OPTIMIZED LINE REACTORS

KDR line reactors are electrical components that help to Benefits of KDR Line Reactors:
protect 6-pulse rectifiers and power conversion devices
• Helps to meet IEEE 519-2014 requirements
such as variable frequency drives (VFDs). When used
in conjunction with a VFD, a KDR line reactor can help • 208 V-690 V; 0.25HP-1250HP
reduce harmonics and protect the drive from harmful • Available in Ultra Low, Low and High Impedance
voltage spikes. KDR line reactors are recommended on
• Strong durable design specifically for VFD
the input of each VFD in multiple drive applications.
applications
Output of a VFD • Drive Lifetime Warranty
KDR reactors are constructed with durability in mind • UL Listed
and can be used on both the input and output of • Made in the USA
a VFD. When used on the output of a drive, KDR • Same Day Shipping
reactors reduce voltage distortion at the motor terminals
extending the service life and minimizing insulation
stress of any motor.

Typical Applications with VFDs


• HVAC Chillers
• Pumps
• Oil rigs
• Conveyors
• Sprinkler irrigation systems
Technical Specifications Input Harmonic Current Distortion- No Reactor
50

Voltage 208 - 690 VAC 40

30

Frequency 50/60 Hz 20

Current Amps
10

Power Rating* 0.25 - 1250 HP 0

-10

Impedance Ultra Low, Low, High Impedance -20

-30

Short Term Tolerate 200% rated I for -40

Overload Rating a maximum of 3 minutes


-50
0 10 20 30 40 50 60

Time (ms)

Minimum 95% L at 110% Load


Inductance Characteristics
Minimum 80% L at 150% Load Input Harmonic Current Distortion- with KDR
Environmental Conditions 50

40

-40°C to 40°C enclosed 30

Ambient Temperature 20
Enclosed: 40° C (104° F)

Current Amps
10

Up to 2,000 m (6,000 ft) without 0

Operating Altitude
derating -10

-20

Reference Technical Standards -30

Agency Approvals cULus


-40

-50
0 10 20 30 40 50 60
For the life of the drive with
Warranty Time (ms)

which the reactor is installed

Part Numbering
Output Motor Terminal
Motor Terminal Voltage-
Voltage No Reactor
no reactor
KDR AA 3 L 2 E01 1500

1250
KDR Series: 1000

Design Frame: 750

500
Sequence Code: 250
Volts

Impedance Rating: 0

-250
P - Ultra Low Impedance -500

L - Low Impedance -750

-1000
H - High Impedance -1250

Foot: -1500
0 5 10 15 20 25 30 35
(Blank if not MA/AA) Time (ms)

1 - Side
2 - Thin OutputMotor
MotorTerminal Voltage
Terminal with KDRwith KDR
Voltage-
Enclosure: 1500

E01 - UL Type 1 1250

E3R - UL Type 3R 1000

750
E3R1 - UL Type 3R (MA/AA) 500
C1 - NEMA 1 (MA/AA) 250
Volts

*May vary based on voltage -250

-500

-750

-1000

-1250

-1500
0 5 10 15 20 25 30 35

Time (ms)

TCI, LLC
W132 N10611 Grant Drive Part #23320
Version 2
Germantown, WI 53022 ©2019
800-824-8282 | www.transcoil.com