Devices and Applications
Description
1
Type XR relays are developments for specific applications from
the AR relay range. They are electro-mechanical relays with a
consistent positive action, a long service life, and comply with
BS142 and IEC 255 standards. The XR range is used as Inter-
posing, Supervision, or Special Purpose Relays.
Interposing Relays: XR105, XR106, XR107, XR205, XR206
• The interposing relays are intended for the remote control
operation of switchgear over pilot wires with a maximum
resistance of 200 Ω. The relays are designed so that they are
not susceptible to certain AC voltage levels which may be
induced onto the pilot wires.
Supply Supervision Relays: XR152, XR153
• The supervision relays are designed to monitor DC voltages.
They have a low operating current, specific settings, time
delayed drop-off, a mechanical flag indicator which shows on
de-energization and contacts for the ability to initiate remote
alarms.
Trip Circuit Supervision Relays: XR151, XR250, XR251, XR350,
XR351
• These relays are for the monitoring of the circuit breakers trip
circuit to ensure integrity at all times. There are differing pref-
erences for monitoring a trip circuit and our range is designed
to meet these requirements.
4 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Devices and Applications
7PG17 Interposing Relay (XR105, XR106 and XR107, XR205 and XR206)
Description
Interposing relays are used for remote control of switchgear
and associated equipment over pilot wires or cross-site cables.
Type XR205 and XR206 are two element versions of the XR105 1.1
and XR106 respectively with the same performance. Type XR
relays are developments for specific applications from the type
AR (7PG11) relay range. They are electro-mechanical relays with
a consistent positive action, a long service life and complying
with BS142.
Type XR105 has no flag indicator, an XR106 has a flag indicator
and an XR107 has a hand reset flag.
XR105 and XR106 have self-reset contacts and an XR107 has
hand reset contacts.
[Reyrolle Product Catalogue, 7PG17 Interposing Relay, 1, --_--]
Both types are available with a suppression diode across the coil
to reduce the effects of the back emf which occurs on switch- Figure 1.1/1 7PG17 Interposing Relay
off.
Application
Types XR105/XR106/XR107 are intended for the remote control
of switchgear and associated equipment over pilot wires with a
maximum resistance of 200 Ω. These relays are designed so that
they are not susceptible to certain AC voltage levels which may
be induced onto the pilots wires.
Benefits
• A robust design for a long, reliable service life
• Supplied in a draw-out type case
• Various combinations of coils, contacts, and operation indi-
cator flags can be specified
[lo_7PG17_7PG173[1,3]-[0,1]xx00-xAA[0,1], 1, en_US]
[lo_7PG17_7PG173[1,3]-[0,1]xx30-xAA[0,1], 1, en_US]
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 5
Devices and Applications
7PG17 Interposing Relay (XR105, XR106 and XR107, XR205 and XR206)
1.1
[lo_7PG17_7PG1732-[0,1]xx10-xCA[0,1], 1, en_US]
[lo_7PG17_7PG1732-[0,1]xx00-xAA[0,1], 1, en_US]
[lo_7PG17_7PG1732-[0,1]xx00-xCA[0,1], 1, en_US]
6 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Devices and Applications
7PG17 Trip Relay Supervision Relay (XR151)
Description
Type XR relays are developments for specific applications of the
type AR relay range. They are electro-mechanical relays with
long service life and complying with the appropriate require-
ments of IEC 255 and BS 142. These relays have a low operating
current, specific settings and time delayed drop-off. This latter
1.2
feature is to keep the relay in the operated condition during
temporary reductions in the battery voltage, such as those
which occur just prior to a fuse blowing or during a busbar fault
when many trip relays operate simultaneously.
Application
Type XR151 relays are designed to allow the supervision of a trip
relay operating coil, supply and associated wiring. This applica-
tion requires relays with low operating current, visual indication
and the ability to initiate a remote alarm. XR151 has a mechan-
ical flag indicator which shows on de-energization, either self
reset or hand reset. [Reyrolle Product Catalogue, 7PG17 Supervision Relay, 1, --_--]
Low burden and consistent operation, positive action. Suitable Figure 1.2/1 7PG17 Trip Relay Supervision Relay
for operating with high burden trip relays (EB2) only.
Exact burden and operating current dependent upon applica-
tion.
Benefits
• A robust design for a long, reliable service life
• Supplied in a draw-out type case
• Various combinations of coils, contacts, and operation indi-
cator flags can be specified
XR151 Applications
[lo_7PG17_7PG1751-[1,3]xx10-4AA0, 1, en_US]
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 7
Devices and Applications
7PG17 Supply Supervision Relay (XR152 and XR153)
Description
Type XR relays are developments for specific applications of the
type AR relay range. They are electro-mechanical relays with
long service life and complying with the appropriate require-
ments of IEC 255 and BS 142. These relays have a low operating
current, specific settings and time delayed drop-off. This latter
feature is to keep the relay in the operated condition during
temporary reductions in the battery voltage, such as those
1.3
which occur just prior to a fuse blowing or during a busbar fault
when many trip relays operate simultaneously. Healthy circuits
therefore do not give spurious alarms and the relay effected by
the fuse failure provides the alarm and indication necessary for
accurate maintenance attention.
Application
Types XR152 and XR153 relays are designed to comply with
CEGB and other specification for protection supervision require-
ments and the monitoring of DC voltage supplies. These applica- [Reyrolle Product Catalogue, 7PG17 Supply Supervision Relay, 1, --_--]
tions require relays with low operating current, visual indication
Figure 1.3/1 7PG17 Supply Supervision Relay
and the ability to initiate a remote alarm. Both these relays have
mechanical flag indicators which show on de-energization, self
reset on the XR152 and hand reset on the XR153.
• Low burden
• Versatile design
• Consistent positive action
Benefits
• A robust design for a long, reliable service life
• Supplied in a draw-out type case
• Various combinations of coils, contacts, and operation indi-
cator flags can be specified
[lo_7PG17_7PG173[1,3]-[0,1]xx10-xAA[0,1], 1, en_US]
8 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Devices and Applications
7PG17 Trip Circuit Supervision Relay (XR250 to XR351)
Description
Type XR relays are developments for specific applications of the
type AR relay range. They are electro-mechanical relays with a
consistent positive action, a long service life and complying with
the appropriate requirements of IEC 255 and BS142. Models
XR250/251 have two attracted armature elements, XR350/351
have three. These relays incorporate a time delay on de-energi-
sation to keep the relay in an operated condition during tempo-
rary reductions in the battery voltage.
• Low burden 1.4
• Versatile design, can provide pre-close supervision
• Consistent positive action
[sc_7PG17_E3Angle, 1, --_--]
Benefits
• A robust design for a long, reliable service life
• Supplied in a draw-out type case
• Various combinations of coils, contacts, and operation indi- [lo_7PG17_7PG1752-[1,3]xx10-xBx0, 1, en_US]
cator flags can be specified
Figure 1.4/2 7PG1752-[1,3]xx10-xBx0 Connection Diagram
• Options are also available for operate and reset modes
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 9
Devices and Applications
7PG17 Trip Circuit Supervision Relay (XR250 to XR351)
1.4
[lo_7PG17_7PG1753-[1,3]xx10-xBx0, 1, en_US]
10 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Devices and Applications
Standard Variants
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 11
Devices and Applications
Standard Variants
12 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
System
Hardware Construction
2.1
[sc_7PG11_HandlesWithdrawing, 1, --_--]
The case earth stud should be solidly earthed to the panel earth Figure 2.1/3 Hand Reset Mechanism
before any connections to the device rear terminal. Located at
the top rear of the case is a case earth stud as shown in , this Relay Information
must be connected to the main panel earth. The device fascia displays the MLFB order code, serial number,
and device identification reference.
Electrical Hazard
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 13
Technical Documentation
Dimension Drawings and Connection Diagrams
Dimension Drawings
3.1
[sc_E2casing, 1, en_US]
14 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Dimension Drawings and Connection Diagrams
3.1
[sc_E3casing, 1, en_US]
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 15
Technical Documentation
Dimension Drawings and Connection Diagrams
3.1
[sc_E4casing, 1, en_US]
16 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Technical Data
7PG17 (XR105, XR106 and XR107, XR205 and XR206) Thermal Withstand 1.15 Vn continuously
External resistor required for DC 125 V operation. Operating Indication A self or hand reset flag indicator
range: With zero pilot resistance 78 to 125 % of nominal rated shows when the relay is de-ener-
voltage gised.
Vibration, relays comply with BS142, Section 2.1 Category S2. IEC 255-21-1
Shock, relays will withstand a 20G shock or impact on the panel The relays meet the requirements of Class 1 for vibration
without operating. Operational/mechanical life, relays will with- response and endurance.
stand in excess of 10,000 operations with the contact rating Shock and Bump
stated.
IEC 255-21-2
Normally Closed Contact Location (Epsilon case terminal numbers) The relays meet the requirements of IEC 255-21-2 and BS142,
1 to 3 2 to 4 5 to 7 6 to 8 sub-section 1.5.2. (1989) with respect to shock and bump
testing for class 1 severity.
1 NC NC
2 NC NC NC Mechanical Life
3 NC NC NC NC The relays will withstand in excess of 10,000 operations with
4 NC NC NC NC NC the contact rating at a rate of 600 operations per hour.
Insulation
7PG17 (XR151)
IEC 255-5
Rated voltage Vn 125 V Relays will withstand: 5 kV peak, 1.2/50 μs, 0.5 J between all
Settings Pick-up: 70 % of Vn terminals and case earth and between adjacent terminals. 2
kVRMS 50 Hz for 1 minute between all case terminals connected
Drop-off: not less than 26 % of Vn
together and the case earth and between independent circuits.
Reset time No less than 100 ms when supply 1 kVRMS 50 Hz for 1 minute between normally open contacts.
is switched from 100 % to 26 % of
V n.
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 17
Technical Documentation
Technical Data
The relays will withstand in excess of 10,000 operations with 56 days at 95 % RH and 40°C.
the contact rating at a rate of 600 operations per hour.
18 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Technical Data
Vibration
IEC 255-21-1
The relays meet the requirements of Class 1 for vibration
response and endurance.
Shock and Bump
IEC 255-21-2
The relays meet the requirements of IEC 255-21-2 and BS142,
sub-section 1.5.2. (1989) with respect to shock and bump
testing for class 1 severity.
Operational/Mechanical Life
The relays will withstand in excess of 10,000 operations with
the contact rating at a rate of 600 operations per hour.
Insulation IEC 255-5
Relays will withstand: 5 kV peak, 1.2/50 μs, 0.5 J between all
terminals and case earth and between adjacent terminals 2
kVRMS 50 Hz for 1 minute between all case terminals connected
together, the case earth and between independent circuits 1
kVRMS 50 Hz for 1 minute between normally open contacts.
Coil and Resistor Data
3.2
Voltage R1 R2 R3 R4
DC 30 V - - 100 100
DC 50 V - - 350 350
DC 125 V 2000 - 3300 3300
DC 240 V 7000 - 10300 10300
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 19
Technical Documentation
Ordering Information
3.3 4 NO E | | | |
| | | |
Contact Arrangement – NC | | | |
0 NC A | | |
1 NC B | | |
2 NC C | | |
3 NC D | | |
4 NC E | | |
| | |
Number of Contacts 1 | | |
Two 0 | |
Four 1 | |
| |
Voltage Rating | |
DC 24 V 1 |
DC 30 V 2 |
DC 50 V 3 |
DC 125 V2 4 |
|
Back Emf Suppression Diode |
Not fitted 0
Fitted 1
20 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Ordering Information
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 21
Technical Documentation
Ordering Information
3.3 1 NC B |
2 NC C |
3 NC D |
4 NC E |
|
Voltage Rating |
DC 24 V 1
DC 30 V 2
DC 50 V 3
DC 125 V 4
DC 240 V 5
22 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Ordering Information
NOTE
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 23
Technical Documentation
Ordering Information
3.3 1 NC B | |
2 NC C | |
3 NC D | |
4 NC E | |
| |
Voltage Rating | |
DC 30 V3 2 |
DC 50 V3 3 |
DC 125 V3 4 |
DC 240 V3 5 |
|
Voltage Rating (Alarm) |
DC 30 V C
DC 50 V D
DC 125 V3 E
DC 240 V3 F
24 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Technical Documentation
Ordering Information
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 25
Technical Documentation
3.3
26 Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1
Appendix
Indication of Conformity
This product is CE-compliant to relevant EU directives.
Disclaimer of Liability
Subject to changes and errors. The information given in this
document only contains general descriptions and/or perform-
ance features which may not always specifically reflect those
described, or which may undergo modification in the course
of further development of the products. The requested perform-
ance features are binding only when they are expressly agreed
upon in the concluded contract.
Copyright
Copyright © Siemens AG 2024.
The disclosure, duplication, distribution and editing of this docu-
ment, or utilization and communication of the content are not
permitted, unless authorized in writing. All rights, including
rights created by patent grant or registration of a utility model
or a design, are reserved.
Trademarks
SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS SAFIR, SICAM, and
MindSphere are trademarks of Siemens. Any unauthorized use is
prohibited.
OpenSSL
4 This product includes software developed by the OpenSSL
Project for use in OpenSSL Toolkit (http://www.openssl.org/).
This product includes software written by Tim Hudson
(tjh@cryptsoft.com).
This product includes cryptographic software written by Eric
Young (eay@cryptsoft.com).
Reyrolle 7PG17 Catalog ⋅ Intertripping, Interposing, Supervision and Special Purpose Relays ⋅ Catalog - Edition 1 27
Published by Subject to change without prior notice.
The information in this document contains
Siemens AG general descriptions of the technical options
Smart Infrastructure available, which may not apply in all cases.
Electrification & Automation The required technical options should therefore
Mozartstrasse 31c be specified in the contract.
91052 Erlangen
Germany
© 2024 by Siemens AG