OK

WH 14.5 GΩ 14.2 GΩ OK OK

Pair-5 BK 11.3 GΩ 12.7 GΩ 17.4 GΩ OK OK

WH 12.8 GΩ 13.0 GΩ OK OK

Pair-6 BK 10.3 GΩ 10.2 GΩ 15.4 GΩ OK OK

WH 10.8 GΩ 12.1 GΩ OK OK

Pair-7 BK 10.1 GΩ 9.77 GΩ 10.6 GΩ OK OK

WH 9.69 GΩ 11.2 GΩ OK OK

Pair-8 BK 9.55 GΩ 11.1 GΩ 17.5 GΩ OK OK

WH 11.5 GΩ 19.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MD-04-01-05-JB-ZD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 17 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 5 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.3 GΩ 14.5 GΩ OK OK

WH 16.0 GΩ OK OK

Pair-2 BK 10.9 GΩ 9.90 GΩ OK OK

WH 10.9 GΩ OK OK

Pair-3 BK 9.58 GΩ 9.71 GΩ OK OK

WH 10.9 GΩ OK OK

Pair-4 BK 9.82 GΩ 9.71 GΩ OK OK

WH 10.9 GΩ OK OK

Pair-5 BK 9.10 GΩ 11.9 GΩ OK OK

WH 14.3 GΩ OK OK

Pair-6 BK 9.88 GΩ 14.1 GΩ OK OK

WH 14.5 GΩ OK OK

Pair-7 BK 9.83 GΩ 15.2 GΩ OK OK

WH 15.1 GΩ OK OK

Pair-8 BK 9.28 GΩ 14.7 GΩ OK OK

WH 14.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # NB-04-01-04-VD2 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, 380 LV Distribution Switchboard Transformer 1 Incomer
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 11.7 GΩ 6.45 GΩ 7.20 GΩ OK OK

WH 16.0 GΩ 9.51 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # LL-04-02-01-VD2 Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, 380 LV Distribution Switchboard Transformer 1 Incomer
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.2 GΩ 7.88 GΩ 9.40 GΩ OK OK

WH 6.64 GΩ 4.61 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # 04-GZ-01-VD-M- Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 101 M

PRETREATMENT METERING
Cable from PRETREATMENT METRING SYSTEM PANEL Cable To,
ANALYZER SHELTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 2.49 GΩ 4.54 GΩ OK OK

WH 5.63 GΩ OK OK

Pair-2 BK 2.56 GΩ 3.89 GΩ OK OK

WH 4.97 GΩ OK OK

Pair-3 BK 3.13 GΩ 5.35 GΩ OK OK

WH 5.95 GΩ OK OK

Pair-4 BK 3.67 GΩ 5.63 GΩ OK OK

WH 6.09 GΩ OK OK

Pair-5 BK 2.30 GΩ 4.35 GΩ OK OK

WH 4.45 GΩ OK OK

Pair-6 BK 792 MΩ 3.63 GΩ OK OK

WH 4.22 GΩ OK OK

Pair-7 BK 2.19 GΩ 3.99 GΩ OK OK

WH 4.65 GΩ OK OK

Pair-8 BK 2.71 GΩ 4.75 GΩ OK OK

WH 4.75 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # MD-04-01-01-JB-ZD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 56 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL DEGRITTING BRIDGE 1 JB


Cable from Cable To,
(PART 1) ANALYZER SHELTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 1.36 MΩ 1.80 GΩ OK OK

WH 2.26 GΩ OK OK

Pair-2 BK 986 MΩ 2.44 GΩ OK OK

WH 2.80 GΩ OK OK

Pair-3 BK 1.01 GΩ 2.87 GΩ OK OK

WH 3.18 GΩ OK OK

Pair-4 BK 951 MΩ 2.93 GΩ OK OK

WH 3.12 GΩ OK OK

Pair-5 BK 769 MΩ 2.95 GΩ OK OK

WH 3.17 GΩ OK OK

Pair-6 BK 754 MΩ 3.38 GΩ OK OK

WH 3.63 GΩ OK OK

Pair-7 BK 801 MΩ 3.41 GΩ OK OK

WH 3.84 GΩ OK OK

Pair-8 BK 780 MΩ 3.89 GΩ OK OK

WH 4.44 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020205
Drawing No Tag# 04-GZ-01-ZC-1M Date 3/4/2024

PVC/ISH/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 99 M

PRETREATMENT METRING SYSTEM PRETREATMENT METERING ANALYZER


Cable from Cable To,
PANEL SHELTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 828 MΩ 37.9 GΩ OK OK

WH 38.3 GΩ OK OK

Pair-2 BK 849 MΩ 46.9 GΩ OK OK

WH 43.3 GΩ OK OK

Pair-3 BK 727 MΩ 74.9 GΩ OK OK

WH 51.6 GΩ OK OK

Pair-4 BK 725 MΩ 51.6 GΩ OK OK

WH 5.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # QW-04-01-01-VD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 17 M
380 LV Distribution Switchboard
PRETREATMENT MAIN SYSTEM CONTROL PANEL
Cable from Cable To, Transformer 1 Incomer
(PART 2)
ANALYZER SHELTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 29.8 GΩ 33.1 GΩ 33.1 GΩ OK OK

WH 29 GΩ 31.2 GΩ OK OK

Pair-2 BK 27.2 GΩ 28.1 GΩ 32.5 GΩ OK OK

WH 27.2 GΩ 34.2 GΩ OK OK

Pair-3 BK 27.2 GΩ 26.5 GΩ 36.1 GΩ OK OK

WH 31.7 GΩ 35.2 GΩ OK OK

Pair-4 BK 26.5 GΩ 27.5 GΩ 35.4 GΩ OK OK

WH 28.7 GΩ 36.1 GΩ OK OK

Pair-5 BK 24.7 GΩ 31.5 GΩ 37.0 GΩ OK OK

WH 33.1 GΩ 33.1 GΩ OK OK

Pair-6 BK 21.2 GΩ 32.7 GΩ 33.7 GΩ OK OK

WH 33.2 GΩ 36.2 GΩ OK OK

Pair-7 BK 22.8 GΩ 36.1 GΩ 33.7 GΩ OK OK

WH 34.2 GΩ 36.1 GΩ OK OK

Pair-8 BK 21.4 GΩ 24.5 GΩ 35.3 GΩ OK OK

WH 27 GΩ 37.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # QW-04-01-02-VD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 17 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 18.3 GΩ 42 GΩ 29 GΩ OK OK

WH 49 GΩ 33.1GΩ OK OK

Pair-2 BK 26.8 GΩ 29 GΩ 35.2 GΩ OK OK

WH 33.1 GΩ 33.2 GΩ OK OK

Pair-3 BK 26 GΩ 35.5 GΩ 36.5 GΩ OK OK

WH 33.1 GΩ 31.5 GΩ OK OK

Pair-4 BK 27.8 GΩ 36.5 GΩ 32.7 GΩ OK OK

WH 35.5 GΩ 36.1 GΩ OK OK

Pair-5 BK 24.9 GΩ 33.1 GΩ 29.2 GΩ OK OK

WH 39.1 GΩ 35.3 GΩ OK OK

Pair-6 BK 21.5 GΩ 31.7 GΩ 33.2 GΩ OK OK

WH 32.7 GΩ 36.1 GΩ OK OK

Pair-7 BK 27.2 GΩ 35.2 GΩ 32.4 GΩ OK OK

WH 37.1 GΩ 37.3 GΩ OK OK

Pair-8 BK 25.5 GΩ 36.1 GΩ 36.2 GΩ OK OK

WH 31.7 GΩ 33.1GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # QW-04-01-03-VD1M Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 17 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 29.8 GΩ 40.5 GΩ 25.9 GΩ OK OK

WH 45.8 GΩ 30.7 GΩ OK OK

Pair-2 BK 20.2 GΩ 23 GΩ 33.1 GΩ OK OK

WH 24.4 GΩ 27.3 GΩ OK OK

Pair-3 BK 22.6 GΩ 31.7 GΩ 28.5 GΩ OK OK

WH 35.5 GΩ 30.3 GΩ OK OK

Pair-4 BK 22.6 GΩ 36.5 GΩ 33.2 GΩ OK OK

WH 39.1 GΩ 36.2 GΩ OK OK

Pair-5 BK 21.1 GΩ 33.1 GΩ 33.1 GΩ OK OK

WH 26.6 GΩ 35.2 GΩ OK OK

Pair-6 BK 20.8 GΩ 38.3 GΩ 37 GΩ OK OK

WH 35.5 GΩ 33.6 GΩ OK OK

Pair-7 BK 22.5 GΩ 36.5 GΩ 27.3 GΩ OK OK

WH 33.1 GΩ 29.7 GΩ OK OK

Pair-8 BK 20.8 GΩ 39.1 GΩ 32.3 GΩ OK OK

WH 33.1 GΩ 35.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# 04-CJA-11.02-VD-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 17 M

PRETREATMENT MAIN SYSTEM PRETREATMENT MAIN SYSTEM CONTROL


Cable from Cable To,
CONTROL PANEL (PART 1) PANEL (PART 2)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 20.2 GΩ 27.3 GΩ 23.7 GΩ OK OK

WH 26.12 GΩ 20.5 V OK OK

Pair-2 BK 30.3 GΩ 24.2 GΩ 21.4 GΩ OK OK

WH 25 GΩ 17.9 GΩ OK OK

Pair-3 BK 20.3 GΩ 20.1 GΩ 19.1 GΩ OK OK

WH 19.3 GΩ 17.9 GΩ OK OK

Pair-4 BK 18.9 GΩ 21.4 GΩ 20.5 GΩ OK OK

WH 19.6 GΩ 19.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum No. 16023-020214
Drawing No Tag# 04-BRV-11-ZD-M Date 3/4/2024

PVC/OSH/PVC/PVC FRLS
Cable Size & Types 500V - 4P x 1.50 Length 20 M

PRETREATMENT MAIN SYSTEM


Cable from Cable To, pretreatment UPS
CONTROL PANEL (PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 BK 27.3 GΩ 24.9 GΩ 28.5 GΩ OK OK

WH 25.1 GΩ 33.5 GΩ OK OK

Pair-2 BK 17.7 GΩ 23 GΩ 31.7 GΩ OK OK

WH 24.4 GΩ 33.1 GΩ OK OK

Pair-3 BK 16 GΩ 26.12 GΩ 35.5 GΩ OK OK

WH 25.09 GΩ 39.1 GΩ OK OK

Pair-4 BK 18.3 GΩ 27.1 GΩ 33.1 GΩ OK OK

WH 26.8 GΩ 27.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # LSH-04-03-01-VD Date 3/4/2024
PVC/OSH/PVC/PVC FRSL
Cable Size & Types Length 10 M
500V - 1P x 1.50

Cable from PRETREATMENT JB DIGITAL Cable To, SCREW COMPACTOR LEVEL DETECTOR

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 55.5 GΩ 51.0 GΩ 62.1 GΩ OK OK

WH 14.8 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # LSH-04-03-02-VD Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 10 M

Cable from PRETREATMENT JB DIGITAL Cable To, SCREW COMPACTOR LEVEL DETECTOR

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 37.6 GΩ 26.4 GΩ OK OK

WH 17.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020228
Drawing No Tag # AIT-04-01-08-RB-M Date 3/4/2024
Cable Size & Types 2CX2.5 mm2, CU/XLPE/PVC/PVC Length 107 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 81 GΩ OK

RD-GND 86.5 GΩ OK

BK-GND 102 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020228
Drawing No Tag # AIT-04-01-09-RB-M Date 3/4/2024
Cable Size & Types 2CX2.5 mm2, CU/XLPE/PVC/PVC Length 107 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 80.5 GΩ OK

RD-GND 93.9 GΩ OK

BK-GND 88.8 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # LSH-04-03-03-VD-- Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 10 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 56.7 GΩ 43.9 GΩ 37.2 GΩ OK OK

WH 16 GΩ 42.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # LSH-04-03-04-VD-- Date 3/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 10 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 59.3 GΩ 47.3 GΩ 39.1 GΩ OK OK

WH 15.3 GΩ 36.7 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020228
Drawing No Tag # AIT-04-03-02-RB-M Date 3/4/2024
Cable Size & Types 2CX2.5 mm2, CU/XLPE/PVC/PVC Length 59 M

Cable from Primary clarifiers and Biological MCC Cable To, Submersible Mixer LUCAS 3C

Test Voltage __________1000v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________600/1000v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD-BK 139 GΩ OK

RD-GND 163 GΩ OK

BK-GND 144 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # DS-04-01-02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 41.2 GΩ 29.5 GΩ 39.4 GΩ OK OK

WH 34.1 GΩ 35.4 GΩ OK OK

Pair-2 BK 22.6 GΩ 21.0 GΩ 22.5 GΩ OK OK

WH 21.2 GΩ 22.4 GΩ OK OK

Pair-3 BK 24.7 GΩ 24.9 GΩ 29.5 GΩ OK OK

WH 24.6 GΩ 29.1 GΩ OK OK

Pair-4 BK 22.9 GΩ 26.4 GΩ 25.6 GΩ OK OK

WH 26.2 GΩ 27.0 GΩ OK OK

Pair-5 BK 20.0 GΩ 24.0 GΩ 25.1 GΩ OK OK

WH 24.4 GΩ 25.8 GΩ OK OK

Pair-6 BK 21.2 GΩ 24.3 GΩ 29.1 GΩ OK OK

WH 25.4 GΩ 26.5 GΩ OK OK

Pair-7 BK 22.0 GΩ 24.7 GΩ 29.4 GΩ OK OK

WH 23.9 GΩ 29.1 GΩ OK OK

Pair-8 BK 21.6 GΩ 27.0 GΩ 28.9 GΩ OK OK

WH 26.4 GΩ 28.4 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MO-04-01-01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 29.0 GΩ 35.2 GΩ 34.5 GΩ OK OK

WH 43.2 GΩ 44.6 GΩ OK OK

Pair-2 BK 23.4 GΩ 21.0 GΩ 25.6 GΩ OK OK

WH 23.8 GΩ 24.7 GΩ OK OK

Pair-3 BK 21.2 GΩ 24.6 GΩ 20.2 GΩ OK OK

WH 28.1 GΩ 27.4 GΩ OK OK

Pair-4 BK 22.6 GΩ 29.6 GΩ 29.6 GΩ OK OK

WH 35.0 GΩ 32.5 GΩ OK OK

Pair-5 BK 20.4 GΩ 27.6 GΩ 28.4 GΩ OK OK

WH 31.3 GΩ 32.5 GΩ OK OK

Pair-6 BK 19.1 GΩ 25.9 GΩ 20.0 GΩ OK OK

WH 30.6 GΩ 32.1 GΩ OK OK

Pair-7 BK 22.7 GΩ 25.4 GΩ 27.5 GΩ OK OK

WH 30.6 GΩ 32.5 GΩ OK OK

Pair-8 BK 21.4 GΩ 24.8 GΩ 25.2 GΩ OK OK

WH 27.5 GΩ 28.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # DS-04-01-01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 68 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 18.8 GΩ 20.4 GΩ 12.8 GΩ OK OK

WH 7.48 GΩ 9.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # QW-04-01-02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 28 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.5 GΩ 13.4 GΩ 15.5 GΩ OK OK

WH 9.65 GΩ 11.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # LL-04-02-02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 16.1 GΩ 12 GΩ 19.1 GΩ OK OK

WH 5.92 GΩ 17.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # DA-04-01-04-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 15.0 GΩ 9.39 GΩ 10.9 GΩ OK OK

WH 7.37 GΩ 9.35 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # LL-04-01-01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 11.4 GΩ 6.8 GΩ 9.3 GΩ OK OK

WH 5.43 GΩ 11.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # DT-04-01-01-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 15.4 GΩ 25.9 GΩ 26.5 GΩ OK OK

WH 33.1 GΩ 25.4 GΩ OK OK

Pair-2 BK 14.9 GΩ 18.6 GΩ 27.3 GΩ OK OK

WH 23.6 GΩ 24.1 GΩ OK OK

Pair-3 BK 16.1 GΩ 19.6 GΩ 29.9 GΩ OK OK

WH 25.4 GΩ 27.8 GΩ OK OK

Pair-4 BK 14.9 GΩ 25.9 GΩ 30.4 GΩ OK OK

WH 16.2 GΩ 24.5 GΩ OK OK

Pair-5 BK 16.1 GΩ 18.9 GΩ 25.1 GΩ OK OK

WH 23.5 GΩ 26.5 GΩ OK OK

Pair-6 BK 15.4 GΩ 19.9 GΩ 27.9 GΩ OK OK

WH 25.5 GΩ 26.3 GΩ OK OK

Pair-7 BK 13.3 GΩ 33.6 GΩ 27.1 GΩ OK OK

WH 25.6 GΩ 29.5 GΩ OK OK

Pair-8 BK 14.9 GΩ 16.3 GΩ 24.3 GΩ OK OK

WH 19.2 GΩ 28.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # DT-04-01-02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 19.1 GΩ 21.2 GΩ 28.6 GΩ OK OK

WH 21.6 GΩ 30.7 GΩ OK OK

Pair-2 BK 19.5 GΩ 21.3 GΩ 31.2 GΩ OK OK

WH 29.6 GΩ 29.6 GΩ OK OK

Pair-3 BK 20.4 GΩ 20.4 GΩ 30.2 GΩ OK OK

WH 20.6 GΩ 31.2 GΩ OK OK

Pair-4 BK 19.1 GΩ 23.4 GΩ 29.8 GΩ OK OK

WH 25.1 GΩ 31.2 GΩ OK OK

Pair-5 BK 19.5 GΩ 21.6 GΩ 33.2 GΩ OK OK

WH 29.5 GΩ 29.5 GΩ OK OK

Pair-6 BK 22.6 GΩ 21.4 GΩ 33.4 GΩ OK OK

WH 20.3 GΩ 31.6 GΩ OK OK

Pair-7 BK 20.4 GΩ 23.6 GΩ 30.2 GΩ OK OK

WH 21.5 GΩ 31.5 GΩ OK OK

Pair-8 BK 20.2 GΩ 20.4 GΩ 33.6 GΩ OK OK

WH 25.7 GΩ 32.7 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # DA-04-01-04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 31 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 18.7 GΩ 28.3 GΩ 34.3 GΩ OK OK

WH 37.4 GΩ 33.1 GΩ OK OK

Pair-2 BK 24.7 GΩ 23.6 GΩ 31.2 GΩ OK OK

WH 22.4 GΩ 35.6 GΩ OK OK

Pair-3 BK 16.8 GΩ 24.6 GΩ 37.4 GΩ OK OK

WH 17.6 GΩ 31.5 GΩ OK OK

Pair-4 BK 15.9 GΩ 19.6 GΩ 33.2 GΩ OK OK

WH 18.4 GΩ 30.1 GΩ OK OK

Pair-5 BK 14.9 GΩ 37.8 GΩ 34.6 GΩ OK OK

WH 24.9 GΩ 32.6 GΩ OK OK

Pair-6 BK 24.7 GΩ 21.4 GΩ 38.5 GΩ OK OK

WH 19.6 GΩ 35.6 GΩ OK OK

Pair-7 BK 15.9 GΩ 28.5 GΩ 33.9 GΩ OK OK

WH 25.4 GΩ 31.4 GΩ OK OK

Pair-8 BK 16.8 GΩ 22.1 GΩ 32.1 GΩ OK OK

WH 25.7 GΩ 34.6 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # MO-04-01-02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 25 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.4 GΩ 39.6 GΩ 41.2 GΩ OK OK

WH 34.2 GΩ 40.6 GΩ OK OK

Pair-2 BK 26.6 GΩ 47 GΩ 39.5 GΩ OK OK

WH 39.2 GΩ 38.4 GΩ OK OK

Pair-3 BK 27.9 GΩ 27.4 GΩ 37.5 GΩ OK OK

WH 30.5 GΩ 33.4 GΩ OK OK

Pair-4 BK 23.8 GΩ 26.5 GΩ 39.6 GΩ OK OK

WH 35.1 GΩ 39.4 GΩ OK OK

Pair-5 BK 19.3 GΩ 30.1 GΩ 37.6 GΩ OK OK

WH 29.7 GΩ 38.6 GΩ OK OK

Pair-6 BK 25.4 GΩ 36.6 GΩ 36.4 GΩ OK OK

WH 34.2 GΩ 37.5 GΩ OK OK

Pair-7 BK 27.9 GΩ 32.1 GΩ 38.2 GΩ OK OK

WH 35.1 GΩ 39.1 GΩ OK OK

Pair-8 BK 28.8 GΩ 39.2 GΩ 42.1 GΩ OK OK

WH 26.8 GΩ 41.7 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # DT-04-01-03-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.3 GΩ 7.51 GΩ 12.3 GΩ OK OK

WH 7.01 GΩ 12.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # DT-04-01-01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 13.4 GΩ 7.7 GΩ OK

WH 6.73 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # NB-04-01-02-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 23.9 GΩ 32.3 GΩ OK OK

WH 37.9 GΩ OK OK

Pair-2 BK 22.7 GΩ 20.7 GΩ OK OK

WH 21.3 GΩ OK OK

Pair-3 BK 20.8 GΩ 24.5 GΩ OK OK

WH 26.1 GΩ OK OK

Pair-4 BK 21.9 GΩ 27.8 GΩ OK OK

WH 28.4 GΩ OK OK

Pair-5 BK 20.4 GΩ 27.2 GΩ OK OK

WH 28.0 GΩ OK OK

Pair-6 BK 19.7 GΩ 25.8 GΩ OK OK

WH 24.7 GΩ OK OK

Pair-7 BK 22.6 GΩ 24.7 GΩ OK OK

WH 23.5 GΩ OK OK

Pair-8 BK 22.3 GΩ 24.1 GΩ OK OK

WH 22.8 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # DA-04-01-01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 8.43 GΩ 12.1 GΩ OK

WH 6.28 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-13
Drawing No Tag # NB-04-01-02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.3 GΩ 8.53 GΩ OK

WH 5.33 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020207
Drawing No Tag # NB-04-01-03-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 14.8 GΩ 20.5 GΩ OK

WH 23.7 GΩ OK

Pair-2 BK 13.1 GΩ 12.8 GΩ OK

WH 14.2 GΩ OK

Pair-3 BK 11.4 GΩ 16.2 GΩ OK

WH 19.3 GΩ OK

Pair-4 BK 11.7 GΩ 20.1 GΩ OK

WH 21.4 GΩ OK

Pair-5 BK 11.1 GΩ 19.6 GΩ OK

WH 20.5 GΩ OK

Pair-6 BK 10.7 GΩ 17.9 GΩ OK

WH 19.1 GΩ OK

Pair-7 BK 12.9 GΩ 17.2 GΩ OK

WH 20.3 GΩ OK

Pair-8 BK 11.9 GΩ 14.7 GΩ OK

WH 16.9 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # NB-04-01-04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 20.7 GΩ 30 GΩ OK

WH 33 GΩ OK

Pair-2 BK 21.0 GΩ 17.7 GΩ OK

WH 20.6 GΩ OK

Pair-3 BK 17.9 GΩ 21.5 GΩ OK

WH 24.6 GΩ OK

Pair-4 BK 17.4 GΩ 24.2 GΩ OK

WH 25.1 GΩ OK

Pair-5 BK 17.3 GΩ 24.1 GΩ OK

WH 25.9 GΩ OK

Pair-6 BK 16.3 GΩ 25.2 GΩ OK

WH 25.1 GΩ OK

Pair-7 BK 20.7 GΩ 24.4 GΩ OK

WH 21.8 GΩ OK

Pair-8 BK 19.9 GΩ 20.8 GΩ OK

WH 21.0 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # NB-04-01-05-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.1 GΩ 7.89 GΩ OK

WH 5.75 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # DT-04-01-04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 30 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 1) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.1 GΩ 40.5 GΩ OK OK

WH 25.4 GΩ OK OK

Pair-2 BK 25 GΩ 27.1 GΩ OK OK

WH 28.4 GΩ OK OK

Pair-3 BK 25.2 GΩ 26.3 GΩ OK OK

WH 25.6 GΩ OK OK

Pair-4 BK 26.6 GΩ 24.1 GΩ OK OK

WH 23.3 GΩ OK OK

Pair-5 BK 19.1 GΩ 24.1 GΩ OK OK

WH 28.3 GΩ OK OK

Pair-6 BK 26.6 GΩ 26.3 GΩ OK OK

WH 25.6 GΩ OK OK

Pair-7 BK 25 GΩ 25.4 GΩ OK OK

WH 27.1 GΩ OK OK

Pair-8 BK 25.2 GΩ 28.4 GΩ OK OK

WH 40.5 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 16023-020206
Drawing No Tag # QW-04-01-04-VD1M Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 26 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard


Cable from Cable To,
(PART 2) Transformer 1 Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 28.5 GΩ 39.1 GΩ OK OK

WH 46.8 GΩ OK OK

Pair-2 BK 27.9 GΩ 35.0 GΩ OK OK

WH 40 GΩ OK OK

Pair-3 BK 24.7 GΩ 27 GΩ OK OK

WH 32.8 GΩ OK OK

Pair-4 BK 23.4 GΩ 39.1 GΩ OK OK

WH 35 GΩ OK OK

Pair-5 BK 19 GΩ 27.1 GΩ OK OK

WH 31.4 GΩ OK OK

Pair-6 BK 24.7 GΩ 25.8 GΩ OK OK

WH 29.4 GΩ OK OK

Pair-7 BK 27.9 GΩ 27.1 GΩ OK OK

WH 46.8 GΩ OK OK

Pair-8 BK 28.5 GΩ 32.8 GΩ OK OK

WH 27 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-01-02-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 2 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 111 GΩ 45.9 GΩ 49 GΩ OK

WH 51.1 GΩ 54 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-01-02-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 2 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 105 GΩ 43 GΩ 47 GΩ OK

WH 37 GΩ 52 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MD-04-01-04-JB-ZD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 42 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 4 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 WH 10.6 GΩ 5.56 GΩ 4.99 GΩ OK OK

BK 5.96 GΩ 2.91 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MD-04-01-03-JB-ZD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 57 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 3 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 12.0 GΩ 7.01 GΩ 5.2 GΩ OK OK

WH 3.40 GΩ 4.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-8
Drawing No Tag # LT-04-01-01-ZC Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 108 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL DEGRITTING INLET CHANNEL LEVEL


Cable from Cable To,
(PART 1) TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.45 GΩ OK

WH 2.06 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # AIT-04-01-09-ZC Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 105 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, AUTOSAMPLER
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.23 GΩ 2.03 GΩ


WH 2.44 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # AIT-04-01-08-ZC Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 107 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, AUTOSAMPLER
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 4.01 GΩ
WH

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # AIT-04-03-02-ZC Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 68 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, AUTOSAMPLER
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.31 GΩ 4.69 GΩ


WH 2.86 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733146 -13
Drawing No Tag # AIT-04-03-01-ZC Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 68 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, AUTOSAMPLER
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 6.44 GΩ 4.70 GΩ 3.11 GΩ OK OK

WH 2.84 GΩ 2.71 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # MD-04-01-01-JB-ZD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 56 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 1 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 9.35 GΩ 5.09 GΩ 4.28 GΩ OK

WH 4.79 GΩ 8.99 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-19
Drawing No Tag # MD-04-01-02-JB-ZD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 56 M

PRETREATMENT MAIN SYSTEM CONTROL PANEL


Cable from Cable To, DEGRITTING BRIDGE 2 JB
(PART 1)

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 11.7 GΩ 5.40 GΩ


WH 6.05 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-02-05-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 5M

PRETREATMENT CHANNEL 5 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 70.2 GΩ 48.9 GΩ 51 GΩ OK OK

WH 34.5 GΩ 47.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-02-05-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 5M

PRETREATMENT CHANNEL 5 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 72.5 GΩ 39.7 GΩ OK OK

WH 40.9 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-02-04-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

PRETREATMENT CHANNEL 4 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 42 GΩ 26.4 GΩ 31 GΩ OK OK

WH 20.7 GΩ 29 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CC-04-02-04-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

PRETREATMENT CHANNEL 2 OUTLET


Cable from PRETREATMENT JB DIGITAL Cable To,
GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 45.8 GΩ 31.3 GΩ 36 GΩ OK OK

WH 20.1 GΩ 33.1 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # LT-04-01-05-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB ANALOGIC Cable To, COARSE SCREEN 04 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 25.9 GΩ 17 GΩ 10.9 GΩ OK

WH 13.6 GΩ 13 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-02-05-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 10 M

Cable from PRETREATMENT JB ANALOGIC Cable To, FINE SCREEN 04 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 37.5 GΩ 23.8 GΩ 22 GΩ OK

WH 17.6 GΩ 17.6 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-02-04-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB ANALOGIC Cable To, FINE SCREEN 03 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 58 GΩ 36.8 GΩ 37 GΩ OK OK

WH 30.3 GΩ 33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-01-04-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB ANALOGIC Cable To, COARSE SCREEN 03 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 26.3 GΩ 16.3 GΩ 21 GΩ OK OK

WH 13.3 GΩ 25.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-02-02-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 8M

Cable from PRETREATMENT JB ANALOGIC Cable To, FINE SCREEN 01 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 42 GΩ 23.2 GΩ 25 GΩ OK OK

WH 21 GΩ 22 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-01-02-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 5M

Cable from PRETREATMENT JB ANALOGIC Cable To, COARSE SCREEN 01 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.4 GΩ 12.2 GΩ 14 GΩ OK OK

WH 12.2 GΩ 11 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-01-03-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB ANALOGIC Cable To, COARSE SCREEN 02 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 21.9 GΩ 13.3 GΩ 17 GΩ OK OK

WH 16.5 GΩ 15 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # LT-04-02-03-ZC- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 8M

Cable from PRETREATMENT JB ANALOGIC Cable To, FINE SCREEN 02 LEVEL TRANSMITTER

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 62.9 GΩ 33.7 GΩ 34 GΩ OK OK

WH 39.2 GΩ 33 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-05-VD1- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 5 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 70 GΩ 47.3 GΩ 42 GΩ OK OK

WH 31.5 GΩ 44 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-04-VD2- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 4 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 44.3 GΩ 30.7 GΩ OK OK

WH 20.3 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-04-VD1- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 9M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 4 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 45.4 GΩ 30.2 GΩ 33 GΩ OK OK

WH 20.5 GΩ 35 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-05-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 5 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 100 GΩ 39.4 GΩ OK OK

WH 40.2 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-01-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 1 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 73.8 GΩ 40.1 GΩ 47 GΩ OK

WH 43.5 GΩ 51 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CC-04-01-01-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT CHANNEL 1 INLET GATE

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 73.89 GΩ 40.1 GΩ 47 GΩ OK

WH 43.5 GΩ 51 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-19
Drawing No Tag # DT-04-01-03-ZD- Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 73 M

380 LV Distribution Switchboard Transformer 1


Cable from Cable To, FINE SCREEN CHANNEL 03
Incomer

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.17 GΩ 5.29 GΩ OK

WH 2.81 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CM-04-01-03-VD2 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 3 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 33.3 GΩ 26.2 GΩ 20.4 GΩ OK

WH 12.1 GΩ 16.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CM-04-01-03-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 3 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 32.6 GΩ 25.3 GΩ 19.5 GΩ OK OK

WH 11.9 GΩ 11.09 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No 2733416-10
Drawing No Tag # CM-04-01-02-VD1 Date 4/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, DEGRITTING CHANNEL 2 INLET PENSTOCK

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 389.7 GΩ 66.6 GΩ 33.4 GΩ OK

WH 34.2 GΩ 35.29 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # NB-04-01-01-VD1M Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRLS 500V - 8P x 1.50 Length 32 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 22.2 G Ω 32 G Ω 35 G Ω OK OK

WH 38.4 G Ω 38 G Ω OK OK

Pair-2 BK 23.3G Ω 19.3 G Ω 20.4 G Ω OK OK

WH 23.6 G Ω 22.2 G Ω OK OK

Pair-3 BK 20.8 G Ω 23.6 G Ω 29.0 G Ω OK OK

WH 29.2 G Ω 29.4 G Ω OK OK

Pair-4 BK 20.8 G Ω 27.2 G Ω 28.4 G Ω OK OK

WH 27.3 G Ω 30.0 G Ω OK OK

Pair-5 BK 19.5 G Ω 33.2 G Ω 27.0 G Ω OK OK

WH 27.2 G Ω 29 G Ω OK OK

Pair-6 BK 18.8 G Ω 28.4 G Ω 29.1 G Ω OK OK

WH 27.7 G Ω 26 G Ω OK OK

Pair-7 BK 22.3 G Ω 27.2 G Ω 29 G Ω OK OK

WH 27.9 G Ω 28.2 G Ω OK OK

Pair-8 BK 21.8 G Ω 34.5 G Ω 35.2 G Ω OK OK

WH 26.0 G Ω 29.1 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum #
Drawing No Tag # MO-04-01-02-VD 2 Date 1/3/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 30 M
PRETREATMENT MAIN SYSTEM CONTROL PANEL 380 LV Distribution Switchboard
Cable from Cable To,
(PART 1) Transformer 1 Incomer
Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 7.48 G Ω 16.7 G Ω 74.9 G Ω OK OK

WH 7.92 G Ω 70.6 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CM-04-01-02-VD1 Date 6/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 6M

Cable from PRETREATMENT JB DIGITAL Cable To, PRETREATMENT JB DIGITAL

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 89.7 GΩ 66.6 GΩ 33.4 GΩ OK

WH 34.2 GΩ 35.2 GΩ OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CM-04-01-03-VD1 Date 6/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB DIGITAL Cable To, COARSE SCREEN CHANNEL 01

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

Pair-1 BK 32.6 GΩ 25.3 GΩ 19.5 GΩ OK OK

WH 11.9 GΩ 11.09 GΩ OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No SA09C2-JVE-00-36-WI-WQ-31016


Project Tittle Buraydah 2 ISTP ITP No. SA09C2-JVE-00-XX-IT-WQ-30007
Subcontractor KJIC Activity No 3.2
Tag Description IR and continuity checking of cable Cable No Drum # 2733416-10
Drawing No Tag # CM-04-01-03-VD1 Date 6/4/2024
Cable Size & Types PVC/OSH/PVC/PVC FRSL 500V - 1P x 1.50 Length 15 M

Cable from PRETREATMENT JB DIGITAL Cable To, COARSE SCREEN CHANNEL 01

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage: ____________500v_____________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Drain Conductor
Core No. Core to Core Core to Ground
Shield Continuity Continuity

RD- OK OK
Pair-1 GREEN 535 GΩ
RD-GND 535 GΩ OK OK
GREEN- OK OK
GND 535 GΩ

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name Abdull Hafeez

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-JBA-01-ZC-M Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 1.57 G Ω 928 M Ω 3.04 G Ω OK OK


WH 1.08 G Ω 4.01 G Ω OK OK
Pair-2 Bk 1.67 G Ω 1.14 G Ω 6.25 G Ω OK OK
WH 1.01 G Ω 2.99 G Ω OK OK
Pair-3 Bk 1.92 G Ω 1.18 G Ω 3.22 G Ω OK OK
WH 957 M Ω 4.11 G Ω OK OK
Pair-4 Bk 1.71 G Ω 1.06 G Ω 2.00 G Ω OK OK
WH 1.35 G Ω 2.11 G Ω OK OK
Pair-5 Bk 1.85 G Ω 998 M Ω 2.00 G Ω OK OK
WH 1.08 G Ω 2.33 G Ω OK OK
Pair-6 Bk 1.61 G Ω 1.35 G Ω 2.4 G Ω OK OK
WH 973 M Ω 2.33 G Ω OK OK
Pair-7 Bk 1.88 G Ω 1.11 G Ω 2.66 G Ω OK OK
WH 971 M Ω 2.8 G Ω OK OK
Pair-8 Bk 1.75 G Ω 1.55 G Ω 2.54 G Ω OK OK
WH 1.09 G Ω 2.58 G Ω OK OK
Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________
Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-JBA-02-ZC-M Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 1.77 G Ω 1.24 G Ω 2.00 G Ω OK OK


WH 1.9 G Ω 2.33 G Ω OK OK
Pair-2 Bk 1.97 G Ω 1.27 G Ω 2.4 G Ω OK OK
WH 1.15 G Ω 2.33 G Ω OK OK
Pair-3 Bk 1.89 G Ω 1.42 G Ω 2.66 G Ω OK OK
WH 1.07 G Ω 2.8 G Ω OK OK
Pair-4 Bk 2.11 G Ω 1.33 G Ω 2.54 G Ω OK OK
WH 1.28 G Ω 2.58 G Ω OK OK
1.91 G Ω 1.28 G Ω 3.1 G Ω OK OK
1.42 G Ω 2.99 G Ω OK OK
2.08 G Ω 1.08 G Ω 1.59 G Ω OK OK
1.57 G Ω 2.55 G Ω OK OK
1.88 G Ω 1.10 G Ω 1.66 G Ω OK OK
1.21 G Ω 2.5 G Ω OK OK
1.96 G Ω 1.19 G Ω 2.88 G Ω OK OK
1.24 G Ω 2.61 G Ω OK OK
Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________
Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# QW-04-01-04-REM Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 3.82 G Ω 3.55 G Ω 3.99 G Ω OK OK


WH 3.13 G Ω 4.35 G Ω OK OK
Pair-2 Bk 2.24 G Ω 3.11 G Ω 4.50 G Ω OK OK
WH 2.83 G Ω 3.41 G Ω OK OK
Pair-3 Bk 2.25 G Ω 2.69 G Ω 2.98 G Ω OK OK
WH 2.78 G Ω 2.62 G Ω OK OK
Pair-4 Bk 1.99 G Ω 3.44 G Ω 3.36 G Ω OK OK
WH 2.44 G Ω 3.11 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# QW-04-01-04-ZD Cable No DRUM# 2733146-13
Drawing No Date 8/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 5.49 G Ω 2.39 G Ω 4.06 G Ω OK OK


WH 2.56 G Ω 3.79 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# QW-04-01-03-ZD Cable No DRUM# 2733146-13
Drawing No Date 8/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 5.68 G Ω 2.20 G Ω 3.2 G Ω OK OK


WH 3.69 G Ω 3.89 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# LL-04-01-03-VD1 Cable No DRUM# 2733146-13
Drawing No Date 8/3/2024
Cable Size & Types 1PX1.5mm2 Length 13 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 73 G Ω 29.2 G Ω 35 G Ω OK OK
WH 61.4 G Ω 57 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# LL-04-01-02-ZD Cable No DRUM# 2733146-13
Drawing No Date 8/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 4.96 G Ω 2.87 G Ω 2.86 G Ω OK OK


WH 2.59 G Ω 2.98 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# LL-04-01-03-VD2 Cable No DRUM# 2733146-13
Drawing No Date 8/3/2024
Cable Size & Types 1PX1.5mm2 Length 13 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 73.2 G Ω 28.8 G Ω 31 G Ω OK OK


WH 61.1 G Ω 49 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# CM-04-01-01-VD1 Cable No DRUM# 2733146-13
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 98.6 G Ω 57.9 G Ω 59.7 G Ω OK OK


WH 31.2 G Ω 77.2 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-BFY-11-VD1-32 Cable No DRUM# 2733146-13
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 2.03 G Ω 1.06 G Ω 1.1 G Ω OK OK


WH 1.16 G Ω 1.17 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-BFY-11-VD2-32 Cable No DRUM# 2733146-13
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 181 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 2.09 G Ω 1.21 G Ω 1.73 G Ω OK OK


WH 1.11 G Ω 1.61 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-BFY-12-VD1-32 Cable No DRUM# 2733146-13
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 176 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 2.1 G Ω 1.65 G Ω 1.18 G Ω OK OK


WH 1.13 G Ω 1.54G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-BFY-12-VD2-32 Cable No DRUM# 27
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 176 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_________________500V____________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 2.07 G Ω 1.27 G Ω 1.5 G Ω OK OK


WH 999 M Ω 1.39 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# CM-04-01-02-VD2 Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 1PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 86.2 G Ω 99.2 G Ω 94.4 G Ω OK OK


WH 79.5 G Ω 101.9 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# QW-04-01-03-REM Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 4.41 G Ω 3.52 G Ω 3.57 G Ω OK OK


WH 4.23 G Ω 5.22 G Ω OK OK
Pair-2 Bk 2.36 G Ω 2.95 G Ω 2.83 G Ω OK OK
WH 3.39 G Ω 3.57 G Ω OK OK
Pair-3 Bk 2.57 G Ω 2.76 G Ω 2.66 G Ω OK OK
WH 2.95 G Ω 3.22 G Ω OK OK
Pair-4 Bk 2.46 G Ω 3.43 G Ω 4.00 G Ω OK OK
WH 3.89 G Ω 3.97 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No 3.2
Tag Description Tag# 04-BJB-11-VD1M Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 1.17 G Ω 1..0 G Ω 4.4 G Ω OK OK


WH 2.1 G Ω 1.99 G Ω OK OK
Pair-2 Bk 846 M Ω 1.24 G Ω 3.22 G Ω OK OK
WH 2.3 G Ω 1.78 G Ω OK OK
Pair-3 Bk 818 M Ω 1.4 G Ω 1.4 G Ω OK OK
WH 2.2 G Ω 2.99 G Ω OK OK
Pair-4 Bk 780 M Ω 1.1.5 G Ω 2.22 G Ω OK OK
WH 2.21 G Ω 1.20 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No
Tag Description Tag# 04-BJA-11-02-VD1M Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 1.37 G Ω 1.66 G Ω 1.6 G Ω OK OK


WH 2.11 G Ω 3.4 G Ω OK OK
Pair-2 Bk 2.01 G Ω 2.24 G Ω 2.22 G Ω OK OK
WH 3.3 G Ω 1.2 G Ω OK OK
Pair-3 Bk 1.21 G Ω 2.4 G Ω 4.4 G Ω OK OK
WH 1.2 G Ω 1.99 G Ω OK OK
Pair-4 Bk 1.21 G Ω 2.5 G Ω 3.22 G Ω OK OK
WH 1.21 G Ω 1.78 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date
Instrument Cable Insulation Resistance Test Record

Project Nymber SA09C2 WIR No


Project Tittle Buraydah 2 ISTP ITP No.
Subcontractor KJIC Activity No
Tag Description Tag# 04-BJA-11-02-VD1M Cable No DRUM# 16023-020212
Drawing No Date 10/3/2024
Cable Size & Types 4PX1.5mm2 Length 170 M

Cable from ___________________________ Cable To, _____________________________________

Test Voltage __________500v_____________ Test Duration ___________1mint___________

Ambient Temerature: _____________ C ______________F Cable Rated Voltage:


_____________________________________

Circuit No./ Insulation Resistance (M-ohms)


Wire
Cable No./ Remarks
Tagging Core to Core to Drain Conductor
Core No. Core to Core
Ground Shield Continuity Continuity

Pair-1 Bk 1.25 G Ω 2 GΩ 3.6 G Ω OK OK


WH 5GΩ 2.4 G Ω OK OK
Pair-2 Bk 1.73 G Ω 2.3 G Ω 3.22 G Ω OK OK
WH 3.1 G Ω 2.2 G Ω OK OK
Pair-3 Bk 1.18 G Ω 1.9 G Ω 3.4 G Ω OK OK
WH 2.4 G Ω 1.99 G Ω OK OK
Pair-4 Bk 1.17 G Ω 3.11 G Ω 2.22 G Ω OK OK
WH 1.1 G Ω 1.7 G Ω OK OK

Cable Jacket integrity Tes: Test Voltage _______________________ IR Value:___________________


Test Equipment Description Equipment ID/ Serial No. Calibration Due Date
5KV IR tester(Megger) FLUkE-1550C/62170004 16-12-2024
Digital multimmeter FlUkE-17B+/62475599WS 21-12-2024
Remarks

Witness By KJIC JVE Client


Name

Signature

Date

You might also like