TAG NUMBER 62PB001 TAG NUMBER 62TB001


DESCRIPTION DESCRIPTION
NOTES
DIESEL TRANSFER PUMP DIESEL STORAGE TANK
(ROTARY)
1. ALL FLANGES DOWNSTREAM OF PUMP SHALL BE WRAPPED TO AVOID FUGITIVE DIESEL MIST/SPRAY.
FLOW AT P/T m³/h 4.1 (~69 lpm) DIMENSION LxWxH (4.7X3.5X5)
L 2. REFERENCE SHALL BE MADE TO NPTF30 FOR MINIMUM VENTING REQUIREMENT (8" CORRESPONDS TO L
DISCHARGE PRESSURE barg 2.58 DESIGN CAPACITY m³ 82.2 ~50M² OF WETTED SURFACE 80% TANK FILLING).
DIFFERENTIAL PRESSURE bar 2.5 DES./OPER. PRESSURE barg ATM + FULL OF DIESEL / ATM DIESEL 3. DEDICATED BUNDED AREA.
HYDRAULIC POWER kW 0.3 DES./OPER. TEMPERATURE °C -10 & 50 / AMB 10 DAYTANK 4. DRY COUPLING HOSE CONNECTION FOR DIESEL SUPPLY VESSEL.
MATERIAL 316/316L SS (UNS S31600/S31603) MATERIAL 316/316L SS (UNS S31600/S31603) 5. PROVISION FOR FILTERS.
INS CODE/THK/MATL 6. ANTI-SYPHON ON INLET. ANTI-STATIC PIPE.
7. BIOCIDE SHOCK DOSE TO BE ACCESSIBLE FROM THE TOP OF THE TANK.
TRIM AD20
TRIM OF-62L0008-AD20-00 73MA001 8.
9.
LOW POINT DRAIN.
DEAD MAN'S HANDLE.
10. INDICATION VISIBLE AT DIESEL GUN.
11. DELETED.
12. PUMP IN INTERMITTENT SERVICE.
K 13. INDICATION VISIBLE AT VALVE HAND SWITCH. K
1.5"x1"
14. OVERFLOW LINE PROVIDED WITH ANTI-SYPHON DIP PIPE AND VENT INSIDE TANK. ANTI-STATIC PIPE.

62V0006
1 15. DRAIN VALVE 62V0005 LOCATED WITHIN THE BUND AREA.
1.5" 16. OUTLET OF VENT PROVIDED WITH BIRD SCREEN. VENT OUTLET ORIENTATION TO PREVENT BLOCKAGE.
1"-DO-62L0009-AD20-00
17. FLAME ARRESTOR INSTALLED IN LINE PROVIDED BY POWER GENERATION VENDOR OF SUITABLE
MATERIAL, TO PREVENT CORROSION.
18. SIZE OF SUPPLY HOSE CONNECTION IS 4".
19. VENT VALVE ON SUPPLY LINE TO BE LOCATED IN AN ACCESSIBLE POSITION AS THIS IS USED PRIOR
BREAKING THE SUPPLY HOSE CONNECTION.
SP 20. BLIND FLANGE OF DRAIN VALVE PROVIDED CHAINED TO THE DRAIN LINE.
21. DIESEL TRANSFER PUMP LOCATED WITHIN THE BUND AREA.
04 04 22. LEVEL TRANSMITTER GWR TYPE WITH FLEXIBLE LEAD PROBE AND WEIGHT.
WEATHER DECK WEATHER DECK 23. FOR DETAILS INSIDE PACKAGE SEE VENDOR P&ID DOC. 118A50-1015-PR-C01-001/002/003/004/005
J 24. SP-05 AT CELLAR DECK ELEVATION.
J
TO OPEN DRAINS 25. RS ELEVATION HIGHER THAN MANUAL VALVE 62V0011 SHOWN ON P&ID AB-TO-ROS-TE-PR-PD-0014.001
SP AB-TO-ROS-TE-PR-PD-0014.001
62 OPEN 16 0004 0003
HS 62
13 PSD ESD ACOUSTIC ALARM LAH 02 02 SET
0001 NEAR 62LI0001A VENT TO SAFE 62V0002 1
CLOSE 0001 2.38 barg
LOCATION LO 62V0004
1.5"-OF-62L0004-AD20-00
19 62
ESV 1
13 3

1.5"-OF-62L0003-AD20-00
0001 HH H 1.5 1.5 62

VA-62L0002 OF-62L004
62 62 PCV
LST LI

8"-VA-62L0001-AD20-00
HOLDS
62V0001

1 5
0002 0001 0002
H 1" FC H
62C0001 LL 62 LI L 1. DELETED.
PSD 2"x1.5
4"
0001A 2 2. DELETED.
1 HIGH 62 62 3. DELETED.
1 LST LT 1"-150#RF E 2"-150#RF
POINT 4. DELETED.
MIN 0002 0001 62
22 22 PSV 5. DELETED.
7 SLOPE 6. DELETED.
2"-VA-62L0002-AD20-00 0003
7. DELETED.
SP=5 barg 8. DELETED.
1
BLOCKED 9. DELETED.
4" 4" 4" OUTLET
4"-OF-62L0001-AD20-00

2"x1"
N1 K1 K2 N7 N3 N5

2"-OF-62L0005-AD20-00
G G
OVERFLOW 62
6 6 XV
N6 FIXED EXHAUST TO SAFE

6"-DO-62L0003-AD20-00
0001 SPEED LOCATION
14 PSD

62TB001
62 SP 62PB001-M01

6"-VA-62L0055-AS20-00
XV M VENT TO SAFE
M 0001 12 01 LOCATION
1 62C0002
LEGEND
F SLOPE RS RS F
N2 TP 17
2"-OF-62L0002-AD20-00
26" FC 2"X1.5" 1 002

62V0005
MW M1 2 1 2
0009 0003

SLOPE
62V0003 1" 62PB001 2"-OF-62L0009-AD20-00
1" 15 82CK001
N4 2"-VA-62L0004-AD20-00
2" 21 12
8 NC 20 TP
LO TP
1
SP 2 2"-OF-62L0006-AD20-00 003 82EG002 001
E 9 SLOPE
62V0008 MAIN POWER GENERATION
E
11 01 TP
23 PACKAGE
3/8" HOSE 2"-DO-62L0004-AD20-00 004
DOC. N.
ADAPTOR 0F-62L007 OF-62L0006
118A50-1015-PR-C01-001/002/003/004/005
CONNECTION
TP TP
2"-DO-62L0001-AD20-00 23
005 006
3
AIR 3" 3"
2"

D COMPRESSOR STORAGE POD 4"x3"


62V0009 1
D
2"-DO-62L0002-AD20-00
RS
MAIN DECK MAIN DECK

FOR DETAILS SEE OFFSHORE OPERATION SCHEME EXHAUST


TO SAFE

6"-VA-62L0056-AS20-00
LOCATION AB-TO-ROS-TE-PR-PD-0007 LEGEND SHEET

VENT TO SAFE REFERENCE DWG No. REFERENCE DWG TITLE


1.5"-DO-97L0006-AS20-00 LOCATION

C 17 C

2"-VA-62L0003-AD20-00
C04 22/04/20 - APPROVED FOR CONSTRUCTION - VALID ONLY FOR HAZOP RECOMM. N. 89 CIM EAI SCA -
84CK001 TP TP
C03 18/02/20 - APPR0VED FOR CONSTRUCTION - VALID ONLY FOR DNV COMMENT N. 205 CIM EAI SCA -
1.5"-DO-97L0005-AS20-00 007 008
C02 11/09/19 - APPROVED FOR CONSTRUCTION CIM EAI SCA -
C01 03/05/19 - APPROVED FOR CONSTRUCTION CIM EAI SCA -
84EG001 B01 30/01/19 - ISSUED FOR DESIGN CIM EAI SCA -
SP EMERGENCY POWER
23 A01 14/09/18 - ISSUED FOR REVIEW CIM EAI SCA -
2"-DO-62L0006-AD20-00 GENERATION PACKAGE
B 05 01 DOC. N. REV. DATE BY ISSUE DESCRIPTION CHK ENGR APPR CLIENT
B
LO
2"-OF-62L0007-AD20-00 118A50-1015-PR-C01-001/002/003/004/005
SLOPE
62V0007
3 TP
TP
RS 009 62V0010 2"-DO-62L0005-AD20-00
18 4 24 010 2" CLIENT: PREMIER OIL
1 PROJECT No.: 11336176 DATE
25 TO OPEN DRAINS DWG TITLE:
SLOPE DESIGNED BY:
4"-DO-56L0002-AD20-00 PIPING & INSTRUMENTATION DIAGRAM
AB-TO-ROS-TE-PR-PD-0014.001 DRAWN BY: DIESEL SYSTEM
A CHECKED BY: C01 A
CELLAR DECK CELLAR DECK
APPROVED BY:
TO OPEN DRAIN SUMP
OVERBOARD SCALE: SIZE: AREA: SYSTEM: SUB-SYS.: DRAWING No.: SHT No.: REV.:
AB-TO-ROS-TE-PR-PD-0014.001
TO SAFE LOCATION 1:1 A1 AB-TO-ROS-TE-PR-PD-0002 01 OF 01 C04
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
FILE: B-TO-ROS-TE-PR-PD-0002_C04.dwg