Feeder Protection

7SC80
SIPROTEC Compact

siemens.com/siprotec
Feeder Protection SIPROTEC 7SC80

1
Page

Description 9/3

Function overview 9/4

2 Applications 9/5

Construction and hardware 9/6

Transformers 9/7

Function description 9/8

3 Application examples 9/14

Selection and ordering data 9/20

Connection diagrams 9/22

4 Connection examples 9/26

Connection types 9/30

5
SNTP Server/Master 9/31

10
You will find a detailed overview of the technical data
(extract of the manual) under:
http://www.siemens.com/siprotec

9/2 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Description

Description

1
The SIPROTEC 7SC80 feeder protection can be used for
protection and automation of medium-voltage distribution
feeders with grounded, low-resistance grounded, isolated,
or compensated neutral.
The SIPROTEC 7SC80 features “flexible protection functions”.
20 additional protection functions can be created by the
user. For example, a rate of change of frequency function or 2
a reverse power function can be created. The relay provides
circuit-breaker control. Additional primary switching devices
(grounding switches, transfer switches and isolating
switches) can also be controlled from the relay. Automation
or PLC logic functionality is also implemented in the device.
The integrated programmable logic (CFC) allows the user to 3

SIP-COM-01.tif
add own functions, e.g. for the automation of switchgear
(including: interlocking, transfer and load shedding
schemes). The user is also allowed to generate user-defined

4
messages.
The upgrade of device and communication firmware is also
possible via Ethernet.

Highlights
• Support of feeder automation applications, e.g. fault isolation
and service restauration
Fig. 9/1 SIPROTEC 7SC80 front view with HMI
5
• Designed for harsh environment
• Extended temperature range –50 °C up to 85 °C

6
• Open for all different communication technologies, e.g.
radio, which are used for feeder automation
• Integrated GPS or IRIG/B module is available for time
synchronisation
• Remote access for firmware and parameter updates
• Fulfills NERC/CIP and BDEW security requirements
• A web based HMI provides complete remote control of the
7
device
• 9 programmable function keys
• 6-line display
• Integrated switch for low-cost and redundant optical 8
rings.
SIP-COM-02.tif

Devices can be connected directly with each other at


electrical modules
• Parallel running communication protocols
• Redundancy protocols RSTP, PRP and HSR for highest
9
availability
• Jump detector for currents and voltages
• Extended CFC capabilities Fig. 9/2 SIPROTEC 7SC80 side view with detached HMI
• 24 km Single mode interface
• RTU version without protection features
• Pluggable terminals • Relay-to-relay communication through Ethernet with

10
• Secondary current transformers values (1 A / 5 A) settable IEC 61850 GOOSE
using DIGSI • Stainless steel housing for flush or surface mounting
• Buffer battery exchangeable without opening the housing • Millisecond-accurate time synchronization through
• USB front port Ethernet with SNTP
• Inputs for Low power CTs and VTs according IEC 61869-6
(formerly IEC 60044-7 and IEC 60044-8).

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/3


Feeder Protection SIPROTEC 7SC80
Function overview

Protection Functions IEC Norm ANSI Norm


Protection function for 3-pole tripping (3-pole)

1 Unbalanced-load protection I2> 46


Negative-sequence system overcurrent protection I2>, I2/11> 46
Thermal overload protection J> 49
Definite time-overcurrent protection I> 50/50N

2 Instantaneous tripping at switch onto fault SOFT


Sensitive ground-current protection INs> 50Ns
Circuit-breaker failure protection CBFP 50BF
Inverse time-overcurrent protection IP, INp 51/51N
Cold load pickup 51C

3 Trip-circuit supervision
Lockout
AKU 74TC
86
Restricted ground-fault protection ΔIN 87N
Synchrocheck, synchronizing function 25

4 Undervoltage protection
Phase-sequence-voltage supervision
U<
L1, L2, L3
27
47
Overvoltage protection, negative-sequence system V2>
Voltage dependent overcurrent protection t=t(I)+V< 51V

5 Power factor
Overvoltage protection
cos j
V>
55
59/59N
Overvoltage protection, zero-sequence system V0> 59N
Measuring-voltage failure detection 60FL

6 Directional time-overcurrent protection, phase I>, ∠ (V,I) 67

Table 9/1 Abstract - Function Overview Further functions: current manual or via relay selector

7 Control functions / programmable logic Communication interfaces


• Commands for the ctrl. of CB, disconnect • Ethernet electrical and optical
switches (isolators/isolating switches) (multimode or singlemode)

8 • Control through keyboard, binary inputs,


DIGSI 4 or SCADA system
• IEC 61850 Edition 1 and 2
• DNP3 TCP
• User-defined PLC logic with CFC • PROFINET
(e.g. interlocking).
• IEC 60870-5-104

9 Monitoring functions • Ethernet redundancy protocols RSTP, PRP and HSR


• USB front interface for DIGSI 4
• Operational measured values V, I, f
• Energy metering values Wp, Wq • Serial DNP3 RS485 module.
• Minimum and maximum values Hardware
• Circuit-breaker wear monitoring • 4 current transformers
• Fuse failure monitor • 1/6 voltage transformers
• Max. 40 oscillographic fault records • 12/20 binary inputs

10
• Trip circuit supervision • 8/15 binary outputs
• Load professional for up to 20 different operating mea- • 1 life contact
sured values • Pluggable current and voltage terminal blocks
• Connection option for low-power current and
voltage transformers.

9/4 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Applications

The feeder protection SIPROTEC 7SC80 is a numerical Operational indication


­protection device that can perform control and monitoring
1
Event logs, trip logs, fault records and statistics documents
functions and therefore provides the user with a cost-
are stored in the relay to provide the user or operator with
effective platform for power system management, that
all the key data required to operate modern substations.
ensures reliable supply of electrical power to the customers.
Device operation was designed according to ergonomic Line protection
­aspects. Top priority was given to good display readability
and large function keys. The 32 LEDs allow displaying
numerous states and alarms.
The SIPROTEC 7SC80 units can also be used for line protec-
tion of medium-voltage distribution feeders with grounded, 2
low-resistance grounded, isolated, or compensated neutral.
Control
Transformer protection
The integrated control function permits control of discon-
The device provides all the functions for backup protection
nect devices, grounding switches or circuit-breakers through
3
for transformer differential protection. The inrush suppres-
the integrated operator panel, binary inputs, DIGSI 4 or the
sion effectively prevents unwanted trips that can be caused
systems control (e.g. SICAM).
by inrush currents. The high-impedance restricted ground-
Programmable logic fault protection detects short-circuits and insulation faults
on the transformer.
The integrated logic characteristics (CFC) allow the user to
add own functions for automation of switchgear (e.g. inter-
locking), switching sequence or of the distribution system.
Backup protection 4
As a backup protection the SIPROTEC 7SC80 devices are
The user can also generate user-defined messages.
universally applicable.
Operational measured values
5
Switchgear cubicles for high/medium voltage
Extensive measured values, metered values and limit
All units are designed specifically to meet the requirements
values provide improved system management as well as
of high / medium-voltage applications. In general, no
commissioning.
­separate measuring instruments (e.g., for current, voltage,
frequency, …) or additional control components are
­necessary.
6
Busbar

Local/remote control
Commands/Feedbacks
CFC logic Operational values V<
27
V>
59
F1-F4
81 V /O
7
Limits
74TC Trip-circuit supervision
AND I, V, P, Q, 25 Synchrocheck
Mean values
cos φ, f
86 Lockout Min/max- memory Flexible protection functions
52
Device operation Communication
module
- Ethernet
Sectionalizer
function
Metered energy: as counting pulses
87L Current-jump detection

P<>,Q<> cos φ df/dt du/dt


8
- IEC 61850
- DNP3 TCP
32 55 81R 27R
59R
- Profinet IO
- IEC60870-5-104 V< V> F1-F4
Supervision Fault locator
27 59 81 V /O

9
- DNP3 Master
60 CTS
60 VTS
Time Directional supplement
synchronization
- GPS
- SNTP
1-pole/3-pole 21FL 47
Phase-rotation
operation supervision
- IRIG-B

INs-1,
I>, I>>, INs-2,
50-1, 50N-1, I>>>, INs-3,
50-2, 50N-2, IN- I-TOC INs-TOC
50-3 I-TOC 50N-3 TOC I2 > ϑ> BF I< 1-4 1-4
50 51
1-4
50N 51N
1-4
46 49 InRush BLC 50BF 51c 37 51V 67 67N

79 AREC
Suppl. determination of ground-
fault direction 10
50N 51N 50Ns 51Ns 87N 67Ns 59N
50N-1, IN-TOC INs-1, INs-TOC REF INs-1, VN>
50N-2, 1-4 INs-2 INs-2,
50N-3 INs-TOC

Fig. 9/3 Function diagram

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/5


Feeder Protection SIPROTEC 7SC80
Construction and hardware

Housing with many advantages

1
The SIPROTEC 7SC80 has a complete other form factor than
all other SIPROTEC Compact devices. All interfaces are at the
left and right hand side of the relay. A small print onto the
enclosure next to the clamps describes each port in detail.
All clamps are pluggable and therefore a pre-wiring and

2
easy replacement in case of maintenance is possible. A short
circuit is integrated in the pluggable CT clamp to avoid any
risk of unclosed secondary CT circuits. The first eight binary
inputs and the second four binary inputs have a common

SIP-COM-04.tif
SIP-COM-03.tif
ground. The threshold is fixed for 24 V and higher. The
secondary values of the CTs 1 A or 5 A can be set via DIGSI.

3 Operation panel/HMI
The relay features both a clip-on and a web-based operation
panel/HMI (web monitor) with 32 LEDs and 9 programmable Fig. 9/4  Process termial Fig. 9/5 Current terminal
keys that can be used to configure shortcuts for menu
operations or other applications (see Fig. 9/6).
4 The web monitor can be started just by entering the device
IP address in an internet browser. All device monitoring and
control functions are thus available in real-time through a
communication link. The access rights can be restricted. If

5
security requirements are more stringent, this function can
also be disabled completely.
The second web monitor view provides a graphic display
which represents control displays and also enables control
operations. Additionally, the web monitor gives access to

6 operational indications, protection indications, fault records,


primary and secondary values.
You can print or save this data.
The operation panel/HMI is not mandatory for the correct

SIP-COM-05.tif
functioning of the SIPROTEC 7SC80. It can be attached or
7 detached during operation without any adverse effects. It is
installed either directly on the SIPROTEC 7SC80 base device
or connected detached using a 3 m cable.
Fig. 9/6  WebMonitor
SIPROTEC 7SC80 is suited for panel flush mounting or panel

8
surface mounting.
The SIPROTEC 7SC80 variants are always equipped with at
Current terminals – single cables
least one single voltage input Vx. This input can be used e.g.
to detect line voltage of a single phase.
Cable cross-sections AWG 14-12 (2.6 mm2 to 3.3 mm2)
An optional internal GPS module can be ordered to provide
9
When using lugs AWG 14-10 (2.6 mm2 to 6.6 mm2)
high accuracy time synchronization to the device. The GPS
Permissible tightening torque 2.7 Nm
coordinates of the device can e.g. be provided to a control
Stripping length 10 mm to 11 mm (0.39 in to 0.43 in) center.
(for solid conductor) Only solid copper wires may be
used. The SIPROTEC 7SC80 devices can be equipped with either an
electrical or an optical Ethernet module. IEC 61850 is always
Process terminal connections
available on the module and optionally together with one of
Cable cross-sections AWG 18-12 (1.0 mm2 to 2.5 mm2) the protocolls IEC 60870-5-104, PROFINET IO or DNP3 TCP.
Permissible voltages 300 V The optical module can be equipped with single mode ports
Permissible currents 5A to bridge distances up to 24 km, the well known integrated
10 Only solid copper wires may be
used.
Ethernet switch functionality is of course included.
The electrical module can be used in a chain mode to con-
Permissible tightening torque 0.4 - 0.5 Nm
nect another Ethernet based device or 7SC80 directly to a
Stripping length 7 mm (0.28 in) 7SC80.
Table 9/2 Wiring specifications for process connection As an option a serial DNP3 module is available.

9/6 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Transformers

Low-power transformer terminals Low-power voltage transformers

1
The SIPROTEC 7SC80 is available in two hardware configura- Resistive voltage dividers are provided as low-power voltage
tions, featuring 3 inputs for connecting low-power current transformers. You can generally connect all sensors that
transformers (if the ground current has to be measured support the following SIPROTEC 7SC80 specifications:
­separately, the input Vx can be used) and optionally 3 inputs
for voltage transformers. Here, the low-power voltage Measuring range 100 mV - 250 V AC
(measuring accuracy +/- 1mV at 25°C)

2
­transformers are connected to the standard voltage trans-
former inputs. The required measuring range is activated via Input impedance 1.2 MOhms (mismatches can be corrected
in the 7SC80 parameters if necessary)
parameter set. Capacitive voltage dividers are supported as
well. Rated voltage 500m V - 40 V
Thermal rating 230 V continuous
Low-power current transformers
Cable 2-pole shielded, open cable end
You can generally connect all sensors to the low-power
­current transformer inputs that support the following
SIPROTEC 7SC80 specifications: This enables various rated operating voltage ranges depend-
3
ing on the sensors used.
Measuring range 20 mV - 50 V AC
(measuring accuracy +/- 1 mV at 25°C)
Input impedance
Rated voltage
40 kOhms
200 mV - 20 V at rated current
4
Thermal rating 200 V for 10s
Cable 2-pole shielded, open cable end

IC_SG_Spannungssensor_W3.sRGB.png
This enables various rated operating current ranges depend-
ing on the sensors used. To prevent early saturation, the
overcurrents to be expected must also be observed in the
low-power transformers.
6
Fig. 9/8  Voltage transformer

7
IC_SG_Stromsensor_W3_sRGB.png

Fig. 9/7  Current transformer 9


For protection related purpose the usability of the sensors has to be checked.
The following low-power transformers can be ordered directly via MLFB:
Type MLFB Ratio Description

Phase current sensor 6MD2320-0GA00-1AA0 300 A / 225 mV ext. 200 % split core transformer for cable systems; internal diameter 55 mm;

10
­accuracy 1, 5P10; impedance > 20 kOhms
Ground current sensor 6MD2320-0AF00-1AA0 60 A / 225 mV sensor split core transformer for cable systems; internal diameter
120 mm; accuracy 1; impedance > 20 kOhms
Voltage sensor 10 kV 6MD2320-0AA04-1AA0 10 kV / √3 -> 3.25/√3 for T-connector with C-taper; accuracy 1, rated burden 200 kOhms
Voltage sensor 20 kV 6MD2320-0AA07-1AA0 20 kV / √3 -> 3.25/√3 for T-connector with C-taper; accuracy 1, rated burden 200 kOhms

Table 9/3 Available low-power transformers

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/7


Feeder Protection SIPROTEC 7SC80
Function description

Protection functions comparison protection, the directional coordinated time-


overcurrent protection is used for complete selective backup
1 Battery monitor protection.
The DC 24/48 V auxiliary voltage version allows monitor- Available inverse-time characteristics
ing an external 24 V or 48 V battery. The DC voltage is
measured directly and provided as measured value. The Characteristics acc. IEC 60255-3 ANSI / IEEE
to
2
battery is tested periodically. For this purpose, the external
battery loader is deactivated temporarily, and after a short Normal invers ● ●

waiting time, an external load impedance is connected to Short inverse ●

the battery. The battery voltage before and after the test is ● ●
Long inveres
measured. If the voltage difference is higher than a given
Moderately inverse ●
threshold, a message can be generated. A number of other
Very inverse ● ●
battery-related messages is available. The battery status is
3 also indicated by a special battery LED. Extremely inverse ●

Table 9/4 Available inverse-time characteristics


Overcurrent protection (ANSI 50, 50N, 51, 51N, 51V)


This function is based on the phase-selective measurement Moreover there are further recloser inverse-time characteris-
of the three phase currents and the ground current (four
4
tic curves available.
transformers). Three definite time-overcurrent protection
elements (DMT) are available both for the phase and the Directional time-overcurrent protection (ANSI 67, 67N)
ground elements. The current threshold and the delay
Direction determination in the 7SC80 is phase-selective and
time can be set in a wide range. 4 inverse-time overcurrent
separate for phase and earth faults. Three stages each for phase
protection characteristics (IDMTL) are available and can also
5 be selected and activated independently.
and earth operate in parallel to the non-directional overcurrent
stages and are adjustable in response value and delay time inde-
Reset characteristics pendently of these. Optionally, inverse directional overcurrent
protection characteristics (AMZ) - up to 4 AMZ curves for phase
Time coordination with electromechanical relays are made
and earth - can be switched in. The tripping characteristic can
easy with the inclusion of the reset characteristics according
6 to ANSI C37.112 and IEC 60255-3 / BS 142 standards. When
using the reset characteristic (disk emulation), the reset pro-
be rotated by ± 180 degrees. By making use of the voltage
memory, the directionality can be determined reliably even
for close-in (local) faults. If the primary switching device
cess is initiated after the fault current has disappeared. This
closes onto a fault and the voltage is too low to determine
reset process corresponds to the reverse movement of the
direction, the direction is determined using voltage from the
Ferraris disk of an electromechanical relay (disk emulation).
7 Inrush restraint
memorized voltage. If no voltages are stored in the memory,
tripping will be according to the set characteristic.
For ground protection, users can choose whether the
The relay features second harmonic restraint. If second
direction is to be calculated using the zero-sequence or
harmonic content is detected during the energization of
negative-sequence system quantities (selectable). If the

8
a transformer, the pickup of stages (I>, Ip, I>dir and Ip dir is
zero-sequence voltage tends to be very low due to the
blocked.
zero-sequence impedance it will be better to use the nega-
Dynamic setting change tive- sequence quantities.

The pickup thresholds and the trip times of the directional

9 and non-directional time-overcurrent protection functions


can be changed via binary inputs or by setable time control.

Static parameter switchover


Numerous protection-relevant parameters can be switched
over statically, e.g. via binary contacts, protocol or internal
logic. 8 parameter groups are available.

Directional comparison protection (cross-coupling)

10
It is used for selective instantaneous tripping of sections
fed from two sources, i.e. without the disadvantage of time
delays of the set characteristic. The directional comparison
protection is suitable if the distances between the protection
zones are not significant and pilot wires are available for
signal transmission. In addition to the directional Fig. 9/9 Directional characteristics of the directional
time-overcurrent protection

9/8 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Function description

(Sensitive) directional ground-fault detection Phase-balance current protection (ANSI 46)


(ANSI 59N/64, 67Ns, 67N) (Negative-sequence protection)
For isolated-neutral and compensated networks, the direc- By measuring current on the high side of the transformer, 1
tion of power flow in the zero sequence is calculated from the two-element phase-balance current/negative-sequence
the zero-sequence current I0 and zero-sequence voltage V0. protection detects high-resistance phase-to-phase faults and
For networks with an isolated neutral, the reactive current phase-to-ground faults on the low side of a transformer. This

2
component is evaluated; for compensated networks, the function provides backup protection for high-resistance faults
active current component or residual resistive current is through the transformer.
evaluated.
(Sensitive) ground-fault detection
For special network conditions, e.g. high-resistance
(ANSI 50Ns, 51Ns / 50N, 51N)
grounded networks with ohmic-capacitive ground-fault
current or lowresistance grounded networks with ohmic- For high-resistance grounded networks, a sensitive input
inductive current, the tripping characteristics can be rotated transformer is connected to a phase-balance neutral current
approximately ± 45 degrees (see Fig.9/10). transformer (also called core-balance CT). The function can
also be operated in the normal mode as an additional short-
3
Two modes of ground-fault direction detection can be
implemented: tripping or “signalling only mode”. circuit protection for neutral or residual ground protection.
It has the following functions: Breaker failure protection (ANSI 50BF)
• TRIP via the displacement voltage VE
• Three instantaneous elements and four stantaneous
If a faulted portion of the electrical circuit is not disconnected 4
when a trip command is issued to a circuit-breaker, another
elements trip command can be initiated using the breaker failure pro-
• Each element can be set to forward, reverse or non- tection which trips the circuit-breaker of an upstream feeder.

5
directional Breaker failure is detected if, after a trip command is issued
• The function can also be operated in the insensitive mode the current keeps on flowing into the faulted circuit. It is also
as an additional short-circuit protection. possible to make use of the circuit-breaker position contacts
for indication as opposed to the current flowing through the
circuit-breaker.

High-impedance restricted ground-fault protection (ANSI


87N)
6
The high-impedance measurement principle is a simple
and sensitive method to detect ground faults, especially on
transformers. It can also be used on motors, generators and
reactors when they are operated on a grounded network. 7
When applying the high-impedance measurement principle,
all current transformers in the protected area are connected
in parallel and operated through one common resistor of
relatively high R. The voltage is measured across this resistor
(see Fig. 9/11).
8

Fig. 9/10 Directional determination using cosine measurements for


compensated networks

10
LSA4115-de.ai

Fig. 9/11 High-impedance restricted ground-fault protection

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/9


4 Pickup
V measured Time
3I0, I1, I2 OFF-

Feeder Protection SIPROTEC 7SC80


3V0, V1, V2 t Command
Voltage4 P,Q Threshold

cos φ
Function 1
f
Function 2
Function description
df/dt
Function 20

The voltage is measured by detecting the current through priority.


Fig. 9/12 Flexible protection functions
the (external) resistor R at the sensitive current measure-
1 ment input IEE. The varistor V serves to limit the voltage in
the event of an internal fault.
Protection functions/stages available are based on the avail-
able measured analog quantities:
It limits the high instantaneous voltage spikes that can
occur at current transformer saturation. At the same time, Function ANSI

2
this results to smooth the voltage without any noteworthy I>, IE> 50, 50N
reduction of the average value. V<, V>, VE> 27, 59, 59N
If no faults have occurred and in the event of external or 3I0>, I1>, I2>, I2 / I1>, 3V0>, V1> <, V2 > < 50N, 46, 59N, 47
through faults, the system is at equilibrium, and the voltage
P> <, Q> < 32
through the resistor is approximately zero. In the event of
cos j 55
internal faults, an imbalance occurs which leads to a voltage
and a current flowing through the resistor R. f>< 81O, 81U

3 The same type of current transformers must be used and


must at least offer a separate core for the high-impedance
df / dt > < 81R
dI / dt > < current jump function
restricted ground-fault protection. They must have the Table 9/5 Available flexible protection functions
same transformation ratio and approximately an identical

4
knee-point voltage. They should also have only minimal For example, the following can be implemented:
measuring errors.
• Reverse power protection (ANSI 32R)
Auto-reclosure (ANSI 79) • Rate-of-frequency-change protection (ANSI 81R)
Multiple re-close cycles can be set by the user and lockout • Rate-of-voltage-change protection (ANSI 27R/59R)
will occur if a fault is present after the last re-close cycle.
5 The following functions are available: • Simplified differential protection via IEC 61850 GOOSE
communication.
• 1/3-pole ARC for all types of faults
• Separate settings for phase and ground faults Synchrocheck, synchronizing function (ANSI 25)
• Multiple ARC, one rapid auto-reclosure (RAR) and up to When closing a circuit-breaker, the units can check

6 nine delayed auto-reclosures (DAR)


• Initiation of the ARC is dependant on the trip command
whether two separate networks are synchronized. Voltage-,
frequency- and phase-angle-differences are checked to
selected (e.g. I2>, I>>, Ip, Idir>) determine whether synchronous conditions exist.
• The ARC function can be blocked by activating a binary input
Trip circuit supervision (ANSI 74TC)

7
• The ARC can be initiated from external or by the PLC logic
(CFC) One or two binary inputs can be used for monitoring the
circuit-breaker trip coil including its incoming cables. An alarm
• The directional and non-directional elements can either
signal is generated whenever the circuit is interrupted.
be blocked or operated non-delayed depending on the
Trafo 2 Wickl mit Erdung
auto-reclosure cycle Lockout (ANSI 86)

8 • If the ARC is not ready it is possible to perform a dynamic


setting change of the directional and non-directional
All binary output statuses can be memorized. The LED reset
key is used to reset the lockout state. The lockout state is
overcurrent elements
also stored in the event of supply voltage failure. Reclosure
• All types of curves can be combined together with various can only occur after the lockout state is reset.
overcurrent elements in different ARC cycles
9 • An additional new input interface is available for entering Thermal overload protection (ANSI 49)
various ARC parameters. To protect cables and transformers, an overload protection
Flexible protection functions function with an integrated warning/alarm element for
temperature and current can be used. The temperature is
SIPROTEC 7SC80 devices enables the user to easily add up
calculated using a thermal homogeneous body model (per
to 20 additional protection functions. Parameter definitions
IEC 60255-8), it considers the energy entering the equip-
are used to link standard protection logic with any chosen
ment and the energy losses. The calculated temperature is
characteristic quantity (measured or calculated quantity).
constantly adjusted according to the calculated losses. The
The standard logic consists of the usual protection elements
function considers loading history and fluctuations in load.
10
such as the pickup set point, the set delay time, the TRIP
command, a block function, etc. The mode of operation for
current, voltage, power and power factor quantities can be
three-phase or single-phase. Almost all quantities can be
operated with ascending or descending pickup stages (e.g.
under and over voltage). All stages operate with protection

9/10 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Function description

Settable dropout delay times deviations. Unwanted frequency changes in the network
can be detected and the load can be removed at a specified
1
If the relays are used in conjunction with electromechanical
frequency setting. Frequency protection can be used over
relays, in networks with intermittent faults, the long dropout
a wide frequency range (40 to 60 (for 50 Hz), 50 to 70 (for
times of the electromechanical relay (several hundred mil-
60 Hz)). There are four elements (individually set as over-
liseconds) can lead to problems in terms of time coordination/
frequency, underfrequency or OFF) and each element can
grading. Proper time coordination/grading is only possible if
be delayed separately. Blocking of the frequency protection
2
the dropout or reset time is approximately the same. This is
can be performed by activating a binary input or by using an
why the parameter for dropout or reset times can be defined
undervoltage element.
for certain functions such as overcurrent protection, ground
short-circuit and phase-balance current protection. Fault locator (ANSI FL)
Undercurrent monitoring (ANSI 37) The integrated fault locator calculates the fault impedance
and the distance to fault. The results are displayed in Ω,
A sudden drop in current, which can occur due to a reduced
load, is detected with this function. This may be due to shaft
that breaks, no-load operation of pumps or fan failure.
kilometers (miles) and in percent of the line length.
3
Customized functions (ANSI 32, 51V, 55 etc.)
Overvoltage protection (ANSI 59) Additional functions, which are not time critical, can be im-
plemented using the CFC measured values. Typical functions
4
The two-element overvoltage protection (possible per
include reverse power, voltage controlled overcurrent, phase
phase)detects unwanted network and machine overvoltage
angle detection, and zero-sequence voltage detection.
conditions. The function can operate either with phase-
to-phase, phase-to-ground, positive phase-sequence or Sectionalizer
negative phase-sequence voltage.
This function can automatically isolate fault current sections
Undervoltage protection (ANSI 27) of a distribution circuit once an upstream breaker or recloser
has interrupted the fault current. The sectionalizer function
5
The two-element undervoltage protection provides protec-
has no capacity to break fault current itself, so it is usually
tion against dangerous voltage drops (especially for electric
needed as an alignment with recloser. When the recloser
machines). Applications include the isolation of generators
opens for the last time, which has been preset to the
or motors from the network to avoid undesired operating
conditions and a possible loss of stability. Proper operating
sectionalizer, the sectionalizer opens and isolates the faulty
section of line.
6
conditions of electrical machines are best evaluated with
the positive-sequence quantities. The protection function is
active over a wide frequency range (45 to 55, 55 to 65 Hz).
Further functions
Even when falling below this frequency range the function
continues to work, however, with decreased accuracy. The Measured values
7
function can operate either with phase-to-phase, phase-
to-ground or positive phase-sequence voltage, and can be The Load profile function records historical measured
monitored with a current criterion. Three-phase and single- values. With this function, you can obtain a load profile with

8
phase connections are possible. desired data such as the measured values, demand values,
minimum/maximum values, and energy values of the cur-
1-pole operation rent, voltage, power, and frequency. The following functions
are available for measured value processing:
1-pole operation is optionally possible; switching objects
can be opened and closed for each phase. Furthermore,
1-pole tripping on a fault and automatic reclosing is possible
for each phase.
9
Frequency protection (ANSI 81O/U)
Frequency protection can be used for overfrequency and
underfrequency protection. Electric machines and parts
of the system are protected from unwanted frequency

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/11


Feeder Protection SIPROTEC 7SC80
Function description

• Currents IL1, IL2, IL3, IN, IEE takes arc-chamber’s physical conditions into account when
• Voltages UL1, UL2, UL3, U12, U23, U31 the CB opens.
1 • Symmetrical components I1, I2, 3I0; U1, U2, 3U0 This is why various methods of determining CB wear have
evolved which reflect the different operator philosophies.
• Various phase angles
To do justice to these, the relay offers several methods:
• Power Watts, Vars, VA/P, Q, S (P, Q: total and phase selec-
• SI
tive)
2 • Power factor (cos ϕ), (total and phase selective)
• SIx, with x = 1..3
• Si2t.
• Frequency
• Energy ± kWh, ± kVarh, forward and reverse power flow The devices also offer a new method for determining the
remaining service life:
• Mean as well as minimum and maximum current and
voltage values • Two-point method

3 • Operating hours counter The CB manufacturers double-logarithmic switching cycle


diagram (see Fig. 9/13) and the breaking current at the time
• Mean operating temperature of the overload function
of contact opening serve as the basis for this method. After
• DC voltage measurement of an external battery CB opening, the two-point method calculates the remaining
• Measurement of the internal device temperature number of possible switching cycles. Two points P1 and P2

4 • Limit value monitoring only have to be set on the device. These are specified in the
Limit values can be monitored using programmable logic CB’s technical data.
in the CFC. Commands can be derived from this limit value All of these methods are phase-selective and a limit value
indication can be set in order to obtain an alarm if the actual value falls
• Zero suppression below or exceeds the limit value during determination of

5 In a certain range of very low measured values, the value


is set to zero to suppress interference.
the remaining service life.

Metered values
For internal metering, the unit can calculate an energy me-
6 tered value from the measured current and voltage values. If
an external meter with a metering pulse output is available,
the 7SC80 can obtain and process metering pulses through
an indication input. The metered values can be displayed
and passed on to a control center as an accumulated value
7 with reset. A distinction is made between forward, reverse,
active and reactive energy.

Binary I/O extension with SICAM I/O-Unit 7XV5673

8
To extend binary inputs and binary outputs for SIPROTEC P1: Permissible number
7SC80 up to two SICAM I/O-Units 7XV5673 can be added. of operating cycles
at rated normal
Each SICAM I/O-Unit 7XV7653 is equipped with 6 binary current
inputs and 6 binary outputs and an Ethernet switch for
P2: Permissible number
cascading. The connection to the protection device can be of operating cycles

9
either through the DIGSI Ethernet service interface Port A or at rated short-
through IEC 61850 GOOSE on Port B (System interface with circuit current
EN100 module).
Fig. 9/13 Permissible number of operating cycles as a function of
Circuit-breaker wear monitoring/
breaking current
circuit-breaker remaining service life
Methods for determining circuit-breaker contact wear or Commissioning
the remaining service life of a circuit-breaker (CB) allow CB
Commissioning could not be easier and is supported by
maintenance intervals to be aligned to their actual degree of
DIGSI 4. The status of the binary inputs can be read individu-
wear. The benefit lies in reduced maintenance costs.
10
ally and the state of the binary outputs can be set individu-
There is no exact mathematical method to calculate the ally. The operation of switching elements (circuit-breakers,
wear or the remaining service life of a circuit-breaker that disconnect devices) can be checked using the switching
functions of the relay. The analog measured values are
represented as wide-ranging operational measured values.

9/12 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Function description

To prevent transmission of information to the control center


during maintenance, the communications can be disabled
to prevent unnecessary data from being transmitted. During
commissioning, all indications with test tag for test pur-
1
poses can be connected to a control and protection system.

Test operation
During commissioning, all indications can be passed to a
control system for test purposes.
2

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/13


Feeder Protection SIPROTEC 7SC80
Application examples

1
Infeed Infeed

Substation 'A' Substation 'B'

2 52 52

27 50/50N 51/51N 79 27 50/50N 51/51N 79


OR Start fault isolation OR Start fault isolation
Current-jump detection Current-jump detection

3 Fault localization Fault localization


Load Communication network Load
jdiff jdiff

52 52

4 50/50N 51/51N 79
OR Start fault isolation
50/50N 51/51N 79
OR Start fault isolation
Current-jump detection Current-jump detection

5 Load
Fault localization
jdiff
Fault localization
jdiff
Load

6 50/50N 51/51N 79
OR Start fault isolation
Current-jump detection

52
7 Disconnect ion

Fig. 9/14 Ring system application with SIPROTEC 7SC80

10

9/14 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80

Radial systems

1
General hints: 1) Auto-reclosure
The relay at the far end (D) from the (ANSI 79) only with
Infeed
overhead lines
infeed has the shortest tripping
2) Unbalanced load
time. Relays further upstream have to protection (ANSI 46) Transformer protection
be time-graded against downstream as backup protection

2
relays in steps of about 0.3 s. against asymmetrical
faults
A 52

Busbar

Further power supply B 52

3
I>t IN>t I2>t AR
51 51N 46 79
2) 1)

Busbar

* C 52
4
I>t IN>t I2>t
51 51N 46

Load
5
Busbar

D
* 52

I>t IN>t I2>t


6
51 51N 46

9_9_LSA4839-us.pdf
Load Load 7
Fig. 9/15 Protection concept with overcurrent protection

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/15


Feeder Protection SIPROTEC 7SC80
Application examples

Earth-fault detection in isolated or


compensated systems 1) The sensitive current

1
Infeed
measurement of
In isolated or compensated systems, the earth current
an occurred earth fault can be should be made by a
easily found by means of sensitive zero-sequence current
transformer
directional earth-fault detection.
Busbar

2
52

I>> I>t
50 51

3 7XR96
1)
IN>t dir.
67Ns
60/1

Load

4 Fig. 9/16 Protection concept for directional earth-fault detection

Ring-main cable

5
Infeed Infeed
With the directional comparison
52
protection, 100 % of the line can be
protected via instantaneous tripping
52 52
in case of infeed from two sources
(ring-main cable).
6
I>t IN>t υ>t I2>t

For lines with infeed from two sourc- 51 51N 49 46 Direct.Compar.Pickup

es, no selectivity can be achieved with


Overhead line Overhead line Protection as in
a simple definite time-overcurrent

9_10_LSA4841-us.pdf
or cable 1 or cable 2 the case of line
protection. Therefore, the directional I>t IN>t dir. I>t IN>t
or cable 1

7
definite time-overcurrent protection 67 67N 51 51N
must be used. A non-directional
definite time-overcurrent protection
is enough only in the corresponding 52 52

busbar feeders. The grading is done 52

8
from the other end respectively.
Advantage: 100% protection of 52 52
the line via instanta-
neous tripping, and 67 67N 51 51N
Direct.Compar.Pickup
easy setting. I>t IN>t dir. I>t IN>t

9 Disadvantage: Tripping times


increase towards the
Overhead line
or cable 3
Overhead line
or cable 4
Protection as in
the case of line
or cable 3
infeed. I>t IN>t dir. I>t IN>t

67 67N 51 51N

52 52

52

52 52

10 I>t

51
IN>t

51N
υ>t

49
I2>t

46

Load Load

Fig. 9/17 Protection concept of ring power systems

9/16 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Application examples

Busbar protection by overcurrent


relays with reverse interlocking
Applicable to distribution busbars Infeed
1
without substantial (< 0.25 x IN) Reverse interlocking
backfeed from the outgoing feeders.
I>>t0

50/50N 51/51N
2
52
t0 = 50 ms

Busbar

3
52 52 52

I>> I>t I>> I>t I>> I>t

9_11_LSA4842-us.pdf
50/50N 51/51N 50/50N 51/51N 50/50N 51/51N

4
Fig. 9/18 Busbar protection via overcurrent relays with reverse interlocking

5
Line feeder with load shedding
In unstable power systems (e.g.
solitary systems, emergency power
supply in hospitals), it may be neces-
sary to isolate selected consumers Busbar
6
from the power system in order to
protect the overall system.
V< f<
The overcurrent protection functions
7
52 27 81U
are effective only in the case of a
short-circuit. I>, I>>, IN>,
I>>> IN>> I>, Ip INTOC
Overloading of the generator can be 50 50N 51 51N
9_12_LSA2216a-us.pdf

measured as a frequency or voltage

8
drop. > I2> Final trip
79M 49 46 86

Fig. 9/19 Line feeder with load shedding

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/17


Feeder Protection SIPROTEC 7SC80
Application examples

Automatic reclosing

1
The Automatic reclosing function (AR)
has starting and blocking options. In the Stage can Stage get slower executes the
opposite example, the application of the 52 be blocked than the fuse or reclosing for
lower protection the hole feeder
blocking of the high-current stages is devices graduated
represented according to the reclosing

2
cycles. The overcurrent protection is ON
52 52
graded (stages I, Ip) according to the TRIP

grading plan. If an Automatic reclosing I>, I>>, I>>> I>t, I>>t, Ip

9_13_LSA2219c-us.pdf
function is installed in the incoming 50 51
supply of a feeder, first of all the complete IN>t, IN>>t,
feeder is tripped instantaneously in case IN>> INTOC AR
50N 51N 79
of fault. Arc faults will be extinguished
3 independently of the fault location. Other
protection relays or fuses do not trip
(fuse saving scheme). After successful
Automatic reclosing, all consumers are
supplied with energy again. If there is 52 Fuse opens by

4
unsuccessful reclosing
a permanent fault, further reclosing
cycles will be performed. Depending on I>t, Ip
the setting of the AR, the instantaneous 67
Circuit-breaker opens
by unsuccessful reclosing
tripping stage in the infeed is blocked in
the first, second or third cycle, i.e., now
5 the grading is effective according to the
grading plan. Depending on the fault Fig. 9/20 Auto-reclosure
location, overcurrent relays with faster
grading, fuses, or the relay in the infeed
will trip. Only the part of the feeder with
6 the permanent fault will be shut down
definitively.

Reverse power protection with parallel


infeeds Infeed Infeed

7
A B
If a busbar is supplied by two parallel
infeeds and there is a fault in one of the
infeeds, the affected busbar shall be
selectively shut down, so that supply to
the busbar is still possible through the
8
52 52
9_14_LSA4116-us.pdf

remaining infeed. To do this, directional


67 67N 32R 67 67N 32R
devices are required, which detect a
short circuit from the busbar towards the
infeed. In this context, the directional 52
time-overcurrent protection is normally
9
52 52
adjusted over the load current. Low-cur-
rent faults cannot be shut down by this
protection. The reverse power protection
can be adjusted far below rated power,
Feeder Feeder
and is thus also able to detect reverse
power in case of low-current faults far
Fig. 9/21 Reverse power protection with parallel infeeds
below the load current. The reverse
power protection is implemented through
the “flexible protection functions”.

10

9/18 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Application examples

Synchrocheck

1
Where two system sections are inter-
Busbar
connected, the synchrocheck
determines whether the connection V2
is permissible without danger to Closing Signal
the stability of the power system. In mm 52

2
1
the example, load is supplied from
a generator to a busbar through a
transformer. The vector group of
Local/remote
the transformer can be considered Transformer control
by means of a programmable angle VT1 1)

Syncro_7SC80-us ai
3
25 SYN
adjustment, so that no external 2)

adjustment elements are necessary. 79 AR

3
Infeed G
Synchrocheck can be used for
auto-reclosure, as well as for control
1)
functions (local or remote). Synchrocheck
2)
Automatic reclosing

Fig. 9/22 Measurement of busbar and feeder voltage for synchronization 4

5
Busbar
Protection of a transformer High-voltage

59-1 PU ,t
The high-current stage enables a
59
cur-
rent grading, the overcurrent
stages work as backup protection to
6
I>, I>> I>t, I>>t, Ip >t I2>t, I2>>t
TRIP
subordinate protection devices, and 52 50 51 49 46

the overload function protects the IN>, IN>>


IN>t, IN>>t,
INTOC
transformer from thermal overload. 50N 51N Inrush blocking

Low-current, single-phase faults


on the low-voltage side, which are
reproduced in the opposite system
on the high-voltage side, can be
52 7
detected with the unbalanced load
protection. The available inrush 87

blocking prevents pickup caused


by the inrush currents of the trans-
former.
e.g.
7UT61
52 8
*

IN>, IN>> IN>t, IN>>t, INTOC


50N 51N

52 9
Busbar
Medium-voltage
TRIP
52 52 52 52
4_17_LSA2203b-us.pdf

I2>>t, I2>t I>, I>> I>t, I>>t, Ip


46 50 51

typical Feeder

10
Unbalanced fault

Fig. 9/23 Typical protection concept for a transformer

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/19


Feeder Protection SIPROTEC 7SC80
Selection and ordering data

Description Order No. Short code

1
12345 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Feeder Protection SIPROTEC 7SC80 7SC80 - -3 +

Housing, binary inputs and outputs


Housing, 12 BI, 8 BO, 1 life contact 2

2
Housing, 20 BI, 15 BO, 1 Life contact, 2 x V4) 3

Specification of CT and VT measurement inputs


3 x I LPS / LoPo, 1 x V 1) 1
4 x I 1 A / 5 A, 1 x V 2
3 x I LPS / LoPo, 4 x V 1) 3

3
4 x I 1 A/5 A, 4 x V 4
3 x I 1 A / 5A, 1 x IEE (sensitive) = 0,001 to 1,6 A / 0,005 to 8 A, 1 x V 5
3 x I 1 A / 5 A, 1 x IEE (sensitive) = 0,001 to 1,6 A / 0,005 to 8 A, 4 x V 6

Rated auxiliary voltage

4 DC 60 V to 250 V; AC 115 V; AC 230 V


DC 24 V / 48 V
1
2
DC 24 V / 48 V, Battery monitoring 3

Unit version

5 Surface mounting housing 5)


Surface / Flush mounting housing with HMI
A
B
Surface mounting housing with detached HMI C

Region-specific default and language settings 2)

6 Region DE, IEC, language German 2)


Region World, IEC / ANSI, language English 2)
A
B
Region US, ANSI, language US-English 2) C
Region World, IEC/ANSI, language French 2) D
Region World, IEC / ANSI, language Spanish 2) E

7 Region World, IEC/ ANSI, language Russian 2) G

System interface L
No port 0
100 Mbit Ethernet, electrical, RJ45 connector 9 R

8 100 Mbit Ethernet, with integrated switch, optical, 2 x LC connector multimode


100 Mbit Ethernet, with integrated switch, optical, 2 x LC connector singlemode 24 km
9
9
S
T

Protocol for system interface


IEC 61850 L 0

9 IEC 61850 + DNP3 TCP


IEC 61850 + PROFINET 3)
L 2
L 3
IEC 61850 + IEC 60870-5-104 L 4
DNP3, RS485 L 6 G

Additional interfaces
No module 0
IRIG-B optical module 6
GPS-module 7
see

10 Functionality
MLFB - number 13, 14, 15, 16 for optional features
next
page

1) The mentioned sensors of SICAM FCM can be used. For protection related purpose the usability of the sensors have to be checked
2) Language selectable
3) Only with 100 Mbit Ethernet electrical and multimode
4) Only with position 7 = 3,4 or 6
5) HMI can be ordered separately: without cable C53207-A406-D242-A / with cable C53207-A406-D243-1.
You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec

9/20 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Selection and ordering data

ANSI No. Description Order No. Short code

1
12345 6 7 8 9 10 11 12 13 14 15 16 17 18 19
7SC80 - -3 +

Software packages Base Package A F A


50 / 51 Time-overcurrent protection phase: I>, I>>, I>>>, Ip

2
50N / 51N Time-overcurrent protection ground IE >, IE >>, IE >>>, IEP
50N(s) / 51N(s) Sensitive ground fault protection IEE>, IEE>>, IEEp 4)
50BF Circuit-breaker failure protection
46 Negative sequence / unbalanced load protection
49 Thermal Overload protection
87N High impedance REF 3)
74TC Trip circuit supervision
37 Undercurrent

3
51c Cold load pickup
81HBL2 Inrush restraint
86 Lockout
60CTS CT supervision
Parameter changeover
Jump detector with Delta measurement
Monitoring functions
Control of circuit breaker
Flexible protection functions (current parameters) 4
Under- / overfrequency
Fault recording, average values, min/max values
Sectionalizer function
Base Package B (containing A) 1) F B
67
67N
Directional overcurrent protection phase I>, I>> , I>>>, IEp
Directional overcurrent protection ground IE>, IE>>, I>>>, IEp
5
67Ns Directional sensitive ground fault protection IEE>, IEE>>, IEEp 4)
27/ 59 Under- / overvoltage
81U / O Under- / overfrequency f< ,f>
25

6
Sync-check
47 Negative-sequence overvoltage protection
64 / 59N Displacement voltage
60VTS VT supervision
32 / 55 / 81R Flexible protection functions (current and voltage parameters)
Protective function for voltage,
power, power factor, frequency change

Base Package N (containing R) 2) 5) FN


7
NTP-server functionality, no protection

Base Package R 2) F R
pure RTU functionality, no protection
Sectionalizer function
8
Additional functions

9
Without 0
79 With autoreclose 1
FL With fault locator 1) 2
79 / FL With autoreclose and fault locator 3
79 / TS With single/triple pole autoreclose 1) 4
79 / TS / FL With single/triple pole autoreclose and fault locator 1) 5

1) Only with position 7 = 3, 4 or 6


2) Only with position 16 = 0 10
3) 87N (REF) only with sensitive ground current input (position 7 = 5 oder 6)
 epending On the ground current Input the function will be either sensitive (I EE) or Non-sensitive (I E)
4) D
5) Only with position 12 = 7

You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/21


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 BI1 + 1

SIP.Com_002_en ai
71 BI2 + 2
70 BI3 + 3
+

2
69 BI4 4
68 BI5 + 5
67 BI6 + 6
66 BI7 + 7
65 BI8 + 8
64 IC - 9
63 10
62 IB/INs BI9 + 11

3
61 BI10 + 12
60 IA/INs BI11 + 13
59 BI12 + 14
58 - 15
57 16
56 Vx/IA BO1 17

4
55 18
54 BO2 19
53 20
52 BO3 21
51 22
50 BO4 23

5
49 24
BO5 25
48
26
46 Life contact BO6 27
28
47
BO7 29

Interference suppression capacitors at the relay


6
45 30
44 BO8 31
43 32
42
41 - contacts, ceramic, 2.2 nF, 250 V
+ BAT IN GPS/IRIG-B connection
40
(optional)

7
39
38 Port F
37 e.g. System interface
36
35 USB-DIGSI interface
- =

8
34
+ (~) Power supply
33 = HMI interface

Fig. 9/24 Connection diagram SIPROTEC 7SC8021

10

9/22 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 IN, INs BI1 + 1

SIP.Com_003_en ai
71 BI2 + 2
70 IC BI3 + 3
+

2
69 BI4 4
68 IB BI5 + 5
67 BI6 + 6
66 IA BI7 + 7
65 BI8 + 8
64 - 9
63 10
62 BI9 + 11

3
61 BI10 + 12
60 BI11 + 13
59 BI12 + 14
58 - 15
57 16
56 Vx BO1 17

4
55 18
54 BO2 19
53 20
52 BO3 21
51 22
50 BO4 23

5
49 24
BO5 25
48
26
46 Life contact BO6 27
28
47
BO7 29

Interference suppression capacitors at the relay


6
45 30
44 BO8 31
43 32
42
41 - contacts, ceramic, 2.2 nF, 250 V
+ BAT IN GPS/IRIG-B connection
40
(optional)

7
39
38 Port F
37 e.g. System interface
36
35 USB-DIGSI interface
- =

8
34
+ (~) Power supply
33 = HMI interface

Fig. 9/25 Connection diagram SIPROTEC 7SC8022 and SIPROTEC


7SC8025

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/23


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 BI1 + 1

SIP.Com_004_en ai
71 BI2 + 2
70 BI3 + 3
+

2
69 BI4 4
68 BI5 + 5
67 BI6 + 6
66 BI7 + 7
65 BI8 + 8
64 IC - 9
63 10
62 IB/INs BI9 + 11

3
61 BI10 + 12
60 IA/INs BI11 + 13
59 BI12 + 14
58 - 15
57 16
56 Vx/IA BO1 17

4
55 18
54 VC BO2 19
53 20
52 VB BO3 21
51 22
50 VA BO4 23

5
49 24
BO5 25
48
26
46 Life contact BO6 27
28
47
BO7 29

Interference suppression capacitors at the relay


6
45 30
44 BO8 31
43 32
42
41 -
contacts, ceramic, 2.2 nF, 250 V
+ BAT IN GPS/IRIG-B connection
40
(optional)

7
39
38 Port F
37 e.g. System interface
36
35 USB-DIGSI interface
- =

8
34
+ (~) Power supply
33 = HMI interface

Fig. 9/26 Connection diagram SIPROTEC 7SC8023

10

9/24 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 IN, INs BI1 + 1

SIP.Com_005_en ai
71 BI2 + 2
70 IC BI3 + 3
+

2
69 BI4 4
68 IB BI5 + 5
67 BI6 + 6
66 IA BI7 + 7
65 BI8 + 8
64 - 9
63 10
62 BI9 + 11

3
61 BI10 + 12
60 BI11 + 13
59 BI12 + 14
58 - 15
57 16
56 Vx BO1 17

4
55 18
54 VC BO2 19
53 20
52 VB BO3 21
51 22
50 VA BO4 23

5
49 24
BO5 25
48
26
46 Life contact BO6 27
28
47
BO7 29

Interference suppression capacitors at the relay


6
45 30
44 BO8 31
43 32
42
41 -
contacts, ceramic, 2.2 nF, 250 V
+ BAT IN GPS/IRIG-B connection
40
(optional)

7
39
38 Port F
37 e.g. System interface
36
35 USB-DIGSI interface
- =

8
34
+ (~) Power supply
33 = HMI interface

Fig. 9/27 Connection diagram SIPROTEC 7SC8024 and SIPROTEC 7SC8026

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/25


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 V2B 73 BI1 + 1
71 74 BI2 + 2
70 V2C 75 BI3 + 3

2
69 76 BI4 + 4
68 77 BI5 + 5
67 78 BI6 + 6
66 79 BI7 + 7
65 - 80 BI8 + 8
BI13 + 81 - 9
64 IC BI14 + 82 10
63 BI15 + 83 BI9 + 11
+ +

3
62 I B/INs BI16 84 BI10 12
61 BI17 + 85 BI11 + 13
60 I A/INs BI18 + 86 BI12 + 14
59 BI19 + 87 - 15
58 BI20 + 88 16
57
56 Vx / V2A BO9 89 BO1 17

4 55
54 VC BO10
90
91
92
BO2
18
19
20
53
52 VB BO11 93 BO3 21
51 94 22
50 VA BO12 95 BO4 23

5
49 96 24
BO13 97 BO5 25
48 98 26
47 Life Contact BO14 99 BO6 27
46 100 28
45 BO15 101 BO7 29

6
44 102 30
43 = - BO8 31
103

Interference Suppression Capacitors at the Relay Contacts,


42 Power Supply (~) + 32
- = 104
41
+ BAT IN
40
39 GPS/IRIG-B connection
38 (optional)

7 37
36
35
Port F
e.g. System interface

34 - =
Ceramic, 2.2 nF, 250 V

+ (~) Power Supply USB-DIGSI-Interface


33 =

8
HMI-Interface

Fig. 9/28 Connection diagram SIPROTEC 7SC8033

10

9/26 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection diagrams

1
72 I N, INS V2B 73 BI1 + 1
71 74 BI2 + 2
70 IC V2C 75 BI3 + 3

2
69 76 BI4 + 4
68 IB 77 BI5 + 5
67 78 BI6 + 6
66 IA 79 BI7 + 7
65 - 80 BI8 + 8
BI13 + 81 - 9
64 BI14 + 82 10
63 BI15 + 83 BI9 + 11
+ +

3
62 BI16 84 BI10 12
61 BI17 + 85 BI11 + 13
60 BI18 + 86 BI12 + 14
59 BI19 + 87 - 15
58 BI20 + 88 16
57
56 Vx / V2A BO9 89 BO1 17

4
55 90 18
54 VC BO10 91 BO2 19
53 92 20
52 VB BO11 93 BO3 21
51 94 22
50 VA BO12 96 BO4 23

5
49 96 24
BO13 97 BO5 25
48 98 26
47 Life Contact BO14 99 BO6 27
46 100 28
45 BO15 101 BO7 29
44 102 30

6
43 31
= - 103
BO8

Interference Suppression Capacitors at the Relay Contacts,


42 Power Supply (~) + 32
- = 104
41
+ BAT IN
40
39 GPS/IRIG-B connection
38 (optional)

7
37
Port F
36
e.g. System interface
35
34 - =
Ceramic, 2.2 nF, 250 V

+ (~) Power Supply USB-DIGSI-Interface


33 =
HMI-Interface

8
Fig. 9/29 Connection diagram SIPROTEC 7SC8034 and SIPROTEC 7SC8036

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/27


Feeder Protection SIPROTEC 7SC80
Connection examples

Connection of current
and voltage transformers
1 Current transformer connections
52 52 52

anschl-3-stromwdl-sternpunktstrom
66 IA 65

68 IB 67

2 70 IC 69
P2 S2

IN
P1 S1 72 71

A B C SIPROTEC

3 Fig. 9/30 Current transformer connections to three current transform-


ers and neutral point current (ground current) (Holmgreen
connection) – appropriate for all networks

4
52 52 52

IA

5
66 65

68 IB 67

anschl-2-stromwdl-110220
70 IC 69
P2 S2

72 IN 71
P1 S1

6 A B C SIPROTEC

Fig. 9/31 Current transformer connections to two current transformers

7
– only for isolated or resonantgrounded networks

8 52 52 52

66 IA 65
IB

9
68 67

70 IC 69
P2 S2
anschl-3-stromwdl-summenstromw

IN
P1 S1 71 72

SIPROTEC
A B C

P2 S2

P1 S1

10
Fig. 9/32 Current transformer connections to three current transformers,
ground current from an additional summation current trans-
former – preferably for effectively or low-resistance grounded
networks

9/28 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection examples

Transformer connections

A
B
C
Busbar 1
A

X
a

x
2
50 VA 49

52 VB 51
52 52 52 VC
54 53

56 Vx 55

66 IA

IB
65 3

dw_7SC80_conn-example
68 67
70 IC 69
P2 S2

4
72 IN 71
P1 S1

SIPROTEC
A B C

Fig. 9/33 Transformer connections to three current transformers

5
and three voltage transformers (phaseto-ground voltages),
normal circuit layout – appropriate for all networks

6
A B C
A X a x VA
50 49

7
52 VB 51

54 VC 53

56 Vx / V2A 55

52 52 52 Circuit bre ake r/Recloser

dw_7SC803_conn-example_6PT 8
A X a x

74 V2B 73

76 V2C 75

SIPROTEC

9
A B C

Fig. 9/34 Transformer connections to three current transformers and


six voltage transformers (phase-toground voltages), normal
circuit layout – appropriate for all networks

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/29


Feeder Protection SIPROTEC 7SC80
Connection examples

Voltage transformer connections

1 A
B Busbar
C
A

2
X
e

n
a

52 52 52 x

3 50 VA-B 49

dw_Vab-Vbc-Vn connection
52 VC-B 51

54 VN 53

4 A B C
56 Vx 55

SIPROTEC

5 Fig. 9/35 Voltage transformer connections to two voltage transformers


(phase-to-phase voltages) and broken delta winding (e-n) –
appropriate for all networks

6 Voltage transformer connections


for two voltage transformers in
open delta voltage connection. In
this connection, determination of
7 zero-sequence voltage V0 is not pos-
sible. Functions using zero sequence A
voltage must be disabled. B
C
A X A X

8 a x a x

52 52 52

50 VA-B 49
VC-B

9
52 51

54 VN 53
dw_Vab-Vbc connection

A B C Vx
56 55

SIPROTEC

Fig. 9/36 Voltage transformer connections for two voltage transformers in open


delta voltage connection.

10

9/30 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection examples

Voltage transformer connections

1
A X e n a x

50 VA-B 49

52 VC-B

VN
51 2
54 53

52 52 52 Circuit breaker/Recloser

A X e n a x
3

dw_7SC803_conn-example-Vab-Vbc-Vn
V2A-V2B

4
56 55

74 V2C-V2B 73
VNS2
76 75

SIPROTEC

5
A B C

Fig. 9/37 Voltage transformer connections to two voltage transformers


(phase-to-phase voltages) and broken delta winding (e-n) –
appropriate for all networks

6
Voltage transformer connections
for two voltage transformers in A a

open delta voltage connection. In


this connection, determination of
X
A
x
a 7
zero-sequence voltage V0 is not pos- X x
50
VA-B
49
sible. Functions using zero sequence VC-B
52 51
voltage must be disabled.
VN

8
54 53
52 52 52 Circuit bre ake r/Recloser
SIPROTEC

A a

X x

9
A a

X x
56 V2A-V2B 55

74 V2C-V2B 73
dw_7SC803_conn-example-Vab-Vbc

76 VNS2 75
A B C
SIPROTEC

10
Fig. 9/38 Voltage transformer connections for two voltage transformers
in open delta voltage connection

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/31


Feeder Protection SIPROTEC 7SC80
Connection examples

Transformer connections
A

1
B Busbar
C

[anschl-3-stromwdl-3-spgwdl-kapazitiv
2
50 VA 49

52 VB 51

54 VC 53

56 Vx 55
52 52 52

66 IA 65
IB

3
68 67

70 IC 69
P2 S2

72 IN 71
P1 S1

A B C SIPROTEC

4
Fig. 9/39 Transformer connections to three current transformers and
three voltage transformers –capacitive

6
A B C

7 50

52
VA

VB
49

51

54 VC 53

56 Vx / V2A 55

8 52 52 52 Circuit bre ake r/Recloser


dw_7SC803_conn-example_6PT_capacitive

9
74 V2B 73

76 V2C 75

SIPROTEC
A B C

Fig. 9/40 Transformer connections to three current transformers and six


10 voltage transformers – capacitive

9/32 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5


Feeder Protection SIPROTEC 7SC80
Connection examples

Standard connection capabilities

52 52 52 64
63 IC 1
62
61 IB

60
59 IA 2
* * *

SIP.Com_012_en ai
SIPROTEC

3
A B C

Fig. 9/41 Standard connection 3 phase currents via LoPo/LPS

9
You will find a detailed overview of the
technical data in the current manual

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5 9/33


Feeder Protection SIPROTEC 7SC80
Connection types

Overview of connection types

1
Type of network Function Current connection Voltage connection
(Low-resistance) grounded Time-overcurrent protection Residual circuit, with 3 phase- –
networks phase/ground non-directional current transformers required,
phase-balance neutral current
transformers possible
(Low-resistance) grounded Sensitive ground-fault protection Phase-balance neutral current –

2 networks
Isolated or compensated Overcurrent protection phases
transformers required
Residual circuit, with 3 or 2 phase- –
networks non-directional current transformers possible
(Low-resistance) grounded Directional time-overcurrent Residual circuit, with 3 phase- Phase-to-ground connection or
networks protection, phase current transformers possible phase-to-phase connection
Isolated or compensated Directional time- overcurrent Residual circuit, with 3 or 2 phase- Phase-to-ground connection or

3
networks protection, phase current transformers possible phase-to-phase connection
(Low-resistance) grounded Directional time-overcurrent Residual circuit, with 3 phase- Phase-to-ground connection
networks protection, ground-faults current transformers required, required
phase-balance neutral current
transformers possible

4
Isolated networks Sensitive ground-fault protection Residual circuit, if ground current 3 times phase-to-ground
> 0.05 IN on secondary side, connection or phase-to-ground
otherwise phase-balance neutral connection with broken delta
current transformers required winding
Compensated networks Sensitive ground-fault protection Phase-balance neutral current 3 times phase-to-ground
cos j measurement transformers required connection or phase-to-ground

5
connection with broken delta
winding

Table 9/5 Overview of connection types

10

9/34 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 5